ac transmission kundur
TRANSCRIPT
-
8/7/2019 AC Transmission Kundur
1/42
AC TRANSMISSIONAC TRANSMISSION
1539pk
Copyright P. KundurThis material should not be used without the author's consent
-
8/7/2019 AC Transmission Kundur
2/42
Performance Equations and ParametersPerformance Equations and Parameters
of Transmission Linesof Transmission Lines
A transmission line is characterized by four
parameters:
series resistance (R) due to conductor resistivity
shunt conductance (G) due to currents along
insulator strings and corona; effect is small and
usually neglected
series inductance (L) due to magnetic field
surrounding the conductor
shunt capacitance (C) due to the electric field
1539pkACT - 1
between the conductors
These are distributed parameters.
The parameters and hence the characteristics of
cables differ significantly from those of overhead
lines because the conductors in a cable are
much closer to each other
surrounded by metallic bodies such as shields,
lead or aluminum sheets, and steel pipes
separated by insulating material such as
impregnated paper, oil, or inert gas
-
8/7/2019 AC Transmission Kundur
3/42
For balanced steady-state operation, the performance of
transmission lines may be analyzed in terms of single-
phase equivalents.
Fig. 6.1 Voltage and current relationship of a distributed
parameter line
1539pkACT - 2
The general solution for voltage and current at adistance x from the receiving end (see book: page 202)
is:
where
(6.8)
(6.9)
xRCRxRCR eIZV
eIZV
V
++
=2
~~
2
~~~
xR
C
R
xR
C
R
eI
ZV
eI
ZV
I
+
=2
~~
2
~~
~
jzy
yzZC
+==
=
-
8/7/2019 AC Transmission Kundur
4/42
The constant ZC is called the characteristic
impedance and is called the propagation constant.
The constants and ZCare complex quantities. The
real part of the propagation constant is called theattenuation constant , and the imaginary part the
phase constant .
If losses are completely neglected,
1539pkACT - 3
)resistance(pure
NumberReal== CLZC
numberImaginary== j
-
8/7/2019 AC Transmission Kundur
5/42
For a lossless line, Equations 6.8 and 6.9 simplify to
When dealing with lightening/switching surges, HV
lines are assumed to be lossless. Hence, ZC with
losses neglected is commonly referred to as the surge
impedance.
The power delivered by a line when terminated by its
(6.17)
(6.18)
xIjZxVV RCR sincos~~
+=
xZ
VjxII
C
RR sin
~cos
~~
+=
1539pkACT - 4
impedance load.
where V0 is the rated voltage
At SIL, Equations 6.17 and 6.18 further simplify to
wattsZ
VSIL
C
2
0=
x
R
x
R
eII
eVV
=
=
~
~~(6.20)
(6.21)
-
8/7/2019 AC Transmission Kundur
6/42
Hence, for a lossless line at SIL,
V and I have constant amplitude along the line
V and I are in phase throughout the length of the line
The line neither generates nor absorbs VARS
As we will see later, the SIL serves as a convenientreference quantityfor evaluating and expressing line
performance
Typical values of SIL for overhead lines:
1539pkACT - 5
SIL (MW): 140 420 1000 2300
Underground cables have higher shunt capacitance;
hence, ZC is much smaller and SIL is much higher than
those for overhead lines.
for example, the SIL of a 230 kV cable is about
1400 MW
generate VARs at all loads
-
8/7/2019 AC Transmission Kundur
7/42
Typical ParametersTypical Parameters
Table 6.1 Typical overhead transmission line parameters
Note: 1. Rated frequency is assumed to be 60 Hz
1539pkACT - 6
Table 6.2 Typical cable parameters
2. Bundled conductors used for all lines listed, except for the 230 kV line.
3. R, xL, and bC are per-phase values.4. SIL and charging MVA are three-phase values.
* direct buried paper insulated lead covered (PILC) and high pressure pipe
type (PIPE)
-
8/7/2019 AC Transmission Kundur
8/42
Voltage Profile of a Radial Line at NoVoltage Profile of a Radial Line at No--LoadLoad
With receiving end open, IR = 0. Assuming a
lossless line from Equations 6.17 and 6.18, we have
At the sending end (x = l),
( )
( ) ( )xsinZV~jI~xcosV
~V~
CR
R
=
=
=
=
cosV~
lcosV~
E~
R
RS
(6.31)
(6.32)
(6.33)
1539pkACT - 7
where = l. The angle is referred to as the
electrical length or the line angle, and is expressed
in radians.
From Equations 6.31, 6.32, and 6.33
(6.35)
(6.36)
=
=
cos
xsin
Z
EjI
cos
xcosE~
V~
C
S
S
-
8/7/2019 AC Transmission Kundur
9/42
As an example, consider a 300 km, 500 kV line with
= 0.0013 rads/km, ZC = 250 ohms, and ES = 1.0 pu:
Base current is equal to that corresponding to SIL.
Voltage and current profiles are shown in Figure 6.5.
The only line parameter, other than line length, thataffects the results of Figure 6.5 is . Since ispractically the same for overhead lines of all voltagelevels (see Table 6.1), the results are universally
pu411.0I
pu081.1V
3.22
rads39.00013.0x300
S
R
=
=
=
==o
1539pkACT - 8
The receiving end voltage for different line lengths:
- forl= 300 km, VR = 1.081 pu- forl= 600 km, VR = 1.407 pu- forl= 1200 km, VR = infinity
Rise in voltage at the receiving end is because of
capacitive charging current flowing through lineinductance.
known as the "Ferranti effect".
-
8/7/2019 AC Transmission Kundur
10/42
(a) Schematic Diagram
1539pkACT - 9
Figure 6.5 Voltage and current profiles for a 300 km lossless
line with receiving end open-circuited
(b) Voltage Profile
(c) Current Profile
-
8/7/2019 AC Transmission Kundur
11/42
VoltageVoltage -- Power CharacteristicsPower Characteristics
of aof a Radial LineRadial Line
Corresponding to a load ofPR+jQRat the receiving end, wehave
Assuming the line to be lossless, from Equation 6.17
with x = l
Fig. 6.7 shows the relationship between VRand PRfor a300 km line with different loads and power factors.
*~~
R
RRR
V
jQPI
=
+=
*~sincos~~
R
RRCRS
V
jQPjZVE
1539pkACT - 10
e oa s norma ze y v ng R y 0, e na ura
load (SIL), so that the results are applicable to overheadlines of all voltage ratings.
From Figure 6.7 the following fundamental properties of actransmission are evident:
a) There is an inherent maximum limit of power that can betransmitted at any load power factor. Obviously, therehas to be such a limit, since, with ESconstant, the only
way to increase power is by lowering the loadimpedance. This will result in increased current, butdecreased VRand large line losses. Up to a certain pointthe increase of current dominates the decrease ofVR,thereby resulting in an increased PR. Finally, thedecrease in VRis such that the trend reverses.
-
8/7/2019 AC Transmission Kundur
12/42
1539pkACT - 11
Figure 6.7 Voltage-power characteristics of a 300 km
lossless radial line
-
8/7/2019 AC Transmission Kundur
13/42
VoltageVoltage -- Power CharacteristicsPower Characteristics
of a Radial Lineof a Radial Line (cont'd)(cont'd)
b) Any value of power below the maximum can be
transmitted at two different values ofVR. The
normal operation is at the upper value, within
narrow limits around 1.0 pu. At the lower voltage,
the current is higher and may exceed thermallimits. The feasibility of operation at the lower
voltage also depends on load characteristics, and
may lead to voltage instability.
c) The load power factor has a significant influence
1539pkACT - 12
transmitted. This means that the receiving end
voltage can be regulated by the addition of shunt
capacitive compensation.
Fig. 6.8 depicts the effect of line length:
For longer lines, VR is very sensitive to variations
in PR.
For lines longer than 600 km ( > 45), VRatnatural load is the lower of the two values which
satisfies Equation 6.46. Such operation is likely
to be unstable.
-
8/7/2019 AC Transmission Kundur
14/42
1539pkACT - 13
Figure 6.8 Relationship between receiving end voltage,line length, and load of a lossless radial line
-
8/7/2019 AC Transmission Kundur
15/42
VoltageVoltage--Power Characteristic of a LinePower Characteristic of a Line
Connected to Sources at Both EndsConnected to Sources at Both Ends
With ESand ERassumed to be equal, the following
conditions exist:
the midpoint voltage is midway in phase between
ESand ER
the power factor at midpoint is unity
with PR>P0, both ends supply reactive power to the
line; with PR
-
8/7/2019 AC Transmission Kundur
16/42
Power Transfer and StabilityPower Transfer and Stability
ConsiderationsConsiderations
Assuming a lossless line, from Equation 6.17 with
x = l, we can show that
where = llll is the electrical length of line and is theangle by which ESleads ER, i.e. the load angle.
IfES= ER= rated voltage, then the natural load is
(6.51)sin
sinC
RSR
Z
EEP =
C
RSO
Z
EEP =
1539pkACT - 15
and Equation 6.51 becomes
The above is valid for synchronous as well as
asynchronous load at the receiving end.
Fig. 6.10(a) shows the ---- PRrelationship for a 400 km
line.
For comparison, the Vm - PRcharacteristic of the line is
shown in Fig. 6.10(b).
sin
sinO
R
PP =
-
8/7/2019 AC Transmission Kundur
17/42
1539pkACT - 16
Figure 6.10 PR- and Vm-PR characteristics of 400 km lossless
line transmitting power between two large systems
-
8/7/2019 AC Transmission Kundur
18/42
Reactive Power RequirementsReactive Power Requirements
From Equation 6.17, with x = land ES= ER= 1.0, we canshow that
Fig. 6.11 shows the terminal reactive powerrequirements of lines of different lengths as a functionofPR.
Adequate VAR sources must be available at the twoends to operate with varying load and nearly
( )
sin
coscos2
C
S
SR
Z
E
QQ
=
=
1539pkACT - 17
cons an vo age.
General Comments
Analysis of transmission line performancecharacteristics presented above represents a highlyidealized situation
useful in developing a conceptual understanding ofthe phenomenon
dynamics of the sending-end and receiving-endsystems need to be considered for accurateanalysis.
-
8/7/2019 AC Transmission Kundur
19/42
1539pkACT - 18
Figure 6.11 Terminal reactive power as a function of power
transmitted for different line lengths
-
8/7/2019 AC Transmission Kundur
20/42
Loadability CharacteristicsLoadability Characteristics
The concept of "line loadability" was introduced by
H.P. St. Clair in 1953
Fig. 6.13 shows the universal loadability curve for
overhead uncompensated lines applicable to allvoltage ratings
Three factors influence power transfer limits:
thermal limit (annealing and increased sag)
voltage drop limit (maximum 5% drop)
1539pkACT - 19
steady-state stability limit (steady-state stability
margin of 30% as shown in Fig. 6.14)
The "St. Clair Curve" provides a simple means of
visualizing power transfer capabilities of transmission
lines.
useful for developing conceptual guides to
preliminary planning of transmission systems
must be used with some caution
Large complex systems require detailed assessment
of their performance and consideration of additional
factors
-
8/7/2019 AC Transmission Kundur
21/42
"St. Clair Curve""St. Clair Curve"
1539pkACT - 20
Figure 6.13 Transmission line loadability curve
-
8/7/2019 AC Transmission Kundur
22/42
Stability Limit Calculation for LineStability Limit Calculation for Line
LoadabilityLoadability
1539pkACT - 21
Figure 6.14 Steady state stability margin calculation
-
8/7/2019 AC Transmission Kundur
23/42
Factors Influencing Transfer of ActiveFactors Influencing Transfer of Active
and Reactive Powerand Reactive Power
Consider two sources connected by an inductive
reactance as shown in Figure 6.21.
representation of two sections of a power system
interconnected by a transmission system
a purely inductive reactance is consideredbecause impedances of transmission elements
are predominately inductive
effects of shunt capacitances do not appear
explicitly
1539pkACT - 22
Figure 6.21 Power transfer between two sources
(a) Equivalent system diagram
(b) Phasor diagram
= load angle
= power factor angle
-
8/7/2019 AC Transmission Kundur
24/42
The complex power at the receiving end is
Hence,
+=
==+=
jX
EjEEE
jX
EEEIEjQPS
RSSR
RSRRRRR
sincos
~~~~~~ *
X
EEEQ
X
EEP
RRSR
RSR
2cos
sin
=
=
(6.79)
(6.80)
1539pkACT - 23
,
Equations 6.79 to 6.82 describe the way in which
active and reactive power are transferred
Let us examine the dependence ofPand Qtransfer
on the source voltages, by considering separately
the effects of differences in voltage magnitudes and
angles
X
EEEQ
X
EEP
RSSS
RSS
cos
sin
2 =
=(6.81)
(6.82)
-
8/7/2019 AC Transmission Kundur
25/42
From Equations 6.79 to 6.82, we have
With ES> ER, QSand QRare positive
With ES< ER, QSand QRare negative
As shown in Fig. 6.22,
transmission of lagging current through an
inductive reactance causes a drop in receiving
end voltage
(a) Condition with = 0:
0== SR PP
( ) ( )X
EEEQ
X
EEEQ RSSS
RSRR
=
= ,
1539pkACT - 24
transmission of leading current through an
inductive reactance causes a rise in receiving
end voltage
Reactive power "consumed" in each case is
Figure 6.22 Phasor diagrams with = 0
( ) 22
XIX
EEQQ RS
RS=
=
(a) ES>ER (b) ER>ES
-
8/7/2019 AC Transmission Kundur
26/42
From Equations 6.79 to 6.82, we now have
With positive, PSand PRare positive, i.e., active
power flows from sending to receiving end
(b) Condition with ES= ERand
0
( )
2
2
2
2
1
cos1
sin
IX
X
EQQ
X
EPP
RS
SR
=
==
==
1539pkACT - 25
In each case, there is no reactive power transferredfrom one end to the other; instead, each end
supplies half ofQconsumed by X.
Figure 6.23 Phasor diagram with ES = ER
(b) < 0(a) > 0
-
8/7/2019 AC Transmission Kundur
27/42
We now have
If, in addition to X, we consider series resistance R
of the network, then
(c) General case applicable to any condition:
( ) 22
22 cos2
sincos
XIX
XI
X
EEEEQQ
jX
EjEEI
RSRSRS
RSS
==
+=
+=
(6.83)
(6.84)
1539pkACT - 26
The reactive power "absorbed" by Xfor all
conditions is X I2. This leads to the concept of
"reactive power loss", a companion term to active
power loss.
An increase in reactive power transmitted increases
active as well as reactive power losses. This has an
impact on efficiency and voltage regulation.
2
222
2
222
R
RRloss
R
RR
loss
E
QPRIRP
E
QP
XIXQ
+==
+
== (6.85)
(6.86)
-
8/7/2019 AC Transmission Kundur
28/42
Conclusions Regarding Transfer of Active andConclusions Regarding Transfer of Active and
Reactive PowerReactive Power
The active power transferred (PR) is a function ofvoltage magnitudes and . However, for satisfactoryoperation of the power system, the voltage magnitudeat any bus cannot deviate significantly from thenominal value. Therefore, control of active power
transfer is achieved primarily through variations inangle .
Reactive power transfer depends mainly on voltagemagnitudes. It is transmitted from the side with highervoltage magnitude to the side with lower voltagemagnitude.
1539pkACT - 27
Reactive power cannot be transmitted over longdistances, since it would require a large voltagegradient to do so.
An increase in reactive power transfer causes anincrease in active as well as reactive power losses.
Although we have considered a simple system, the general
conclusions are applicable to any practical system, In fact, the basic
characteristics of ac transmission reflected in these conclusions
have a dominant effect on the way in which we operate and control
the power system.
-
8/7/2019 AC Transmission Kundur
29/42
Appendix to Section on AC TransmissionAppendix to Section on AC Transmission
1. Copy of Section 6.4 from the book Power System
Stability and Control
provides background information related topower flow analysis techniques
1539pkACT - 28
-
8/7/2019 AC Transmission Kundur
30/42
1539pkACT - 29
-
8/7/2019 AC Transmission Kundur
31/42
1539pkACT - 30
-
8/7/2019 AC Transmission Kundur
32/42
1539pkACT - 31
-
8/7/2019 AC Transmission Kundur
33/42
1539pkACT - 32
-
8/7/2019 AC Transmission Kundur
34/42
1539pkACT - 33
-
8/7/2019 AC Transmission Kundur
35/42
1539pkACT - 34
-
8/7/2019 AC Transmission Kundur
36/42
-
8/7/2019 AC Transmission Kundur
37/42
1539pkACT - 36
-
8/7/2019 AC Transmission Kundur
38/42
1539pkACT - 37
-
8/7/2019 AC Transmission Kundur
39/42
1539pkACT - 38
-
8/7/2019 AC Transmission Kundur
40/42
1539pkACT - 39
-
8/7/2019 AC Transmission Kundur
41/42
1539pkACT - 40
-
8/7/2019 AC Transmission Kundur
42/42