ac transmission kundur

Upload: zasfaried

Post on 08-Apr-2018

253 views

Category:

Documents


7 download

TRANSCRIPT

  • 8/7/2019 AC Transmission Kundur

    1/42

    AC TRANSMISSIONAC TRANSMISSION

    1539pk

    Copyright P. KundurThis material should not be used without the author's consent

  • 8/7/2019 AC Transmission Kundur

    2/42

    Performance Equations and ParametersPerformance Equations and Parameters

    of Transmission Linesof Transmission Lines

    A transmission line is characterized by four

    parameters:

    series resistance (R) due to conductor resistivity

    shunt conductance (G) due to currents along

    insulator strings and corona; effect is small and

    usually neglected

    series inductance (L) due to magnetic field

    surrounding the conductor

    shunt capacitance (C) due to the electric field

    1539pkACT - 1

    between the conductors

    These are distributed parameters.

    The parameters and hence the characteristics of

    cables differ significantly from those of overhead

    lines because the conductors in a cable are

    much closer to each other

    surrounded by metallic bodies such as shields,

    lead or aluminum sheets, and steel pipes

    separated by insulating material such as

    impregnated paper, oil, or inert gas

  • 8/7/2019 AC Transmission Kundur

    3/42

    For balanced steady-state operation, the performance of

    transmission lines may be analyzed in terms of single-

    phase equivalents.

    Fig. 6.1 Voltage and current relationship of a distributed

    parameter line

    1539pkACT - 2

    The general solution for voltage and current at adistance x from the receiving end (see book: page 202)

    is:

    where

    (6.8)

    (6.9)

    xRCRxRCR eIZV

    eIZV

    V

    ++

    =2

    ~~

    2

    ~~~

    xR

    C

    R

    xR

    C

    R

    eI

    ZV

    eI

    ZV

    I

    +

    =2

    ~~

    2

    ~~

    ~

    jzy

    yzZC

    +==

    =

  • 8/7/2019 AC Transmission Kundur

    4/42

    The constant ZC is called the characteristic

    impedance and is called the propagation constant.

    The constants and ZCare complex quantities. The

    real part of the propagation constant is called theattenuation constant , and the imaginary part the

    phase constant .

    If losses are completely neglected,

    1539pkACT - 3

    )resistance(pure

    NumberReal== CLZC

    numberImaginary== j

  • 8/7/2019 AC Transmission Kundur

    5/42

    For a lossless line, Equations 6.8 and 6.9 simplify to

    When dealing with lightening/switching surges, HV

    lines are assumed to be lossless. Hence, ZC with

    losses neglected is commonly referred to as the surge

    impedance.

    The power delivered by a line when terminated by its

    (6.17)

    (6.18)

    xIjZxVV RCR sincos~~

    +=

    xZ

    VjxII

    C

    RR sin

    ~cos

    ~~

    +=

    1539pkACT - 4

    impedance load.

    where V0 is the rated voltage

    At SIL, Equations 6.17 and 6.18 further simplify to

    wattsZ

    VSIL

    C

    2

    0=

    x

    R

    x

    R

    eII

    eVV

    =

    =

    ~

    ~~(6.20)

    (6.21)

  • 8/7/2019 AC Transmission Kundur

    6/42

    Hence, for a lossless line at SIL,

    V and I have constant amplitude along the line

    V and I are in phase throughout the length of the line

    The line neither generates nor absorbs VARS

    As we will see later, the SIL serves as a convenientreference quantityfor evaluating and expressing line

    performance

    Typical values of SIL for overhead lines:

    1539pkACT - 5

    SIL (MW): 140 420 1000 2300

    Underground cables have higher shunt capacitance;

    hence, ZC is much smaller and SIL is much higher than

    those for overhead lines.

    for example, the SIL of a 230 kV cable is about

    1400 MW

    generate VARs at all loads

  • 8/7/2019 AC Transmission Kundur

    7/42

    Typical ParametersTypical Parameters

    Table 6.1 Typical overhead transmission line parameters

    Note: 1. Rated frequency is assumed to be 60 Hz

    1539pkACT - 6

    Table 6.2 Typical cable parameters

    2. Bundled conductors used for all lines listed, except for the 230 kV line.

    3. R, xL, and bC are per-phase values.4. SIL and charging MVA are three-phase values.

    * direct buried paper insulated lead covered (PILC) and high pressure pipe

    type (PIPE)

  • 8/7/2019 AC Transmission Kundur

    8/42

    Voltage Profile of a Radial Line at NoVoltage Profile of a Radial Line at No--LoadLoad

    With receiving end open, IR = 0. Assuming a

    lossless line from Equations 6.17 and 6.18, we have

    At the sending end (x = l),

    ( )

    ( ) ( )xsinZV~jI~xcosV

    ~V~

    CR

    R

    =

    =

    =

    =

    cosV~

    lcosV~

    E~

    R

    RS

    (6.31)

    (6.32)

    (6.33)

    1539pkACT - 7

    where = l. The angle is referred to as the

    electrical length or the line angle, and is expressed

    in radians.

    From Equations 6.31, 6.32, and 6.33

    (6.35)

    (6.36)

    =

    =

    cos

    xsin

    Z

    EjI

    cos

    xcosE~

    V~

    C

    S

    S

  • 8/7/2019 AC Transmission Kundur

    9/42

    As an example, consider a 300 km, 500 kV line with

    = 0.0013 rads/km, ZC = 250 ohms, and ES = 1.0 pu:

    Base current is equal to that corresponding to SIL.

    Voltage and current profiles are shown in Figure 6.5.

    The only line parameter, other than line length, thataffects the results of Figure 6.5 is . Since ispractically the same for overhead lines of all voltagelevels (see Table 6.1), the results are universally

    pu411.0I

    pu081.1V

    3.22

    rads39.00013.0x300

    S

    R

    =

    =

    =

    ==o

    1539pkACT - 8

    The receiving end voltage for different line lengths:

    - forl= 300 km, VR = 1.081 pu- forl= 600 km, VR = 1.407 pu- forl= 1200 km, VR = infinity

    Rise in voltage at the receiving end is because of

    capacitive charging current flowing through lineinductance.

    known as the "Ferranti effect".

  • 8/7/2019 AC Transmission Kundur

    10/42

    (a) Schematic Diagram

    1539pkACT - 9

    Figure 6.5 Voltage and current profiles for a 300 km lossless

    line with receiving end open-circuited

    (b) Voltage Profile

    (c) Current Profile

  • 8/7/2019 AC Transmission Kundur

    11/42

    VoltageVoltage -- Power CharacteristicsPower Characteristics

    of aof a Radial LineRadial Line

    Corresponding to a load ofPR+jQRat the receiving end, wehave

    Assuming the line to be lossless, from Equation 6.17

    with x = l

    Fig. 6.7 shows the relationship between VRand PRfor a300 km line with different loads and power factors.

    *~~

    R

    RRR

    V

    jQPI

    =

    +=

    *~sincos~~

    R

    RRCRS

    V

    jQPjZVE

    1539pkACT - 10

    e oa s norma ze y v ng R y 0, e na ura

    load (SIL), so that the results are applicable to overheadlines of all voltage ratings.

    From Figure 6.7 the following fundamental properties of actransmission are evident:

    a) There is an inherent maximum limit of power that can betransmitted at any load power factor. Obviously, therehas to be such a limit, since, with ESconstant, the only

    way to increase power is by lowering the loadimpedance. This will result in increased current, butdecreased VRand large line losses. Up to a certain pointthe increase of current dominates the decrease ofVR,thereby resulting in an increased PR. Finally, thedecrease in VRis such that the trend reverses.

  • 8/7/2019 AC Transmission Kundur

    12/42

    1539pkACT - 11

    Figure 6.7 Voltage-power characteristics of a 300 km

    lossless radial line

  • 8/7/2019 AC Transmission Kundur

    13/42

    VoltageVoltage -- Power CharacteristicsPower Characteristics

    of a Radial Lineof a Radial Line (cont'd)(cont'd)

    b) Any value of power below the maximum can be

    transmitted at two different values ofVR. The

    normal operation is at the upper value, within

    narrow limits around 1.0 pu. At the lower voltage,

    the current is higher and may exceed thermallimits. The feasibility of operation at the lower

    voltage also depends on load characteristics, and

    may lead to voltage instability.

    c) The load power factor has a significant influence

    1539pkACT - 12

    transmitted. This means that the receiving end

    voltage can be regulated by the addition of shunt

    capacitive compensation.

    Fig. 6.8 depicts the effect of line length:

    For longer lines, VR is very sensitive to variations

    in PR.

    For lines longer than 600 km ( > 45), VRatnatural load is the lower of the two values which

    satisfies Equation 6.46. Such operation is likely

    to be unstable.

  • 8/7/2019 AC Transmission Kundur

    14/42

    1539pkACT - 13

    Figure 6.8 Relationship between receiving end voltage,line length, and load of a lossless radial line

  • 8/7/2019 AC Transmission Kundur

    15/42

    VoltageVoltage--Power Characteristic of a LinePower Characteristic of a Line

    Connected to Sources at Both EndsConnected to Sources at Both Ends

    With ESand ERassumed to be equal, the following

    conditions exist:

    the midpoint voltage is midway in phase between

    ESand ER

    the power factor at midpoint is unity

    with PR>P0, both ends supply reactive power to the

    line; with PR

  • 8/7/2019 AC Transmission Kundur

    16/42

    Power Transfer and StabilityPower Transfer and Stability

    ConsiderationsConsiderations

    Assuming a lossless line, from Equation 6.17 with

    x = l, we can show that

    where = llll is the electrical length of line and is theangle by which ESleads ER, i.e. the load angle.

    IfES= ER= rated voltage, then the natural load is

    (6.51)sin

    sinC

    RSR

    Z

    EEP =

    C

    RSO

    Z

    EEP =

    1539pkACT - 15

    and Equation 6.51 becomes

    The above is valid for synchronous as well as

    asynchronous load at the receiving end.

    Fig. 6.10(a) shows the ---- PRrelationship for a 400 km

    line.

    For comparison, the Vm - PRcharacteristic of the line is

    shown in Fig. 6.10(b).

    sin

    sinO

    R

    PP =

  • 8/7/2019 AC Transmission Kundur

    17/42

    1539pkACT - 16

    Figure 6.10 PR- and Vm-PR characteristics of 400 km lossless

    line transmitting power between two large systems

  • 8/7/2019 AC Transmission Kundur

    18/42

    Reactive Power RequirementsReactive Power Requirements

    From Equation 6.17, with x = land ES= ER= 1.0, we canshow that

    Fig. 6.11 shows the terminal reactive powerrequirements of lines of different lengths as a functionofPR.

    Adequate VAR sources must be available at the twoends to operate with varying load and nearly

    ( )

    sin

    coscos2

    C

    S

    SR

    Z

    E

    QQ

    =

    =

    1539pkACT - 17

    cons an vo age.

    General Comments

    Analysis of transmission line performancecharacteristics presented above represents a highlyidealized situation

    useful in developing a conceptual understanding ofthe phenomenon

    dynamics of the sending-end and receiving-endsystems need to be considered for accurateanalysis.

  • 8/7/2019 AC Transmission Kundur

    19/42

    1539pkACT - 18

    Figure 6.11 Terminal reactive power as a function of power

    transmitted for different line lengths

  • 8/7/2019 AC Transmission Kundur

    20/42

    Loadability CharacteristicsLoadability Characteristics

    The concept of "line loadability" was introduced by

    H.P. St. Clair in 1953

    Fig. 6.13 shows the universal loadability curve for

    overhead uncompensated lines applicable to allvoltage ratings

    Three factors influence power transfer limits:

    thermal limit (annealing and increased sag)

    voltage drop limit (maximum 5% drop)

    1539pkACT - 19

    steady-state stability limit (steady-state stability

    margin of 30% as shown in Fig. 6.14)

    The "St. Clair Curve" provides a simple means of

    visualizing power transfer capabilities of transmission

    lines.

    useful for developing conceptual guides to

    preliminary planning of transmission systems

    must be used with some caution

    Large complex systems require detailed assessment

    of their performance and consideration of additional

    factors

  • 8/7/2019 AC Transmission Kundur

    21/42

    "St. Clair Curve""St. Clair Curve"

    1539pkACT - 20

    Figure 6.13 Transmission line loadability curve

  • 8/7/2019 AC Transmission Kundur

    22/42

    Stability Limit Calculation for LineStability Limit Calculation for Line

    LoadabilityLoadability

    1539pkACT - 21

    Figure 6.14 Steady state stability margin calculation

  • 8/7/2019 AC Transmission Kundur

    23/42

    Factors Influencing Transfer of ActiveFactors Influencing Transfer of Active

    and Reactive Powerand Reactive Power

    Consider two sources connected by an inductive

    reactance as shown in Figure 6.21.

    representation of two sections of a power system

    interconnected by a transmission system

    a purely inductive reactance is consideredbecause impedances of transmission elements

    are predominately inductive

    effects of shunt capacitances do not appear

    explicitly

    1539pkACT - 22

    Figure 6.21 Power transfer between two sources

    (a) Equivalent system diagram

    (b) Phasor diagram

    = load angle

    = power factor angle

  • 8/7/2019 AC Transmission Kundur

    24/42

    The complex power at the receiving end is

    Hence,

    +=

    ==+=

    jX

    EjEEE

    jX

    EEEIEjQPS

    RSSR

    RSRRRRR

    sincos

    ~~~~~~ *

    X

    EEEQ

    X

    EEP

    RRSR

    RSR

    2cos

    sin

    =

    =

    (6.79)

    (6.80)

    1539pkACT - 23

    ,

    Equations 6.79 to 6.82 describe the way in which

    active and reactive power are transferred

    Let us examine the dependence ofPand Qtransfer

    on the source voltages, by considering separately

    the effects of differences in voltage magnitudes and

    angles

    X

    EEEQ

    X

    EEP

    RSSS

    RSS

    cos

    sin

    2 =

    =(6.81)

    (6.82)

  • 8/7/2019 AC Transmission Kundur

    25/42

    From Equations 6.79 to 6.82, we have

    With ES> ER, QSand QRare positive

    With ES< ER, QSand QRare negative

    As shown in Fig. 6.22,

    transmission of lagging current through an

    inductive reactance causes a drop in receiving

    end voltage

    (a) Condition with = 0:

    0== SR PP

    ( ) ( )X

    EEEQ

    X

    EEEQ RSSS

    RSRR

    =

    = ,

    1539pkACT - 24

    transmission of leading current through an

    inductive reactance causes a rise in receiving

    end voltage

    Reactive power "consumed" in each case is

    Figure 6.22 Phasor diagrams with = 0

    ( ) 22

    XIX

    EEQQ RS

    RS=

    =

    (a) ES>ER (b) ER>ES

  • 8/7/2019 AC Transmission Kundur

    26/42

    From Equations 6.79 to 6.82, we now have

    With positive, PSand PRare positive, i.e., active

    power flows from sending to receiving end

    (b) Condition with ES= ERand

    0

    ( )

    2

    2

    2

    2

    1

    cos1

    sin

    IX

    X

    EQQ

    X

    EPP

    RS

    SR

    =

    ==

    ==

    1539pkACT - 25

    In each case, there is no reactive power transferredfrom one end to the other; instead, each end

    supplies half ofQconsumed by X.

    Figure 6.23 Phasor diagram with ES = ER

    (b) < 0(a) > 0

  • 8/7/2019 AC Transmission Kundur

    27/42

    We now have

    If, in addition to X, we consider series resistance R

    of the network, then

    (c) General case applicable to any condition:

    ( ) 22

    22 cos2

    sincos

    XIX

    XI

    X

    EEEEQQ

    jX

    EjEEI

    RSRSRS

    RSS

    ==

    +=

    +=

    (6.83)

    (6.84)

    1539pkACT - 26

    The reactive power "absorbed" by Xfor all

    conditions is X I2. This leads to the concept of

    "reactive power loss", a companion term to active

    power loss.

    An increase in reactive power transmitted increases

    active as well as reactive power losses. This has an

    impact on efficiency and voltage regulation.

    2

    222

    2

    222

    R

    RRloss

    R

    RR

    loss

    E

    QPRIRP

    E

    QP

    XIXQ

    +==

    +

    == (6.85)

    (6.86)

  • 8/7/2019 AC Transmission Kundur

    28/42

    Conclusions Regarding Transfer of Active andConclusions Regarding Transfer of Active and

    Reactive PowerReactive Power

    The active power transferred (PR) is a function ofvoltage magnitudes and . However, for satisfactoryoperation of the power system, the voltage magnitudeat any bus cannot deviate significantly from thenominal value. Therefore, control of active power

    transfer is achieved primarily through variations inangle .

    Reactive power transfer depends mainly on voltagemagnitudes. It is transmitted from the side with highervoltage magnitude to the side with lower voltagemagnitude.

    1539pkACT - 27

    Reactive power cannot be transmitted over longdistances, since it would require a large voltagegradient to do so.

    An increase in reactive power transfer causes anincrease in active as well as reactive power losses.

    Although we have considered a simple system, the general

    conclusions are applicable to any practical system, In fact, the basic

    characteristics of ac transmission reflected in these conclusions

    have a dominant effect on the way in which we operate and control

    the power system.

  • 8/7/2019 AC Transmission Kundur

    29/42

    Appendix to Section on AC TransmissionAppendix to Section on AC Transmission

    1. Copy of Section 6.4 from the book Power System

    Stability and Control

    provides background information related topower flow analysis techniques

    1539pkACT - 28

  • 8/7/2019 AC Transmission Kundur

    30/42

    1539pkACT - 29

  • 8/7/2019 AC Transmission Kundur

    31/42

    1539pkACT - 30

  • 8/7/2019 AC Transmission Kundur

    32/42

    1539pkACT - 31

  • 8/7/2019 AC Transmission Kundur

    33/42

    1539pkACT - 32

  • 8/7/2019 AC Transmission Kundur

    34/42

    1539pkACT - 33

  • 8/7/2019 AC Transmission Kundur

    35/42

    1539pkACT - 34

  • 8/7/2019 AC Transmission Kundur

    36/42

  • 8/7/2019 AC Transmission Kundur

    37/42

    1539pkACT - 36

  • 8/7/2019 AC Transmission Kundur

    38/42

    1539pkACT - 37

  • 8/7/2019 AC Transmission Kundur

    39/42

    1539pkACT - 38

  • 8/7/2019 AC Transmission Kundur

    40/42

    1539pkACT - 39

  • 8/7/2019 AC Transmission Kundur

    41/42

    1539pkACT - 40

  • 8/7/2019 AC Transmission Kundur

    42/42