![Page 1: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/1.jpg)
LOCATION MAPNN
VICINITY MAP
CD
BA
1 2 3 4 5G001
COVER SHEET
ABC COMMISSION WAREHOUSEELECTRICAL IMPROVEMENTS
JOB ORDER # 4059
SCO ID # 19-21377-01A
400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
ARCHITECT/ENGINEERS OF RECORD
ELECTRICAL WILLIAM STEVENS (919) 324-1258
ARCHITECTJOHN BIGGS (919) 324-1263
DRAWING INDEX
REV. GENERAL
G001 COVER SHEET
G002 BUILDING DATA
ELECTRICAL
E001 ELECTRICAL GENERAL NOTES, ABBREVIATIONS & SYMBOL LEGEND
E101 PARTIAL FLOOR PLAN
E102 PARTIAL FLOOR PAN
E401 FLOOR PLAN & DISTRIBUTION RISER DIAGRAM
E501 DETAILS
E502 DETAILS
E601 SCHEDULES
JO4059-G001
JB
JB
JB
#
PAGE
N
#
####ROOM NAME
PAGE#
A
1111A
SYMBOLS LEGEND
ELEVATION SYMBOL
SECTION SYMBOL
NORTH ARROW
ROOM NAME AND NUMBER
ELEVATION MARKER
KEYED NOTE MARKER
REVISION MARKER
WINDOW TYPE
DOOR NUMBER
WHERE THEELEVATION IS
LOCATED
WHERE THESECTION IS
LOCATED
1234567
A PARTITION TYPE
1
2
3
4 ROOM FINISH INDICATOR
13895
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
![Page 2: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/2.jpg)
2018 APPENDIX B
BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS
(EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)
Name of Project: _______________________________________________________________________
Address: _______________________________________________________ Zip Code _____________
Owner/Authorized Agent: _____________ Phone # _____________
Owned By: City/County
Code Enforcement Jurisdiction: City____________
Private
County_________
E-Mail ________________________
State
State
CONTACT: ___________________________________________________________________________
DESIGNER FIRM
Architectural
Civil
Electrical
Fire Alarm
Plumbing
Mechanical
NAME LICENSE # TELEPHONE # E-MAIL
___________________ ____________ _________ ____________ _________________
___________________ ____________ _________ ____________ _________________
___________________ ____________ _________ ____________ _________________
___________________ ____________ _________ ____________ _________________
___________________ ____________ _________ ____________ _________________
___________________ ____________ _________ ____________ _________________
Sprinkler-Standpipe ________________ ____________ _________ ____________ _________________
Structural ___________________ ____________ _________ ____________ _________________
___________________ ____________ _________ ____________ _________________
New Building
Addition
Shell/Core 1st Time Interior Completions
2018 NC EXISTING BUILDING CODE:
(check all that apply)
CONSTRUCTED: (date) __________
(date) __________RENOVATED:
BASIC BUILDING DATA
Construction Type:
(check all that apply)
Sprinklers:
Standpipes:
No
Primary Fire District:
FLOOR
3rd Floor
2nd Floor
Mezzanine
1st Floor
Basement
TOTAL
Historic Property
Change of Use
Retaining Walls >5' High ____________ ____________ _________ ____________ _________________
Other
(“Other” should include firms and individuals such as truss, precast, pre-engineered, interior designers, etc.)
2018 NC BUILDING CODE:
Prescriptive
Repair
Chapter 14
Phased Construction – Shell Core
Alteration Level I
Alteration Level II
Alteration Level III
CURRENT OCCUPANCY(S) (Ch. 3): _________________
PROPOSED OCCUPANCY(S) (Ch. 3): _______________
OCCUPANCY CATEGORY (Table 1604.5): Current: __________
I-A
I-B
Partial
No Class
No
Special Inspections Required:
I
Yes
No
EXISTING (SQ FT)
II-A
II-B
NFPA 13
II
Yes
GROSS BUILDING AREA TABLE
NEW (SQ FT)SUB-TOTAL
III-A
III-B
NFPA 13R
III Wet Dry
Flood Hazard Area: No Yes
Proposed: __________
IV
NFPA 13D
V-A
V-B
ALLOWABLE AREA
Primary Occupancy Classification(s):
Assembly A-1
Business
Educational
Factory
Hazardous
Institutional
I-1 Condition
I-2 Condition
I-3 Condition
Mercantile
Residential
Storage
R-1
S-1 Moderate
Parking Garage
Utility and Miscellaneous
Accessory Occupancy Classification(s):
Incidental Uses (Table 509):
This separation is not exempt as a Non-Separated Use (see exceptions).
Special Uses (Chapter 4 – List Code Sections):
Special Provisions: (Chapter 5 – List Code Sections):
Mixed Occupancy:
Allowable Area of Occupancy A
+
STORY
NO.
DESCRIPTION AND
USE
(A)
BLDG AREA PER
STORY (ACTUAL)
Separation: Exception: ___________________
Select one
Actual Area of Occupancy A + Actual Area of Occupancy B
Allowable Area of Occupancy B
_____________________ + …… = ___________
(B)
TABLE 506.24
AREA
(C)
AREA FOR FRONTAGE
INCREASE1,5
(D)
ALLOWABLE AREA PER
STORY OR UNLIMITED2,3
< 1.00
< 1
F-1 Moderate
H-1 Detonate
I-1
1
1
1
2
2
2
A-2
F-2 Low
H-2 Deflagrate
I-2
3
R-2
Open
4
H-3 Combust
I-3
5
R-3
S-2 Low
Enclosed
R-4
High-piled
Repair Garage
H-4 Health
I-4
H-5 HPM
A-3 A-4 A-5
1 Frontage area increases from Section 506.2 are computed thus:
a. Perimeter which fronts a public way or open space having 20 feet minimum width = _______ (F)
b. Total Building Perimeter = ________ (P)
c. Ratio (F/P) = ___________ (F/P)
d. W = Minimum width of public way = ________ (W)
2 Unlimited area applicable under conditions of Section 507.
3 Maximum Building Area = total number of stories in the building x D (maximum3 stories) (506.2).
4 The maximum area of open parking garages must comply with Table 406.5.4. The maximum area of air
traffic control towers must comply with Table 412.3.1.
5 Frontage increase is based on the unsprinklered area value in Table 506.2.
ALLOWABLE HEIGHT
ALLOWABLE
Building Height in Feet (Table 504.3)
Building Height in Stories (Table 504.4)
1 Provide code reference if the “Shown on Plans” quantity is not based on Table 504.3 or 504.4.
FIRE PROTECTION REQUIREMENTS
BUILDING ELEMENT
FIRE
SEPARATION
DISTANCE
(FEET)
Structural Frame,
including columns, girders,
trusses
Bearing Walls
Exterior
North
East
West
South
Interior
Nonbearing Walls and
Partitions
Exterior walls
North
East
West
South
Interior walls and partitions
Floor Construction
Including supporting beams
and joists
Floor Ceiling Assembly
Columns Supporting Floors
Roof Construction, including
supporting beams and joists
Roof Ceiling Assembly
Columns Supporting Roof
Shaft Enclosures - Exit
Shaft Enclosures - Other
Corridor Separation
Occupancy/Fire Barrier Separation
Party/Fire Wall Separation
Smoke Barrier Separation
Smoke Partition
Tenant/Dwelling Unit/
Sleeping Unit Separation
Incidental Use Separation
* Indicate section number permitting reduction
REQ'D
RATING
PROVIDED
(W/_________*
REDUCTION)
DETAIL #
AND
SHEET #
DESIGN #
FOR
RATED
ASSEMBLY
SHEET # FOR
RATED
PENETRATION
SHEET #
FOR
RATED
JOINTS
SHOWN ON PLANS CODE REFERENCE
PERCENTAGE OF WALL OPENING CALCULATIONS
FIRE SEPARATION DISTANCE
(FEET) FROM PROPERTY LINES
DEGREE OF OPENINGS
PROTECTION
(TABLE 705.8)
ALLOWABLE AREA
(%)
ACTUAL SHOWN ON PLANS
(%)
LIFE SAFETY SYSTEM REQUIREMENTS
Emergency Lighting:
Exit Signs:
Fire Alarm:
Smoke Detection Systems:
Carbon Monoxide Detection:
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
LIFE SAFETY PLAN REQUIREMENTS
Life Safety Plan Sheet #: _____________________
Fire and/or smoke rated wall locations (Chapter 7)
Assumed and real property line locations (if not on the site plan)
Exterior wall opening area with respect to distance to assumed property lines (705.8)
Occupancy Use for each area as it relates to occupant load calculation (Table 1004.1.2)
Occupant loads for each area
Exit access travel distances (1017)
Common path of travel distances (Tables 1006.2.1 & 1006.3.2(1))
Dead end lengths (1020.4)
Clear exit widths for each exit door
Maximum calculated occupant load capacity each exit door can accommodate based on egress width (1005.3)
Actual occupant load for each exit door
A separate schematic plan indicating where fire rated floor/ceiling and/or roof structure is provided for
purposes of occupancy separation
Location of doors with panic hardware (1010.1.10)
Location of doors with delayed egress locks and the amount of delay (1010.1.9.7)
Location of doors with electromagnetic egress locks (1010.1.9.9)
Location of doors equipped with hold-open devices
Location of emergency escape windows (1030)
The square footage of each fire area (202)
The square footage of each smoke compartment for Occupancy Classification I-2 (407.5)
Note any code exceptions or table notes that may have been utilized regarding the items above
ACCESSIBLE DWELLING UNITS
(SECTION 1107)
TOTAL
UNITS
ACCESSIBLE
UNITS
REQUIRED
ACCESSIBLE
UNITS
PROVIDED
TYPE A
UNITS
REQUIRED
TYPE A
UNITS
PROVIDED
TYPE B
UNITS
REQUIRED
TYPE B
UNITS
PROVIDED
TOTAL
ACCESSIBLE UNITS
PROVIDED
ACCESSIBLE PARKING
(SECTION 1106)
LOT OR PARKING
AREA
TOTAL # OF PARKING SPACES
REQUIRED
PROVIDED REGULAR WITH
5' ACCESS AISLE
# OF ACCESSIBLE SPACES PROVIDED
VAN SPACES WITH
132” ACCESS
AISLE
8' ACCESS
AISLE
TOTAL #
ACCESSIBLE
PROVIDED
TOTAL
PLUMBING FIXTURE REQUIREMENTS
(TABLE 2902.1)
USE
SPACE EXIST’G
NEW
REQ’D
WATERCLOSETS
MALE FEMALE UNISEX
URINALS LAVATORIES
MALE FEMALE UNISEX
SHOWERS
/ TUBS
DRINKING FOUNTAINS
REGULAR ACCESSIBLE
SPECIAL APPROVALS
Special approval: (Local Jurisdiction, Department of Insurance, OSC, DPI, DHHS, etc., describe below)
_____________________________________________________________________________________
_____________________________________________________________________________________
ENERGY SUMMARY
ENERGY REQUIREMENTS:
Existing building envelope complies with code: .
Exempt Building: . Provide code or statutory reference:
Climate Zone: .
Method of Compliance: .
(If “Other” specify source here) .
THERMAL ENVELOPE (Prescriptive method only)
Roof/ceiling Assembly (each assembly)
Description of assembly: .
U-Value of total assembly: .
R-Value of insulation: .
______________________________
___________
___________
Skylights in each assembly: ___________
U-Value of skylight: ___________
total square footage of skylights in each assembly: .
Exterior Walls (each assembly)
Description of assembly: .
U-Value of total assembly: .
R-Value of insulation: .
___________
______________________________
___________
___________
Openings (windows or doors with glazing)
U-Value of assembly: .
Door R-Values: .
Walls below grade (each assembly)
Description of assembly: .
U-Value of total assembly: .
R-Value of insulation: .
___________
Solar heat gain coefficient: ___________
projection factor: .___________
___________
______________________________
___________
___________
Floors over unconditioned space (each assembly)
Description of assembly: .
U-Value of total assembly: .
R-Value of insulation: .
Floors slab on grade
Description of assembly: .
U-Value of total assembly: .
R-Value of insulation: .
______________________________
___________
___________
______________________________
___________
___________
Horizontal/vertical requirement: ___________
slab heated: .___________
.
.
.
.
The following data shall be considered minimum and any special attribute required to meet the energy code
shall also be provided. Each Designer shall furnish the required portions of the project information for the
plan data sheet. If performance method, state the annual energy cost for the standard reference design vs
annual energy cost for the proposed design.
ABC COMMISSION WAREHOUSE POWER IMPROVEMENTS
400 EAST TRYON ROAD, RALEIGH, NC 28347
. .
NCDPS
.
NCDPS
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
13895
.
041481
.
.
.
.
.
.
.
.
.
.
.
.
.
324-1263
.
324-1282
.
.
.
.
.
.
1983
N/A
H-3
H-3
IIII
. . .
. . .
. . .
200,000 0 200,000
. . .
200,000 0 200,000
OFFICE/ADMIN AREAS
.
.
.
. . .
. . .
1
.
.
.
WAREHOUSE
.
.
.
200,000
.
.
.
14,000
.
.
.
10,500
.
.
.
24,500
.
.
.
1800 LF
1800 LF
1
30 FT
55 FT
2 STORIES
22 FT AT EAVES
1 STORY
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
. . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
. . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
JOHN BIGGS
WILLIAM STEVENS
N/A - ALTERATION LEVEL 2
NO CHANGE TO FIRE PROT REQMTS
N/A - ALTERATION LEVEL 2
NO CHANGE TO LIFE SAFETY
SYSTEM REQUIREMENTS
N/A - ALTERATION LEVEL 2
NO CHANGE TO LIFE SAFETY
PLAN REQUIREMENTS
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
N/A - ALTERATION LEVEL 2
. . . ..
CD
BA
1 2 3 4 5
BUILDING DATA
G002
JB
JB
JB
13895
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
JO4059-G001
![Page 3: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/3.jpg)
HEAT DETECTOR, 135° UON
GC
UON UNLESS OTHERWISE NOTED
GENERAL CONTRACTOR
HP
HZHTRHRHPF
HIDHHHOAGRSGEC
TRANSFORMER
WATTS,WIREVOLT AMPHERE(S)
UNINTERRUPTABLE POWER SUPPLY
GROUNDING ELECTRODE CONDUCTOR
HORSEPOWERHIGH POWER FACTOR
HERTZHEATERHOUR
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTOMATICGALVANIZED RIGID STEEL
HANDHOLE
XFMR
WVAVUPS
VOLTS
G,GND
EX, (E), EXIST
AWG
FTFLUORFLRFLAFIXTFACUF°
EWC
ENGEMTELECECDWGDNDISCDEGDC
ARCH
C/B
CUCTCKT
CC°BLDGBFGBFC
ATS
ALAICAFGAFF
AASD
UNDERWRITERS LABORATORIES
TO BE DETERMINEDSWITCHGEARSWITCHBOARD
SQUARE FEETSERVICE ENTRANCERECEPTACLE(S)POLYVINYL CHLORIDEPANELBOARD
ON CENTERNOT TO SCALENORMALLY OPEN
NATIONAL ELECTRICAL CODENORMALLY CLOSEDNON APPLICABLEMANUAL TRANSFER SWITCHMOUNTED
ØPH, PHASE
FIRE ALARM CONTROL UNIT (PANEL)
FLUORESCENT
GROUNDFEET
FLOORFULL LOAD AMPS
FAHRENHEIGHT
FIXTURE
EXISTING
SWGRSWBD
UL
TBD
SW SWITCH
RECEPT(S)
SFSE
PVCPNL
ELECTRICAL METALLIC TUBING
ELECTRIC WATER COOLER
ELECTRIC/ELECTRICAL
ENGINEER
ELECTRICAL CONTRACTOR
DISCONNECT
DIRECT CURRENT
DRAWINGDOWN
DEGREES
NO
POCNTS
POLE
N/A
NECNC
MTSMTD
MISCELLANEOUSMANHOLEMANUFACTUREDMECHANICALMECHANICAL CONTRACTORLIGHTINGLIGHT(S)LIGHT EMITTING DIODEKILOWATT HOUR(S)KILOWATT(S)KILOVOLT AMPHERE(S)KILOVOLT(S)THOUSAND CIRCULAR MILS(KILO) THOUSANDJUNCTION BOXINCANDESCENTINTERMEDIATE METAL CONDUIT
KW
ARCHITECTAUTOMATIC TRANSFER SWITCH
CIRCUIT BREAKER
CURRENT TRANSFORMERCOPPER
CIRCUIT
CELSIUS
BELOW FINISHED GRADEBELOW FINISHED CEILING
CONDUIT
BUILDING
MISC
MECH
MHMFG
LT(S)
KWH
MCLTG
LED
AMPERES INTERRUPTING CAPACITYABOVE FINISHED GRADEABOVE FINISHED FLOOR
AMERICAN WIRE GUAGE
ALUMINUM
AMPEREADJUSTABLE SPEED DRIVE
KCMIL
INCAND
KVAKV
KJB
IMC
SMOKE DETECTOR
PAGING SPEAKER, MOUNTING HEIGHTS AS PER PLANS
A. ALL EQUIPMENT AND MATERIALS SHALL BE NEW AND LISTED FOR THE APPLICATION.THIRD PARTY AGENCIES SHALL BE AMONGST THOSE ACCREDITED BY THE NORTHCAROLINA BUILDING CODE (NCBCC) TO LABEL ELECTRICAL AND MECHANICALEQUIPMENT.
B. ALL CONDUCTORS SHALL BE MINIMALLY SIZED PER THE 75 DEGREE CELSIUS TABLES INTHE NEC. ADJUST TO THE HIGHER RATING WHERE RECOMMENDED BY EQUIPMENTMANUFACTURER.
C. ALL CONDUCTORS SHALL BE INSTALLED IN APPROVED RACEWAYS. MINIMUM CONDUITSIZE SHALL BE 3/4 INCH.
D. SIZE ALL CONDUITS AND RACEWAYS PER THE THHN/THWN INSULATION TABLES IN THENEC. RESIZE CONDUITS WHERE THICKER CONDUCTOR INSULATION IS USED.
E. PROVIDE AN NEC SIZED GROUND WIRE IN ALL POWER CIRCUITS.
F. ALL ITEMS USED AS SERVICE ENTRACE EQUIPMENT SHALL BE LISTED AND LABELEDFOR THAT PURPOSE.
G. THE STATE CONSTRUCTION OFFICE (SCO) IS THE AUTHORITY HAVING JURISDICTIONFOR THE ELECTRICAL INSPECTIONS ON THIS PROJECT. NOTIFY THE STATE PROPERTYELECTRICAL INSPECTORS IN THE CONSTRUCTION ADMINISTRATION SECTION OF THESCO TO SCHEDULE THE REQUIRED ROUGH-IN, ABOVE CEILING AND FINALINSPECTIONS. NO WORK IS TO BE COVERED UP UNTIL AFTER THE INSPECTION HASBEEN COMPLETED AND APPROVED BY AN AUTHORIZED SCO INSPECTOR. ALLELECTRICAL INSPECTIONS WITH THE SCO ELECTRICAL INSPECTOR SHALL BESCHEDULED FOR MONDAY THROUGH FRIDAY UNLESS SPECIFICALLY EXEMPTED ANDAPPROVED BY SCO.
H. POWER PHASE CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS:
120/240 VOLT 208/120 VOLT 480/277 VOLT1 PHASE SYSTEMS 3 PHASE SYSTEM 3 PHASE SYSTEM
PHASE A BLACK BLACK BROWNPHASE B RED RED ORANGEPHASE C N/A BLUE YELLOWNEUTRAL WHITE WHITE GREY
I. INSTALL DETECTABLE WARNING TAPE 6" BELOW GRADE FOR ALL UNDERGROUNDCONDUIT.
4" - 12"
CEILING
NEVER HERE
ACCEPTED HERE
WALL MOUNTEDSMOKE / HEATDETECTOR
CEILINGMOUNTEDSMOKE /HEATDETECTOR
FIRE
FOR CEILINGHEIGHTS LESS THAN
86", THE VISUALLENS MOUNTINGHEIGHT SHALL BEWITHIN 6" OF THE
CEILINGAUDIBLE /VISUAL ANDVISUAL ONLYDEVICES
96" MAXNFPA)
80" (ADA)80" MIN (NFPA)
REF. 80" MIN (IBC)REF. 96" MAX (IBC)
FINISHEDFLOOR
FIRE
48" MAX (ADA)
FINISHEDWALL
TO EXIT DOOR5'-0" MAX
MANUALPULLSTATION
MAGNETICDOORHOLDER
DOORWIDTHLESS 3"
6"
NOTE:MEASUREMENTSSHOWN ARE TOTHE CLOSESTEDGE OF THEDETECTOR.
3' -0" MINWEATHERPROOFWP
DEVICE WITH THIS SUBSCRIPT INDICATES WIRE GUARDWG
FIRE ALARM AUDIO/VISUAL UNIT, SUBSCRIPTINDICATES CANDELA RATING
FIRE ALARM VISUAL ONLY UNIT, SUBSCRIPTINDICATES CANDELA RATING
FIRE ALARM MANUAL PULL STATION
FIRE ALARM CONTROL UNIT (PANEL)
FIRE ALARM ANNUNCIATOR PANEL
DUCT DETECTOR
FLOW SWITCH
TAMPER SWITCH
REMOTE ALARM INDICATOR LIGHT WITH KEYEDTEST SWITCH
DOOR HOLDER
EVENT PRINTER
VOICE/DATA OUTLET, SUBSCRIPT INDICATES CONFIGURATION
LIGHT LINEWEIGHT INDICATES EXISTING UON
ON DEMOLITION PLANS, HEAVY DASHED LINEWEIGHTINDICATES EXISTING TO BE REMOVED UON
HEAVY SOLID LINEWEIGHT INDICATES NEW TO BEPROVIDED UON
DRAWING NOTE
A
a
INDICATESFIXTURE TYPE
INDICATES SWITCHINGDESIGNATION
12
INDICATES CIRCUIT
CEILING MOUNTED LUMINAIRE
WALL OR CEILING MOUNTED LINEAR LUMINAIRE
EMERGENCY LUMINAIRE
ROUND, CEILING MOUNTED LUMINAIRE, SIZE AS SHOW ON PLANSAND AS SCHEDULED
TRACK LIGHTING, PROVIDE NUMBER OF LIGHTING HEADS ASINDICATED
EXIT LIGHT, BATTERY POWERED, UON. SHADED QUADRANTSINDICATE FACES. CONNECT TO LOCAL LIGHTING CIRCUIT AHEADOF SWITCHING. ARROWS INDICATE DIRECTION ARROWS.
EMERGENCY BATTERY LUMINAIRE, WALL MOUNTED, 90MINUTES BATTERY POWERED. CONNECT TO LOCAL LIGHTINGCIRCUIT AHEAD OF SWITCHING/CONTROLS UON.
POLE-MOUNTED SITE LUMINAIRE
REMOTE MOUNTED EMERGENCY LIGHTING HEADS
ENCLOSED CIRCUIT BREAKER DISCONNECT SWITCH,CURRENT RATING/FUSE SIZE
PANELBOARD (PANEL)
COMBINATION STARTER
UTILITY POLE
JUNCTION BOX
DUPLEX RECEPTACLE, NEMA 5-20R
DUPLEX RECEPTACLE, NEMA 5-20RSUBSCRIPT INDICATES SECURITY WALL PLATE
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE. NEMA 5-20R,WITH COMMUNICATION/DATA CAPABILITY
SPECIAL PURPOSE RECEPTACLE, FOR ELECTRICAL EQUIPMENT.REFER TO PLANS FOR NEMA CONFIGURATION.
FACTORY WIRED PLUGMOLD
LUMINAIRE SYMBOLS: REFER TO LUMINAIRE SCHEDULE FOR ADDITIONALREQUIREMENTS. LETTER DESIGNATES TYPE.
CADWELD CONNECTION
GROUND TEST WELL
AIR TERMINAL, 1/2" DIAMETER, 12" LONG, ALUMINUM, TAPERED POINT
DOWN CONDUCTOR, CLASS I, COPPER, 29 STRAND, 17 GUAGE, COPPER WIRE
GROUND PIGTAIL
LIGHTNING CONDUCTOR CONNECTION
TRIP ELEMENTS - ELECTRONIC TRIP UNITL - LONG TIMES - SHORT TIME
I - INSTANTANEOUSG - GROUND FAULT
G
TRANSIENT VOLTAGE SURGE SUPPRESSOR
CHANGE IN ELEVATION, LIGHTNING CONDUCTOR
HOMERUN - NUMBER OF ARROWS EQUALS NUMBEROF INDIVIDUAL CIRCUITS. PROVIDE 20-1P BREAKERWITH 2-#12,1-#12G EACH IN 3/4"C TO PANEL ASINDICATED MINIMUM, UON
SINGLE-POLE WALL SWITCH
3-WAY WALL SWITCH
4-WAY WALL SWITCH
DIMMER SWITCH, TYPE SHALL MATCH LUMINAIRES BEINGCONTROLLED
SINGLE-POLE WALL SWITCH WITH PILOT LIGHT (LIT WHENIN THE ON POSITION)
SINGLE-POLE MOTOR RATED SWITCH. A "2"SUBSCRIPT INDICATES A 2-POLE SWITCH.
WALL SWITCH, SUBSCRIPT INDICATESASSOCIATED LUMINAIRES BEING CONTROLLED.PROVIDE A SEPARATE SWITCH FOR EACHSUBSCRIPT LETTER INDICATED.
PHOTOCELL
GROUND BAR
GROUND LOOP
GROUND ROD, 10' LONG, 3/4" DIAMETER
4" MIN.
A/CSUPPLY
ORRETURN
DIFFUSER
48"42" MIN / 54"MAX (NFPA)
LIGHTSWITCH
18"UON
RECEPTACLE
MAXIMUM CODEALLOWED HEIGHT6'-7" HIGHESTSWITCH ORBREAKER
SAFETY SWITCH,STARTER ORCIRCUITBREAKER
SCALE: NONE
TYPICAL EQUIPMENT AND WIRING DEVICE MOUNTING HEIGHTSA1
E002
800A LSIG CIRCUIT BREAKER WITH ASSOCIATED AMPACITY ANDFEATURES
DUPLEX RECEPTACLE, NEMA 5-20RSUBSCRIPT INDICATES THE FOLLOWING:
S SECURITY WALL PLATEGFI GROUND FAULT CIRCUIT INTERRUPTERWP GROUND FAULT CIRCUIT INTERRUPTER
WITH WEATHERPROOF COVERPED GROUND FAULT CIRCUIT INTERRUPTER MOUNTED
IN WEATHER-PROOF POWER PEDESTALH HOSPITAL GRADEEWC ELECTRIC WATER COOLER. WIRE TO GFCI
BREAKERIG ISOLATED GROUNDAC ABOVE COUNTER
WALL MOUNTED SCONCE TYPE LUMINAIRE
INDICATES DISTRIBUTION EQUIPMENTFAULT CURRENT RATING
INDICATES FAULT CURRENTAVAILABLE AT THE EQUIPMENT
ER EXISTING TO BE RELOCATED
NIGHT LIGHTNL
DISCONNECT SWITCH - HEAVY DUTY, UNFUSEDWITH CURRENT RATING
AUTOMATIC TRANSFER SWITCH - BYPASS ISOLATION TYPE
GROUND
PANELBOARD - WITH MAIN LUGS ONLY
PANELBOARD - WITH MAIN CIRCUIT BREAKER
TRANSFORMER
AUTOMATIC TRANSFER SWITCH
28,269A
42,000A
ADJUSTABLE SPEED DRIVE (VFD)
ENCLOSED CIRCUIT BREAKER
FUSED SAFETY SWITCH
3'-8"MAX.
ABOVECOUNTERDEVICE
EXIT
6'-3"
EXIT SIGN PREFERREDLOCATION IS ABOVETHE DOOR, ALTERNATELOCATION AS SHOWN
ELECTRICAL SYMBOLS LEGEND
ELECTRICAL DIAGRAM SYMBOLS LEGEND
ELECTRICAL DRAWING PRESENTATION
COMMUNICATIONS SYMBOLS LEGEND
GENERAL ELECTRICAL NOTES: ABBREVIATIONSFIRE ALARM SYMBOLS LEGEND
S
GFI
A
B
D
F
X1
EMB-1
ER
30A
30A/20A
3
4
J
ASD
D
P
M
a,b
PC
TVSS
E N
L
E L N
S
H
F
15CD
F
15CD
F
RAIL
FACU
FAA
DD
DH
TS
FS
PRINTER
SP
a
1
HANDHOLEHH
UNDERGROUNDUG
ELECTRICAL GENERALNOTES, ABBREVIATIONS &
SYMBOL LEGEND
E001
JO4059-E001SYMBOLS LIST
WWS
WWS
WWS
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
![Page 4: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/4.jpg)
PANEL 'PP-7'
MOUNT AT 48" AFF(TYPICAL)
PROPOSED ROUTING,SAWCUT/TRENCH ASREQUIRED. REPAIR TOMATCH EXISTINGCONDITIONS
T
PANEL 'PP-8'
T
MA
TC
HLI
NE
MA
TC
HLI
NE
T
16 17 18 4 5 6 7 8 9 11
10,11,12,PP-8
7,8,9,PP-8
4,5,6,PP-8
1,2,3,PP-8
1
2
3
4
56
7
8
9
10
1112
15
14
13
1
2
3
4
5
6
7
8
9
10
11
12
13
14
POWER PEDESTAL WITHWPGFI DUPLEXRECEPTACLE (TYPICAL)
1
6#4,3#8G, 2"C (SIZEDTO ACCOMMODATEVOLTAGE DROP)
6#6,3#10G,2"C (SIZEDTO ACCOMMODATEVOLTAGE DROP)
C3
E501HOMERUN CIRCUITS ASNOTED IN THIS AREA TOPANEL 'PP-7' UNLESSNOTED OTHERWISE
HOMERUN CIRCUITS ASNOTED IN THIS AREA TOPANEL 'PP-8' UNLESSNOTED OTHERWISE
10
HO
ME
RU
N C
IRC
UIT
S A
SN
OT
ED
IN T
HIS
AR
EA
TO
PA
NE
L 'P
P-8
' UN
LES
SN
OT
ED
OT
HE
RW
ISE
HO
ME
RU
N C
IRC
UIT
S A
SN
OT
ED
IN T
HIS
AR
EA
TO
PA
NE
L 'P
P-9
' UN
LES
SN
OT
ED
OT
HE
RW
ISE
6#4,3#8G, 2"C (SIZEDTO ACCOMMODATEVOLTAGE DROP)
6#4,3#8G, 2"C (SIZEDTO ACCOMMODATEVOLTAGE DROP)
2
REFER TO BRANCH CIRCUITVOLTAGE DROP TABLE FORADDITIONAL WIRINGREQUIREMENTS (TYPICAL)
REFER TO BRANCH CIRCUITVOLTAGE DROP TABLE FORADDITIONAL WIRINGREQUIREMENTS (TYPICAL)
MOUNT AT 48" AFF(TYPICAL)
HH3
C4
E501
4321
B
A
C
D
E
F
G
H
(TYPICAL)4
XFMR-PP84
PANEL 'PP-9'
XFMR-PP9
XFMR-PP7HH
HH
HH
HH
LARGE RADIUS FIELDBENDS AS REQUIRED(TYPICAL)
CIRCUIT UG VIAHANDHOLE(TYPICAL)
(TYPICAL)
MAINTENANCE BUILDING
WAREHOUSE
5
5REFER TO A2/E501 FORADDITIONAL REQUIREMENTS(TYPICAL)
REFER TO A1/E501FOR ADDITIONALREQUIREMENTS FORTHIS AREA
PARTIAL FLOOR PLAN
E101
JO4059-E101FLOOR PLAN
WWS
WWS
WWS-mlb
A. ALL DUPLEX RECEPTACLES SHALL BE DEDICATED CIRCUITS.
B. PROVIDE UNISTRUT TO ACCOMMODATE PANEL MOUNTING AS REQUIRED.
C. COORDINATE FINAL DEVICE LOCATIONS WITH FACILITY PRIOR TO ROUGH-IN.MAINTAIN ALL NEC REQUIRED CLEARANCES.
D. FACILITY TO PROVIDE ANY TREE CLEARING REQUIRED TO ACCOMMODATEINSTALLATION. COORDINATE WITH THE FACILITY ANY IMPACTS TO TREESAS A RESULT OF INSTALLATION SHOWN. ADJUST SCHEDULE WITH FACILITYTO ACCOMMODATE WORK AS REQUIRED.
GENERAL NOTES:
SCALE: 1/16"=1'-0" 0 16'8'4'2'
PARTIAL FLOOR PLAN
A3
E101
1. POWER PEDESTAL: 9" (W) X 9"(D) X 13" (H), 2-GANG, NEMA-3R RATED, RUST-FREEPEDESTAL SUITABLE FOR INSTALLATION OF IPLC CONTROLLED RECEPTACLE.PROVIDE WITH RECEPTACLE (SEE NOTE 5), WHILE-IN-USE COVER. PROVIDE ALLMOUNTING HARDWARE AND ACCESSORIES REQUIRED PER MANUFACTURERSRECOMMENDATIONS. DESIGN MAKE: IPLC.COM PARKING POWER IP3 SERIESPEDESTAL #IP3-13-N-FS OR EQUAL.
2. TRANSITION FROM CONDUCTORS AS SHOWN TO #12 AWG IN PEDESTAL TOACCOMMODATE FINAL TERMINATIONS.
3. 24" X 24" HANDHOLE AND ASSOCIATED COVER WITH LOGO THAT READS "ELECTRIC",TIER 22 ASSEMBLY LOAD RATING. PROVIDE MINIMUM OF 1" GRAVEL BASE ANDINSTALL SO THAT TOP IS 1" ABOVE FINISHED GRADE. DESIGN MAKE: QUAZITE STYLE'PG' OR APPROVED EQUAL.
4. TRANSFORMER, WALL MOUNT FROM STRUCTURE USING MANUFACTURERSMOUNTING HARDWARE. MAINTAIN 6'-0" CLEARANCE ABOVE ANY PANELBOARD.
5. SMART POWER RECEPTACLE, 20A/120V SUITABLE FOR GFCI. RECEPTACLE SHALLMONITOR TEMPERATURE AND WIND CHILL PROGRAMMED TO WORK WITH BLOCKHEATER TO ENSURE VEHICLE STARTING WHILE REDUCING ENERGY USAGE. PROVIDEWITH HANDHELD FIELD PROGRAMMER AND FACTORY/FIELD PROGRAMMING AND ALLHARDWARE REQUIRED FOR A COMPLETE INSTALLATION. CIRCUIT TO GFCI TYPECIRCUIT BREAKER. DESIGN MAKE: IPLC.COM PARKING POWER MODEL#M210TN-WR20-DM4/DATA MATE MODEL DM4 OR EQUAL.
# SHEET KEYED NOTES:
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
CIRCUITLENGTH
MIN. WIRE SIZE(PHASE/NEUT)
MIN. WIRESIZE (GND)
BRANCH CIRCUIT VOLTAGE DROP TABLE
AMPACITY/VOLTAGE
20A/120V 0' - 55' #12
20A/120V 56' - 90'' #10
20A/120V 91' -140' #8
20A/120V 141' -225' #6
#12
#10
#10
#8
MIN. CONDUITSIZE
3/4"
3/4"
1"
1"
SCALE: NONEKEY PLAN
N
![Page 5: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/5.jpg)
PANEL 'DP-2'
EXIST. MAINSWITCHBOARD'MSB'
T
MA
TC
HLI
NE
MA
TC
HLI
NE
PANEL 'PP-6'
T
XFMR-PP6
1 2 3 4 5 6 7 8 9 11 12 13 14 15 1612 13
1
HOMERUN CIRCUITS ASNOTED IN THIS AREA TOPANEL 'PP-6' UNLESSNOTED OTHERWISE
10
HOMERUN CIRCUITS ASNOTED IN THIS AREA TOPANEL 'PP-7' UNLESSNOTED OTHERWISE
MOUNT AT 48" AFF(TYPICAL)
REFER TO BRANCH CIRCUITVOLTAGE DROP TABLE FORADDITIONAL WIRINGREQUIREMENTS (TYPICAL)
B
A
C
D
E
F
G
H
1110987654
2
WAREHOUSE
PARTIAL FLOOR PLAN
E102
JO4059-E102FLOOR PLAN
WWS
WWS
WWS-mlb
A. ALL DUPLEX RECEPTACLES SHALL BE DEDICATED CIRCUITS.
B. COORDINATE FINAL DEVICE LOCATIONS WITH FACILITY PRIOR TOROUGH-IN.
GENERAL NOTES:
SCALE: 1/16"=1'-0" 0 16'8'4'2'
PARTIAL FLOOR PLAN
A3
E102
1. EXISTING MAIN SWITCHBOARD 'MSB', 1200A MLO, 480Y/277V,3Ø,4W, SQUARE DPOWER-STYLE SWITCHBOARD, CAT. NO. 42-78784-1, TYPE I/L. NEW BREAKER IS PARTOF NEC SIX DISCONNECT RULE AND SHALL BE SERVICE ENTRANCE RATED, SAMEMAKE AND AIC RATING AS EXISTING. PROVIDE ALL MOUNTING HARDWARE REQUIRED.
2. TRANSFORMER, WALL MOUNT FROM STRUCTURE USING MANUFACTURERSMOUNTING HARDWARE. MAINTAIN 6'-0" CLEARANCE ABOVE ANY PANELBOARD.
# SHEET KEYED NOTES:
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
CIRCUITLENGTH
MIN. WIRE SIZE(PHASE/NEUT)
MIN. WIRESIZE (GND)
BRANCH CIRCUIT VOLTAGE DROP TABLE
AMPACITY/VOLTAGE
20A/120V 0' - 55' #12
20A/120V 56' - 90'' #10
20A/120V 91' -140' #8
20A/120V 141' -225' #6
#12
#10
#10
#8
MIN. CONDUITSIZE
3/4"
3/4"
1"
1"
SCALE: NONEKEY PLAN
N
![Page 6: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/6.jpg)
~
EXIST. SWITCHBOARD'MSB', 1200A,480Y/277V,3Ø,4W
EXIST.MOTORCONTROLCENTER'MCC-2'
EXIST.MOTORCONTROLCENTER'MCC-1'
400A
-3P
(E
)
700A
-3P
(E
)
400A
-3P
125A
-3P
(E
)
EXIST.PANEL'DP-1'
PANEL'DP-2'
400AMCB
70A-3P(TYPICAL OF 4)
PANEL'PP-7'
150AMCB
EXIST. INCOMINGSERVICE (3 SETS OF)3#600KCMIL,1#4/0N,3-1/2"C EACH
(2 SETS OF)4#350KCMIL, 1#1/0G,3"C EACH
3#4,1#8G.,1-1/4"C
EXIST.
EXIST.
WAREHOUSE MAINTENANCE
1PROVIDE SERATEDBREAKER
7,691A
10,000A
PANEL'PP-8'
150AMCB
3,752A
10,000A
XFMR-PP9
PANEL'PP-9'
150AMCB
2,693A
10,000A
3#3/0,1#6G.,2-1/2"C
3#2/0,1#6G.,2"C
PANEL'PP-6'
150AMCB
3#3/0,1#6G.,2-1/2"C
4,817A
10,000A 8,991A
22,000A
1#4, 3/4"C
1#4, 3/4"C
1#4, 3/4"C
1#4, 3/4"C
4#1/0,1#6G.,2"C4#1/0,1#6G.,2"C4#1/0,1#6G.,2"C
2
2
2
2
XFMR-PP8
XFMR-PP7
XFMR-PP6
4#1/0,1#6G.,2"C
3
FLOOR PLAN & DISTRIBUTIONRISER DIAGRAM
E401
JO4059-E401 RISERDIAGRAM
WWS
WWS
WWS
A. CONDUCTORS SHOWN ARE SIZED TO ACCOMMODATE VOLTAGEDROP.
B. PROVIDE BREAKER TYPES AND EQUIPMENT WITH LUGS SIZED TOACCOMMODATE INCREASED WIRE SIZE DUE TO VOLTAGE DROP.
GENERAL NOTES:
SCALE: NONE
PARTIAL DISTRIBUTION RISER DIAGRAM
A3
E101
1. EXISTING MAIN SWITCHBOARD 'MSB', 1200A MLO, 480Y/277V,3Ø,4W, SQUARE DPOWER-STYLE SWITCHBOARD, CAT. NO. 42-78784-1, TYPE I/L. NEW BREAKER SHALLBE SERVICE ENTRANCE RATED, SAME MAKE AND AIC RATING AS EXISTING. PROVIDEALL MOUNTING HARDWARE REQUIRED.
2. 45KVA TRANSFORMER, 480V PRIMARY, 208Y/120V SECONDARY.
3. LABEL BREAKER AS SERVING PANEL 'DP-2' ABOVE THE EXISTING "SERVICEDISCONNECT" LABEL TO MATCH EXISTING FORMAT.
# SHEET KEYED NOTES:
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
EXISTING PEAK LOAD INFORMATIONAT THE MAIN SWITCHBOARD 'MSB'BASED ON THREE YEAR UTILITY DATA
ADDED LOAD
TOTAL
LOAD DATA
196KVA OR 235A @480V,3Ø
87 KVA OR 105A @480V,4Ø
283KVA OR 341A @ 480V, 3Ø
![Page 7: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/7.jpg)
18" DIA. ROUND FOOTINGWITH (6) #5 VERTICAL REBARSAND #3 TIES 12" O.C. MAX ANDAS SHOWN AT THE TOP OFTHE FOOTING
6'-0
"M
IN
2" CLR
3'-0
"
2"4"
CONDUIT, TRANSITION TORGS LARGE RADIUSSWEEP, (TYPICAL)
(4) -L BOLTS ASRECOMMENDED BY THEMAUFACTURER
POWER PEDESTAL
PROVIDE YELLOW REFLECTIVETAPE (3" WIDE MINIMUM)
PAINT EXPOSED SURFACEWITH YELLOW REFLECTIVECONCRETE PAINT ALLAROUND
HEIGHT TOACCOMMODATEVEHICLE BUMPERPROTECTION
#3 TIES 12" O.C.MAX.
3 5/8"CLR
1'-6"
#5 VERTICAL REBAR
4"
CONTROLLABLE WPRECEPTACLE
DETAIL GENERAL NOTES:
A. PLACE BACKFILL AND FILL SOIL MATERIALS IN LAYERS NOT MORE THAN 8"IN LOOSE DEPTH FOR MATERIAL COMPACTED BY HEAVY COMPACTIONEQUIPMENT, AND NOT MORE THAN 4" IN LOOSE DEPTH FOR MATERIALCOMPACTED BY HAND-OPERATED TAMPERS. COMPACT SOIL MATERIALSTO NOT LESS THAN 95% OF MAXIMUM DRY UNIT WEIGHT ACCORDING TOASTM D698,
#6 DOWELS (16" LONG) @ 12" O.C.EACH SIDE. DRILL & EPOXY 6" INTOEXISTING SLAB AT MID-DEPTH.
MATCH TO EXISTINGREINFORCEMENT
EXISTING SLAB
4" STONE BASE
BACKFILL TRENCHWITH #57 STONE ORCOMPACTED SOIL.
SEE C1, C3 OR C4FORADDITIONALINFORMATION
COAT THIS END W/ GREASE TOPREVENT BOND - CENTER IN SLAB
REPLACE CONCRETE SLABWITH NEW SLAB OF SAMETHICKNESS (F'c =4500 PSI)
BITUMINOUS SEAL - 1" DEEP
12" NON-EXTRUDINGPRE-MOLDED FILLER
DETAILS
E501
JO4059-E501DETAILS
WWS
WWS
WWS
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
FINISHED GRADE
6" - 8"
24" MIN. CLEARANCETO OTHER SERVICES
3000 P.S.I. CONCRETE
P.V.C. CONDUIT REFER TORISER DIAGRAM FOR SIZEAND QUANTITIES (TYPICAL)
PROVIDE 3" SAND BEDALL AROUND
NO ROCKS, DEBRIS INBACKFILL
COMPACT BACKFILL TOMATCH SURROUNDINGCONDITIONS
PROVIDE PAVING ORTOPSOIL TO MATCH SITECONDITIONS
BASE AND INTERMEDIATESPACERS 4'-0" ONCENTER
DETECTABLE TYPEWARNING MARKING TAPE
#4 REBAR (TYPICAL) 1'-6"ON CENTER
7 1/2" ℄ TO ℄ MINIMUMSEPARATION
#4 REBAR (TYPICAL)
3" MINIMUM
MASONRY LEVELING BLOCKSAT BASE OF SPACERS
NOTE: REBAR REQUIREDUNDER ROADWAYS ONLY
SCALE: NONE
TYPICAL TRENCHING DETAIL
C1
E501
FINISHED GRADE
SCALE: NONE
TRENCHING DETAIL
C3
E501
GENERAL DETAIL NOTES:
A. REFER TO TYPICAL TRENCHING DETAIL FOR ADDITIONAL REQUIREMENTS.
CIRCUITS ASINDICATED IN 2"P.V.C. CONDUIT(TYPICAL OF 4)
18" MINIMUM (600V AND BELOW)30" MINIMUM (ABOVE 600V)
SCALE: NONE
PEDESTAL BASE DETAIL
A4
E501
FINISHED GRADE
SCALE: NONE
TRENCHING DETAIL
C4
E501
GENERAL DETAIL NOTES:
A. APPLIES TO NON-ROADWAY AREA TERMINATING AT HANDHOLE AND DEVICE.REFER TO TYPICAL TRENCHING DETAIL FOR ADDITIONAL REQUIREMENTS.CONCRETE ENCASEMENT NOT REQUIRED.
B. REFER TO TYPICAL TRENCHING DETAIL FOR ADDITIONAL REQUIREMENTS.
CIRCIR
CIR CIR
CIRCUITS ASINDICATED IN 2"P.V.C. CONDUIT(TYPICAL OF 4)
CIRCIR
CIR CIR
SCALE: NONE
TYPICAL SLAB INFILL
A1
E501
PR
OFESSIONAL
NORTH CAROLINA
E N GINEER
AR
M
E N A R ME NA KYA
N
THIS SEALAPPLIES TODETAILS A1/E501AND A4/E501
![Page 8: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/8.jpg)
DETAILS
E502
J04059-E502DETAILS
WWS
WWS
WWS
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
STRUCTURAL CEILING
SUSPENDED CEILING
LIGHT FIXTURE
WALL
ELECTRICAL EQUIPMENT
PLANE OF FRONT EDGE OFELECTRICAL EQUIPMENT
EXCLUSIVE DEDICATEDSPACE
VOLTAGE TOGROUND NOMINAL
0-150151-600
CONDITION: 1 2 3
3 3 33 31
2 4
WHERE THE "CONDITIONS" ARE AS FOLLOWS:
1. EXPOSED LIVE PARTS ON ONE SIDE AND NO LIVE OR GROUNDED PARTS ON THE OTHER SIDE OF THE WORKING SPACE, OR EXPOSED LIVE PARTS ON BOTH SIDES EFFECTIVELY GUARDED BY SUITABLE WOOD OF OTHER INSULATING MATERIALS. INSULATED WIRE OR INSULATED BUSBARS OPERATING AT NOT OVER 300V SHALL NOT BE CONSIDERED LIVE PARTS.
2. EXPOSED LIVE PARTS ON ONE SIDE AND GROUNDED PARTS ON THE OTHER SIDE.
3. EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORK SPACE (NOT GUARDED AS PROVIDED IN CONDITION 1) WITH THE OPERATOR BETWEEN.
NOTE:
THIS FIGURE ILLUSTRATES THEWORKING SPACE IN FRONT OF THEELECTRICAL EQUIPMENT REQUIREDBY SECTION 110-26 OF THENATIONAL ELECTRICAL CODE.
SEE
TABLE "A"
FOR THIS
DISTANCE
6'-6
" M
IN.
30" OR WIDTH OF EQUIP.
SCALE: NONE
WORKING CLEARANCE FOR ELECTRICAL EQUIPMENT
C4
E502
NOTE:
TRANSFORMER GROUNDINGELECTRODE TO GROUNDING BARTHAT IS CONNECTED TO GROUNDLOOP IS ACCEPTABLE.
GROUNDING BUSBONDED TO ENCLOSURE
TYPICAL PANELBOARD
EQUIPMENT BONDINGJUMPER
A B C
BONDING BUSHING WITHBONDING JUMPER
NEUTRAL BUS
FLOOR LEVEL
TRANSFORMERWINDING
5 WIRES
4" CONCRETE PAD
4 WIRESH2 X3 H1 X2 H3 X1X0
FROM TRANSFORMERPRIMARY SOURCE
GROUNDING ELECTRODE TO THE STEELFRAME OF THE BLDG.; WHERE PROVEN TO BESUITABLY GROUNDED, OR TO THE METALLICWATER PIPE WITHIN 5 FT. FROM THE POINTOF ENTRANCE INTO THE BUILDING (250-30(a))
EQUIPMENTBONDINGJUMPER
SYSTEM BONDINGJUMPER
GROUND PAD
NOTES:
1. TRANSFORMER BONDING STRAP. IF NOT PROVIDED BY THE TRANSFORMER MANUFACTURER THIS STRAP SHOULD BE THE SAME SIZE AS THE SYSTEM BONDING JUMPER. (250-30).
2. USE A BONDING BUSHING AND EQUIPMENT BONDING JUMPER AT THE CONDUIT TERMINATION. JUMPER SHOULD BE THE SAME SIZE AS THE GROUNDING ELECTRODE CONDUCTOR CONTAINED IN THE CONDUIT.
3. USE A BONDING CLAMP AT THE TERMINATION OF THE GROUNDING ELECTRODE CONDUCTOR TO THE ELECTRODE.
STRUCTURAL CEILING
SUSPENDED CEILING
WALL
DEDICATED SPACE CONTINUESTHROUGH SUSPENDEDCEILING PER N.E.C. ARTICLE110-26.
LIGHT FIXTURE
EXCLUSIVELY DEDICATED SPACEOF 6 FEET. ANY FOREIGNSYSTEMS TO THE ELECTRICALEQUIPMENT SHALL NOT RUNWITHIN THE 6 FEET ABOVE THEELECTRICAL EQUIPMENT.
ELECTRICAL EQUIPMENT
EXCLUSIVELY DEDICATED SPACE
NOTE:
THIS FIGURE ILLUSTRATES THE ADDITIONALEXCLUSIVELY DEDICATED SPACE REQUIRED OVERAND UNDER THE ELECTRICAL EQUIPMENT FOR THECABLES, RACEWAYS, ETC. TO AND FROM THEELECTRICAL EQUIPMENT REQUIRED BY SECTION110-26 OF THE NATIONAL ELECTRICAL CODE.
NEUTRAL(WHITE)
DEDICATED SPACE FOR ELECTRICAL EQUIPMENT
SCALE: NONE
C3
E502
DRY TYPE TRANSFORMER GROUNDING DETAIL
SCALE: NONE
A4
E502
SYSTEM NO. W-L-1001
JUNE 15, 2005
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)T RATINGS - 0, 1, 2, 3, AND 4 HR (SEE ITEM 3)L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FTL RATING AT 400 F - LESS THAN 1 CFM/SQ FT
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALLBE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THEFOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 H FIRE RATED ASSEMBLIES) ORSTEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEELSTUDS TO BE MIN 3-5/8 IN. (92 MM) WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM)OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE ORTAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE ANDSHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE ULFIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 26 IN. (660 MM).
2. THROUGH-PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLYOR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT ORTUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN / (0 MM). (POINT CONTACT) TO MAX 2 IN. (51MM) PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THEFOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST IRON SOILPIPE, NOM 12 IN (305 MM) DIAM (OR SMALLER) OR CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN (102 MM) DIAM (ORSMALLER) STEEL ELECTRICAL METALLIC TUBING
D. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING
E. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. THROUGH PENETRATING PRODUCT* - FLEXIBLE METAL PIPING THE FOLLOWING TYPES OF STEELFLEXIBLE METAL GAS PIPING MAY BE USED:
1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ONPIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
OMEGA FLEX INC
2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ONPIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
TITEFLEX CORP A BUNDY CO
3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING ONPIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
WARD MFG INC
3. FILL, VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. , 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHINANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM BEAD OF CAULK APPLIED TOGYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT LOCATION ON BOTH SIDES OF WALL. THEHOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THEWALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATINGOF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE OR CONDUIT AND THEHOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
+WHEN COPPER PIPE IS USED, T RATING IS 0 H.
3M COMPANY - CP 25WB+ OR FB-3000 WT.
*BEARING THE UL CLASSIFICATION MARK
---------------------------------------------------------------------------------------------------------------------------------------------------------------LAST UPDATED ON 2005-06-15
COPYRIGHT - 2006 UNDERWRITERS LABORATORIES INC. ®
THE APPEARANCE OF A COMPANY'S NAME OR PRODUCT IN THIS DATABASE DOES NOT IN ITSELF ASSURETHAT PRODUCTS SO IDENTIFIED HAVE BEEN MANUFACTURED UNDER UL'S FOLLOW-UP SERVICE. ONLYTHOSE PRODUCTS BEARING THE UL MARK SHOULD BE CONSIDERED TO BE LISTED AND COVERED UNDERUL'S FOLLOW-UP SERVICE. ALWAYS LOOK FOR THE MARK ON THE PRODUCT.
"REPRINTED FROM THE ONLINE CERTIFICATIONS DIRECTORY WITH PERMISSION FROM UNDERWRITERSLABORATORIES INC." "COPYRIGHT © 2006 UNDERWRITERS LABORATORIES INC. ®
UL DESIGN #W-L-1001
1. FLOOR OR WALL ASSEMBLY - MIN 2-1/2 IN. THICK LIGHTWEIGHT OR NORMAL WEIGHT
(100-150 PCF) CONCRETE. WHEN CONFIGURATION A IS USED, ON CONFIGURATION B IS USED IN
CONJUNCTION WITH THE STEEL SLEEVE (ITEM 1A), FLOOR MAY BE CONSTRUCTED OF ANY MIN 6 IN.
THICK UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS*. WALL MAY ALSO BE
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF CIRCULAR THROUGH
OPENING IS 10 IN.
SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN THE FIRE
RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
1A. STEEL SLEEVE (OPTIONAL) - NO. 10 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL
PIPE SLEEVE CAST INTO CONCRETE FLOOR OR WALL. SLEEVE TO BE FLUSH WITH OR PROJECT MAX 2
IN. FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL.
2. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED
EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. MAX ANNULAR SPACE
BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF THROUGH OPENING NOT TO EXCEED 1-3/8 IN.
MIN ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND EDGE OF THROUGH OPENING IS ZERO IN.
(POINT CONTACT). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR
OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING
MAY BE USED:
A. STEEL PIPE - NOM 8 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) RIGID STEEL CONDUIT.
C. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
D. IRON PIPE - NOM 4 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
E. COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.
F. COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
FIRESTOP CONFIGURATION A
3. PACKING MATERIAL - MIN 1 IN. THICKNESS OF TIGHTLY-PACKED MINERAL WOOL BATT
MATERIAL USED AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP OR
BOTTOM SURFACE OF FLOOR OR FROM EITHER SURFACE OF SOLID CONCRETE WALL AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF CAULK FILL MATERIAL (ITEM 4). WHEN WALL IS
CONSTRUCTED OF CONCRETE BLOCK, PACKING MATERIAL IS TO BE INSTALLED ON BOTH SIDES OF
WALL ASSEMBLY. WHEN PRECAST HOLLOW CORE FLOOR IS USED, PACKING MATERIAL MUST BE
INSTALLED ON BOTTOM SURFACE OF FLOOR.
4. FILL,VOID OR CAVITY MATERIALS* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR
SPACE TO A MIN DEPTH OF 1/2 IN. FLUSH WITH THE TOP OR BOTTOM SURFACE OF THE FLOOR OR
EITHER SURFACE OF THE SOLID CONCRETE WALL. A MIN 1/4 IN. DIAM BEAD OF CAULK SHALL BE
APPLIED TO THE FLOOR OR WALL SURFACE WHERE THE PIPE, CONDUIT OR EMT IS INSTALLED IN
POINT CONTACT WITH THE EDGE OF THE THROUGH OPENING. WHEN WALL IS CONSTRUCTED OF
CONCRETE BLOCK, CAULK TO BE INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY.
WHEN PRECAST HOLLOW CORE FLOOR IS USED, CAULK FILL MATERIAL MUST BE INSTALLED ON
BOTTOM SURFACE OF FLOOR.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT.
(THE W RATING APPLIES ONLY WHEN FB-3000 WT IS USED FLUSH WITH THE TOP SURFACE OF
FLOOR.)
FIRESTOP CONFIGURATION B
3. PACKING MATERIAL - POLYETHYLENE BACKER ROD OR NOM 1 IN. THICKNESS OF
TIGHTLY-PACKED MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A
PERMANENT FORM. PACKING MATERIAL TO BE RECESSED MIN 1/2 IN. FROM TOP SURFACE OF FLOOR
OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF
CAULK FILL MATERIAL (ITEM 4).
4. FILL,VOID OR CAVITY MATERIALS* - CAULK OR SEALANT - APPLIED TO FILL THE ANNULAR
SPACE TO A MIN DEPTH OF 1/2 IN. FLUSH WITH THE TOP SURFACE OF THE FLOOR OR BOTH
SURFACES OF THE WALL. A MIN 1/4 IN. DIAM BEAD OF CAULK SHALL BE APPLIED TO THE FLOOR OR
WALL SURFACE WHERE THE PIPE, CONDUIT OR EMT IS INSTALLED IN POINT CONTACT WITH THE
EDGE OF THE THROUGH OPENING.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT. (THE W RATING APPLIES ONLY WHEN
FB-3000 WT IS USED.)
*BEARING THE UL CLASSIFICATION MARK
UL DESIGN #C-AJ-1175
SECTION A-A
3
2
31A
1BA
A
Max Pipe or ConduitDiam in. (mm)
F Rating Hr T Rating Hr
1 (25) 1 or 2 0+, 1 or 21 (25) 3 or 4 3 or 44 (102) 1 or 2 06 (152) 3 or 4 0
12 (305) 1 or 2 0
SECTION A-A
SECTION A-A
A
2
4
FIRESTOP CONFIGURATION - B
FIRESTOP CONFIGURATION - A
A
2
4
A
1A
A 1A
3
4
2
4
1
3 1
![Page 9: ABC COMMISSION WAREHOUSE ELECTRICAL IMPROVEMENTS · 2020-01-27 · 2020 YONKERS ROAD FAX TEL (919) 716-3400 (919) 716-3978 DEPARTMENT CAROLINA NORTH ... Parking Garage Utility and](https://reader031.vdocuments.site/reader031/viewer/2022011908/5f5d8b4cbb759829d80dd770/html5/thumbnails/9.jpg)
SCHEDULES
E601
JO4059-E601SCHEDULES
WWS
WWS
WWS
OF
RALEIGH, N.C. 27699-4216
PUBLIC SAFETY
4216 MSC2020 YONKERS ROAD
FAXTEL (919) 716-3400
(919) 716-3978
DEPARTMENTCAROLINANORTH
01/22/2020
NO DATE REVISION
CADD DWG NO:
JOB ORDER NO:
CHECKED BY:
PLOT DATE:
DESIGNED BY:
DRAWN BY:
4059
CD
BA
1 2 3 4 5
CENTRAL ENGINEERING
Plan ● Design ● Construct
SCO ID # 19-21377-01A
1/24/2020 ISSUED FOR CONSTRUCTION
ABC COMMISSION
WAREHOUSEBUILDING400 EAST TRYON ROADRALEIGH, NORTH CAROLINA 27610
POWER IMPROVEMENTS
DP2 PP-6
PP-8PP-7
PP-9