User frendly Configuration Full integration Real savings A_LIFE2_0102_1004_201306_EN (The photo of the unit is purely indicative and may vary depending on the model) Climaveneta Technical Bulletin 0102 ÷ 1004 Fan-coil for professional applications, with cabinet or built-in version 1,5 ÷ 7,5 kW a-LIFE2

Upload: others

Post on 25-May-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

User frendlyConfiguration

Full integrationReal savings

<

<

<

<

A_LIFE2_0102_1004_201306_EN

(The photo of the unit is purely indicative and may vary depending on the model)

Climaveneta Technical Bulletin

0102 ÷ 1004 Fan-coil for professional applications, with cabinet or built-inversion1,5 ÷ 7,5 kW

a-LIFE2

Page 2: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

1. RANGE 3

2. GENERAL DEsCRiPTioN 4

3. ACCEssoRiEs CoMPATiBiLiTY 6

4. UNiT DEsCRiPTioN 8

5. oPERATiNG LiMiTs 9

6. TEChNiCAL DATA shEET 10

7. FAN PERFoRMANCEs 16

8. PREssURE DRoP 20

9. CoRRECTioN FACToRs iN CooLiNG oPERATioNWiTh GLYCoL WATER 22

10. CoRRECTioN FACToRs iN hEATiNG oPERATioNWiTh GLYCoL WATER 23

11. soUND PREssURE LEVEL 24

12. soUND PoWER LEVEL 24

13. FANCoiL CoNTRoLs 25

14. ACCEssoRiEs 31

15. DiMENsioNAL DATA AND WATER CoNNECTioNs 48

16. ELECTRiCAL CoNNECTioNs 53

SUMMARY

a-LIFE2

2A_LIFE2_0102_1004_201306_EN

Waiver of liability

This publication represents the sole property of Climaveneta.Any reproduction or disclosure of such is strictly prohibited with-out the written authorisation of Climaveneta.This document has been prepared with maximum care andattention paid to the content shown. Nonetheless, Climavenetawaives all liability deriving from the use of such document.Read this document carefully.

All work must be performed, components selected and materi-als used professionally and in complete accordance with thelegislation in force in material in the country concerned, andconsidering the operating conditions and intended uses of thesystem, by qualified personnel.The data contained in this publication may be changed withoutprior notice.

This company participates in the Eurovent Certifi cation Programme.The products are listed in the Directory of certifi ed products.Eurovent certifi cation applied to units with cooling capacity up to 1500 kWfor air cooled water chillers and water cooled liquid chillers.

Page 3: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

WITh cABINET ModEL

a-LIFE2 dLMV/dLMo

version with cabinet, low air intakea-LIFE2 dFMV/dFMo

version with cabinet, front air intake

1. RANGE

BUILT-IN ModEL

a-LIFE2 dLIo/dLIV

built-in version, low air intakea-LIFE2 dFIV/dFIo

built-in version, front air intake

a-LIFE2

A_LIFE2_0102_1004_201306_EN3

100 mm

100 mm

Vertical wall mounted horizontal ceiling installation

Vertical wall mounted horizontal ceiling installation

100 mm

100 mm

Vertical wall mounted horizontal ceiling installation

Vertical wall mounted horizontal ceiling installation

Page 4: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

Fan Coil is a terminal unit for air conditioning during summer(cooling) and winter (heating).a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds ofwhich 3 are factory-set. other speeds may be requested on theorder by the customer.

a-LIFE2 dLMV

version with cabinet, low air intake, vertical installation

a-LIFE2 dLMo

version with cabinet, low air intake, horizontal installation

a-LIFE2 dFMV

version with cabinet, front air intake, vertical installation

a-LIFE2 dFMo

version with cabinet, front air intake, horizontal installation

a-LIFE2 dLIV

built-in version, low air intake, vertical installation

a-LIFE2 dLIo

built-in version, low air intake, horizontal installation

a-LIFE2 dFIV

built-in version, front air intake, vertical installation

a-LIFE2 dFIo

built-in version, front air intake, horizontal installation

output from 1,5 kW - 7,5 kW. Standard water fittings,

reversible on site.

Available in 10 different versions with centrifugal fans, suitablefor use in the tertiary sector and for small ducted installations.structure made in metal panel, with inlet and outlet plasticgrilles. Available controls Ps, MT, AT and EK, iK with use of hBpower boardAvailable wall mounted controls: PsW, MTW, ATW and EKW, iKwith use of hB Power Board.Air filter on all models.

a-LIFE2

4A_LIFE2_0102_1004_201306_EN

2. GENERAL dEScRIPTIoN

1 Casing made from galvanised and coated sheet metal with ABs front intake grill on versions DFMo/DFMV (1’), and without grill on versionsDLMo/DLMV (1)

2 Load-bearing structure made from thick galvanised sheet metal, with holes for wall/ceiling mounting + thermal insulation and soundproofingon the inside (class M1)

3 Centrifugal fan with double-sided intake4 Electric motor coupled directly to the fan5 heat exchanger coil (1 coil for 2-pipe units; 2 coils for 4-pipe units)6 Coil water connections7 Manual air vent valve8 Manual water drain valve9 Condensate collection pan with drains + thermal insulation10 Condensate drain11 Air filter (filtration grade G2)

Page 5: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN5

2. GENERAL dEScRIPTIoN

dimensions

LiFE2 DLiVbuilt-in version, low air intake,vertical installation

LiFE2 DLMVversion with cabinet, low airintake, vertical installation

LiFE2 DLiobuilt-in version, low air intake,horizontal installation

LiFE2 DLMoversion with cabinet, low airintake, horizontal installation

LiFE2 DFiVbuilt-in version, front air intake,vertical installation

LiFE2 DFMVversion with cabinet, front airintake, vertical installation

LiFE2 DFiobuilt-in version, front air intake,horizontal installation

LiFE2 DFMoversion with cabinet, front airintake, horizontal installation

Built-in

version

dLIV

0102-0104

dLIV

0202-0204

dLIV

0302-0304

dLIV

0402-0404

dLIV

0502-0504

dLIV

0602-0604

dLIV

0702-0704

dLIV

0802-0804

dLIV

0902-0904

dLIV

1002-1004

L (mm) 450 450 650 650 850 850 1050 1050 1250 1250

h (mm) 450 450 450 450 450 450 450 450 450 450

s (mm) 215 215 215 215 215 215 215 215 215 215

Built-in

version

dLIo

0102-0104

dLIo

0202-0204

dLIo

0302-0304

dLIo

0402-0404

dLIo

0502-0504

dLIo

0602-0604

dLIo

0702-0704

dLIo

0802-0804

dLIo

0902-0904

dLIo

1002-1004

L (mm) 545 545 745 745 945 945 1145 1145 1345 1345

h (mm) 450 450 450 450 450 450 450 450 450 450

s (mm) 215 215 215 215 215 215 215 215 215 215

With cabinet

version

dLMV

0102-0104

dLMV

0202-0204

dLMV

0302-0304

dLMV

0402-0404

dLMV

0502-0504

dLMV

0602-0604

dLMV

0702-0704

dLMV

0802-0804

dLMV

0902-0904

dLMV

1002-1004

L (mm) 922 922 1112 1112 1302 1302 1492 1492 1682 1682

h (mm) 499 499 499 499 499 499 499 499 499 499

s (mm) 233 233 233 233 233 233 233 233 233 233

With cabinet

version

dLMo

0102-0104

dLMo

0202-0204

dLMo

0302-0304

dLMo

0402-0404

dLMo

0502-0504

dLMo

0602-0604

dLMo

0702-0704

dLMo

0802-0804

dLMo

0902-0904

dLMo

1002-1004

L (mm) 922 922 1112 1112 1302 1302 1492 1492 1682 1682

h (mm) 499 499 499 499 499 499 499 499 499 499

s (mm) 233 233 233 233 233 233 233 233 233 233

Page 6: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

6A_LIFE2_0102_1004_201306_EN

3. AccESSoRIES coMPATIBILITY

description a-LIFE2

dFMo dLMo dFMV dLMV dFIo dLIo dFIV dLIV

AiR iNLET GRiLLE + FiLTER LiFE2 √ √ √ √

AiR oUTLET GRiLLE + FiLTER LiFE2 √ √ √ √

PLENUM KiT LiFE2 iNLET AiR 90° √ √

PLENUM KiT LiFE2 oUTLET AiR 90° √ √ √ √

PLENUM KiT LiFE2 sTREiGhT oUTLET √ √ √ √

PLENUM KiT LiFE2 sTREiGhT iNLET √ √ √ √

PLENUM KiT LiFE2 CiRCULAR 1XD.200/180/160 (iNLET) √ √ √ √

PLENUM KiT LiFE2 CiRCULAR 1XD.200/180/160 (oUTLET) √ √ √ √

ELECTRiCAL hEATER √ √ √ √

TERMiNAL MAMUT iP20 √ √ √ √ √ √ √ √

AUXiLiARY CoNDENsATE TRAY VERTiCAL iNsT. LiFE2 √ √ √ √

AUXiLiARY CoNDENsATE TRAY hoRiZ. iNsT. LiFE2 √ √ √ √

KiT VALV MAiN CoiL 1/2" oN/oFF 2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 1/2" PWM 2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 3/4" oN/oFF 2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 3/4" PWM 2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 1/2" 3P LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 3/4" 3P LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 1/2" 0-10V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 3/4" 0-10V 2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 1/2" oN/oFF 3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 1/2" PWM 3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 3/4" oN/oFF 3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 3/4" PWM 3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 1/2" 3P3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 3/4" 3P3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 1/2" 0-10V 3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV MAiN CoiL 3/4" 0-10V 3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV ADD. CoiL 1/2" oN/oFF 2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV ADD. CoiL 1/2" PWM 2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV ADD. CoiL 1/2" 3P2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV ADD. CoiL 0-10V 2V LiFE2 √ √ √ √ √ √ √ √

KiT VALV ADD. CoiL 1/2 oN/oFF 3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV ADD. CoiL 1/2" PWM 3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV ADD. CoiL 1/2" 3P3V LiFE2 √ √ √ √ √ √ √ √

KiT VALV ADD. CoiL 0-10V 3V LiFE2 √ √ √ √ √ √ √ √

WATER KiT FoR 3-WAYs 3/4" AND 2 BALL VALVE √ √ √ √ √ √ √ √

WATER KiT FoR 2-WAYs 3/4 AND 2 BALL VALVE √ √ √ √ √ √ √ √

WATER KiT FoR 3-WAYs 1/2" AND 2 BALL VALVE √ √ √ √ √ √ √ √

WATER KiT FoR 2-WAYs 1/2” AND 2 BALL VALVE √ √ √ √ √ √ √ √

MANUAL DAMPER FoR BUiLT-iN UNiTs LiFE2 √ √ √ √

MoT. DAMPER FoR BUiLT-iN UNiTs LiFE2 √ √ √ √

MoT. DAMPER FoR WiTh CABiNET UNiTs √

MANUAL DAMPER FoR WiTh CABiNET UNiTs √

DAMPER MoToR LiFE2 √ √ √ √ √

Page 7: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN7

3. AccESSoRIES coMPATIBILITY

description a-LIFE2

dFMo dLMo dFMV dLMV dFIo dLIo dFIV dLIV

AiR iNLET GRiLL FoR WiTh CABiNET UNiTs √ √

EsTETiCAL AND sTRUTURAL FEEDs √ √ √ √

KiT ADDiTioNAL CoiL 1 RoW √ √ √ √ √ √ √ √

CLosURE PANELs LiFE2 √ √ √ √

KiT LiFE2 BoX √ √

KiT CoNTRoL MT CLiMAVENETA LiFE2 √ √

KiT REMoTE CoNTRoL PsW CLiMAVENETA LiFE2 √ √ √ √ √ √ √ √

KiT CoNTRoL MT CLiMAVENETA LiFE2 √ √

KiT REMoTE CoNTRoL REMoTo MTW CLiMAVENETA LiFE2 √ √ √ √ √ √ √ √

KiT CoNTRoL AT MoDBUs CLiMAVENETA LiFE2 √ √

KiT REMoTE CoNTRoL ATW MoDBUs CLiMAVENETA LiFE2 √ √ √ √ √ √ √ √

KiT CoNTRoL EK CLiMAVENETA LiFE2 √ √

KiT REMoTE CoNTRoLD REMoTo EKW CLiMAVENETA LiFE2 √ √ √ √ √ √ √ √

KiT CoNTRoL iK CLiMAVENETA LiFE2 √ √

CARBoN FiLTER LiFE2 DFMo/V √ √

CARBoN FiLTER LiFE2 √ √ √ √ √ √

KiT PoWE BoARD LiFE2 hB √ √ √ √ √ √ √ √

KiT Rs485 LiFE2 √ √ √ √ √ √ √ √

KiT EsPANsioNE VALV. 0-10VDC LiFE2 √ √ √ √ √ √ √ √

KiT EsPANsioNE VALV. 3PUNTi LiFE2 √ √ √ √ √ √ √ √

KiT BUs ADAPTER √ √ √ √ √ √ √ √

KiT GATEWAY BiTiCiNo √ √ √ √ √ √ √ √

KiT sPB FoR MULTRiPLE CoNNECTioNs √ √ √ √ √ √ √ √

KiT FLEssiBLE TUBEs LiFE2 √ √ √ √ √ √ √ √

Page 8: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

8A_LIFE2_0102_1004_201306_EN

4. UNIT dEScRIPTIoN

a-LIFE2 dLMV, dLMo

covering cabinet

Comprising components made from ABs for the sides andoutlet grills (adjustable by 180°) and thick coated sheet metalfor the front panel.Protective flap for controls in ABs with tamperproof fixing screwin conformity with directive EN iso 60335-2-40 in relation toamendment A1 concerning the automatic closure of the flap andprotection of electrical controls against spillage of water.Quick-fitting controls fixing bracket.

Bearing structure

Galvanised steel frame with high rust resistance.insulated with self-extinuishing Class 1heat insulating panels.Unit fitted with condensate collection pan made from insulatedgalvanised sheet metal for vertical and horizontal installation.Terminal block for power and control connections with screwterminals for remote controls.

heat exchange

Coil with corrugated aluminium fins and copper pipes, 100%tested with dried air.The water fittings are provided with anti-torsion lock with airvent and water drainage.All units are delivered with left-hand water connections, easilyconvertible into right-hand by simply turning the coil.

Fan motor

Double intake centrifugal fans, statically and dinamically bal-anced and coupled directly to the electric motor.Powered by auto-trasformer with 6 speeds of which 3 are facto-ry-set.

Air filter

Made of metal frame and hosting the filtering material, classifi-cation G2.Comprising components made from ABs for the sides andoutlet grills (adjustable by 180°) and thick coated sheet metalfor the front panel.

a-LIFE2 dFMV, dFMo

covering cabinet

Comprising components made from ABs for the sides andoutlet grills (adjustable by 180°) and thick coated sheet metalfor the front panel.Protective flap for controls in ABs with tamperproof fixing screwin conformity with directive EN iso 60335-2-40 in relation toamendment A1 concerning the automatic closure of the flap andprotection of electrical controls against spillage of water.Quick-fitting controls fixing bracket

Bearing structure

Galvanised steel frame with high rust resistance.insulated with self-extinuishing Class 1heat insulating panels.Unit fitted with condensate collection pan made from insulatedgalvanised sheet metal for vertical and horizontal installation.Terminal block for power and control connections with screwterminals for remote controls.

heat exchange

Coil with corrugated aluminium fins and copper pipes, 100%tested with dried air.The water fittings are provided with anti-torsion lock with airvent and water drainage.All units are delivered with left-hand water connections, easilyconvertible into right-hand by simply turning the coil.

Fan motor

Double intake centrifugal fans, statically and dinamically bal-anced and coupled directly to the electric motor.Powered by auto-trasformer with 6 speeds of which 3 are facto-ry-set.

Air filter

Made of metal frame and hosting the filtering material, classifi-cation G2.Easily removable intake grille/filter by the ¼ turn screws.

Page 9: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN9

4. UNIT dEScRIPTIoN

a-LIFE2 dLIo, dLIV

Bearing structure

Galvanised steel frame with high rust resistance.insulated with self-extinuishing Class 1heat insulating panels.Unit fitted with condensate collection pan made from insulatedgalvanised sheet metal for horizontal and vertical installation.Double terminal block for power and control connections withquick connector for plug-in controls. Wall mounted controls arefixed by screws.

heat exchange

Coil with corrugated aluminium fins and copper pipes, 100%tested with dried air.The water fittings are provided with anti-torsion lock with airvent and water drainage.All units are delivered with left-hand water connections, easilyconvertible into right-hand by simply turning the coil.

Fan motor

Double intake centrifugal fans, statically and dinamically bal-anced and coupled directly to the electric motor.Powered by auto-trasformer with 6 speeds of which 3 are facto-ry-set.

Air filter

Made of metal frame and hosting the filtering material, classifi-cation G2.Filter removal is completely safe, and is simplified by turning theguides at the side to release the filter.

a-LIFE2 dFIo, dFIV

Bearing structure

Galvanised steel frame with high rust resistance.insulated with self-extinuishing Class 1heat insulating panels.Unit fitted with condensate collection pan made from insulatedgalvanised sheet metal per the horizontal and vertical installa-tion.Double terminal block for power and control connections withquick connector for plug-in controls. Wall mounted controls arefixed by screws.

heat exchange

Coil with corrugated aluminium fins and copper pipes, 100%tested with dried air.The water fittings are provided with anti-torsion lock with airvent and water drainage.All units are delivered with left-hand water connections, easilyconvertible into right-hand by simply turning the coil.

Fan motor

Double intake centrifugal fans, statically and dinamically bal-anced and coupled directly to the electric motor.Powered by auto-trasformer with 6 speeds of which 3 are facto-ry-set.

Air filter

Made of metal frame and hosting the filtering material, classifi-cation G2.The filter removal requires a tool as safety measure (accordingwith anti-tamper regulation).

5. oPERATING LIMITS

MINIMUM AVERAGE WATER TEMPERATUREdry bulb room temperature °c

21 23 25 27 29 31

Wet bulb room temperature °c.

15 3 3 3 3 3 3

17 3 3 3 3 3 3

19 3 3 3 3 3 3

21 6 5 4 3 3 3

23 - 8 7 7 5 5

Maximum water inlet temp. 80°CMaximum working pressure: 15 bar

Minimum room air temperature: 0°CMaximum room air temperature 45°C

Minimum average water temperature:

The limits specified above refer to operation with the fan at minimum speed.During extended periods in which the fan is off and of cold water is flowing through the coil, condensate may form on the outside of theappliance; consequently, the three-way valve should be installed.

FAcToRY-SET SPEEd

a-LiFE2 is provided with centrifugal fan, powered by auto-trasformer with 6 speeds of which 3 (speed wired standard 2-3-5) are factory-set by Climaveneta. other speeds may be selected on request in the order.

Page 10: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

10A_LIFE2_0102_1004_201306_EN

6. TEchNIcAL dATA ShEET

a-LIFE2 / DLIO-DFIO 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating (2) m³/h 0,258 0,345 0,489 0,584 0,654 0,758 0,878 0,979 1,060 1,288Pressure drop in heating (2) kPa 7,6 10,9 26,0 34,5 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating (2) m³/h 0,200 0,300 0,400 0,487 0,529 0,650 0,779 0,875 0,927 1,138Pressure drop in heating (2) kPa 4,7 8,3 17,7 24,9 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating (2) m³/h 0,173 0,257 0,355 0,398 0,489 0,519 0,701 0,775 0,814 0,923Pressure drop in heating (2) kPa 3,5 6,2 14,1 17,3 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 545 545 745 745 945 945 1145 1145 1345 1345B (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 11 12 14 15 20 21 23 25 27 29

Notes:1 Room temperature 27°C d.b./19°C w.b.; Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b.; Hot water (in/out) 50/* °C (with identical flow note1)3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

Page 11: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN11

6. TEchNIcAL dATA ShEET

a-LIFE2 / DLIV-DFIV 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating (2) m³/h 0,258 0,345 0,489 0,584 0,654 0,758 0,878 0,979 1,060 1,288Pressure drop in heating (2) kPa 7,6 10,9 26,0 34,5 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating (2) m³/h 0,200 0,300 0,400 0,487 0,529 0,650 0,779 0,875 0,927 1,138Pressure drop in heating (2) kPa 4,7 8,3 17,7 24,9 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating (2) m³/h 0,173 0,257 0,355 0,398 0,489 0,519 0,701 0,775 0,814 0,923Pressure drop in heating (2) kPa 3,5 6,2 14,1 17,3 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mmB (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 11 12 14 15 20 21 23 25 27 29

Notes:1 Room temperature 27°C d.b./19°C w.b.; Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b.; Hot water (in/out) 50/* °C (with identical flow note1)3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

450 450 650 650 850 850 1050 1050 1250 1250

Page 12: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

12A_LIFE2_0102_1004_201306_EN

6. TEchNIcAL dATA ShEET

a-LIFE2 / DLMV-DFMV / DLMO-DFMO 0102 0202 0302 0402 0502 0602 0702 0802 0902 1002ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1752 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 2,17 2,82 3,86 4,40 5,17 6,06 6,94 7,74 8,09 10,1Water flow in heating (2) m³/h 0,258 0,345 0,489 0,584 0,654 0,758 0,878 0,979 1,060 1,288Pressure drop in heating (2) kPa 7,6 10,9 26,0 34,5 10,7 14,6 20,3 23,3 29,1 40,9Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 1,62 2,32 3,09 3,84 4,18 5,14 6,15 6,92 7,16 8,89Water flow in heating (2) m³/h 0,200 0,300 0,400 0,487 0,529 0,650 0,779 0,875 0,927 1,138Pressure drop in heating (2) kPa 4,7 8,3 17,7 24,9 7,2 10,9 16,2 18,8 22,8 32,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 1,40 2,08 2,80 3,07 3,82 4,15 5,42 6,12 6,29 7,13Water flow in heating (2) m³/h 0,173 0,257 0,355 0,398 0,489 0,519 0,701 0,775 0,814 0,923Pressure drop in heating (2) kPa 3,5 6,2 14,1 17,3 6,2 7,1 13,3 15,0 17,9 22,1Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682B (5) mm 233 233 233 233 233 233 233 233 233 233H (5) mm 499 499 499 499 499 499 499 499 499 499Operating weight (5) kg 16 17 20 21 27 28 32 33 37 38

Notes:1 Room temperature 27°C d.b./19°C w.b.; Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b.; Hot water (in/out) 50/* °C (with identical flow note1)3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

Page 13: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN13

6. TEchNIcAL dATA ShEET

a-LIFE2 / DLIO-DFIO 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1754 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32Water flow in heating (2) m³/h 0,110 0,146 0,203 0,242 0,293 0,339 0,382 0,423 0,454 0,554Pressure drop in heating (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 37,5 45,2 54,6 79,1Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57Water flow in heating (2) m³/h 0,085 0,127 0,166 0,203 0,238 0,289 0,334 0,375 0,400 0,488Pressure drop in heating (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 29,2 36,3 43,1 62,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55Water flow in heating (2) m³/h 0,073 0,109 0,147 0,165 0,220 0,232 0,301 0,334 0,348 0,399Pressure drop in heating (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 24,0 29,2 33,3 42,9Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mmB (5) mm 215 215 215 215 215 215 215 215 215 215H (5) mm 450 450 450 450 450 450 450 450 450 450Operating weight (5) kg 12 12 14 15 21 22 24 25 28 29

Notes:1 Room temperature 27°C d.b./19°C w.b., Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b., hot water (in/out) 70/60°C3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

545 545 745 745 945 945 1145 1145 1345 1345

Page 14: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

14A_LIFE2_0102_1004_201306_EN

6. TEchNIcAL dATA ShEET

Page 15: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN15

6. TEchNIcAL dATA ShEET

a-LIFE2 / DLMV-DFMV / DLMO-DFMO 0104 0204 0304 0404 0504 0604 0704 0804 0904 1004ELECTRICAL DATAPower supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50Max absorbd power W 55 55 85 85 75 75 145 145 175 1754 PIPES SYSTEM CONFIGURATIONMAX SPEEDAir flow m³/h 300 360 520 590 660 815 890 980 1140 1310Total capacity in cooling mode (1) kW 1,50 2,00 2,85 3,40 3,80 4,40 5,15 5,70 6,15 7,50Sensible capacity in cooling mode (1) kW 1,24 1,59 2,22 2,61 2,95 3,52 3,99 4,38 4,66 5,81Max water flow (1) m³/h 0,258 0,344 0,491 0,585 0,654 0,757 0,887 0,981 1,059 1,291Mad pressure drop (1) kPa 9,0 12,7 30,8 36,1 12,6 17,2 24,2 26,9 32,9 46,8Total capacity in heating mode (2) kW 1,25 1,67 2,31 2,76 3,34 3,87 4,36 4,82 5,18 6,32Water flow in heating (2) m³/h 0,110 0,146 0,203 0,242 0,293 0,339 0,382 0,423 0,454 0,554Pressure drop in heating (2) kPa 6,2 10,7 13,3 18,6 27,0 35,6 37,5 45,2 54,6 79,1Noise Pressure (3) dB(A) 39 45 42 47 45 50 47 50 48 55Noise Power (4) dB(A) 48 54 51 56 54 59 56 59 57 64MED SPEEDAir flow m³/h 210 290 410 500 560 670 780 910 1010 1180Total capacity in cooling mode (1) kW 1,16 1,74 2,33 2,85 3,08 3,75 4,50 5,06 5,41 6,62Sensible capacity in cooling mode (1) kW 0,90 1,31 1,77 2,22 2,43 2,95 3,49 3,99 4,16 5,16Max water flow (1) m³/h 0,200 0,300 0,401 0,491 0,530 0,646 0,775 0,871 0,931 1,140Mad pressure drop (1) kPa 5,4 9,6 20,5 28,0 8,2 12,4 18,5 21,2 25,5 36,5Total capacity in heating mode (2) kW 0,97 1,45 1,89 2,31 2,71 3,30 3,81 4,28 4,56 5,57Water flow in heating (2) m³/h 0,085 0,127 0,166 0,203 0,238 0,289 0,334 0,375 0,400 0,488Pressure drop in heating (2) kPa 3,9 8,2 9,1 13,3 18,3 26,4 29,2 36,3 43,1 62,5Noise Pressure (3) dB(A) 31 39 37 42 39 45 44 47 45 51Noise Power (4) dB(A) 40 48 46 51 48 54 53 56 54 60MIN SPEEDAir flow m³/h 180 270 350 380 500 550 640 760 790 920Total capacity in cooling mode (1) kW 1,00 1,49 2,07 2,31 2,85 3,02 4,06 4,50 4,71 5,40Sensible capacity in cooling mode (1) kW 0,78 1,18 1,59 1,75 2,22 2,39 3,00 3,44 3,59 4,14Max water flow (1) m³/h 0,172 0,257 0,356 0,398 0,491 0,520 0,699 0,775 0,811 0,930Mad pressure drop (1) kPa 4,0 7,0 16,2 20,7 7,0 8,0 15,0 16,8 19,4 24,3Total capacity in heating mode (2) kW 0,83 1,24 1,68 1,88 2,51 2,65 3,43 3,81 3,97 4,55Water flow in heating (2) m³/h 0,073 0,109 0,147 0,165 0,220 0,232 0,301 0,334 0,348 0,399Pressure drop in heating (2) kPa 2,9 6,1 7,2 9,0 15,8 17,5 24,0 29,2 33,3 42,9Noise Pressure (3) dB(A) 28 37 36 37 37 39 41 44 41 45Noise Power (4) dB(A) 37 46 45 46 46 48 50 53 50 54SIZE AND WEIGHTA (5) mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682B (5) mm 233 233 233 233 233 233 233 233 233 233H (5) mm 499 499 499 499 499 499 499 499 499 499Operating weight (5) kg 17 18 21 22 29 30 33 35 38 40

Notes:1 Room temperature 27°C d.b./19°C w.b.; Chilled water (in/out) 7/12°C2 Room temperature 20°C d.b.; Hot water (in/out) 70/60 °C; Supplementary coil 1-row3 Sound pressure in semianechoic room at 1 (m.) from fan front and 1 (m.) from the ground4 Sound power on the basis of measurements made in compliance with Eurovent 8/2.5 Unit in standard configuration/execution, without optional accessories.

Page 16: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

7. FAN PERFoRMANcES

a-LIFE2

16A_LIFE2_0102_1004_201306_EN

a-LiFE2 is designed to assure high pressure also with pressuredrops due to complex ducts. They come with six different fanspeeds. A particular care has been reserved to the configurationsof the three fan speeds cabled by the manufacturer.The other three fan speeds can be cabled on site.

The graphs on the following pages show the useful head or work-ing pressures in relation to the air flow and the fan speed.

NoTE: the graphs refer to the versions with 3-row coils.

a-LIFE2 0102-0104

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

L2L3L5

0

10

20

30

40

50

60

70

80

90

100

Portata aria [m3/h] - Air Flow [m3/h]

0 50 100 150 200 250 300 350

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

Portata aria [m3/h] - Air Flow [m3/h]

L2L3L5

a-LIFE2 0202-0204

0

10

20

30

40

50

60

70

80

90

100

0 50 100 150 200 250 300 350 400 450

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

Portata aria [m3/h] - Air Flow [m3/h]

a-LIFE2 0302-0304

0

10

20

30

40

50

60

70

80

90

100

0 50 100 150 200 250 300 350 400

L2L3L5 L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

Page 17: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

7. FAN PERFoRMANcES

a-LIFE2

A_LIFE2_0102_1004_201306_EN17

a-LIFE2 0402-0404

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

0

10

20

30

40

50

60

70

80

90

100

Portata aria [m3/h] - Air Flow [m3/h]

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

0 50 100 150 200 250 300 350 400 450 500 550 600 650

L2L3L5

a-LIFE2 0502-0504

Portata aria [m3/h] - Air Flow [m3/h]

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6 0

10

20

30

40

50

60

70

80

90

100

110

120

0 50 100 150 200 250 300 350 400 450 500 550 600 650 700

L2L3L5

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

a-LIFE2 0602-0604

Portata aria [m3/h] - Air Flow [m3/h]

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

L2L3L5

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

0

10

20

30

40

50

60

70

80

90

100

110

120

0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850

Page 18: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

18A_LIFE2_0102_1004_201306_EN

7. FAN PERFoRMANcES

a-LIFE2 0702-0704

Portata aria [m3/h] - Air Flow [m3/h]

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

0

10

20

30

40

50

60

70

80

90

100

110

120

130

0 100 200 300 400 500 600 700 800 900 1000

L2L3L5

a-LIFE2 0802-0804

Portata aria [m3/h] - Air Flow [m3/h]

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

0

10

20

30

40

50

60

70

80

90

100

110

120

130

0 100 200 300 400 500 600 700 800 900 1000 1100

L2L3L5

Page 19: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN19

7. FAN PERFoRMANcES

a-LIFE2 0102-0104

Portata aria [m3/h] - Air Flow [m3/h]

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

0

10

20

30

40

50

60

70

80

90

100

110

120

130

0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

L2L3L5

a-LIFE2 0902-0904

Portata aria [m3/h] - Air Flow [m3/h]

L1

Velocità cablate in fabbricaFactory Wired speed

L2 Velocità massima Maximum speed L3 Velocità media Medium Speed L4

L5 Velocità minima Minimum Speed L6

Pre

vale

nza

utile

[Pa]

- S

tatic

use

ful h

ead

[Pa]

0

10

20

30

40

50

60

70

80

90

100

110

120

130

0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300

L2L3L5

Page 20: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

8. PRESSURE dRoP

a-LIFE2

20A_LIFE2_0102_1004_201306_EN

1

10

100

0,10 1,00

Perd

ita d

i car

ico

[kPa

] - P

ress

ure

drop

[kPa

]

Portata acqua [m3/h] - Water Flow [m3/h]

a-LIFE2 0102 a-LIFE2 0202 a-LIFE2 0302 a-LIFE2 0402

MAIN coIL

cooLING

a-LIFE2 0102÷0402 (2 pipes)

1

10

100

0,10 1,00

Perd

ita d

i car

ico

[kPa

] - P

ress

ure

drop

[kPa

]

Portata acqua [m3/h] - Water Flow [m3/h]

a-LIFE2 0102-0302 a-LIFE2 0202 a-LIFE2 0402

MAIN coIL

hEATING

a-LIFE2 0102÷0402 (2 pipes)

1

10

100

0,10 1,00

Perd

ita d

i car

ico

[kPa

] - P

ress

ure

drop

[kPa

]

Portata acqua [m3/h] - Water Flow [m3/h]

a-LIFE2 0104-0204a-LIFE2 0304-0404

AddITIoNAL coIL

hEATING

a-LIFE2 0104÷0404 (4 pipes)

Page 21: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN21

8. PRESSURE dRoP

1

10

100

0,15 1,50

Perd

ita d

i car

ico

[kPa

] - P

ress

ure

drop

[kPa

]

Portata acqua [m3/h] - Water Flow [m3/h]

a-LIFE20502-0602-0702

a-LIFE20802-0902-1002

MAIN coIL

cooLING

a-LIFE2 0502÷1002 (2 pipes)

1

10

100

0,15 1,50

Perd

ita d

i car

ico

[kPa

] - P

ress

ure

drop

[kPa

]

Portata acqua [m3/h] - Water Flow [m3/h]

a-LIFE20502-0602-0702

a-LIFE20802-0902-1002

MAIN coIL

hEATING

a-LIFE2 0502÷1002 (2 pipes)

1

10

100

0,10 1,00

Perd

ita d

i car

ico

[kPa

] - P

ress

ure

drop

[kPa

]

Portata acqua [m3/h] - Water Flow [m3/h]

a-LIFE2 0504-0604a-LIFE2 0704-0804 a-LIFE2 0904-1004

AddITIoNAL coIL

hEATING

a-LIFE2 0504÷1004 (4 pipes)

Page 22: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

22A_LIFE2_0102_1004_201306_EN

9. coRREcTIoN FAcToRS IN cooLING oPERATIoN WITh GLYcoL WATER

1,2

1,1

1,0

0,9

0,8 6 7 8 9 10 11 12 13 14 15 16 17 °C

GLYcoL WATER AT 10%

Perdite di caricoPressure drop

ResaCapacity

PortataWater flow

Fa

tto

re d

i c

orr

ezio

ne

- C

orr

ec

tio

n f

ac

tor

1,2

1,1

1,0

0,9

0,8

0,7

0,6 6 7 8 9 10 11 12 13 14 15 16 17 °C

GLYcoL WATER AT 20%

Perdite di caricoPressure drop

ResaCapacity

PortataWater flow

Fatt

ore

di

co

rrezio

ne -

Co

rrecti

on

facto

r

1,6 1,5 1,4 1,3 1,2 1,1 1,0 0,9 0,8 0,7 0,6 0,5

6 7 8 9 10 11 12 13 14 15 16 17 18 °C

GLYcoL WATER AT 35%

Perdite di caricoPressure drop

ResaCapacity

PortataWater flow

Fatt

ore

di co

rrezio

ne -

Co

rrecti

on

facto

r

Page 23: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN23

10. coRREcTIoN FAcToRS IN hEATING oPERATIoN WITh GLYcoL WATER

1,4

1,3

1,2

1,1

1,0

0,6

0,830 40 50 60 70 80 90 °C

1

GLYcoL WATER AT 10%

Perdite di caricoPressure drop

ResaCapacity

PortataWater flow

Fa

tto

re d

i c

orr

ezio

ne

- C

orr

ec

tio

n f

ac

tor

1,4

1,3

1,2

1,1

1,0

0,6

0,830 40 50 60 70 80 90 °C

1

GLYcoL WATER AT 20%

Perdite di caricoPressure drop

ResaCapacity

PortataWater flow

Fatt

ore

di

co

rrezio

ne -

Co

rrecti

on

facto

r

1,4

1,3

1,2

1,1

1,0

0,6

0,830 40 50 60 70 80 90 °C

GLYcoL WATER AT 35%

Perdite di caricoPressure drop

ResaCapacity

PortataWater flow

Fatt

ore

di co

rrezio

ne -

Co

rrecti

on

facto

r

Page 24: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

24A_LIFE2_0102_1004_201306_EN

11. SoUNd PRESSURE LEVEL

sound pressure levels in semi-anechoic chamber 1 (m) from fan at front and 1 (m) above the floor

Modela-LIFE2

0102-0104 0202-0204 0302-0304 0402-0404 0502-0504 0602-0604 0702-0704 0802-0804 0902-0904 1002-1004

sound pressure level at the minimum air flow dB(A) 28 37 36 37 37 39 47 44 41 45

sound pressure level at the average air flow dB(A) 31 39 37 42 39 45 44 47 45 51

sound pressure level at the maximum air flow dB(A) 39 45 42 47 45 50 41 50 48 55

a-LIFE2 0102-0104 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 29,1 29,9 28,3 20,3 14,3 10,5 4,7Medium speed 29,6 31,2 30,4 24,0 20,2 12,3 1,3Maximum speed 36,6 38,2 37,6 32,6 29,7 24,7 14,4

a-LIFE2 0302-0304 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 38,3 35,4 36,3 30,2 25,6 17,6 10,8Medium speed 36,3 38,1 35,5 30,1 28,1 21,9 13,1Maximum speed 41,2 43,0 39,6 35,0 33,3 28,9 24,4

a-LIFE2 0402-0404 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 36,6 39,1 37,0 30,9 26,3 18,3 11,5Medium speed 42,0 43,8 41,2 35,8 33,8 27,6 18,8Maximum speed 46,6 48,4 44,6 39,7 38,0 33,6 29,1

a-LIFE2 0502-0504 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 36,5 38,5 37,9 28,6 25,3 20,7 15,1Medium speed 37,9 39,7 39,3 32,9 29,3 22,0 12,9Maximum speed 42,6 44,9 44,1 38,2 35,3 28,6 20,0

a-LIFE2 0202-0204 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 37,6 37,7 37,0 29,0 23,0 19,2 13,4Medium speed 38,3 39,2 39,1 32,7 28,9 21,0 10,0Maximum speed 43,3 44,1 44,3 39,3 36,4 31,4 21,1

a-LIFE2 0602-0604 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 38,2 40,2 39,6 30,3 27,0 22,4 16,8Medium speed 44,8 45,7 45,0 38,6 35,0 27,7 18,6Maximum speed 49,9 50,2 49,8 43,9 41,0 34,3 25,7

a-LIFE2 0702-0704 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 42,7 47,5 46,5 40,3 37,5 28,8 17,2Medium speed 38,5 42,8 42,5 37,9 35,8 30,7 21,3Maximum speed 37,4 41,0 39,3 35,1 34,2 29,5 22,2

a-LIFE2 0802-0804 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 39,7 44,5 43,5 37,3 34,5 25,8 14,2Medium speed 41,5 45,8 45,5 40,9 38,8 33,7 24,3Maximum speed 46,4 50,0 48,3 44,1 43,2 38,5 31,2

a-LIFE2 0902-0904 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 34,5 40,5 39,9 35,3 33,3 24,8 15,4Medium speed 39,3 42,5 41,9 40,9 37,2 31,9 23,4Maximum speed 43,8 47,6 45,5 42,1 40,7 37,1 29,5

a-LIFE2 1002-1004 125 hz 250 hz 500 hz 1 khz 2 khz 4 khz 8 khz

dB(A)

Minimum speed 34,2 40,2 39,6 35,0 33,0 24,5 15,1Medium speed 40,0 43,2 43,5 39,9 37,9 32,6 24,1Maximum speed 43,5 47,3 45,2 41,8 40,4 36,8 29,2

12. SoUNd PoWER LEVEL

sound power on the basis of measurements made in compliance with Eurovent 8/2

Modela-LIFE2

0102-0104 0202-0204 0302-0304 0402-0404 0502-0504 0602-0604 0702-0704 0802-0804 0902-0904 1002-1004

sound power level max. speed (2) dB(A) 48 54 51 56 54 59 56 59 57 64

sound power level med. speed (3) dB(A) 40 48 46 51 48 54 53 56 54 60

sound power level min. speed (5) dB(A) 37 46 45 46 46 48 50 53 50 54

Page 25: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN25

13. FANcoIL coNTRoLS

on board controls PS

The Ps control is used to regulate the airflow (3 speeds), select the summer/winter mode of operation and switch the fan-coil on/off andhot start function by minimun thermostat kit.

Function selector

Cooling

heating

off

Fan selector

Maximum fan speed

Medium fan speed

Minimum fan speed

Electrical connections

IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer)

ComBU RD WH BN GNYE

MaxMedMin

CMV

AU

TR

BU BN

YV2 BU BN

L

N L L L L L L

PEN

230V~50/60Hz

IG

1 2 3 4 5 6 7

123456789

10

YV1 2 1

J2 Acqua - Water BT2

GNYEBN BU

Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue

WHRD

Bianco - White Rosso – Red

L N PE

Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth

Com Min Med Max

Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)

MV C AUTR BT2

Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda acqua – Water sensor

ACCESSORI – ACCESSORIESYV1 YV2

Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve

J2

3 4 5 6 7

L L N

UNITÀ 2-TUBI: Eseguire questo collegamento sempre in caso di una sola valvola. 2-PIPES UNIT: Always carry out this connection when there is just one valve.

Valvola Valve7

8BN BU

Page 26: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

26A_LIFE2_0102_1004_201306_EN

13. FANcoIL coNTRoLS

on board controls MT

The MT control is used to regulate the air (3 speeds), the temperature through electronic thermostat, to select the summer/winter modeof operation and to switch the fan-coil on/off.

Temperature selector

Adjust the temperature as required by turning the temperature selectorfrom +14°C to 30°C.

Led description

Blue Led: indicates fan-coil thermostat call

Function selector

Cooling

heating

off

Fan selector

Maximum fan speed

Medium fan speed

Minimum fan speed

Electrical connections

IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer)

ComBU RD WH BN GNYE

MaxMedMin

CMV

AU

TR

BU BN

YV2 BU BN

L

N L L L L L L

PEN

230V~50/60Hz

IG

1 2 3 4 5 6 7

YV1 2 1

J2 Acqua - Water BT2

J1 Aria - Air BT1

J2

3 4 5 6 7

GNYEBN BU

Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue

WHRD

Bianco - White Rosso – Red

L N PE

Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth

Com Min Med Max

Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)

MV C AUTR BT1 BT2

Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda aria – Air sensor Sonda acqua – Water sensor

ACCESSORI – ACCESSORIESYV1 YV2

Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve

L L N

UNITA’ 2-TUBI: Eseguire questo collegamento sempre in caso di una sola valvola. 2-PIPES UNIT: Always carry out this connection when there is just one valve.

Valvola ValveBN

BU

123456789

10

78

Page 27: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN27

13. FANcoIL coNTRoLS

on board controls AT

The AT control is used to regulate the air (3 speeds + auto), the temperature through electronic thermostat, to select the summer/win-ter/auto mode of operation and to switch the fan-coil on/off.

Temperature selector

Adjust the temperature as required by turning the temperature selectorfrom +14°C to 30°C.

Function button

La scelta del modo di funzionamento è possibile tramite il pulsante

Mode led

Cooling

heating

off

Automatic setting

Speed button

select the fan speed pushing the button.The repeated pressure of fan button determines speed required.

Maximum fan speed

Medium fan speed

Minimum fan speed

Automatic fan speed

Led

Blue LED: heating / Cooling plus regulator callBlue LED blinking: hot start / Too Cool function active

Blue LED: operation in Cooling mode

Blue LED: operation in heating mode

Blue LED: automatic cooling / heating mode selection

Electrical connections

GNYEBN BU

Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue

WHRD BK

Bianco - White Rosso - Red Nero - Black

L N PE

Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth

Com Min Med Max

Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)

MV C AUTR BT1 BT2

Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda aria – Air sensor Sonda acqua – Water sensor

ACCESSORI – ACCESSORIESYV1 YV2

Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve

AT BUS-ADAPTER

Kit BUS-ADAPTER

TTL J5

TTL

BUS L N

230V~

AT GATEWAY

Kit GATEWAY

TTL J5

TTL

BUS BTICINO

IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer) SA1 Contatto multifunzionale (a cura del cliente) - Multifunctional contact (by the customer)

ComBU RD WH BN GNYE

MaxMedMin

CMV

AU

TR

BU BN

YV2 BU BN

L

N L L L L L L

PEN

230V~50/60Hz

IG

1 2 3 4 5 6 7

SA1 1312

123456789

10

YV1 2 1

J2 Acqua - Water BT2

J1 Aria - Air BT1

Page 28: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

28A_LIFE2_0102_1004_201306_EN

13. FANcoIL coNTRoLS

PSW wall-mounted control

The PsW control is used to regulate the airflow (3 speeds), select the summer/winter mode of operation and switch the fan-coil on/offand hot start function by minimun thermostat kit.

Function selector

Cooling

heating

off

Fan selector

Maximum fan speed

Medium fan speed

Minimum fan speed

Electrical connections

GNYEBN BU

Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue

WHRD

Bianco - White Rosso – Red

L N PE

Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth

Com Min Med Max

Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)

MV C AUTR BT2

Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda acqua – Water sensor

ACCESSORI – ACCESSORIESYV1 YV2

Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve

J2

3 4 5 6 7

L L N

UNITA’ 2-TUBI: Eseguire questo collegamento sempre in caso di una sola valvola. 2-PIPES UNIT: Always carry out this connection when there is just one valve

Valvola Valve7

8BN BU

Acqua - Water BT2 98

IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer)

ComBU RD WH BN GNYE

MaxMedMin

CMV

AU

TR

BU BN

YV2 BU BN

L

N L L L L L L

PEN

230V~50/60Hz

IG

1 2 3 4 5 6 7

123456789

10

YV1 2 1

Page 29: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN29

13. FANcoIL coNTRoLS

MTW wall-mounted control

The MTW control is used to regulate the air (3 speeds), the temperature through electronic thermostat, to select the summer/wintermode of operation and to switch the fan-coil on/off.

Temperature selector

Adjust the temperature as required by turning the temperature selectorfrom +14°C to 30°C.

Led

Blue Led: indicates fan-coil thermostat call

Function selector

Cooling

heating

off

Fan selector

Maximum fan speed

Medium fan speed

Minimum fan speed

Electrical connections

IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer)

ComBU RD WH BN GNYE

MaxMedMin

CMV

AU

TR

BU BN

YV2 BU BN

L

N L L L L L L

PEN

230V~50/60Hz

IG

1 2 3 4 5 6 7

YV1 2 1

J2

3 4 5 6 7

GNYEBN BU

Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue

WHRD

Bianco - White Rosso – Red

L N PE

Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth

Com Min Med Max

Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)

MV C AUTR BT1 BT2

Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda aria – Air sensor Sonda acqua – Water sensor

ACCESSORI – ACCESSORIESYV1 YV2

Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve

L L N

UNITA’ 2-TUBI: Eseguire questo collegamento sempre in caso di una sola valvola. 2-PIPES UNIT: Always carry out this connection when there is just one valve.

Valvola ValveBN

BU

123456789

10

78

Acqua - Water BT2 98

Page 30: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

30A_LIFE2_0102_1004_201306_EN

13. FANcoIL coNTRoLS

ATW wall-mounted control

The ATW control is used to regulate the air (3 speeds + auto), the temperature through electronic thermostat, to select the summer /winter / auto mode of operation and to switch the fan-coil on / off.

Electrical connections

GNYEBN BU

Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue

WHRD BK

Bianco - White Rosso - Red Nero - Black

L N PE

Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth

Com Min Med Max

Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)

MV C AUTR BT1 BT2

Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer Sonda aria – Air sensor Sonda acqua – Water sensor

ACCESSORI – ACCESSORIESYV1 YV2

Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve

AT BUS-ADAPTER

Kit BUS-ADAPTER

TTL J5

TTL

BUS L N

230V~

AT GATEWAY

Kit GATEWAY

TTL J5

TTL

BUS BTICINO

3 4 5 6 7

L

Collegamento con accessorio Resistenza elettrica Connection with accessory Electrical heater

L N

230V~50/60Hz

BKResist.el. – El.heater Relay

WH RD

BU BU

TS1 TS2

Power Min = BK-RD Power Max = WH-RD Termostati Sicurezza:

TS1 riamo automatico TS2 riarmo manuale

Safety Thermostats: TS1 automatic resetTS2 manual reset

910

11

12

IG Interruttore di protezione (a cura del cliente) - Thermomagnetic switch (by the customer) SA1 Contatto multifunzionale (a cura del cliente) - Multifunctional contact (by the customer)

ComBU RD WH BN GNYE

MaxMedMin

CMV

AU

TR

BU BN

YV2 BU BN

L

N L L L L L L

PEN

230V~50/60Hz

IG

1 2 3 4 5 6 7

123456789

10

YV1 2 1

SA1 1312

Acqua - Water BT2 98

Temperature selector

Adjust the temperature as required by turning the temperature selectorfrom +14°C to 30°C.

Function selector

select the mode of operation pushing the button.

Mode led

Cooling

heating

off

Automatic setting

Speed button

select the fan speed pushing the button.The repeated pressure of fan button determines speed required.

Maximum fan speed

Medium fan speed

Minimum fan speed

Automatic fan speed

Led

Blue LED: heating / Cooling plus regulator callBlue LED blinking: hot start / Too Cool function active

Blue LED: operation in Cooling mode

Blue LED: operation in heating mode

Blue LED: automatic cooling / heating mode selection

Page 31: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN31

14. ACCESSORIES

LIFE2 BOX

Kit composed by formwork, cover panel, frame and manual flap.

All components are in galvanised steel varnished finish. Life2

Box is placed in the wall niche arranging in advance hydraulic

connections. At work finished the fan-coil is positionate inside

the structure.

Main coil 2-way valve unit 1/2" and 3/4" kit

Kit with copper fittings and electromechanical actuator (oN-

off) 230V, PWM, 0-10V and suitable for 2-pipe systems.

This kit may be used to stop the flow of water of the main coil in

the fan coils. The electromechanical actuator is NC.

Additional coil 2-way valve unit 1/2" kit

Kit with copper fittings and electromechanical actuator (oN-

off) 230V, PWM, 0-10V and suitable for 4-pipe systems.

This kit may be used to stop the flow of water of the additional

coil in the fan coils. The electromechanical actuator is NC.

Main coil 3-way valve unit with by-pass way (4 idraulic con-

nections) 1/2" and 3/4” kit

Kit with copper fittings and electromechanical actuator (oN-

off) 230V, PWM, 0-10V and suitable for 2-pipe systems.

This kit may be used to divert the flow of water of the main coil

in the fan coils. The electromechanical actuator is NC.

Additional coil 3-way valve unit with by-pass way (4 idraulic

connections) 1/2" kit

Kit with copper fittings and electromechanical actuator (oN-

off) 230V, PWM, 0-10V and suitable for 4-pipe systems.

This kit may be used to divert the flow of water of the additional

coil in the fan coils. The electromechanical actuator is NC.

Water circuit kits

Water circuit kits complete with copper pipes and 2 ball valves,

only available as accessories, not fitted on the unit.

Hot water coil kit

The additional hot water 1 row is installed on top of the main

coil in the four-pipe systems. Using the controls with the addi-

tional coil valve kit, the additional coil may be regulated by

selecting the suitable mode of operation.

Straight plenum kit for air outlet

Made in galvanised sheet metal, this kit allows air conveyance

into ducts in horizontal and vertical built-in installations.

Angular plenum kit for air outlet (90°)

Made in galvanised sheet metal, this kit allows air conveyance

into ducts lying at 90° to the fan coil outlet. Suitable for horizon-

tal and vertical built-in installations.

Plenum kit with roud air ducts

Made in galvanised sheet metal, this kit allows air conveyance

into round ducts in horizontal and vertical built-in installations.

Straight plenum kit for air inlet

Made in galvanised sheet metal, this kit allows air conveyance

into ducts in horizontal and vertical built-in installations.

Angular plenum kit for air inlet (90°)

Made in galvanised sheet metal, this kit allows air conveyance

into ducts lying at 90° to the fan coil outlet. Suitable for horizon-

tal and vertical built-in installations.

Pair of decorative and structural feet

Plastic feet, granting a uniform colour and design, with cabinet.

This kit supports fan coil with cabinet.

Rear panel for vertical housing kit

This kit covers the back side of the fan coil with cabinet. it is

necessary to installation separate from the wall. The user can

not access to the terminal block.

Horizontal Fan Coil auxiliary tray

Made in thermoplastic material, this tray collects the conden-

sate that forms during summer operation. The kit is suitable for

horizontal fan coil installations.

Vertical Fan Coil auxiliary tray

Made from insulated galvanised sheet metal, this pan collects

the condensate that forms during cooling operation.

Interface SPB kit

The SPB interface kit is used for multiple connection of hydronic

terminal units, which may be managed with a single control. for

correct installation, install an SPB interface on every terminal

unit.

Hose kit

The hose kit is a manifold coupling for connecting the fan coil to

the main water system.

Air intake grid with filter

Grid with simple filter removal in order to easify cleaning main-

tenance without access directly to the fan coil installed into the

duct.

Air outlet grid

Grid with orientable louvers for installation in ducted system.

Manual damper kit for fresh air intake.

This kit is used to control the external fresh air that is put into

the room. The quantity of air put into the room varies from 0 to

approx. 30% of the volume handled by the fan coil.

Motor drive for external air intake lock

Motor drive for automatic adjustment of the fresh air intake lock

or damper.

Air intake grille for enclosed versions

Used to mask the lower part of the fan coil.

Page 32: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

32A_LIFE2_0102_1004_201306_EN

14. AccESSoRIES

LIFE2 BoX

LiFE2 BoX is a wall-mounted accessory that allows users to pre-pare the fan coil water and electrical connections in advance. The fan coil is fitted inside the structure when the work has beencompleted, thus simplifying the operations to be performed onsite.

• The kit consists of a galvanised sheet metal structure, frontclosing panel and frame with manually adjustable flap. The kit isavailable in the galvanised sheet metal version and the coatedversion (RAL9010).

• LiFE2 BoX can house LiFE2 fan- coils, DLi version: low airinlet, vertical outlet. it is available for sizes 102÷602 - 104÷604.

739

103

40

40A

70

min. 240-max.247

660

B

240

206

7

1012

102

740

Modelli

LIFE2

0102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

A (mm) 812 812 1012 1012 1212 1212B (mm) 740 740 940 940 1140 1140

Page 33: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN33

14. AccESSoRIES

VALVE KIT ModULANTING 0-10V - 2 WAYS 1/2” FITTINGS

The water flow to be diverted for fan coil. Main coil or additionalcoil 2-ways valve kit allow valve unit 0-10V could be manageddirectly with Climaveneta's controls; install hB power board withcontrol board 0-10V on fan-coil's side.

2 WAYS MAIN coIL KIT VALVE 1/2" ANd

ModULANTING AcTUAToR 0-10V

2 WAY AddITIoNAL coIL KIT VALVE 1/2"

ANd ModULANTING AcTUAToR 0-10V

2 WAY MAIN ANd AddITIoNAL coIL KIT

VALVE WITh BY PASS 1/2”-1/2” ANd

ModULANTING AcTUAToR 0-10V

VALVE KIT ModULANTING 0-10V - 2 WAYS 3/4” FITTINGS

The water flow to be diverted for fan coil. Main coil or additionalcoil 2-ways valve kit allow valve unit 0-10V could be manageddirectly with Climaveneta's controls; install hB power board withcontrol board 0-10V on fan-coil's side.

2 WAYS MAIN coIL KIT VALVE 3/4" ANd

ModULANTING AcTUAToR 0-10V

2 WAY AddITIoNAL coIL KIT VALVE 3/4"

ANd ModULANTING AcTUAToR 0-10V

2 WAY MAIN ANd AddITIoNAL coIL KIT

VALVE WITh BY PASS 1/2”-3/4” ANd

ModULANTING AcTUAToR 0-10V

Page 34: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

34A_LIFE2_0102_1004_201306_EN

14. AccESSoRIES

MAIN coIL VALVE KIT - 2 WAY - 1/2" FITTINGS

(oN/oFF - PWM)

This valve kit allows the main coil water flow to be diverted forfan coil with centrifugal fan.

2 WAYS MAIN coIL KIT VALVE 1/2"

+ AcTUAToR 230V

2 Way additional Coil Kit valve 1/2"

+ aCtUatoR 230v

2 Way Main and additional Coil Kit

valve With by Pass 1/2''-1/2'' + aCtUa-

toR 230v

MAIN coIL VALVE KIT - 2 WAY - 3/4" FITTINGS

(oN/oFF - PWM)

This valve kit allows the main coil water flow to be diverted forfan coil with centrifugal fan.

2 WAYS MAIN coIL KIT VALVE 3/4” 2 WAY AddITIoNAL coIL KIT VALVE 1/2” 2 WAY MAIN ANd AddITIoNAL coIL KIT

VALVE WITh BY PASS 3/4” ANd 1/2”

Page 35: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN35

14. AccESSoRIES

VALVE KIT ModULANTING 0-10V - 3 WAYS - 1/2” FITTINGS

The water flow to be diverted for fan coil. Main coil or additionalcoil 3-ways valve kit allow valve unit 0-10V could be manageddirectly with Climaveneta's controls; install hB power board withcontrol board 0-10V on fan-coil's side.

3 WAYS MAIN coIL KIT VALVE 1/2" + BY-

PASS 1/2” + ModULANTING AcTUAToR

0-10V

3 WAY AddITIoNAL coIL KIT VALVE 1/2" +

BY-PASS 1/2” + ModULANTING AcTUA-

ToR 0-10V

3 WAY MAIN ANd AddITIoNAL coIL KIT

VALVE WITh BY PASS 1/2”-1/2” +

ModULANTING AcTUAToR 0-10V

VALVE KIT ModULANTING 0-10V - 3 WAYS - 3/4” FITTINGS

The water flow to be diverted for fan coil. Main coil or additionalcoil 3-ways valve kit allow valve unit 0-10V could be manageddirectly with Climaveneta's controls; install hB power board withcontrol board 0-10V on fan-coil's side.

3 WAYS MAIN coIL KIT VALVE WITh BY

PASS 3/4" ANd ModULANTING AcTUA-

ToR 0-10V

3 WAY AddITIoNAL coIL KIT VALVE WITh

1/2" BYPASS ANd ModULANTING AcTUA-

ToR 0-10V

3 WAY MAIN ANd AddITIoNAL coIL KIT

VALVE WITh BY PASS 3/4” ANd 1/2” ANd

ModULANTING AcTUAToR 0-10V

Page 36: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

36A_LIFE2_0102_1004_201306_EN

14. AccESSoRIES

MAIN coIL VALVE KIT - 3 WAY - 1/2" FITTINGS

(oN/oFF - PWM)

The valve kit allows the main coil water flow to be diverted forfan coil with centrifugal fan.

3 WAYS MAIN coIL KIT VALVE WITh 1/2"

BYPASS + AcTUAToR

3 WAYS AddITIoNAL coIL KIT VALVE

WITh BY PASS 1/2" + AcTUAToR

3 WAY MAIN ANd AddITIoNAL coIL KIT

VALVE WITh BY PASS 1/2”-1/2'' + AcTUA-

ToR

MAIN coIL VALVE KIT - 3 WAY - 3/4" FITTINGS

(oN/oFF - PWM)

The valve kit allows the main coil water flow to be diverted forfan coil with centrifugal fan.

3 WAY AddITIoNAL coIL KIT VALVE WITh

1/2" BYPASS

3 WAYS MAIN coIL KIT VALVE WITh BY

PASS 3/4"

3 WAY MAIN ANd AddITIoNAL coIL KIT

VALVE WITh BY PASS 3/4” ANd 1/2''

Page 37: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN37

14. AccESSoRIES

WATER KIT FoR 2-WAYS VALVE 1/2" FITTING WATER KIT FoR 2-WAYS VALVE 3/4" FITTING

WATER KIT FoR 3-WAYS VALVE + BY-PASS 1/2" FITTING WATER KIT FoR 3-WAYS VALVE + BY-PASS 3/4" FITTING

AddITIoNAL hoT WATER coIL KIT

This accessory kit is used for heating mode in four-pipe systems.

Page 38: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

38A_LIFE2_0102_1004_201306_EN

14. AccESSoRIES

AIR SUPPLY PLENUM KIT

The plenum kit allows connection to the ductwork.

A

166

100

B

C

141

A140

200

STRAIGhT PLENUM

90° PLENUM

a-LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) 425 425 625 625 825 825 1025 1025 1225 1225c (mm) 437 437 637 637 837 837 1037 1037 1237 1237

description Qty.

straight plenum 1

self-tapping screws Ø 3.5x9.5 4

a-LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 400 400 600 600 800 800 1000 1000 1200 1200

description Qty.

90° plenum 1

self-tapping screws Ø 3.5x9.5 4

A

215

150

B

RoUNd PIPES PLENUM Ø 160-180-200

a-LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) / / 300 300 400 400 350 350 300 300N. pipes 1 1 2 2 2 2 3 3 4 4

description Qty.

Round pipes plenum 1

self-tapping screws Ø 3.5x9.5 4

Page 39: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN39

14. AccESSoRIES

STRAIGhT PLENUM:

Made of galvanized steel, it is used to convery the air supply on the concealed units. optional suitable for installation on all concealedversions without cabinet.

90° PLENUM:

Made of galvanized steel, it is used to convery the air supply on the concealed units. optional suitable for installation on all concealedversions without cabinet.

Dimensioni in mm Dimensions in mm

L 200

Flangia da 15 mm 15 mm flange

140

H =

450

14

0

15 L 15

15

H = 450 90

S =

215

Flangia da 15 mm15 mm flange

50

110 21

5

15

90

140 15

15 L 15

200

15

90° PLENUM (PM 90°)

Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000

Dimensions L (mm) 400 600 800 1000 12002 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004

L

100

140

Flangia da 15 mm 15 mm flange

Dimensioni in mm Dimensions in mm

15 L 15

140

15

15

H =

450

10

0 15 L 15

H = 450 100

140

S =

215 60

15

15

Flangia da 15 mm15 mm flange

STRAIGhT PLENUM (PM)

Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000

Dimensions L (mm) 400 600 800 1000 12002 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004

Page 40: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

40A_LIFE2_0102_1004_201306_EN

14. AccESSoRIES

RoUNd PIPES PLENUM:

Made of galvanized steel + internal Thermal-acoustic insulation. it is used to convery the air supply on the concealed units. optional suitablefor installation on all concealed versions without cabinet.

Dimensioni in mm Dimensions in mm

L 150

No. x Ø 160-180-200

A/2 15 A A/2 15 L

H =

450

50

150

215

= =

H = 450 150

Ø 2

00

S =

215

140

Ø 2

15

Ø 1

60

Ø 1

80

4545

RoUNd PIPES PLENUM Ø 160-180-200

Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000

Dimensions A (mm) / 300 400 350 300Dimensions L (mm) 400 600 800 1000 1200N° x d. (mm) 1x 2x 2x 3x 4x2 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004Spigots (made of plastic material): Ø 160, 180, 200

Page 41: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN41

14. AccESSoRIES

PLENUM KIT FoR AIR oUTLET

The plenum kit allows connection to the ductwork.

A

166

100

B

C

141

A140

200

STRAIGhT PLENUM

90° PLENUM

a-LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) 425 425 625 625 825 825 1025 1025 1225 1225B (mm) 437 437 637 637 837 837 1037 1037 1237 1237

description Qty.

Straight plenum 1

self-tapping screws Ø 3.5x9.5 4

a-LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 400 400 600 600 800 800 1000 1000 1200 1200

description Qty.

90° plenum 1

self-tapping screws Ø 3.5x9.5 4

A

215

150

B

RoUNd PIPES PLENUM Ø 160-180-200

a-LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) / / 300 300 400 400 350 350 300 300N. pipes 1 1 2 2 2 2 3 3 4 4

description Qty.

Round pipes plenum 1

self-tapping screws Ø 3.5x9.5 4

Page 42: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

42A_LIFE2_0102_1004_201306_EN

14. AccESSoRIES

STRAIGhT PLENUM:

Made of galvanized steel, it is used to convery the air intake on the concealed units. optional suitable for installation on all concealedversions without cabinet.

90° PLENUM:

Made of galvanized steel, it is used to convery the air intake on the concealed units. optional suitable for installation on all concealedversions without cabinet.

Dimensioni in mm Dimensions in mm

L

200

Flangia da 15 mm 15 mm flange

140

H =

450

14

0

15 L 15 15

Flangia da 15 mm 15 mm flange

H = 450

S =

215

15

90

215 90

11

0

50

140 15

15 L 15

200

15

90° PLENUM (PM 90°)

Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000

Dimensions L (mm) 400 600 800 1000 12002 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004

Dimensioni in mm Dimensions in mm

100

L

140

Flangia da 15 mm 15 mm flange

Flangia da 15 mm 15 mm flange

H = 450

37,5

S =

215

15

15

100

140

37,5

H =

450

10

0

15 L 15

15 L 15

140

15

15

STRAIGhT PLENUM (PM)

Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000

Dimensions L (mm) 400 600 800 1000 12002 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004

Page 43: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN43

14. AccESSoRIES

RoUNd PIPES PLENUM:

Made of galvanized steel + internal Thermal-acoustic insulation. it is used to convery the air intake on the concealed units. optional suitablefor installation on all concealed versions without cabinet.

Dimensioni in mm Dimensions in mm

150

L

215

A/2 15 A A/2 15 L

H =

450

50

15

0 45

45

H = 450

Ø 2

00

215

140

S =

215

= =

150

Filtro aria Air filter

Ø 1

60

Ø 1

80

No. x Ø 160-180-200

RoUNd PIPES PLENUM Ø 160-180-200

Model LIFE2 100-200 LIFE2 300-400 LIFE2 500-600 LIFE2 700-800 LIFE2 900-1000

Dimensions A (mm) / 300 400 350 300Dimensions L (mm) 400 600 800 1000 1200N° x d. (mm) 1x 2x 2x 3x 4x2 pipe system (1 coil) LiFE2 102-202 LiFE2 302-402 LiFE2 502-602 LiFE2 702-802 LiFE2 902-10024 pipe system (2 coil) LiFE2 104-204 LiFE2 304-404 LiFE2 504-604 LiFE2 704-804 LiFE2 904-1004Spigots (made of plastic material): Ø 160, 180, 200

Page 44: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

44A_LIFE2_0102_1004_201306_EN

14. AccESSoRIES

FEET KIT

The feet kit allows the fan coils with housing to be placed on theground.

REAL PANEL FoR VERTIcAL hoUSING

This accessory kit covers the back side of the fan coil with cabi-net.

AUXILIARY coNdENSATE TRAY KIT FoR hoRIZoNTAL

INSTALLATIoN

The auxiliary condensate tray is designed to collect the conden-sate which forms on coil connections during operation in thecooling mode.

100

186,5 186,5 232,7

AUXILIARY coNdENSATE TRAY KIT FoR VERTIcAL

INSTALLATIoN

The auxiliary condensate tray is designed to collect the conden-sate which forms on coil connections during operation in thecooling mode.

d

Page 45: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN45

14. AccESSoRIES

71 mm 60 mm

mm 09

SPB INTERFAcE KIT

SIGILLARECON MASTICEDI TENUTA

SEAL WITHMASTIC SEALING

hoSE coNNEcTIoN KIT

The hose kit is a header connection for connecting the fan coilto the mains water supply.

AIR INTAKE GRId WITh FILTER

Kit accessory for air inlet of duct system. Accessory is providedwith air filter.

70 80

1018

0

B

A

130

GRIGLIA / GRILLEFILTRO ARIA / AIR FILTER

TELAIO DI CONTENIMENTO FILTROFRAME FILTER

a-LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) 450 450 650 650 850 850 1050 1050 1250 1250

Page 46: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

46A_LIFE2_0102_1004_201306_EN

DAMPER MOTOR

2 X 6MA NUTS FORFASTENING ON THE PIN

FASTEN THE DAMPER OPENINGWITH THE Ø3.9X9.5 SCREW

14. AccESSoRIES

AIR oUTLET GRILLE

Kit accessory is used for air outlet in duct system. Air grille hasadjustable louvers.

FRESh AIR INTAKE dAMPER KIT

La serranda di ripresa aria può essere installata nei fan-coilLiFE2 con ripresa aria inferiore in versione mantellata o incasso.

KIT A – Manual fresh air intake damper kit. The kit is used toadjust the amount of fresh air introduced into the environment.The amount of fresh air introduced varies from 0 to approx. 30%of the volume handled by the fan coil.

KIT B – Motorised fresh air intake damper kit.Motor for motorised damper position adjustment. The two kits are supplied separately with their own productcodes. The air intake damper can be installed on LiFE2 fan coilswith air intake from below, in the version with casing or built-in.KIT c – Motor for fresh air intake damper

45

130

B

180

A

8011

a-LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 400 400 600 600 800 800 1000 1000 1200 1200B (mm) 450 450 650 650 850 850 1050 1050 1250 1250

KIT A (manual damper) KIT B (motorised damper)

dAMPER FoR UNITS WITh cASING

KIT A (manual damper) KIT B (motorised damper)

dAMPER FoR BUILT-IN UNITS

FISSARE VITE DA Ø3,9x9,5IN BASE ALL'APERTURADELLA SERRANDA

MOTORE SERRANDA

Nr.2 DADI da 6MAFISSAGGIO SU PERNO

Page 47: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN47

14. AccESSoRIES

“MRS1” TERMINAL BLocK KIT FoR ASYNchRoNoUS Fc

• Terminal block featuring a number of terminals based on unit configuration (min. PE+1+2+3+4) ; (max PE+….12)• Wiring according to the requirements of the configuration

Power Min = BK-RD Power Max = WH-RD Termostati Sicurezza:

TS1 riamo automatico TS2 riarmo manuale

Safety Thermostats: TS1 automatic resetTS2 manual reset

GNYEBN BU

Giallo/Verde-Yellow/Green Marrone - Brown Blu - Blue

WHRD BK

Bianco - White Rosso - Red Nero - Black

L N PE

Fase (linea 230V~) - Phase (230V~line) Neutro - Neutral Terra - Earth

Com Min Med Max

Comune ventilatore - Common of the fan Velocità Minima - Min. speed (Low) Velocità Media - Med. speed (Medium) Velocità Massima - Max. speed (High)

MV C AUTR

Motore ventilatore – Fan motor Condensatore – Capacitor Autotrasformatore – Autotransformer

ACCESSORI – ACCESSORIESYV1 YV2

Valvola batteria principale – Main coil valve Valvola batteria aggiuntiva – Secondary coil valve

A CURA DEL CLIENTE - BY THE CUSTOMERCR IG

Comando remoto - Remote control Interruttore di protezione - Thermomagnetic switch

Collegamento con accessorio Resistenza elettrica

Connection with accessory Electrical heater

230V

~50/

60Hz

BK

Resist.el.El.heater Relay

WH RD

BU BU

TS1 TS2

9101112

ComBU RD WH BN GNYE

MaxMedMin

CMV

AU

TR

BU BN

YV2 BU BN

IG

123456789

10

YV1

L L L N

L NL N

CR

L N

L N

NL

PE

230V

~50/

60Hz

Potenza - Power

Potenza - Power

AIR INTAKE GRId FoR WITh cABINET VERSIoN

Kit accessory allows to cover space between feet of LiFE2 fancoil. Air intake grid for with cabinet is suitable for DLMV version(with cabinet and bottom air inlet). Air intake grille is painted asfan coil cabinet’s colour (RAL 9003) ensuring suitable anddesired aesthetic solution.

A

B

100

LIFE20102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (mm) 922 922 1112 1112 1302 1302 1492 1492 1682 1692B (mm) 566 566 756 756 946 946 1136 1136 1326 1326

Page 48: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

48A_LIFE2_0102_1004_201306_EN

Fan coils have been designed and made for installation in heating and air-conditioning systems.

15. dIMENSIoNAL dATA ANd WATER coNNEcTIoNS (VERToIcAL VERSIoN)

450 1512030217

25 15

261134

450

12033669

175,

9

4212

0155178

Atta

cchi

idra

ulic

i

1/2'

' GF

Wat

er c

onne

ctio

ns 1

/2'' F

emal

e

120230

D

Ø10

Ø16

33

C

Ø20

2525

15 185,8 15,815

B15

A

Mo

dello

a-L

IFE

2

0102

0104

020

2

020

4

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (

mm

)43

043

063

063

083

083

010

3010

3012

3012

30

B (

mm

)40

040

060

060

080

080

010

0010

0012

0012

00

c (

mm

)45

045

065

065

085

085

010

5010

5012

5012

50

d (

mm

)42

542

562

562

582

582

510

2510

2512

2512

25

Page 49: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN49

Fan coils have been designed and made for installation in heating and air-conditioning systems.

15. dIMENSIoNAL dATA ANd WATER coNNEcTIoNS (hoRIZoNTAL VERSIoN)

25

261134

450

33669

4212

0155178

Atta

cchi

idra

ulic

i

1/2'

' GF

Wat

er c

onne

ctio

ns 1

/2'' F

emal

e

120230

D

Ø16

33

C

204,8

75

Ø20

3010630

105

40

E

E

210 3312

Ø10

1560

015

630

15,8185,815

Mo

dello

a-L

IFE

2

0102

0104

0202

0204

0302

0304

0402

0404

0502

0504

0602

0604

0702

0704

0802

0804

0902

0904

1002

1004

A (

mm

)43

043

063

063

083

083

010

3010

3012

3012

30

B (

mm

)40

040

060

060

080

080

010

0010

0012

0012

00

c (

mm

)45

045

065

065

085

085

010

5010

5012

5012

50

d (

mm

)42

542

562

562

582

582

510

2510

2512

2512

25

E (

mm

)54

554

574

574

594

594

511

4511

4513

4513

45

Page 50: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

50A_LIFE2_0102_1004_201306_EN

INVERTING ThE WATER coNNEcTIoNS

1

1

5

7

8

10

A

B

C

D

E

6

Premere sul fermoe ruotare per toglierel'imbuto

1211

F

G

14

H

3

2

4

13

15

14

9

WARNING! Run the electrical wiring on the opposite side to the final water connections.

Remove the transformer and the terminal block and reposition them on the opposite side.

If the controller is installed on the unit, remove the controller complete with fastening bracket.

If the room temperature probe cable is not long enough, move the room temperature probe to the opposite side.

INSTRUcTIoNS To MoVE ThE MAIN coIL FRoM LEFT To RIGhT oN VERTIcAL FAN coILS

A. Unscrew the 4 x Ø 3.9x9.5 screwsB. Remove the panel in the direction indicated by the arrow “2”. Unscrew the 4 x Ø 3.9x9.5 screws “3” that support the coil from the

left and right shoulders.c. slightly tilt the coil in the direction indicated by the arrow “4” and move it away from the left shoulder in the direction indicated by

arrow “5”.Press the catch that holds the funnel “6” to release it.

d. Move the coil from pos. 7 to pos. 8.E. open the knock-outs on the opposite shoulder “9”. insert the coil at an angle, as shown in the figure “10”, inserting the water con-

nections through the openings made.F. Tighten the 4 x Ø 3.9x9.5 screws in the holes aligning the shoulder - coil bracket “11”, on the right and left shoulders.

Remove the knock-out “12” and insert the funnel, making sure it is secured in place.G. Reposition the panel “13” and tighten the 4 x Ø 3.9x9.5 screws “14”.h. Use closed-cell insulation to cover in the holes left open on the left shoulder “15”.

INSTRUcTIoNS To MoVE ThE MAIN coIL FRoM RIGhT To LEFT oN VERTIcAL FAN coILS

To invert the position of the coil, follow the previous instructions, swapping the references to the right shoulder and left shoulder.

Page 51: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN51

INVERTING ThE WATER coNNEcTIoNS

A

1

1

B

2

3

6

7

9

D

E

10

F

G

H

12

5

C

4

12

13

8

11

96,5

WARNING! Run the electrical wiring on the opposite side to the final water connections.

Remove the transformer and the terminal block and reposition them on the opposite side.

If the controller is installed on the unit, remove the controller complete with fastening bracket.

If the room temperature probe cable is not long enough, move the room temperature probe to the opposite side.

INSTRUcTIoNS To MoVE ThE MAIN coIL FRoM LEFT To RIGhT oN hoRIZoNTAL FAN coILS:

A. Unscrew the 4 x Ø 3.9x9.5 screwsB. Remove the panel in the direction indicated by the arrow “2”. Unscrew the 4 x Ø 3.9x9.5 screws “3” that support the coil from the

left and right shoulders.c. slightly tilt the coil in the direction indicated by the arrow “4” and move it away from the left shoulder in the direction indicated by

arrow “5”.d. Move the coil from pos. 6 to pos. 7.E. open the knock-outs on the opposite shoulder “8”.

insert the coil at an angle, as shown in the figure “9”, inserting the water connections through the openings made.F. Tighten the 4 x Ø 3.9x9.5 screws in the holes aligning the shoulder - coil bracket “10”, on the right and left shoulders.G. Reposition the panel “11”, ensuring the distance of 96.5 mm, as shown in the figure.h. Tighten the 4 x Ø 3.9x9.5 screws “12”. Use closed-cell insulation to cover in the holes left open on the left shoulder “13”.

INSTRUcTIoNS To MoVE ThE MAIN coIL FRoM RIGhT To LEFT oN hoRIZoNTAL FAN coILS

To invert the position of the coil, follow the previous instructions, swapping the references to the right shoulder and left shoulder.

Page 52: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

52A_LIFE2_0102_1004_201306_EN

15. dIMENSIoNAL dATA (WITh cABINET VERSIoN)

a-LIFE2 dLMV 0102-0104 0202-0204 0302-0304 0402-0404 0502-0504 0602-0604 0702-0704 0802-0804 0902-0904 1002-1004

A mm 922 922 1112 1112 1302 1302 1492 1492 1682 1682B mm 566 566 756 756 946 946 1136 1136 1326 1326

100

A

599499

186,5 233

A

547

1112

Page 53: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

a-LIFE2

A_LIFE2_0102_1004_201306_EN53

The fan coil comes fully wired and only requires:

- Connecting to the mains electricity supply and to any room

control.

It is also recommended to check that:

- The characteristics of the mains electricity supply are suitable

for the input indicated in the table below, which (with maxi-

mum values) should serve for sizing both the circuit breakers

and the power cables (any other appliances working in paral-

lel should also be taken into consideration).

- The supply voltage corresponds to the rated value +/- 10%.

The following is compulsory:

Installation near the appliance of a delayed-action single-

pole linked magnetothermal circuit breaker, padlockable,

line isolating switch, in compliance with CEI-EN standards

(contact separation of at least 3 mm).

16. ELECTRICAL CONNECTIONS

Table electrical connections

Sizing table

a-LIFE2 Power supply Max. input (W) Max. absorbed current (A)

0102-0104 230 ~ 50 45 0,20

0202-0204 230 ~ 50 45 0,20

0302-0304 230 ~ 50 60 0,30

0402-0404 230 ~ 50 60 0,30

0502-0504 230 ~ 50 63 0,30

0602-0604 230 ~ 50 63 0,30

0702-0704 230 ~ 50 130 0,60

0802-0804 230 ~ 50 130 0,60

0902-0904 230 ~ 50 160 0,73

1002-1004 230 ~ 50 160 0,73

Sizing table with HEATER power 1

a-LIFE2 Power supply Max. input (W) Max. absorbed current (A)

0102-0104 230 ~ 50 1045 4,6

0202-0204 230 ~ 50 1045 4,6

0302-0304 230 ~ 50 1560 6,9

0402-0404 230 ~ 50 1560 6,9

0502-0504 230 ~ 50 2063 9,1

0602-0604 230 ~ 50 2063 9,1

0702-0704 230 ~ 50 3130 13,7

0802-0804 230 ~ 50 3130 13,7

0902-0904 230 ~ 50 3160 13,9

1002-1004 230 ~ 50 3160 13,9

Sizing table with HEATER power 1

a-LIFE2 Power supply Max. input (W) Max. absorbed current (A)

0102-0104 230 ~ 50 745 3,3

0202-0204 230 ~ 50 745 3,3

0302-0304 230 ~ 50 1060 4,7

0402-0404 230 ~ 50 1060 4,7

0502-0504 230 ~ 50 1563 6,9

0602-0604 230 ~ 50 1563 6,9

0702-0704 230 ~ 50 2130 9,4

0802-0804 230 ~ 50 2130 9,4

0902-0904 230 ~ 50 2160 9,5

1002-1004 230 ~ 50 2160 9,5

Page 54: a-LIFE2 - climacon · a-LiFE2 is provided with centrifugal fan, double intake and for-ward blades, powered by auto-trasformer with 6 speeds of which 3 are factory-set. other speeds

www.climaveneta.com

Climaveneta S.p.A. Via Sarson 57/c36061 Bassano del Grappa (VI)ItalyTel +39 0424 509 500Fax +39 0424 509 [email protected]

Climaveneta France 3, Village d’EntreprisesZA de la Couronne des PrésAvenue de la Mauldre78680 EpôneFranceTel +33 (0)1 30 95 19 19Fax +33 (0)1 30 95 18 [email protected]

Climaveneta Deutschland GmbHLyrenstraße 13 44866 Bochum Germany Tel +49 2327-95428-0 Fax +49 2327-95428-99 [email protected] www.climaveneta.de

Climaveneta España - Top Clima Londres 67, 1 4 08036 BarcelonaSpainTel +34 934 195 600Fax +34 934 195 [email protected]

Climaveneta Chat Union Refrig. Equipment Co Ltd88 Bai Yun Rd, Pudong XinghuoNew dev. zone 201419 ShanghaiChinaTel 008 621 575 055 66Fax 008 621 575 057 97

Climaveneta Polska Sp. z o.o. Ul. Sienkiewicza 13A,05-120 Legionowo,PolandTel +48 22 766 34 55-57Fax +48 22 784 39 [email protected]

Climaveneta Climate Technologies (P) Ltd #3487, 14th Main, HAL 2nd stage,Indiranagar, Bangalore 560008IndiaTel:+91-80-42466900 - 949, Fax: [email protected]

Climaveneta UK LTD. Highlands Road,Shirley SolihullWest Midlands B90 4NLTel: +44 (0)871 663 0664Fax: +44 (0)871 663 1664Freephone: 0800 801 [email protected]