A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Energy Postgraduate Conference 2013

Upload: clifton-preston

Post on 25-Dec-2015

239 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

A hybrid dephlegmator for incorporation into an air-cooled steam condenser

Michael Owen

Univ. of Stellenbosch/Dept. M&M Eng./STERG

Energy Postgraduate Conference 2013

Page 2: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

Overview

• Air-cooled condensers (ACCs): what, where, why?

• Hybrid (dry/wet) dephlegmator concept

• HDWD performance evaluation

• Concluding remarks

2

Page 3: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

ACCs: what, where, why?3

Page 4: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

ACCs: what, where, why? (cont.)

• Wet cooling using evaporative condensers

o Approximately ½ of all power plants in the U.S. use evaporative cooling¹

o 36 of the 37 major operating solar thermal power plants are wet cooled²

o Water intensive: >30 000 litres per day per MW installed³o Typically accounts for > 80 % of the water consumption at a plant4

The use of alternative means of cooling therefore holds the greatest potential for decreasing water consumption related to

electricity production

4

Page 5: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

5

ACCs: what, where, why? (cont.)

Page 6: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

• ACCs use ambient air to cool and condense the process fluid• No water is directly consumed in the cooling process

o ACCs are therefore an attractive option considering current global water security concerns

o ACCs allow for flexibility in plant location Location not constrained by proximity to water resources Plants can be built nearer fuel/energy supplies or load centers →

increased reliability and reduced transmission costs

6

ACCs: what, where, why? (cont.)

• ACCs experience a reduction in cooling effectiveness at high ambient temperatureso Q α Tv - Ta

• A dynamic relationship exists between condenser and turbine performance

• Reduced cooling effectiveness → decreased plant output on hot days

Page 7: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

• Replace conventional dephlegmator with a HDWD

• Originally proposed by Heyns and Kröger5

• 2 stages connected in series:o 1st stage – ACC (inclined finned

tubes)o 2nd stage – hybrid plain tube bundle

• 2nd stage operation:o Low ambient temperatures → DRYo High ambient temperatures → WET

• Wet modeo Both latent and sensible heat

transfero Measurably enhanced air-side heat

transfer coefficient

7

Hybrid (dry/wet) dephlegmator

Conventional

Hybrid

Page 8: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

8

HDWD performance evaluation

• 3 street ACC with a HDWD (operating wet) provides the same turbine output benefits as:o A 33% over-sized ACC (4 streets vs 3) - at a much

reduced costo A conventional ACC with spray cooling enhancement –

while consuming 20 % - 30 % less water and avoiding fouling and corrosion issues

Page 9: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

• One-dimensional performance analysis to identify the best configuration for the 2nd stage HDWD bundle

• More rows of smaller diameter tubes in a multipass arrangement with a single tube row in the final passo Highest heat transfer rates (up to 35% increase for

an ACC)o Lowest ejector loadingo Slightly higher water consumption (although still

negligible compared to an evaporative cooler)o Higher steam-side pressure drops

9

HDWD performance evaluation (cont.)

A B C D E F G H I J K

Tube dia., mm 38.1 38.1 38.1 38.1

19.0 19.0

19.0 19.0

19.0 19.0

19.0

No. of tube rows

16 16 16 16 16 16 16 16 25 25 25

No. of tubes/row

156 156 156 156 314 314 314 314 314 314 314

No. of passes 3 12/3/1

213/2

214/1

115

3 12/3/1

213/2

214/1

115

320/5/

1

220/5

125

38.1 19.0

16 16 25

Page 10: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

• While ACCs offer water consumption advantages over evaporative cooling towers they experience decreased performance during hot periods

• Alternative and enhancement strategies have thus far proven problematic

• A novel hybrid dephlegmator concept is proposed that:

o Offers enhanced cooling performance

o While consuming only a small amount of water

o Is able to reduce the load on the ejector

o Simple and cost effective

• Experimental data is required to fully quantify the exact performance characteristics of the HDWD

10

Concluding remarks

Page 11: A hybrid dephlegmator for incorporation into an air-cooled steam condenser Michael Owen Univ. of Stellenbosch/Dept. M&M Eng./STERG Michael Owen Univ. of

References1. Carney B, Feeley T, McNemar A. NETL Power Plant Water Research

Program. EPRI Workshop on Advanced Thermoelectric Cooling Technologies 2008; Charlotte NC.

2. NREL 2010: http://www.nrel.gov/csp/solarpaces/project_detail.cfm/projectID=6

3. Gadhamshetty V, Nirmalakhandan N, Myint M, Ricketts C. Improving Air-cooled Condenser Performance in Combined Cycle Power Plants. J Energy Eng 2006; 132/2:81-88.

4. DiFilippo M., Reclaiming Water for Cooling at SCE’s Mountainview Power Plant, Presentation: EPRI workshop on Advanced Thermoelectric Cooling Technologies, Charlotte, 2008.

5. Heyns, J.A., Krӧger, D.G., Performance characteristics of an air-cooled steam condenser with a hybrid dephlegmator, R&D Journal of the South African Institute of Mechanical Engineers, Vol. 28, pp. 31-36, 2012.