a bulletin 1102c 400a vacuum contactor vacuum interrupter ... · vacuum interrupter phase assembly...
TRANSCRIPT
ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.
42052-094G. Ushakow
N/A
N/A
N/A42052
10064901
INSTRUCTION SHEETBULLETIN 1102C 400A VACUUM CONTACTORVACUUM INTERRUPTER PHASE ASSEMBLY
REPLACEMENT
2-19-04
Mark Jutz 2-19-04
D. Josef 2-19-04
1 2
42052-104
REVISION AUTHORIZATION
DIMENSIONS APPLY BEFORESURFACE TREATMENT
H
A
B
C
D
E
F
G
(DIMENSIONS IN INCHES)TOLERANCES UNLESSOTHERWISE SPECIFIED
REFERENCE
SHEET OFDWG.
B
DR.
CHKD.
APPD.
DATE
DATE
DATE±
±
±
ANGLES:
.XXX:
.XX:
THIS DRAWING IS THE PROPERTY OF THE ALLEN-BRADLEY CO. INC.
AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT
AS AUTHORIZED IN WRITING BY THE ALLEN-BRADLEY CO. INC.
LOCATION : MILWAUKEE, WISCONSIN U.S.A.
SIZE
1 2 3 4 5 6 7 8
E - DOC
Bulletin 1102C 400A Vacuum Contactor Vacuum Interrupter Phase Assembly Replacement Instructions(Cat 1102-VB4)
Vacuum Interrupter Phase Assembly Replacement (Used with Vacuum Contactors: 1102C-COA93,-COB93, -COD93, -COG93, -COH93, -CON93)
Cover
Coil Leads
Control-Pak
Control-Pak
Disconnect Coil Wires from Control-Pak Disconnect Coil Wires
from Auxiliary
Auxiliary
VACUUM CONTACTOR
1. Disconnect all power cables (or bus work) and all control wiring to the contactor.
2. Remove the contactor from its mounted location. The contactor is best serviced in the tabletop position.
3. Remove the cover attachment hardware from the contactor and remove the cover (Figure 1).
4. Disconnect the coil wire leads from the Control-Pak or Auxiliary (Figure 2B).
5. Remove the Control-Pak from the contactor by first rotating the retainer to release the top tab of the Control-Pak. Then pull out the top of the Control-Pak (the tab must clear the notch) and then push Control-Pak slightly downward to release lower tab that holds the Control-Pak to the housing (Figures 2A & 2B).
This tab must clear notch priorto pushingControl-Pak downward.
Rotate retainer torelease Control-Pak
Figure 2A Figure 2B
AC Coil (With Control-Pak) Figure 1 DC Coil (With Auxiliary 1195C-N5)
VACUUM CONTACTOR
Note: The following instructions pertaining to the removal and reinstallation of the Control-Pak are applicable to the Auxiliary.
42052-094G. Ushakow
N/A
N/A
N/A42052
10064901
INSTRUCTION SHEETBULLETIN 1102C 400A VACUUM CONTACTORVACUUM INTERRUPTER PHASE ASSEMBLY
REPLACEMENT
2-19-04
Mark Jutz 2-19-04
D. Josef 2-19-04
2 2
REVISION AUTHORIZATION
DIMENSIONS APPLY BEFORESURFACE TREATMENT
H
A
B
C
D
E
F
G
(DIMENSIONS IN INCHES)TOLERANCES UNLESSOTHERWISE SPECIFIED
REFERENCE
SHEET OFDWG.
B
DR.
CHKD.
APPD.
DATE
DATE
DATE±
±
±
ANGLES:
.XXX:
.XX:
THIS DRAWING IS THE PROPERTY OF THE ALLEN-BRADLEY CO. INC.
AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT
AS AUTHORIZED IN WRITING BY THE ALLEN-BRADLEY CO. INC.
LOCATION : MILWAUKEE, WISCONSIN U.S.A.
SIZE
1 2 3 4 5 6 7 8
E - DOC
Vacuum Interrupter Phase Assembly Replacement (Cont'd)6. Locate the replacement Interrupter Phase Assembly that needs to be replaced. It is recommended that all three interrupters be replaced at the same time.
7. For the outer interrupters, remove the Retainer. While holding the Interrupter in position with the provided wrench, remove the screw from the line side terminal (Figure 3).
8. Remove the shunt screw from the load side terminal (See Section A-A). This will free the shunt. Carefully remove the interrupter assembly (Figure 4).
9. The replacement interrupter is factory set for contact gap and does not require adjustment. The flexible shunt will feed through the flexible shunt path in the molding of the contactor and the assembly can be pushed firmly back into place (See Figure 4 showing locations for applying hand pressure to snap interrupter into plastic molding), observe the adjacent phases to see precisely how this is positioned. While holding the Interrupter in position with the provided wrench, replace the line terminal screw (Figure 3). Replace the shunt connection hardware (Figure 4). Torque screw to 60 - 80 lb-inches.
10. Reinstall the Control-Pak (Figures 5A & 5B). First, insert the lower tab into the recess on the side of the contactor base. With proper installation, the Actuator will fit into the hole in the slot in the side of the contactor housing. Using a thin rod or flat blade, lift the Actuator up as necessary to insert it into the slot mentioned.
11. Reinstall the cover and secure it with the original mounting hardware. NOTE: Cover must fit under metal bracket on Control-Pak. Tighten the four screws in a diagonal pattern to 12 lb-inches. (Figure 1).
12. Reattach the coil wire leads and any auxiliary control wires to the Control-Pak (tighten to 7 lb-inches).
13. Reinstall the contactor. Torque mounting screws to 50 - 75 lb-inches.
14. Reconnect the line and load conductors and tighten the main terminal hardware and bolts to 180 - 210 lb-inches.
Figure 5A Figure 5B
42052-094-01 (1)Printed in U.S.A.
Figure 3 Figure 4
Shunt
Shunt
SECTION A-A
A
A
Special wrenchsupplied with kit
Retainer
Actuatormust fit into slot shown
Control-PakActuator
Auxiliary Control-Pak
Thin rod orflat blade
ShuntScrew
ShuntScrew
InterrupterPhase Assembly
TerminalScrew
Pressure points for interrupter installation
PARTNO. MATERIALCHG.
LTR. SIZEFLAT FOLD
-01 1ONE SIDE PRINTED
8-1/2" W x 11" HBODY STOCK WHITEBODY INK BLACK
4-1/4" W x 5-1/2" H