9.0 electrical systems · switchyard via nats (no fast transfer necessary) 6 • 4 trains • each...

15
9.0 Electrical Systems 1

Upload: others

Post on 30-Apr-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

9.0 Electrical Systems

1

Page 2: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

Objectives1. State the purposes of the following:

a. Emergency Power Supply System (EPSS)b. Normal Power Supply System System (NPSS)c. Class 1E Uninterruptible Power Supply System (EUPS)d 12 Hour Uninterruptible Power Supply System (12UPS)

2

d. 12-Hour Uninterruptible Power Supply System (12UPS)e. Non-Class 1E Uninterruptible Power Supply System

(NUPS)f. Station blackout diesel generators (SBODGs)

2. Describe the major differences between the electrical system design of the US-EPR and those of currently operating PWRs.

Page 3: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

EPSS• 6.9-kV buses always supplied from

switchyard via EATs (no fast transfer necessary)

• 4 divisions• Each EAT feeds 2 divisions• Each EAT is alternate to the other

3

Each EAT is alternate to the other• Alternate feed capability between divs. 1 &

2, 3 & 4• Each division has standby EDG• 2 diesels per EPGB• Each division can be supplied by an

SBODG via manual lineup

Page 4: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

Emergency Power (EPSS)

4Figure 9-1 (Sheet 1)

Page 5: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

• EAT• Standby EDGs• Connections to

SBODG

Figure 9-1 (Sht 1),Divisions 1 & 2

5

• Alternate feed (example)

Page 6: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

NPSS• Main generator supplies switchyard, but

not onsite distribution• 13.8-kV buses always supplied from

switchyard via NATs (no fast transfer necessary)

6

• 4 trains• Each NAT feeds 2 trains• Each NAT is also an alternate supply• 2 trains have SBODGs• Each SBODG-backed bus can supply either

of 2 EPSS divisions via manual lineup

Page 7: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

Normal Power (NPSS)

7Figure 9-3 (Sheet 1)

• Main Generator

• NATs• SBODGs• Connections

to EPSS

Page 8: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

EUPS

• Supplies safety-related loads

• 4 divisions supplied from EPSS

• Each division:– 2 100%-capacity 480-Vac/250-Vdc battery

h

8

chargers

– 250-Vdc 2-hr battery

– 250-Vdc/480-Vac inverter

– Several ac/dc & dc/dc converters

Page 9: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

Class 1E Uninterruptible Power Supply (EUPS)

9Fig. 9-2 (typical of all divisions)

Page 10: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

12UPS

• Supplies nonsafety-related loads– SBODG auxiliary loads & control power for

aligning SBODGs to NPSS & EPSS

– I&C support of severe accident mitigation

• 2 trains supplied from NPSS

10

• 2 trains supplied from NPSS

• Each train:– 480-Vac/250-Vdc battery charger (1 spare)

– 250-Vdc 12-hr battery

– 250-Vdc/480-Vac inverter

– Several ac/dc & dc/dc converters

Page 11: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

12-Hr Uninterruptible Power Supply (12UPS)

11

Fig. 9-4

Page 12: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

NUPS• Supplies nonsafety-related loads needed to

remain operational for investment protection

• 2 trains supplied from NPSS

• Each train:

12

Each train:– 480-Vac/250-Vdc battery charger (1 spare)

– 250-Vdc battery

– 250-Vdc/480-Vac inverter

– Several ac/dc & dc/dc converters

– Supplies CRDMs via 2 sets of in-series reactor trip breakers

Page 13: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

Non-Class 1E Uninterruptible Power Supply (NUPS)

13

Figure 9-5

Page 14: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

SBO Considerations

• Worst-case coping duration per RG 1.155: 8 hrs

• No coping analysis necessary; SBODGs meet 10CFR50.63 & RG 1.155 req’ts for lt t AC

14

alternate AC sources:

– Not normally connected

– Low potential for CCF with EDGs

– Can be connected to EPSS buses w/in 10 min

– Sufficient capacity for SBO coping

Page 15: 9.0 Electrical Systems · switchyard via NATs (no fast transfer necessary) 6 • 4 trains • Each NAT feeds 2 trains • Each NAT is also an alternate supply • 2 trains have SBODGs

SBODGs• Located in separate areas of the switchgear

building

• Separate support subsystems

• Start on undervoltage on associated NPSS buses

Manually loaded

15

• Manually loaded

• Major SBO loads:– Division 1 & 4 EFW pumps

– HVAC for MCR, SBO equipment

– Selected I&C

– MCR lighting

– MSRTs