7 construction details
TRANSCRIPT
-
8/10/2019 7 Construction Details
1/83
7.
7.1.1
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
Module Module
PVC sealing tape (factory applied) or Butylsealing tape (site applied)
Side lap stitching screw (P03)(at 500 mm)
Wall purlin
Vapour sealing putty when
required (site applied)
Self-adhesive sealant tape PE 205 mm to be continuously applied
between liner and steel support only at ridge/eaves/end lap locations where
the internal junction requires sealing (P17)
Module Module
PVC sealing tape (factory applied)
or Butyl sealing tape (site applied)
Roof purlin
Anti-condensation tape (factory applied)
Vapour sealing tape 6 mm when required (site applied)
Side lap stitching screw (P03)
(at 500 mm)
Self-adhesive sealant tape PE 205 mm to be
continuously applied between liner and steel
support only at ridge /eaves /end lap locations
where the internal junction requires sealing (P17)
Panel Side Lap (FF)
Panel Side Lap (RW)
-
8/10/2019 7 Construction Details
2/83
7.
7.1.2
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
102K
12P
07P
12P
04P
103aK
04P
12P
07P
14
P
101
K
14
P
03P
12P
102K
03P
a
at 333 mm at 333 mmSite applied
insulation
Back putty Back putty
Outer sheet
turned up
P
50
aa
50
21
P
17
P
18
P
04
P
03
P6 fasteners per end lap
Panel End Lap
Ridge
Note:
P Cut back dimensions:
for roof slope > 10% 200 mm (supplied / delivered to site with cut backs)
for roof slope 10% 250 mm (supplied / delivered to site with cut backs)
Maximum cut backs available on panels from Kingspan is 250 mm.
a according to structural / static requirements
Note:
a according to structural / static requirements
P12 for roof slope 10% 4 pcs / m> 10% 2 pcs / m
-
8/10/2019 7 Construction Details
3/83
7.
7.1.3
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
08
P
08
P
17
P
04
P
132
K
14
P
131K
02P
08P
17P
Site applied insulation
at 300 mm
at 300 mm at 300 mm
Gable
a
129K
08P
02P
03P
04P
07P
102K
12P
07P
14P
Outer sheet turned up
Site applied
insulation Back putty
at 300 mm
at 333 mm
Mono Ridge
Note:
a according to structural / static requirements
P12 for roof slope 10% 4 pcs / m> 10% 2 pcs / m
-
8/10/2019 7 Construction Details
4/83
7.
7.1.4
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
130K
08P
04P
17P
02P
D
L
03
P
14
P
08
P
137
K
132
K
105K
at 300 mm
Site applied
insulation
at 500 mm at 300 mm
104K
08P
14P
02
P
130K
08P
115K
12
P
07
P
03
P
12
P
102
K
04
P
07P a
D
L(250mm)
at 300 mm
at 300 mm
at 333 mm
Site applied insulation
Back putty
Outer sheet
turned up
Side Wall Parapet
Parapet in Slope Single
Note:
a according to structural / static requirements
P12 for roof slope 10% 4 pcs / m
> 10% 2 pcs / m
-
8/10/2019 7 Construction Details
5/83
7.
7.1.5
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
04P
130K
08P
04P
07P
14P
167K
04P
04P
08
P
04P
04P
14P
133K
08P
132K
a
b
b
D
D X d
at 300 mm
at 300 mm
Trapezoidal sheet
Profiled sealing filler type A
Site applied insulation
04P
20P
03L
08P
21P
135K
130K
21
P
08P
02P
50
a
L
D
m
ax.200
Overflow
at 150 mm
at 300 mm
Parapet in Slope Double
Eaves Parapet Gutter Prefabricated
Note:
a according to structural / staticrequirements
L, X specify dimension to defineflashing K105 and K130
Note:The prefabricated gutter is recommend to be supported every 2,000 mm.
-
8/10/2019 7 Construction Details
6/83
7.
7.1.6
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
04P
08P
20P
123K
08P
07Z
33P
130K
08P
02P
50
a
D
at 333 mm
at 150 mm
at 300 mm
min.120mm Overflow
Trough grate
Adhered membrane
liner
Site applied rigid
urethane board
Galvanised gutter
support
Eaves Parapet Gutter Membrane Lined
Note:
a according to structural / static requirements
L specify dimension to define flashing K135
P33, Z07, K123 when required
-
8/10/2019 7 Construction Details
7/83
7.
7.1.7
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
04P
130K
17P
08P
04P
21P
02L
17P
08P
12P
08P
13P
20P
04P
D X D
50
50
a
at 333 mm
at 333 mm
at 150 mm
Back putty
Site applied rigid urethane board
Overflow
Eaves Gutter Parapet Prefabricated
Note:
a according to structural / static requirements
X specify dimension to define flashing K130
The prefabricated gutter is recommended to be supported every 2,000 mm.
-
8/10/2019 7 Construction Details
8/83
7.
7.1.8
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
08P
110K
16P
107K
136K
10P
14P
04P
01b
Z
07
P
193
K
02
P
07P
109K
30
d
a
at 333 mm
at 666
or 1,000 mmSite applied insulation
min.190mm
at 666
or 1,000 mm
08P
08P
127K
03P
13P
08P
03P
04P
07P
14P
07P
109K
126K
108K
08P
02P
a
d
20 35 25
at 333 or 666 or
1,000 mm
Back putty
80 (cut back)
at 333 or 666 or
1,000 mm
Site applied insulation
at 333 mm
at 300 mm
at 333 mm
600mm
External Gutter
External Gutter
Note:
a according to structural / static requirements
To order eaves gutters systems and accessory
components please contact Kingspan technicalServices Department.
-
8/10/2019 7 Construction Details
9/83
7.
7.1.9
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
04P
20P
01L
20P
04P
a
5050
a
530
Overflow
Valley Gutter
Note:
a, b according to structural / static requirements
The prefabricated gutter is recommended to support by 2,000 mm.
To order eaves gutters systems and accessory components please contact Kingspan technical ServicesDepartment.
-
8/10/2019 7 Construction Details
10/83
7.
7.1.10
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
12R 0
6P 04P 1
7P
06P
08P
20P
04P
142
K
04L
20P
04P
20P 0
8P
D
D
A
A
D
a
50
06P
154
K
08P
21P
08P
14P
a
a
at150mm
at150mm
Overflow
at150mm
at150mm
Sec
tionAA
Siteappliedinsulation
Siteappliedinsulation
Curved Eaves with Gutter Roof to Wall
Note:
a
accor
dingtostructural/staticrequirements
Theprefa
bricatedgutterisrecommendedto
supportb
y2,0
00mm.
-
8/10/2019 7 Construction Details
11/83
7.
7.1.11
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
10
07P
16P
08P
132K
133K
D
D
14P
07P
169K
04P
at 300 mm
Site applied insulation
16P
08
P
172K
14P
07P
04P
04P
13P
12P
07P
03P
139K
102K
d
50
D
a
at 333 mm
at 150 mm
Site applied insulation
Back putty
Back putty
Outer sheet turned up
Roof to Wall Junction
Roof to Wall Junction in Slope
Note:
a according to structural / static requirements
P12 for roof slope 10% 4 pcs / m> 10% 2 pcs / m
-
8/10/2019 7 Construction Details
12/83
7.
7.1.12
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
31
P
120K
31P
141K
03P
106K
14P
08P
132K
31P
14P
07P
04P
at 200 mm
at 200 mm
at 200 mm
at 500 mm
at 300 mm
Site applied insulation
Butyrub building cement
04P
102K
114K
03P
07P
12P
31P
120K
31P
07P
14P
31P
104K
a
at 200 mm
at 200 mmat 333 mm
at 200 mm
Butyrub building cement
Site applied insulation
Outer sheet turned up
Back putty
Roof to Brickwork Junction
Roof to Brickwork Junction in Slope
Note:
a according to structural / static requirementss
P12 for roof slope 10% 4 pcs / m> 10% 2 pcs / m
-
8/10/2019 7 Construction Details
13/83
7.
7.1.13
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
14P
07P
122K
07P
14P
14
P
08P
08P
132
K
04
P
121
K
04
P
132
K
14
P
50
35P
at 300 mm at 300 mm
Site applied insulation PE pipe
50
EPDM sealant supplied and installed
Cover collar
For extractor flue exhaust high temperature
gases/pollutants a suitable fire rated/non-combustible
barrier gasket should be installed by specialist contractor
Sealing designed/supplied and
installed by specialist contractor
diameter varies
Expansion Joint
Roof Penetration Extractor Flue
-
8/10/2019 7 Construction Details
14/83
7.
7.1.14
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
2730mm
5060mm
d
23
P
PE pipe
Roof Pipe Extractor Flue
Note:
Complete installation contents:
passage piping packing sealing material necessary quantity of fasteners
Piping sleeves for better additional sealing of passages can be ordered according to diameter of piping.
See to the section of the Accessories or contact Kingspan Technical Service Department for range of pipingsleeves.
-
8/10/2019 7 Construction Details
15/83
7.
7.1.15
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
102K
03P
07P
12P
04P
17P
08
P
111
K
a
at 300 mm
at 333 mm
Back putty
Roof/skylight Support curb
Site applied rigid urethane board
Site applied insulation
Outer sheet turned up
132K
111K
08P
14P
04P
17P
03P
08P
at 300 mm
at 300 mm
at 500 mm
Roof/skylight Support curb
Site applied rigid urethane board
Site applied insulation
Ridge Roof / Skylight
Ridge Roof / Skylight Downslope (RW)
Note:
a according to structural / static requirements
P12 for roof slope 10% 4 pcs / m> 10% 2 pcs / m
-
8/10/2019 7 Construction Details
16/83
7.
7.1.16
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
50
300
50
50
250
500
50
d
60
820
a
a
21P
03P
04P
18P
07P
247
K
18P
17P
18P
07P
04P
03P
21P
21P
slope
1,0
00
min.
100
6pcsperpanel
6pcs
perpanel
01A
Alupstand
Note:
a
accordingtostructural/staticrequirements
Dome Type Roof / Skylight
-
8/10/2019 7 Construction Details
17/83
7.
7.1.17
Construction details
Trapezoidal Roof Panels
All technical information is subject to alterations. Errors and omissions excepted.
50
d
17P
a
a
04P
12P
08P
203
K
217
K
03P
13P
17P0
4P
21P 2
0P
SiteappliedflashingS
iteap
plied
insulation
Outersheet
turned
up
Backputty
slope
slope
at333mm
at333mm
Note:
d,
D
specify
dimensionstodefineflashingsK203andK217
P12
forroof
slope10%
2pcs/m
>10%
1pcs/m
a
according
tostructural/staticrequirements
Change of Roofslope
-
8/10/2019 7 Construction Details
18/83
7.
7.2.18
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Flat Roof Panels
Fixing solution (X-DEK)
Preliminary hole, filled with PUR canister foam
after installation of fastener
Waterproof membrane adhered
or mechanically fixed by others
Site applied butyl sealant
Direct fastener at each rib
diameter min 5.5 + washer 19 mm
Steel support
Top finish PVC membrane
FACTORY APPLIED
fully bonded
to the IPN insulation core
Site welded membrane (hot air weld) with adjacent panel after fastener installation
Preliminary hole, filled
with PUR canister foam
after installation of fastener
PVC membrane
side-lap
Site applied butyl sealant
Direct fastener at each rib diameter min 5.5
+ washer 19 mm or Self Coring Helical fastener (SFS)
Steel support
90100 mm
Preliminary hole, filled with PUR canister foam
after installation of fastener
Waterproof membrane adhered
or mechanically fixed by others
Site applied butyl sealant
Direct fastener at each rib
diameter min 5.5 + washer 19 mm
Steel support
Waterproof membrane adhered
or mechanically fixed by others Spreader plate
Site applied butyl sealant
Through fasteners at each rib
diameter min 5.5
Steel support
KS1000 XD option 1 KS1000 XD option 2
KS1000 XD TR20 / TR27 KS1000 XD PVC
-
8/10/2019 7 Construction Details
19/83
7.
7.2.19
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Flat Roof Panels
04
P
Site applied insulation
gap > 10 mm
Preliminary hole, filled with PUR canister foam
after installation of fastener
Waterproof membrane adhered
or mechanically fixed by others
Back putty
Trapezoidal XD profile filler
03
P
21
P
site applied max at 500 mm centres if the fire performance is required
max at 1,000 mm centres if the fire performance not required
Waterproof membrane adhered or mechanically fixed by others
04
P
Site applied insulation
gap > 10 mm
Cut-back
size 50650 mm
Preliminary hole, filled with PUR canister foam
after installation of fastener
Waterproof membrane adhered
or mechanically fixed by others
Butt joint (X-DEK)
Side lap Stitching detail (X-DEK)
Panel End Lap (X-DEK)
-
8/10/2019 7 Construction Details
20/83
7.
7.2.20
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Flat Roof Panels
04
P
04
P
04
P
16
P
16
P
08
P
08
P
401a
K
404
K
Preliminary hole, filled with PUR canister foam
after installation of fastener
Waterproof membrane adhered
or mechanically fixed by othersSite applied insulation
04
P
404
K
Preliminary hole, filled with PUR canister foam
after installation of fastenerSite applied insulation
Waterproof membrane adhered
or mechanically fixed by others
Ridge (X-DEK)
Valley (X-DEK)
-
8/10/2019 7 Construction Details
21/83
7.
7.2.21
Construction details
All technical information is subject to alterations. Errors and omissions excepted.
Flat Roof Panels
at 500 mm
at 300 mm
2 at 500 mm
08
P
183
K
07
P
08w
P
28
P
04
P
Preliminary hole, filled with PUR canister foam
after installation of fastener
Hot air weld
150