EXISTING DEVICE OR EQUIPMENT TO BE REMOVED(R)
REQUIRED
SHEET
SQUARE
TYPICAL
VESDA LASER PLUS AIR SAMPLING DETECTOR
WATT
UNLESS OTHERWISE NOTED
WITH
WEATHERPROOF
SIGNAL
UON
W/
WP
W
VLC
SIGN.
TYP.
SQ.
SHT
REQD
QUANTITY
FAN COIL UNIT
HOT WATER PUMP
GROUND
JUNCTION BOX
GROUND FAULT CURRENT INTERRUPTER
KILO-VOLT AMP
KILO-WATT
LIGHTING
MANHOLE, MOUNTING HEIGHT
LIGHT EMITTING DIODE
MOUNTING
NUMBER
NOT IN CONTRACT
OVERHEAD
POWER FACTOR
NATIONAL ELECTRICAL CODE
OWNER FURNISHED, CONTRACTOR INSTALLED
PANEL
POWER
POWER POLE
FURNISH, INSTALL AND CONNECT
PHASE
PROVIDE
QTY.
PWR
PH
PNL
PP
PF
NEC
OFCI
OH
N.I.C.
NO.
MTG
MH
LED
LTG
KVA
KW
JB
HWP
GFCI
GND
FCU
AMPERES
CONDUIT
BUILDING
CIRCUIT BREAKER
CONDUIT ONLY
ABOVE FINISHED FLOOR
EXISTING
DRAWING
DISCONNECT
EXHAUST FANEF
(E)
DISC
DWG
C.O.
C
CB
BLDG.
A, AMP
AFF
T TRANSFORMER
4’ LONG FLUORESCENT WALL MOUNTED LIGHT FIXTURE
EXIT LIGHT, SINGLE FACE - WALL MOUNTED
(SHADED PORTION INDICATES FACE OF THE EXIT SIGN)
INDICATES KEY NOTE#
(CONTACT SWITCH: a, b, c, ETC = INDICATES OUTLET CONTROLLED)
(SUFFIX INDICATES THE FOLLOWING: "3" = 3-WAY, "4" = 4-WAY)
TOGGLE SWITCH, SPST - MOUNTED @ +48" A.F.F., U.O.N.
2’ X 4’ FLUORESCENT RECESSED MOUNTED LIGHT FIXTURE
WALLPACK HPS LIGHT FIXTURE
1’ X 4’ FLUORESCENT PENDANT LIGHT FIXTURE
PANELBOARD (LIGHTING OR POWER)
20A, 120V, 1P DUPLEX RECEPTACLE "U" GROUND,
(SHADED PORTION INDICATES FACE OF THE EXIT SIGN)
EXIT LIGHT, SINGLE FACE - CEILING MOUNTED
JUNCTION BOX - CEILING MOUNTED OR ABOVE CEILING
CONDUIT STUBBED UP
CONDUIT STUBBED DOWN
EXPOSED
CONDUIT RUN CONCEALED UNDERGROUND OR IN SLAB
INDICATES HOMERUN TO DESIGNATED PANEL (i.e. "PP4") WITH
CONDUIT RUN CONCEALED ABOVE CEILING OR IN WALLS OR
3/4"C-4#12 & 1#12 GND
PP4-1,3,5
MCC MOTOR CONTROL CENTER
THOUSAND AMPERES INTERRUPTING CAPACITYKAIC
MOTOR CIRCUIT PROTECTIONMCP
AHU AIR HANDLING UNIT
CHILLERCH
CWP CHILLED WATER PUMP
CWBP COOLING WATER BOOSTER PUMP
CONDENSING UNITCU
EMERG. EMERGENCY
FLUORESCENTFL
HEIGHTHT
MAKE-UP AIR UNITMAU
XFMR TRANSFORMER
AF AMP FUSE
AS AMP SWITCH2’ X 4’ FLUORESCENT SURFACE MOUNTED LIGHT FIXTURE
INTERRUPTER TYPE, NEMA 5-20R, FLUSH MOUNTED, +18" AFF, U.O.N.
20A, 120V, 1P DUPLEX RECEPTACLE, GROUND FAULT CIRCUIT
S
J
TELEPHONE OUTLET, FLUSH MOUNTED, @+18" A.F.F., U.O.N.
PROVIDE 3/4"C MINIMUM WITH REQUIRED CABLES ROUTED
UP TO 6" ABOVE CEILING SPACE, U.O.N.
UP TO 6" ABOVE CEILING SPACE, U.O.N.
PROVIDE 3/4"C MINIMUM WITH REQUIRED CABLES ROUTED
DATA OUTLET, FLUSH MOUNTED, @+18" A.F.F., U.O.N.
NL NIGHT LIGHT OR EMERGENCY LIGHT
END OF LINEEOL
FACP FIRE ALARM CONTROL PANEL
ST SHUNT TRIP
V VOLT
VPS VESDA SINGLE OR MULTI ZONE POWER SUPPLY
FIRE ALARMF.A.
PT POTENTIAL TRANSFORMER
CIRCUITS 1, 3 & 5
(NTS)
DRAWING INDEX
GENERAL NOTES:
ABBREVIATIONS(NOT ALL ABBREVIATIONS HAVE BEEN USED)
SYMBOLS LIST
DESCRIPTIONDRAWING NO’s.
TITLE SHEET
GENERAL
FACET LASER ROOM
KLYSTRON GALLERY SECTOR 20
PRIOR WRITTEN PERMISSION OF STANFORD UNIVERSITY / SLAC.
NOT BE COPIED, PUBLISHED OR OTHERWISE FURTHER DISSEMINATED WITHOUT
THE DRAWINGS, SPECIFICATIONS AND OTHER DATA HEREIN PROVIDED SHALL
06/13/12
06/13/12
06/13/12
DATE
DO NOT SCALE DRAWING
E
K.S. WONG
D. BRITT
APPROVALS
K.S. WONG CHKR
F.Y. DES
V. LONGA ENGR
/ /
/ /
/ /
DATE
ID-383-700-21 -
C0
SCALE: AS NOTED
DRAWING NUMBER REVISION
SECTOR 20 ALCOVE-TITLE SHEET
F:\ID38370021C0.dgn
ID-383-700-21 C0 E
DESCRIPTIONREV DRN CHK APP DATE
208V, 3 PHASE RECEPTACLE, FLUSH MOUNTED
NEMA 5-20R, FLUSH MOUNTED, +18" AFF, U.O.N.
NEMA 5-20R, FLUSH MOUNTED, +18" AFF, U.O.N.
20A, 120V, 1P DOUBLE DUPLEX RECEPTACLE "U" GROUND,
1.
2.
5.
6.
K10A
SECTOR 20 ALCOVE
261
21 22 2523 24
GATE 27
FR
EE
WA
Y I-
280
20-1
20-5
20-3
20-4
20-2
WORK LOCATION
ID-383-700-24-C0
ID-383-700-23-C0
ID-383-700-22-C0
ID-383-700-21-C0
KEY PLAN
KLYSTRON GALLERY SECTOR 20, FACET LASER ROOM, ARCHITECTURAL, PLAN, SECTION AND DETAILSID-383-100-03-C0 SHT 1
ID-383-100-03-C0 SHT 2 KLYSTRON GALLERY SECTOR 20, FACET LASER ROOM, ARCHITECTURAL, PLAN, SECTION AND DETAILS
FACET LASER ROOM
SECTOR 20 - ALCOVE
KLYSTRON GALLERY B002
KLYSTRON GALLERY SECTOR 20, FACET LASER ROOM, GENERAL, TITLE SHEET
KLYSTRON GALLERY SECTOR 20, FACET LASER ROOM, ELECTRICAL, POWER DEMO/NEW WORK PLAN
KLYSTRON GALLERY SECTOR 20, FACET LASER ROOM, ELECTRICAL, LIGHTING DEMO/NEW WORK PLAN
ID-383-600-01-C0 KLYSTRON GALLERY SECTOR 20, FACET LASER ROOM, HVAC, DEMO AND NEW WORK PLAN
RETURN REGISTER
SPECIFICATION SLAC-I-383-100-03-R000.
THE SUBCONTRACTOR SHALL COMPLY WITH THE UNIVERSITY TECHNICAL
TECHNICAL REPRESENTATIVE (UTR)/FIELD CONSTRUCTION MANAGER (FCM).
ALL WORK WILL BE INSPECTED AND APPROVED BY THE UNIVERSITY
AND FOLLOWING BEST INDUSTRY PRACTICES.
AND OF FIRST QUALITY, THE WORKMANSHIP SHALL BE OF FIRST QUALITY
ALL MATERIALS PROVIDED BY THE SUBCONTRACTOR SHALL BE OF NEW
OF DUST.
SUBCONTRACTOR SHALL MAINTAIN THE WORK AREA CLEAN FREE
APPLY TEXTURED FINISHED.
PAINT ALL INTERIOR WALLS WITH NAVAJO WHITE BY KELLY MOORE.
AND LOCATIONS ARE APPROXIMATE.
PROPOSAL AND INSTALLATION OF PARTITION WALL. ALL DIMENSIONS
ALL THE DIMENSIONS AND LOCATIONS PRIOR TO PROVIDING A PRICE
A PRICE PROPOSAL. THE SUBCONTRACTOR SHALL ALSO FIELD VERIFY
THE SUBCONTRACTOR SHALL VISIT THE SITE PRIOR TO PROVIDING
3.
7.
AS REQUIRED.
SUB-SUBCONTRACTORS WITH CURRENT CONSTRUCTION DOCUMENTS,
CONSTRUCTION FOR USE ALL TRADES AND SHALL PROVIDE ALL
OF CONSTRUCTION DOCUMENT ON THE JOBSITE DURING ALL PHASES OF
THE SUBCONTRACTOR SHALL MAINTAIN A CURRENT AND COMPLETE SET
SERVICE.
AND ANY MECHANICAL OR ELECTRICAL DISRUPTIONS TO BUILDING
A DETAILED CONSTRUCTION SCHEDULE SHOWING PHASING OF WORK
THE SUBCONTRACTOR SHALL SUBMIT TO THE OWNER, FOR APPROVAL.
4.
TO PROTECT THE PUBLIC DURING THE PERIOD OF CONSTRUCTION.
AND MAINTAIN TEMPORARY PATITIONS, CLOSURE WALLS, ETC. AS REQUIRED
CONSTRUCTION, DEMOLITION DUST, WATER, ETC. AND SHALL PROVIDE
MATERIALS AND FINISHES FROM DAMAGE, WHICH MAY OCCUR FROM
THE SUBCONTRACTOR SHALL PROTECT THE AREA, NEW OR EXISTING
10.
11.
8.
9.
PERMIT FROM OWNER.
ENGINEER PRIOR TO PERFORMING THE WORK AND REQUIRES PENETRATION
FLOOR SLAB SHALL REQUIRED APPROVAL BY THE SLAC & STRUCTURAL
ALL PENETRATION THROUGH STRUCTURAL MEMBERS, CEILING ROOF AND
MANAGEMENT COORDINATE WITH FCM.
OWNER (SLAC) PROVIDED BINS TO BE DISPOSED BY OWNER (SLAC) WASTE
ALL HAZARDOUS, CLASS II AND UNIVERSAL WASTE WILL BE COLLECTED IN
KLYSTRON GALLERY SECTOR 20, FACET LASER ROOM, ELECTRICAL, FIRE ALARM REOLOCATE/NEW WORK PLAN
ID38370021C0.dgn 6/19/2012 8:50:34 AM
-
20-4
8’-2" 8’-0"
1’-0"8’-2" 8’-0"
26"
48"
18"
27�
"
AREAAND WORKLOADING
6
7
-
C0
PLAN, SECTION, AND DETAILS
ARCHITECTURAL
FACET LASER ROOM
KLYSTRON GALLERY SECTOR 20
DESCRIPTIONREV DRN CHK APP DATE
PRIOR WRITTEN PERMISSION OF STANFORD UNIVERSITY / SLAC.
NOT BE COPIED, PUBLISHED OR OTHERWISE FURTHER DISSEMINATED WITHOUT
THE DRAWINGS, SPECIFICATIONS AND OTHER DATA HEREIN PROVIDED SHALL
06/13/12
06/13/12
06/13/12
DATE
F:\ID38310003.DGN
E
E
KS WONG
APPROVALS
CHKR V. LONG
DES KL/FY
ENGR V. LONGA
/ /
/ /
/ /
DATE
ID-383-100-03-
C0
ID-383-100-03
SCALE: AS SHOWN SHT 1 OF 2
DRAWING NUMBER REVISION
SEC 20-ALCOVE-FACET WORK
GENERAL NOTES:
ABBREVIATIONS:
LEGEND:
DEMOLITION PLAN - ALCOVE FLOOR
NEW PLAN - ALCOVE FLOOR
DEMOLITION PLAN - ALCOVE FLOOR
NEW PLAN - ALCOVE FLOOR
DEMOLOTION NOTES:
NEW WORK NOTES:
2
5.
4.
3.
2.
1.
LASERROOM
20-3
24 25 26 27 28 29 30 31 32
A
D
C
23
DN.
A.8
B
TO (E) TUNNEL
FREE OF DUST.SUBCONTRACTOR SHALL MAINTAIN THE WORK AREA CLEAN AND
INDUSTRY PRACTICES. SHALL BE OF FIRST QUALITY AND FOLLOWING BEST BE NEW AND OF FIRST QUALITY. THE WORKMANSHIP ALL MATERIALS PROVIDED BY THE SUBCONTRACTOR SHALL
FIELD CONSTRUCTION MANAGER (FCM) AND BIO.ALL WORK SHALL BE INSPECTED AND APPROVED BY THE
AND LOCATIONS ARE APPROXIMATE.PRIOR TO PROVIDING A PRICE PROPOSAL. ALL DIMENSIONS ALSO FIELD VERIFY ALL THE DIMENSIONS AND LOCATIONS PROVIDING A PRICE PROPOSAL. THE SUBCONTRACTOR SHALL THE SUBCONTRACTOR SHALL VISIT THE SITE PRIOR TO
TECHNICAL SPECIFICATION IS-383-100-03-R0.THE SUBCONTRACTOR SHALL COMPLY WITH THE UNIVERSITY
SCALE: �"=1’-0"
20-2
LASERROOM
20-3
20-4
20-5
24 25 26 27 28 29 30 31 32
A
D
C
23
DN.
A.8
B
TO (E) TUNNEL
SCALE: �"=1’-0"
D4
D1
(E) DDC
1
EXISTING KLYSTRON GALLERY
EXISTING KLYSTRON GALLERY
AREAENTRYCONTROLLED
AREAAND WORKLOADING
20-2
AREAENTRYCONTROLLED
20-5
AREAWORKOPTICAL
20-1
LOCK ROOMLOAD
ROOMLASERFACET
3
D1
D2
D2
D3
1
1
2
3
2’-
0"
23’-
5"
10’-0" 10’-0" 10’-0" 10’-0" 10’-0" 10’-0" 10’-0" 10’-0" 10’-0"
23’-
5"
2’-
0"
23’-
5"
10’-0" 10’-0" 10’-0" 10’-0" 10’-0" 10’-0" 10’-0" 10’-0" 10’-0"
5
-
2
3
4
D3
D4 REMOVE DOOR AND HINGES AS SHOWN.
FOR FUTURE INSTALLATION.DEMO CABLE TRAY AND SUPPORTS AS SHOWN. PROVIDE TO CUSTOMER
FOR RE -INSTALLATION AFTER FRAMING FOR OPENING IS COMPLETE. DEMO PARTIAL CABLE TRAY AND SUPPORTS AS SHOWN. SECURE
ELECTRICAL WORK PER ELECTRICAL DRAWINGS.DEMO SECTION OF THE WALL PER SPECIFIED DIMENSION SHOWN.
ROOMFACET LASER
5
6
5
4
4
-
2
PROVIDE AND INSTALL RETURN AIR CENTERED IN WALL. LOCATED 12" AFF.
NE CORNER ALONG THE EXISTING FUR-OUT WALL.
PROVIDE AND INSTALL WALL 30"X12"X9�’H" AS SHOWN. LOCATION
AS SHOWN. LOCATION NW CORNER.
PROVIDE AND INSTALL SOFFIT 48"X26"X12" AND WALL 30"WX12"DX9�’H
DRAWING ID-383-700-24-C0 FOR GRID LAYOUT.
INSTALL 10’ HIGH T-BAR ACOUSTICAL CEILING, 2’X4’ GRID. SEE
REPLACE EXISTING DOOR HARDWARE WITH PANIC EXIT ONLY.
WALLS TO MATCH EXISTING. REPAIR FLOOR AS REQUIRED.
INSTALL NEW WALL WITH OPENING INSTALL NEW 3’-0" DOOR & PAINT
(E) DDC
TYP
RM
DEMO
TYPICAL
ROOM
DEMOLITION
NEW
FIRE SPRINKLER HEAD
EXISTING
REMOVE
DEMOLITION
CENTER LINE OF PIPE
id38310003c0.dgn 6/20/2012 2:40:50 PM
C0
PLAN, SECTION, AND DETAILS
ARCHITECTURAL
FACET LASER ROOM
KLYSTRON GALLERY SECTOR 20
DESCRIPTIONREV DRN CHK APP DATE
PRIOR WRITTEN PERMISSION OF STANFORD UNIVERSITY / SLAC.
NOT BE COPIED, PUBLISHED OR OTHERWISE FURTHER DISSEMINATED WITHOUT
THE DRAWINGS, SPECIFICATIONS AND OTHER DATA HEREIN PROVIDED SHALL
06/13/12
06/13/12
06/13/12
DATE
F:\ID38310003.DGN
E
E
KS WONG
APPROVALS
CHKR V. LONGA
DES KL/FY
ENGR V. LONGA
/ /
/ /
/ /
DATE
ID-383-100-03-
C0
ID-383-100-03
SCALE: AS SHOWN SHT 2 OF 2
DRAWING NUMBER REVISION
SEC 20-ALCOVE-FACET WORK
TYPICAL METAL STUD WALL
SECTION
SECTION (EAST WALL) SECTION (NORTH WALL) SECTION (WEST WALL) 3 5
6
7
4
(E) 8" FUR-OUT
12"x30"x9�" (N) WALL
18"x27�"x10�" (N) WALL
ALTERNATE LINTEL SECTION
LINTEL SECTIONHEADER TRACK TO JAMB STUD C
ATTACH WITH SCREWS
BEND WEB OF STUD:
BETWEEN WEB AND
LINTEL TO JAMB STUD A
LINTELS: 2-TRACK
SCREW ATTACH
OR STUD SECTIONS
TO JAMB FLANGES
TYPICAL OPENING FRAMING ELEVATION
CONTINUOUS
OVER OPENINGS
D
OF PARTITION
TOP TRACK
TRACK SECTION
LINTEL BEAM
OVER OPENINGS
HANGER STUDS
CONTINUOUS
TRACK SECTION
B
CONT TOP TRACK
OF PARTITION
MAX. LINTEL SPAN LINTEL SIZE
3’-4"
12’-0" DBL 20HDS358
20HDT358
DOUBLE STUD
LINTEL (TYP)
TYPICAL STUD FRAMING
(SINGLE/DBL
STUD, TYP.)
FLANGES
NOTES:
BOTTOM TRACK
C
JA
MB
ST
UD
HEADERTRACK
LINTELS/HEADER
A
JA
MB
ST
UD
PER WALL TYPE
DBL MTL. STUD
1 1/2" CHANNEL OR TRACK
BLOCKING AT DOOR JAMBS,
TOP TRACK
B
MTL. STUD PER
WALL TYPE
2-STUD SPACES, TYP.
D
TYPICAL DOOR OPENING
THE ADJACENT MATERIALS, CONSTRUCTION AND FINISH.
TO RECEIVE THE FINISH. PATCHED AREAS ARE SHALL MATCH
AND FREE OF ANY IMPERFECTIONS AND IN A PROPER CONDITION
2. ALL NEW FINISHED AND PATCHED SURFACES SHALL BE SMOOTH
MOUNTED FIXTURES SHELVING AND ACCESSORIES.
3. PROVIDE ALL REQUIRED BLOCKING, FURRING AND BACKING FOR ANY WALL
CONCRETE OR FACE OF (E) WALL.
EXISTING WALLS AND BUILDING SHELL ARE FROM FACE OF
FINISH OR EDGE OF WALL, U.N.O DIMENSIONS FROM
1. DIMENSIONS INDICATED ON THE FLOOR PLANS ARE TO FACE OF
A C DA.8 B
LINE OF CABLE TRAY
LINE OF FINISH CEILING
(N) DOOR
EXISTING KLYSTRON GALLERY
(E) WALL
ROOMLASERFACET
1
16’-
2"
9’-
6"
10’-
6"
12"
26"
18"
10’-
0"
10’-
0"
8’-
0"
27�"
10’-
6"
6
20"WX12"H(N) RETURN AIR
16"WX12"(N) RETURN AIR
16"WX12"(N) RETURN AIR
SCALE: �"=1’-0"SCALE: �"=1’-0"
SCALE: NONE
SCALE: �"=1’-0"
SCALE: �"=1’-0"
ACD A.8B
LINE OF CABLE TRAY
LINE OF FINISH CEILING
EXISTING KLYSTRON GALLERY
ROOMLASERFACET
16’-
2"
10’-
0"
8’-
0"
10’-
6"
6
20"WX12"H(N) RETURN AIR
(E) DOOR
48"
(E) CONC FLR EL 0’-0"
(TYPICAL)
2" MIN EMBEDMENT,
WITHIN 6" OF EA ENDS,
FASTENER @ 32" O.C. AND
0.145" DIA POWER DRIVEN
SEISMIC SUPPORT (TYP)
3-5/8" 20 GA MTL STUD
(TYP 8)
METAL STUD SCREWS,
(TYP)
DRIVEN FASTENER,
0.145" DIA POWER
LIKE MATERIAL
& REPLACE TILE WITH
TILE FOR SEISMIC SUPPORT
REMOVE/CUT (E) CEILING
EXISTING ROOF DECK
EL 10’-0"
EXISTING CEILING
CAULK/SEALANT (TYP)
INSTALL ACOUSTICAL
INSULATION R-11
GYPSUM AND ACOUSTICAL
WALL @ 16" OC W/ 5/8"
3"- 5/8"20 GA MTL STUD
WALL BASE (TYP)
MATCH EXISTING VINYL
W/ TEXTURED COAT FINISH
5/8" GYP BOARD WALL
FILL-IN DETAIL
252423
id38310003c0.dgn 6/19/2012 9:31:39 AM
POWER DEMO/NEW WORK PLAN
ELECTRICAL
FACET LASER ROOM
KLYSTRON GALLERY SECTOR 20
PRIOR WRITTEN PERMISSION OF STANFORD UNIVERSITY / SLAC.
NOT BE COPIED, PUBLISHED OR OTHERWISE FURTHER DISSEMINATED WITHOUT
THE DRAWINGS, SPECIFICATIONS AND OTHER DATA HEREIN PROVIDED SHALL
06/13/12
06/13/12
06/13/12
DATE
DO NOT SCALE DRAWING
E
K.S. WONG
D. BRITT
APPROVALS
K.S. WONG CHKR
F.Y. DES
V. LONGA ENGR
/ /
/ /
/ /
DATE
ID-383-700-22 -
C0
SCALE: AS NOTED
DRAWING NUMBER REVISION
SECT. 20 ALCOVE- POWER WORK
F:\ID38370022C0.dgn
ID-383-700-22 C0 E
LAMINAR
FLOW HOOD
"PP-4"
POWER PANEL
"PP-1"
POWER PANEL
WP
1
TO XFMR "T-1"
CONDUIT OPENING FOR
BASEMENT LEVEL
PP1-2,4,6
PP1-1,3,5
PP4-4
PP4-2
PP4-6
PP4-4
PP4-2
PP4-4PP4-6
PP4-2
PP4-6
PP4-8 PP4-10
PP4-8
PP4-12
PP4-8
PP4-10 PP4-12 PP4-10
PP4-16
PP1-1,3,5
1"C-4#6
& 1#10 GND & 1#10 GND
1"C-4#6
PP1-2,4,6
& 1#12 GND
3/4"C-4#12
PP4-2,4,6
PP4-12
PP4-8,10,12
3/4"C-4#12
& 1#12 GND
& 1#12 GND
3/4"C-4#12
30A
PP4-13
3/4"C-2#12
& 1#12 GND
& 1#12 GND
3/4"C-2#12
PP4-17
MCC S20-9
WP
30A
FOR SUPPLY FAN "SF-1"
STOP/START PUSHBUTTON
MCC S20-23
1
SECONDARY FUSED
DISCONNECT SW.
J
& 1#12 GND
3/4"C-2#12
PP1-26
(FOR PPS-ACCESS MOD 1)
PP1-28
3/4"C-2#12 & 1#12 GND
J
23 282726252423 2827262524
LOAD
LOCK ROOM20-1
LOADING ANDWORK AREA
20-4
OPTICAL
WORK AREA20-5
EXISTING TUNNELACCESS SHAFT
AND STAIRS20-6
POWER
SUPPLIES20-7
CONTROLLEDENTRY AREA
20-2
DEMOLITION NOTES:
SCALE: �" = 1’-0"
SECTOR 20 - ALCOVE PARTIAL PLAN - ELECTRICAL DEMOLITION PLAN
D1
D2
J
D1
LAMINAR
FLOW HOOD
"PP-4" "PP-1"
WP
1
TO XFMR "T-1"
CONDUIT OPENING FOR
BASEMENT LEVEL
PP1-2,4,6
PP1-1,3,5
PP4-4
PP4-2
PP4-6
PP4-4
PP4-2
PP4-6
PP4-2
PP4-8 PP4-10
PP4-8
PP4-12
PP4-8
PP4-10 PP4-12 PP4-10
PP4-16
1"C-4#6
& 1#10 GND & 1#10 GND
1"C-4#6
PP1-2,4,6
PP4-12
PP4-8,10,12
3/4"C-4#12
& 1#12 GND
& 1#12 GND
3/4"C-4#12
30A
PP4-13
3/4"C-2#12
& 1#12 GND
MCC S20-9
WP
30A
FOR SUPPLY FAN "SF-1"
STOP/START PUSHBUTTON
MCC S20-23
SECONDARY FUSED
DISCONNECT SW.
(FOR PPS-ACCESS MOD 1)
PP1-28
3/4"C-2#12 & 1#12 GND
J
23 282726252423 2827262524
LOADING ANDWORK AREA
20-4
EXISTING TUNNELACCESS SHAFT
AND STAIRS20-6
POWER
SUPPLIES20-7
CONTROLLEDENTRY AREA
20-2
SCALE: �" = 1’-0"
1
2
2 & TELECOM RACK
SIGNAL BOARD
PP1-37
NEW WORK NOTES:
8’-2in 8’-0in
FOR LASER SAFETY SYSTEM LOCATION 88" AFF.
PROVIDE AND INSTALL 20A, 120V, 3W, SINGLE PHASE RECEPTACLE
1PP4-22
D2
8’-0in8’-2in
ROOM
FACET LASER
ROOM
FACET LASER
PP3-14
3
3
33
33
33
3
3
3
BETWEEN CONDUCTORS AND TO GROUND.
CIRCUITS, GROUNDS, AND INSULATION RESISTANCE
THE ENTIRE WIRING SYSTEM TO BE TESTED FOR SHORT
TO.
WITHSTAND RATING OF THE BUS THEY ARE CONNECTED
WHICH THEY MAY BE SUBJECTED & NO LESS THAN THE
LESS THAN THE MAXIMUM SHORT CIRCUIT CURRENT TO
EQUIPMENT SHALL HAVE AN INTERRUPTING RATING NOT
ALL CIRCUIT BREAKERS, FUSES, AND ELECTRICAL
MADE.
SCHEDULES THAT ACCURATELY REFLECT ALL CHANGES
PROVIDE UPDATED, TYPED CIRCUIT BREAKER PANEL
REQUIREMENTS AND VERIFY ALL DIMENSIONS.
DETERMINE ACTUAL MATERIAL AND HARDWARE
TO MEET FIELD CONDITIONS. CONTRACTOR SHALL
BOXES, PULL BOXES, AND EXPANSION FITTINGS REQUIRED
NOT SHOW ALL OFFSETS, BENDS, FITTINGS, JUNCTION
THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND DO
USED FOR SUPPORT.
SUSPENDED CEILING. SEISMIC WIRES ARE NOT TO BE
INDEPENDENTLY SUPPORT ALL CONDUIT ABOVE
CONCEALED, UNLESS OTHERWISE NOTED.
IN FINISHED INTERIOR AREAS, RUN ALL CONDUITS
1.
2.
3.
4.
5.
6.
7.
8.
PP1-37
GENERAL NOTES:
TYPE THHN/THWN, NO. 12 AWG MINIMUM.
STRANDED ONLY, UL LISTED, RATED FOR 600 VOLTS,
UNLESS OTHERWISE NOTED, ALL WIRE SHALL BE COPPER,
OUTLET ON A CIRCUIT.
DESIGNATED SINGLE POINT GROUND FOR EACH DUPLEX
INCLUDE A SEPARATE GROUND WIRE CONNECTED TO THE
GROUND WIRE. DEDICATED BRANCH CIRCUITS SHALL
ALL BRANCH CIRCUITS SHALL INCLUDE A CODE SIZED
FLOOR.
PROVIDE AND INSTALL RECEPTACLE FOR LSS SIGN AT 72" ABOVE FINISHED
SECTOR 20 - ALCOVE PARTIAL PLAN - ELECTRICAL NEW WORK PLAN
J (N)PP4-2,4,6
J
(N)
PP4-22
IN �"C
+ #12G
(N)2 #12 PP4-22
X
1
3
5
7
9
11
13
15
19
21
23
17
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
20
22
24
18
26
28
30
32
34
36
38
40
42
TOTAL CONNECTED LOAD: BUS A: BUS B: BUS C: TOTAL (AMPS):
DESCRIPTIONA B C
BREAKER
AMPPOLE
CKT.
N0.
CKT.
N0.
BUS
CONN. A B C
BREAKER
AMPPOLE
FEEDERBONDED ENTRY
YES NO TOP BOT MOUNTING
MLO:YES
NO LUG SIZE:
NEMA ENCL. TYPE BUS: CU. AL.
MFR. CAT# DATE:
SERVICE V PH W Hz
KAIC (RMS) @ V
MAIN C.B.
MAIN BUS
A
A
PANEL:
LOCATION:
FED FROM: LOC :
X
X
X
DESCRIPTION
208/120
1
3 604
10 240
-
SIZE: N0 / PH:
(1)
INS. TYPE NEUT. SIZE: GND SIZE:
THHN/THWN 1 #6 AWG
150
1
***
20
1 20
720
1560
500
500
632
480
1080
1080
720
360
528
55203328
9260 6928
3600
1200
1200
500
3764
1080
3740
7172
3408
(E) CIRCUIT BREAKER
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
1 20
PP-4LOADING&WORKING AREA
KLY GALLERY
225
SURFACE
RM #20-1,20-4
RM #20-2, 20-5
RM #20-3, 20-7
RM #20-3, 20-7
EXT LIGHTS PHOTOCELL
OUTSIDE/EXT RECEPT
LAMINAR FLOW HOOD
SPARE
RM #20-5 "DDCP"
MXL / FACP
VSDA POWER SUPPLY
STAIRWELL - LIGHTS
INJ HOUSING - LIGHTS
SPARE
FIRE ALARM PNL
OUTSIDE CHILLER
SPACE
30
2
1460
1096
1412
1320
532
0
500
0
RM #20-1, 20-4, 20-5
RM #20-2, 20-5, 30-7
RM #20-1
RM #20-1, 20-5
RM #20-5, 20-7
RM #20-4, 20-7
RM #20-3
RM #20-3, 20-7
RM #20-3
TRAP PRIMER
RECPT. - FACET LASER ROOM
LIGHTS - FACET LASER ROOM
SPARE
SPARE
SPARE
SPACE
0
0
0
VIA XFMR
3 #1/0 1 #1/0
1080
1080
VAVA
1080
1080
1080
500
TOTAL (KVA): 23.360
(N) CIRCUIT BREAKER
************************************
**
**
*
****
*
**
**********
********
D3
J (N)
5
(E)POWER PANEL (E)POWER PANEL
J (N)IN �"C
+ #10G
1 #10 N,
(N)3 #10 AWG,
WIRING BACK TO J-BOX ON WALL. UPDATE PANEL SCHEDULE.
REMOVE POWER CONNECTIONS TO EQUIPMENT. REMOVE CONDUIT
D3
4
CEILING.
PROVIDE AND INSTALL 1-30A, 208V 3 PHASE CIRCUIT TO 4�" J-BOX ABOVE
5
X
1
3
5
7
9
11
13
15
19
21
23
17
25
27
29
31
33
35
37
39
41
2
4
6
8
10
12
14
16
20
22
24
18
26
28
30
32
34
36
38
40
42
TOTAL CONNECTED LOAD: BUS A: BUS B: BUS C: TOTAL (AMPS):
DESCRIPTIONA B C
BREAKER
AMPPOLE
CKT.
N0.
CKT.
N0.
BUS
CONN. A B C
BREAKER
AMPPOLE
FEEDERBONDED ENTRY
YES NO TOP BOT MOUNTING
MLO:YES
NO LUG SIZE:
NEMA ENCL. TYPE BUS: CU. AL.
MFR. CAT# DATE:
SERVICE V PH W Hz
KAIC (RMS) @ V
MAIN C.B.
MAIN BUS
A
A
PANEL:
LOCATION:
FED FROM: LOC :
X
X
X
DESCRIPTION
208/120
1
3 604
10 240
-
SIZE: N0 / PH:
(1)
INS. TYPE NEUT. SIZE: GND SIZE:
1 #2 AWG
400
***
(E) CIRCUIT BREAKER
30
1 20
1 20
1 20
1 20
1 20
1 30
1 20
1 20
1 20
1 20
1 20
PP-1LOADING&WORKING AREA
KLY GALLERY
400
SURFACE
VIA XFMR
VAVA
TOTAL (KVA):
(N) CIRCUIT BREAKER
*********************************
**
******
**
**********
*****
3
****
SPARE 3
60
INJECTOR HOUSING RECEPT.
INJECTOR HOUSING RECEPT.
INJECTOR HOUSING RECEPT.
FERMAN 3
40
SCR HEATER
70
3
SPARE
PPS RECEPTS.**SPARE
SPARE
****
3
60
RM #20-4 208v, 30A RECPT.
30
3 INJ HOUSING 208V 30A
INJ HOUSING RECEPT.
INJ HOUSING RECEPT.
INJ HOUSING RECEPT.
1 20
UPS- VAULT
SPARE
3
30
INJ HOUSING 208V 30A
201
201
201
201
1 20
THHN/THWN
30
3
**********
3 #500 KCMIL 1 #500 KCMIL
6
7
7
7
FACET LASER #1 (RM #20-1)
FACET LASER #2 (RM 20-1)
PROVIDE AND INSTALL NEW 30A 3PH BREAKER, TERMINATE WIRING.
REPLACE EXISTING J-BOX W/NEW 6"X6"X4" SCREW TYPE ENCLOSURE.
TO J-BOX ABOVE NEW CEILING.
REMOVE EXISTING SURFACE MOUNTED RECEPTACLE, CONDUIT, BOX AND WIRE
(E)PP1-1,3,5
6IN �"C
+ #10G
1 #10 N,
(N)3 #10 AWG,
6
64.71
PP1-26,28,30
8
ORIENTATION.
PLACEMENT IS APPROXIMATE, COORDINATE WITH FCM PER USER EQUIPMENT
PROVIDE AND INSTALL CONDUIT, WIRING, SUPPORTS AND L21-30R RECEPTACLE.
8
RECEPTACLES PP4-2,4,6.
PROVIDE AND INSTALL NEW J-BOX ABOVE CEILING, RE-FEED END USE
RECEPTACLES AS NEEDED.
ABOVE CEILING. RE-WORK CONDUIT AND WIRING TO AFFECTED
REMOVE RECEPTACLE, WIRING, CONDUIT AND BOXES BACK TO NEW J-BOX
REMOVE EXISTING RECEPTACLES AND REPLACE WITH 20A L5-20 DUPLEX AS SHOWN.
ID38370022C0.dgn 6/21/2012 2:19:38 PM
S3
PP4-1 PP4-1 PP4-1
PP4-1 PP4-1 PP4-1
PP4-1PP4-1PP4-1
PP4-3
PP4-3 PP4-3
PP4-3
PP4-1
PP4-1
PP4-9
PP4-9
PP4-9
PP4-3PP4-5 PP4-7 PP4-7PP4-5
PP4-5
PP4-5,7
3/4"C-3#12
&1#12 GND
J
J
PP4-23
&1#12 GND
3/4"C-2#12
PP4-23FOR EXIST. TUNNEL SHAFT
AND STAIRS LIGHTS
(TYP. 3)
DN.
DN.
PP4-23
(TYP. 6)
S3
PP4-1 PP4-1 PP4-1
PP4-1 PP4-1 PP4-1
PP4-1PP4-1PP4-1
PP4-3
PP4-3 PP4-3
PP4-3
PP4-1
PP4-1
PP4-9
PP4-9
PP4-9
PP4-3PP4-5 PP4-7 PP4-7PP4-5
PP4-5
PP4-5,7
3/4"C-3#12
&1#12 GND
J
J
PP4-23
&1#12 GND
3/4"C-2#12
PP4-23FOR EXIST. TUNNEL SHAFT
AND STAIRS LIGHTS
(TYP. 3)
DN.
DN.
PP4-23
(TYP. 6)
CONTROLLEDENTRY AREA
20-2
LOADING ANDWORK AREA
20-4
EXISTING TUNNELACCESS SHAFT
AND STAIRS20-6
POWER
SUPPLIES20-7
(TYP. 5)
23 282726252423 2827262524
S3
(TYP. 8)
H
80
(TYP. 8)
B
120
B
120
B
120
C
58
PP4-1 PP4-1 PP4-1
PP4-1PP4-1PP4-1
PP4-1PP4-1PP4-1 PP4-1 PP4-1 PP4-1
PP4-1 PP4-1 PP4-1
PP4-1PP4-1PP4-1
PP4-3 PP4-3 PP4-3 PP4-3 PP4-3
PP4-3 PP4-3 PP4-3
PP4-3 PP4-3
PP4-3
PP4-1
PP4-1
PP4-9
PP4-9
PP4-9
PP4-3PP4-5 PP4-7 PP4-7PP4-5
PP4-5
PP4-1
PP4-5,7
3/4"C-3#12
&1#12 GND
J PP4-1,3
3/4"C-3#12
&1#12 GND
J
OS
PP4-23
&1#12 GND
3/4"C-2#12
PP4-23FOR EXIST. TUNNEL SHAFT
AND STAIRS LIGHTS
(TYP. 3)
DN.
DN.
PP4-23
(TYP. 6)
(TYP. 2)
S3
(TYP. 8)
H
80
(TYP. 8)
B
120
B
120
B
120
C
58
PP4-1 PP4-1 PP4-1
PP4-1PP4-1PP4-1
PP4-1PP4-1PP4-1 PP4-1 PP4-1 PP4-1
PP4-1 PP4-1 PP4-1
PP4-1PP4-1PP4-1
PP4-3 PP4-3 PP4-3 PP4-3 PP4-3
PP4-3 PP4-3 PP4-3
PP4-3 PP4-3
PP4-3
PP4-1
PP4-1
PP4-9
PP4-9
PP4-9
PP4-3PP4-5 PP4-7 PP4-7PP4-5
PP4-5
PP4-1
PP4-5,7
3/4"C-3#12
&1#12 GND
J PP4-1,3
3/4"C-3#12
&1#12 GND
J
PP4-23
&1#12 GND
3/4"C-2#12
PP4-23FOR EXIST. TUNNEL SHAFT
AND STAIRS LIGHTS
(TYP. 3)
DN.
DN.
PP4-23
(TYP. 6)
(TYP. 2)
LOAD
LOCK ROOM20-1
CONTROLLEDENTRY AREA
20-2
LOADING ANDWORK AREA
20-4
OPTICAL
WORK AREA20-5
EXISTING TUNNELACCESS SHAFT
AND STAIRS20-6
POWER
SUPPLIES20-7
23 282726252423 2827262524
LIGHTING DEMO/NEW WORK PLAN
ELECTRICAL
FACET LASER ROOM
KLYSTRON GALLERY SECTOR 20
PRIOR WRITTEN PERMISSION OF STANFORD UNIVERSITY / SLAC.
NOT BE COPIED, PUBLISHED OR OTHERWISE FURTHER DISSEMINATED WITHOUT
THE DRAWINGS, SPECIFICATIONS AND OTHER DATA HEREIN PROVIDED SHALL
06/13/12
06/13/12
06/13/12
DATE
DO NOT SCALE DRAWING
E
K.S. WONG
D. BRITT
APPROVALS
K.S. WONG CHKR
F.Y. DES
V. LONGA ENGR
/ /
/ /
/ /
DATE
ID-383-700-24 -
C0
SCALE: AS NOTED
DRAWING NUMBER REVISION
SECT. 20 ALCOVE-LIGHTING WORK
F:\ID38370024C0.dgn
ID-383-700-24 C0 E
SCALE: �" = 1’-0"
SCALE: �" = 1’-0"
SECTOR 20 - ALCOVE PARTIAL PLAN - LIGHTING DEMOLITION PLAN
SECTOR 20 - ALCOVE PARTIAL PLAN - LIGHTING NEW PLAN
DEMOLITION NOTES:
D1
MATCH CEILING TILE TYPE WITH ADJACENT CEILING TYPE.
REMOVE LIGHT FIXTURE FOR INSTALLATION OF (N) WALL.
D1
1
2
3
NEW WORK NOTES:
120
(TYP. 6)
C
120
1
PROVIDE AND INSTALL CEILING GRID AS SHOWN.
2
PROVIDE AND INSTALL EXIT LIGHT, SINGLE FACE WALL MOUNTED AS SHOWN.
3E1
10
8’-2in 8’-0in
8’-2in 8’-0in
ROOM
LASER
FACET
ROOM
LASER
FACET
4
D2 REMOVE LIGHTING FIXTURES, CONDUIT AND WIRING.
D3
D3
S
SS 4
SYMBOL
IN=INCANDESCENT
FL=FLUORESCENT
HPS=HIGH PRESSURE SODIUM
HAL=HALOGEN
LAMPS
DESCRIPTIONALTERNATE MANUFACTURERSCATALOG NO.MANUFACTURERTYPE FIXTURE
DESCRIPTION TYP
LIGHTING FIXTURE SCHEDULE
MTGVOLTQTY.
FIXT.
INPUT REMARKS
P=PENDANT
PL=POLE
S=SURFACE
R=RECESSED
C=CHAIN
C
120
R1202 120FLCOLUMBIA
H.E. WILLIAMS
LITHONIA 2PM3 B4 32 18LD 120
MH=METAL HALIDE
GEB10RS
E1
10
WALL MOUNTED
2’x4’ 2-LAMP PARABOLIC LOUVER WITH
18 CELL LOUVER IN T-BAR CEILING
LETTERS IN WHITE BACKGROUND
WITH EMERGENCY BATTERY PACK AND GREEN
DUAL LITE LTUGWLITHONIA LED 1 120 10 S
BETWEEN CONDUCTORS AND TO GROUND.
CIRCUITS, GROUNDS, AND INSULATION RESISTANCE
THE ENTIRE WIRING SYSTEM TO BE TESTED FOR SHORT
TO.
WITHSTAND RATING OF THE BUS THEY ARE CONNECTED
WHICH THEY MAY BE SUBJECTED & NO LESS THAN THE
LESS THAN THE MAXIMUM SHORT CIRCUIT CURRENT TO
EQUIPMENT SHALL HAVE AN INTERRUPTING RATING NOT
ALL CIRCUIT BREAKERS, FUSES, AND ELECTRICAL
MADE.
SCHEDULES THAT ACCURATELY REFLECT ALL CHANGES
PROVIDE UPDATED, TYPED CIRCUIT BREAKER PANEL
REQUIREMENTS AND VERIFY ALL DIMENSIONS.
DETERMINE ACTUAL MATERIAL AND HARDWARE
TO MEET FIELD CONDITIONS. CONTRACTOR SHALL
BOXES, PULL BOXES, AND EXPANSION FITTINGS REQUIRED
NOT SHOW ALL OFFSETS, BENDS, FITTINGS, JUNCTION
THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND DO
USED FOR SUPPORT.
SUSPENDED CEILING. SEISMIC WIRES ARE NOT TO BE
INDEPENDENTLY SUPPORT ALL CONDUIT ABOVE
CONCEALED, UNLESS OTHERWISE NOTED.
IN FINISHED INTERIOR AREAS, RUN ALL CONDUITS
1.
2.
3.
4.
5.
6.
7.
8.
GENERAL NOTES:
TYPE THHN/THWN, NO. 12 AWG MINIMUM.
STRANDED ONLY, UL LISTED, RATED FOR 600 VOLTS,
UNLESS OTHERWISE NOTED, ALL WIRE SHALL BE COPPER,
OUTLET ON A CIRCUIT.
DESIGNATED SINGLE POINT GROUND FOR EACH DUPLEX
INCLUDE A SEPARATE GROUND WIRE CONNECTED TO THE
GROUND WIRE. DEDICATED BRANCH CIRCUITS SHALL
ALL BRANCH CIRCUITS SHALL INCLUDE A CODE SIZED
REMOVE SWITCH, WIRING, BOX AND CONDUIT TO J-BOX ABOVE NEW CEILING.
EMERGENCY LIGHTING UNIT/EXIT SIGN
7
5
5
PP4-3
3
PP4-3
TYP. 6 (E)
D4
IN ROOM 20-5.
DEMO EXISTING WIRING FROM ABOVE CEILING JUNCTION BOX TO FIXTURES
D4
TYP. 6 (E)
D4
PP4-24
(E)J
IN �"C
+ #12G
(N)2 #12
PP4-24 PP4-24 PP4-24
PP4-24 PP4-24
PP4-24
PP4-24
PP4-24
PP4-24
PP4-24
PP4-24
PP4-24
PP4-24
POWER PANEL
"PP-4"
POWER PANEL
"PP-1"
"PP-4"
(E)POWER PANEL (E)POWER PANEL
"PP-1"
6
D5
D5 REMOVE OCCUPANCY SENSOR, SAVE FOR RE-USE, SEE LIGHTING NEW PLAN.
6 INSTALL OCCUPANCY SENSOR FOR LIGHTING AT ENTRY AND IN VESTIBULE AREA.
FURNISHED BY SLAC
LED LAMPS
NEW SWITHCH LOCATION.
PROVIDE AND INSTALL 6 LIGHTING FIXTURES AS SHOWN. A/B SWITCH FROM
EACH W/2 LED LAMPS FURNISHED BY SLAC.
RE-WIRE FIXTURES TO A/B SWITCHING FROM NEW SWITCH LOCATION. RETROFIT
7 RETROFIT NEW FIXTURES W/2 LED LAMPS FURNISHED BY SLAC.
D2
TYP. 9 (E)
FROM PANEL PP-4.
INSTALL BOX, CONDUIT AND WIRING TO SWITCHES AND DEDICATE CIRCUIT #24
ID38370024C0.dgn 6/21/2012 10:30:20 AM
TS
TS
TS
PS
24 2523
TS
PS
24 2523
AIR DISTIBUTION SCHEDULE
C0
DEMO, NEW WORK PLAN
HVAC
FACET LASER ROOM
KLYSTRON GALLERY SECTOR 20
DESCRIPTIONREV DRN CHK APP DATE
PRIOR WRITTEN PERMISSION OF STANFORD UNIVERSITY / SLAC.
NOT BE COPIED, PUBLISHED OR OTHERWISE FURTHER DISSEMINATED WITHOUT
THE DRAWINGS, SPECIFICATIONS AND OTHER DATA HEREIN PROVIDED SHALL
06/13/12
06/13/12
06/13/12
DATE
F:\ID38360001C0.DGN
E
E
KS WONG
APPROVALS
H. SHIN CHKR
F.Y. DES
H. SHIN ENGR
/ /
/ /
/ /
DATE
ID-383-600-01-
C0
ID-383-600-01
SCALE: AS SHOWN
DRAWING NUMBER REVISION
SEC 20-ALCOVE-MECH. WORK
OPTICALWORKAREA20-5
46"x24" RA DUCT
VD
VD
VD
12"x12"
14"x16"
20"x16"
CD1
800(TYP. 5)
48"x30" SA DUCT.
FLEX. CONN. BELOW
48"x16" RA DUCT WITH
14"x12"
VD VD
R-1
- (TYP.6)
12"x12" 6" ABV. FLR.
VD
46"x24" RA DUCT
CD2
600(TYP. 5)
14"x12"
VD VD
CD-2
14" FLEX.
12"X14"
SECTOR 20 ALCOVE PARTIAL PLAN - DEMO WORK"=1’-0"8
3SCALE: "=1’-0"83SCALE:
SECTOR 20 ALCOVE PARTIAL PLAN - NEW WORK
DETAIL 1
-
GENERAL NOTES:
CD2
600
SYMBOL DESIGN
BASIS OF
RANGE
CFM
(CFM)
FLOWRATE
OR GRILL
TO DIFFUSER
BRANCH DUCT SIZE
N.C.
MAX.
MOUNTING REMARKS
LAMI-VENT PAT 2448-C
PRECISION AIR PRODUCT SO. 0-1030 600
IN
NECK SIZE
SQ. OR ROUND
14"Ø 12" 45
W/ VOLUME CONTROL CONE
48"X24" PERORATED FACEPLATE MODULE
1.
T-BAR
DAMPER
(E) VOLUME
TO INSTALL A TOTAL JOB.
MATERIALS AND INCIDENTALS NECESSARY TO PREPARE FOR AND PERFORM THE WORK
THE SUBCONTRACTOR SHALL FURNISH ALL LABOR, TOOL, EQUIPMENT, SUPERVISION,
2.
FINAL LOCATION TO INSTALLATION IN T-BAR CEILING.
DUCKWORK LAYOUT IS DIAGRAMMATIC - SUBCONTRACTOR SHALL FIELD DETAIL
3.
STANDARD".
INSTALLED IN ACCORDANCE WITH THE LATEST SMACNA "HVAC DUCT CONSTRUCTION
NEW DUCTWORK SHALL BE OF GALVANIZED SHEET STEEL CONSTRUCTED AND
4.
AT EACH TAKEOFF FROM MAIN DUCTS.
PROVIDE DAMPERS WITH HANDLE STYLE REGULATOR SET AND NOTCHED HEX NUT
5.
SMACNA HVAC DUCT CONSTRUCTION STANDARDS.
THE DUCTWORK HANGING SYSTEM SHALL COMPLY WITH LATEST EDITION OF
ROOM
FACET LASER
ROOM
FACET LASER
ROOM
FACET LASER
LEGEND:
FLEX DUCT
DIFFUSER
RECTANGULAR DUCT
RETURN REGISTER
1
SHEET NOTES:
ABBREVIATION:
DET
BOD
BOP
(E) EXISTING
BOTTOM OF PIPE
BOTTOM OF DIFFUSER
DETAIL
(N) NEW
RA
SA
RETURN AIR
SUPPLY AIR
REMOVE EXISTING DIFFUSER AS SHOWN.
2 PROVIDE AND INSTALL NEW DIFFUSER AS SHOWN.
1 2
ID38360001C0.dgn 6/19/2012 9:03:51 AM
VLC
& DEVICES
VESDA PANEL
F
F
75cd
75cd
STROBE/HORN DEVICE
(TYP.)
ZONE 2
ZONE 2
LOAD
LOCK ROOM20-1
CONTROLLEDENTRY AREA
20-2
LOADING ANDWORK AREA
20-4
OPTICAL
WORK AREA20-5
EXISTING TUNNELACCESS SHAFT
AND STAIRS20-6
POWER
SUPPLIES20-7
23 282726252423 2827262524
FIRE ALARM RELOCATE/NEW WORK
ELECTRICAL-TEL.,DATA&SPRINKLER
FACET LASER ROOM
KLYSTRON GALLERY SECTOR 20
PRIOR WRITTEN PERMISSION OF STANFORD UNIVERSITY / SLAC.
NOT BE COPIED, PUBLISHED OR OTHERWISE FURTHER DISSEMINATED WITHOUT
THE DRAWINGS, SPECIFICATIONS AND OTHER DATA HEREIN PROVIDED SHALL
06/13/12
06/13/12
06/13/12
DATE
DO NOT SCALE DRAWING
E
K.S. WONG
D. BRITT
APPROVALS
K.S. WONG CHKR
F.Y. DES
V. LONGA ENGR
/ /
/ /
/ /
DATE
ID-383-700-23 -
C0
SCALE: AS NOTED
DRAWING NUMBER REVISION
SECT. 20 ALCOVE-DATA FA, WORK
F:\ID38370023C0.dgn
ID-383-700-23 C0 E
SCALE: �" = 1’-0" SCALE: �" = 1’-0"
F
F
75cd
75cd
STROBE/HORN DEVICE
(TYP.)
ZONE 2
ZONE 2
CONTROLLEDENTRY AREA
20-2
LOADING ANDWORK AREA
20-4
EXISTING TUNNELACCESS SHAFT
AND STAIRS20-6
POWER
SUPPLIES20-7
23 282726252423 2827262524
& DEVICES
VESDA PANEL
RELOCATED & TELECOM RACK
SIGNAL BOARD
DEMOLITION NOTES:
D4
D1
D2
D3
1
NEW WORK NOTES:
VLC
D1
D1
RELOCATE AIR SAMPLING TO NEW CEILING T-BAR
D3
RELOCATE VESDA TO NEW LOCATION. SEE NEW WORK PLAN
D4
1
8’-2in 8’-0in
8’-2in 8’-0in
ROOM
FACET LASER
ROOM
LASER
FACET
2
AT NEW CEILING.
INSTALL VESDA AIR SAMPLING INLETS W/ESCUTCHEON RING
2
2
2
3 INSTALL NEW SPRINKLER HEADS AT NEW CEILING.
SECTOR 20 - ALCOVE PARTIAL PLAN - DATA, SPRINKLER & FIRE ALARM NEW PLAN
3
SECTOR 20 - ALCOVE PARTIAL PLAN - DATA, SPRINKLER & FIRE ALARM DEMO/RELOCATE PLAN
D2
TYP. 6
RELOCATE FIRE SPRINKLER PIPING TO NEW CEILING.
WIRING ABOVE CEILING
REMOVE VOICE/DATA OUTLET AS SHOWN. COIL VOICE/DATA
(TYP. 6)
HEADS
(E) SPRINKLER
WITH FCM TO OBTAIN EXACT LOCATION PER USER.
APPROXIMATE NEW LOCATION OF RELOCATED VESDA. COORDINATE
ID38370023C0.dgn 6/20/2012 2:39:40 PM