    Oil Analysis An Important Tool for Transformer Diagnosis

    Conference on Electrical Power Equipment Diagnostics

    Bali, Indonesia

    Thomas Prevost

  • 8/12/2019 4 Prevost Oil Analysis

    2/42

    Oil Analysis

    Study and test the oil to determine

    the condition of overall insulation

    system

    1. Dissolved Gas Analysis DGA

    2. Oil Quality

    3. Furans

    Page 2 OMICRON

  • 8/12/2019 4 Prevost Oil Analysis

    3/42

  • 8/12/2019 4 Prevost Oil Analysis

    4/42

    Source of Gas Byproducts of Faults

    Oil

    Hydrogen

    Hydrocarbons

    Cellulose

    Carbon Oxides

    Water

    Page 4 OMICRON

  • 8/12/2019 4 Prevost Oil Analysis

    5/42

  • 8/12/2019 4 Prevost Oil Analysis

    6/42

    OMICRON

    Page 6

    Degradation of cellulose

    O

    H

    O

    HO

    H

    OH

    OH

    O

    H H

    CH2O

    CH2OH

    H

    O

    HH

    O

    OH

    H

    Heating

    Heating

    C O O C O

    O

    H H

    Carbon Monoxide Carbon Dioxide

    Water

    Section of

    Cellulose

    Molecule

  • 8/12/2019 4 Prevost Oil Analysis

    7/42

    DGA Analysis

    1. Fault Gas Levels

    2. Rate of Gas Generation (Trend)

    3. Ratio of Gas Levels

    Page 7 OMICRON

  • 8/12/2019 4 Prevost Oil Analysis

    8/42

    OMICRON

    Page 8

    Gases reported:

    Fault Gases

    Methane CH4 Ethane C2H6

    Ethylene C2H4Acetylene C2H2

    Carbon Monoxide CO

    Carbon Dioxide CO2

    Atmospheric Gases

    Nitrogen N2

    Oxygen O2

  • 8/12/2019 4 Prevost Oil Analysis

    9/42

    OMICRON

    Page 9

    Thermal Faults:

    Normal Operating Temperature:

    Carbon Monoxide CO

    Carbon Dioxide CO2

    150 C 500 C:

    150-250 C : Relatively large quantities of low molecular

    weight hydrocarbons

    Hydrogen H2 Methane CH4

    250-350 C : Increasing hydrogen relative to methane

    Ethane C2H6

    350-500 C : Still increasing hydrogen and ethylene

    Ethylene C2H4

    Sources of Fault Gases in Transformers

  • 8/12/2019 4 Prevost Oil Analysis

    10/42

    OMICRON

    Page 10

    Electrical Faults:

    Partial Discharges:

    Oil: HydrogenCellulose: Hydrogen, Carbon Monoxide

    Arcing:

    Oil: Acetylene, Hydrogen

    Sources of Fault Gases in Transformers

  • 8/12/2019 4 Prevost Oil Analysis

    11/42

    OMICRON

    Page 11

    Gas Generation(Not to Scale)

    Approximate Oil Decomposition

    Temperature above 150oC

    IEEE and IEC Codes to Interpret Incipient Faults in Transformers, Using Gas in Oil Analysis,

    by R.R. Rogers C.E.G.B, Transmission Division, Guilford, England. Circa 1978.

    Partial Discharge (Not TemperatureDependent)

    Range of Normal OperationHot Spots

    (Of increasingtemperature)

    Arcing Conditions

    65o

    150

    o

    200o

    300o

    800o

    700o

    500o

    350o

    250o

    Hydrogen (H2)

    Methane

    (CH4)

    Ethane (C2H6)

    Ethylene (C2H

    4)

    Acetylene (C2H2)

    CH4>H2

    C2H6>CH4

    C2H4>C2H6

    C2H2>10% of C2H4

    Trace

    Combustible Gas Generation vs.

    Approximate Oil Decomposition Temperature

  • 8/12/2019 4 Prevost Oil Analysis

    12/42

    DGA Diagnostic Methodology

    1. Determine if DGA results are Normal1. Single sample compare results to C57.104-2008 Table 1

    2. If greater than condition 1 then retest sample within two months1. Verifies results from first test

    2. Establishes gas generation rate

    3. Greater than one sample

    1. Calculate gas generation rate2. Compare rate to values in C57.104-2008 Table 3

    1. Sampling interval

    2. Action

    2. If DGA results are abnormal then follow various methodologies todetermine fault type and possible cause.1. Key gas

    2. Gas ratios

    Page 12 OMICRON

  • 8/12/2019 4 Prevost Oil Analysis

    13/42

    OMICRON

    Page 13

    Dissolved Key Gas Concentration Limits (L/L

    (ppm))

    StatusH2

    HydrogenCH4

    MethaneC2H2

    AcetyleneC2H4

    EthyleneC2H6

    Ethane

    CO

    CarbonMonoxide

    CO2

    CarbonDioxide TDCGb

    Condition 1 100 120 1 50 65 350 2500 720

    Condition 2 101-700 121-400 2-9 51-100 66-100 351-570 2500-4000 721-1920

    Condition 3 701-1800 401-1000 10-35 101-200 101-150 571-1400 4001-10000

    1921-4630

    Condition 4 >1800 >1000 >35 >200 >150 >1400 >10000 >4630

    IEEE C57.104-2008 Table 1

  • 8/12/2019 4 Prevost Oil Analysis

    14/42

    OMICRON

    Page 14

    TDCG

    Levels(L/L)

    TDCG Rate

    (L/L/day)

    Sampling Intervals and Operating Procedures for Gas

    Generation Rates

    SamplingInterval Operating Procedures

    Condition 4 >4630 >30 Daily Consider removal from service.

    Advise manufacturer10-30 Daily

    30 Weekly Exercise extreme caution.

    Analyze for individual gases.

    Plan outage.

    Advise manufacturer.

    10-30 Weekly

    30 Monthly Exercise caution.

    Analyze for individual gases.

    Determine load dependence.10-30 Monthly

    30 Monthly Exercise caution.

    Analyze for individual gases.

    Determine load dependence.

    10-30 Quarterly Continue normal operation.

  • 8/12/2019 4 Prevost Oil Analysis

    15/4215

    Factors influencing the interpretation of results:

    Type of faults:

    -PD: partial discharges of the corona-type.

    -D1: discharges of low energy.

    -D2: discharges of high energy.

    -T1: thermal fault (T < 300C).

    -T2: thermal fault (300 C < T < 700C).

    -T3: thermal fault (T > 700C).

    -DT: mixtures of discharges and thermal faults.

    -S: stray gassing of oil (T < 200 C), catalytic reactions (notrelated to faults).

  • 8/12/2019 4 Prevost Oil Analysis

    16/4216

    Typical faults in the equipment:

    -PD: corona partial discharges in voids or gas bubbles(poor drying, impregnation).

    -D1: partial discharges of the sparking type, tracking in

    paper, small arcing, arc breaking in LTC oil.

    -D2: short circuits with power follow-through, flashovers,

    tripping, gas alarms; extensive damage, metal fusion.

  • 8/12/2019 4 Prevost Oil Analysis

    17/4217

    Typical faults in the equipment:

    -T3: large circulating currents, shorts in laminations,carbon particles in oil.

    -T2: circulating currents, defective contacts,

    carbonization of paper.

    -T1: overloading, insufficient cooling.

    -S: stray gassing , catalytic reactions on wet metal

    surfaces.

  • 8/12/2019 4 Prevost Oil Analysis

    18/4218

    Mixtures of faults

    -mixtures of faults sometimes occur rather than pure faults and may be more difficult to identify with certainty.

    -for instance, mixtures of faults D1 and T3 may appear

    as faults D2 in terms of gas formation.

  • 8/12/2019 4 Prevost Oil Analysis

    19/4219

    Energy/ temperature required to produce gases:

    -Low energy/temperature: H2, CH4, C2H6, CO, CO2.

    -High temperature: C2H4.

    -Very high temperature/energy: C2H2.

    -In practice, always mixtures of gases are formed.

  • 8/12/2019 4 Prevost Oil Analysis

    20/4220

    Fault identification methods

    -Key gas

    -Rogers

    -Duval Triangle

    -CO and CO2(paper involvement in faults)

    -O2/N2 (hot spots, membrane leaks)

    -C2H2/H2(OLTC leaks)

  • 8/12/2019 4 Prevost Oil Analysis

    21/42

    OMICRON

    Page 21

    Oil

    Cellulose

    Hydrogen

    Carbon Monoxide, Carbon Dioxide

    Partial Discharge

    Oil Low Temperature Hydrogen, Methane, Ethane

    High Temperature Hydrogen, Ethylene, Methane, Ethane

    Cellulose Low Temperature Carbon Dioxide

    High Temperature Carbon Monoxide, Carbon Dioxide

    Pyrolysis

    (Acetylene is most significant)

    Hydrogen, Acetylene, Methane, Ethane, Ethane, Ethylene

    Arcing

    IEEE C57.104-2008 Key Fault Gases

  • 8/12/2019 4 Prevost Oil Analysis

    22/42

    Possible Faults

  • 8/12/2019 4 Prevost Oil Analysis

    23/42

    Possible Reasons

  • 8/12/2019 4 Prevost Oil Analysis

    24/42

    Rogers Ratio

  • 8/12/2019 4 Prevost Oil Analysis

    25/42

    DGA Diagnosis (Duval)

  • 8/12/2019 4 Prevost Oil Analysis

    26/42

    OMICRON

    Page 26

    Oil Quality Tests

    Tests the condition of the insulating fluid.

    Use results for maintenance action No action

    Recondition

    Reclaim

    Replace Use the results to access the condition of the

    Insulation System

    Dielectric Strength

    Power Factor

    Moisture Acid

    Furans

  • 8/12/2019 4 Prevost Oil Analysis

    27/42

    OMICRON

    Page 27

    Oil Quality Tests

    Several standards are referenced for oil quality testsand result interpretation:

    IEC 60422 Mineral Insulating Oil in Electrical Equipment

    Supervision and Maintenance Guide

    IEEE Guides

    C57.106-2006 Guide for Acceptance and Maintenance of

    Insulating Oil in Equipment

    C57.152 IEEE Guide for Diagnostic Field Testing of FluidFilled Power Transformers, Regulators, and Reactors

  • 8/12/2019 4 Prevost Oil Analysis

    28/42

    Dielectric, Physical and

    Chemical Analysis

    Dielectric measurementsBreak down voltage ASTM D 877

    Break down voltage ASTM D 1816 IEC 60156Power factor ASTM D 924 IEC 60247 Physical propertiesInterfacial tension ASTM D 971 EN 14210

    Particle Count ASTM D 6786 IEC 60970Sludge ASTM D 1698

    Water content ASTM D 1533 IEC 60814Visual ASTM D 1500 ISO 2049

    Specific gravity ASTM D 1298 ISO 3675Color (lab) ASTM D 1500 ISO 2049Color (field) ASTM D 1524Chemical propertiesPolychlorinated biphenyl ASTM D 4059 IEC 61619Acidity ASTM D 974 IEC 62021

    Dissolved gas ASTM D 3612 IEC 60599

  • 8/12/2019 4 Prevost Oil Analysis

    29/42

    OMICRON

    Page 29

    IEEE Oil Classifications

    Class I This group contains oils that are in satisfactory

    condition for continued use.

    Class II This group contains oils that do not meet the

    dielectric strength and/or water content requirement of Table 5 andshould be reconditioned by filter pressing or vacuum dehydration.

    Class III This group contains oils in poor condition that should

    be reclaimed using Fullers earth or an equivelent method. Oils that

    do not meet the interfacial tension (IFT), dissipation factor, and

    neutralization number limits provided in table 5 should be reclaimed.

  • 8/12/2019 4 Prevost Oil Analysis

    30/42

    OMICRON

    Page 30

    IEEE C57.106-2006 Suggested Limits

    If limits for:

    IFT

    Dissipation Factor

    Acidity

    are exceeded theoil should be

    reclaimed

    otherwise the oil

    can be

    reconditioned if the

    limits areexceeded.

  • 8/12/2019 4 Prevost Oil Analysis

    31/42

    OMICRON

    Page 31

    Moisture Content

    Karl Fisher Titration

    Requires approximately 10 mL of oil.

    Results are in ppm (mg/kg)

  • 8/12/2019 4 Prevost Oil Analysis

    32/42

    OMICRON

    Page 32

    Interfacial Tension (IFT)

    Measures the strength of the interface between the oil

    under test and water.

    Indicator of the presence of polar contaminents.

  • 8/12/2019 4 Prevost Oil Analysis

    33/42

    OMICRON

    Page 33

    Dielectric Strength

  • 8/12/2019 4 Prevost Oil Analysis

    34/42

    OMICRON

    Page 34

    Aging process : Cellulose depolymerization

    CH2OH

    O

    OH

    OH

    O

    CH2OH

    OH

    OH

    O

    O

    CH2OH

    OH

    OH

    O

    CH2OH

    O

    OH

    OH

    OH

    CH2OH

    OH

    OH

    O

    O

    CH2OH

    OH

    OH

    O

    OH

  • 8/12/2019 4 Prevost Oil Analysis

    35/42

  • 8/12/2019 4 Prevost Oil Analysis

    36/42

    OMICRON

    Page 36

    Degree of Polymerization

    Measurement of intrinsic viscosity after dissolving the cellulose

    in a specific solvent.

    Gives an average measurement of the number of glucose units

    per molecular chain.

    DP of Insulation Components prior to processing ~1200

    DP of Insulation Components following processing ~1000

    DP level considered as over-processed ~800

    DP level considered end of life ~200

  • 8/12/2019 4 Prevost Oil Analysis

    37/42

  • 8/12/2019 4 Prevost Oil Analysis

    38/42

    OMICRON

    Page 38

    HOH

    CO HOH

    HOH

    CH2OH

    OH

    O

    O H

    H

    H H OC

    OH

    H

    OCHO

    H

    H

    H

    WATER

    WATER

    WATER

    FURAN

    CARBON

    MONOXIDE

    Degradation of Cellulose

  • 8/12/2019 4 Prevost Oil Analysis

    39/42

    OMICRON

    Page 39

    Most labs determine the concentration of five furanic compounds:

    1. 2-furaldehyde (2FAL)

    2. 5-methyl-2-furaldehyde (5M2F)

    3. 5-hydroxylmethyl-2-furaldehyde (5H2F)

    4. 2-acetyl furan (2ACF)5. 2-furfuryl alcohol (2FOL)

    Note: 2FAL is stable for years while all other furanic compounds are less

    stable. They tend to form and then degrade to 2FAL over a time period of

    months.

    Furans

  • 8/12/2019 4 Prevost Oil Analysis

    40/42

    OMICRON

    Page 40

    2- Furfural vs. DP Correlation Plots

    Correlation of DP with 2-FAL

  • 8/12/2019 4 Prevost Oil Analysis

    41/42

    OMICRON

    Page 41

    Summary & Conclusions

    DGA is a valuable tool to detect transformer problems

    Sample can be taken while transformer is in service

    Can trend fault gases

    Industry Acceptance

    Oil Quality Testing can detect transformer problems as well as

    indicate maintenance actions

    Oil can be reconditioned or reclaimed

    Inceases life of insulation system

    Remove moisture, acids, particles etc.

    The remaining life of the insulation can be estimated with Furan

    analysis

  • 8/12/2019 4 Prevost Oil Analysis

    42/42

    Questions