    FBP FieldBusPlugTechnical Description

    V6

    Universal Motor Controller

    UMC22-FBP

    2CDC3

    42011F0003

    Docume

    ntatio

    n

    Version3

  • 8/2/2019 2CDC135001D0204

    2/80

  • 8/2/2019 2CDC135001D0204

    3/80

    UMC22-FBP 3

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Fig. 1: Universal Motor Controller UMC22-FBP2CDC

    342012F0003

    Contents Page

    Features ....................................................................................................................................................... 5

    Device construction ................................................................................................................................... 6Overview ................................................................................................................................................ 6

    Terminals, monitoring LEDs and operating elements on the front plate .............................................. 7

    Planning and commissioning ................................................................................................................... 8

    Guide to an operating installation (Overview) ....................................................................................... 8

    Wiring and internal 24 V / 0 V connections ........................................................................................... 9

    Interfacing with contactors ................................................................................................................... 10

    Motor current = Set current versus wiring ........................................................................................... 12

    External current transformer for higher currents ................................................................................. 13

    Interfacing to the fieldbus, addressing ................................................................................................ 14

    Configuring the bus master and binding in the UMC22-FBP as slave ............................................... 16

    Parameterization of the UMC22-FBP, proceeding .............................................................................. 18

    Switch on / off motor, local control ...................................................................................................... 19

    Info available on LEDs ......................................................................................................................... 20

    Info available on the Control Panel ..................................................................................................... 21

    Universal Motor Controllerfor high-grade motor protection and control, current range 0.24 to 63 A,

    with 6 digital inputs and 3 digital outputs, to connect to fieldbuses via FieldBusPlug

  • 8/2/2019 2CDC135001D0204

    4/80

    4 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Maintenance .............................................................................................................................................. 23

    Replacement of an UMC22-FBP in an operating installation ............................................................. 23

    Replacement of the controller unit only ............................................................................................... 23

    Data overview ............................................................................................................................................ 24

    Device inputs and outputs ................................................................................................................... 24

    Monitored signals / Commands ........................................................................................................... 25

    Diagnosis ............................................................................................................................................. 27

    Parameters, Overview ......................................................................................................................... 28

    Parameters, Description ...................................................................................................................... 29

    Technical data ........................................................................................................................................... 32

    Main power lines .................................................................................................................................. 32

    Control unit ........................................................................................................................................... 33

    Digital inputs ........................................................................................................................................ 33

    Digital outputs ...................................................................................................................................... 33

    FieldBusPlug connection ..................................................................................................................... 34

    Environment and mechanical data ...................................................................................................... 34

    Ordering data ....................................................................................................................................... 35

    Dimensions .......................................................................................................................................... 36

    Appendix A: Control Functions

    Transparent .........................................................................................................................................A-2

    Overload relay.....................................................................................................................................A-4

    Direct starter .......................................................................................................................................A-8

    Reversing starter ..............................................................................................................................A-13

    Star-delta starter 1 ............................................................................................................................A-19

    Pole-changing starter 1 ....................................................................................................................A-25

    Appendix B: Control Panel

    Overview .............................................................................................................................................B-2

    Menu ...................................................................................................................................................B-3

  • 8/2/2019 2CDC135001D0204

    5/80

    UMC22-FBP 5

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Features

    Overview

    - The Universal Motor Controller UMC22-FBP provides high-grade motor protection and control for the

    current range 0.24 up to 63 A with one type.

    For higher currents additional protection current transformers (class 5P10) can be used.

    - With the integrated FieldBusPlug interface the UMC22-FBP can be connected to different fieldbuses

    using the appropriate type of FieldBusPlug.

    - 6 digital inputs and 3 relay outputs offer to realize a wide range of predefined control functions and

    applications such as direct starterand star-delta starterincluding local operation via digital inputsand others as selected by parameters.

    - Depending on the parameterization, the status of the digital inputs and outputs, the actual current,

    detailed diagnosis information and all parameters are accessible via the fieldbus (supposed the

    fieldbus offers the appropiate features).

    - LEDs on the UMC22-FBP monitor 'Ready', 'Motor On' or 'Fault'.

    - Additional Control Panel ACS100-PAN (separate delivery) offers similar access to all important

    information. The Control Panel is necessary to set the fieldbus slave address and can be snapped in

    on the front of the UMC22-FBP.

    - Also, the overload protection behaviour and other functions can be changed by parameters in a wide

    range. More details see chapters "Data overview, Parameters ...".

    - The control function Overload relayis dedicated to use the UMC22-FBP similar to an overload relay

    with and without fieldbus connection. The other control functions can be used stand-alone, too.

    Construction

    - The UMC22-FBP consists of two separate parts: Current transformer set and controller unit,

    mounted as one device.

    - Mounting on DIN rail or with screws. W x H x D = 70 x 105 x 110 mm. Degree of protection IP20.

    - Current-carrying motor lines are lead through the current transformer set.

    - Replacement of the controller unit without removing the current-carrying motor lines.

    - Parameters are stored in the current transformer set even if power down happens. This allows to

    replace the controller unit without reparameterization.

    Overload protection

    - Measuring the motor current (value is also provided to be sent to the fieldbus)

    - Electronic overload protection for nominal currents of 0.24 A to 63 A (whole range with onIy one type

    of device). Set currents selectable with parameter via fieldbus or Control Panel.

    - Trip classes 5, 10, 20 and 30 (selectable with parameter)

    - Phase-loss protection

    - Short circuit protection of the motor lines by external fuses on the line side.

    Other features

    - With parameter it can be selected between 'Relays off' or 'Relays retain status' in case of control

    system or fieldbus failure.

    - Diagnostic information available via LEDs, fieldbus and Control Panel.

    - Preventive diagnosis functions (e.g. number of starts)

    - Function blocks or similar software tools to be implemented into the program of the control system

  • 8/2/2019 2CDC135001D0204

    6/80

    6 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Device construction

    Overview

    UMC22-FBP:

    current transformer set

    UMC22-FBP:

    controller unit

    Control PanelACS100-PAN:

    (optional)

    complete

    device

    label

    Fig. 2: UMC22-FBP: Device construction 2CDC

    342013

    F0003

    FieldBusPlug

  • 8/2/2019 2CDC135001D0204

    7/80

    UMC22-FBP 7

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    181716151413121110

    DIDIDIDIDIDI24240

    543210VVV

    EXT.

    1

    8

    DO

    1

    7

    DO

    0

    6

    DO

    C

    5

    DO

    C

    9

    DO

    2

    8765 92 3 4

    UMC22

    READY

    MOT.ON

    FAULT

    INT.

    EXT.

    SWITCH

    LOC REM

    MENU

    ENTER

    Fig. 3: UMC22-FBP: Terminals, indicators and operating elements

    switch for selecting the internal electronics supply voltage:left position: external supply (via terminals 10/11)

    right position: supply via FieldBusPlug

    current path (for measuring the motor current)

    connecting terminals for the digital outputs

    plug connection for the Control Panel

    pawl to snap on the Control Panel

    LEDs:

    green READY (ready for operation)

    yellow MOT. ON (motor on)

    red FAULT (overload, failure)

    DIN rail

    connector for the FieldBusPlug

    front label, e.g. for slave address

    Control Panel holder. Insert the Control Panel at this

    holder and then snap it into the pawl on the upper side.The electrical contacts are automatically connected.

    connecting terminals for the digital inputs

    connecting terminals for the external supply voltage

    (supply for internal electronics)

    Snap-mountable Control Panel ACS100-PAN for

    monitoring and control / adjust:

    slave address

    control function

    overload parameters

    local diagnosis

    etc.

    The Control Panel ACS100-PAN is not shipped together

    with the UMC22-FBP. It must be ordered separately.

    mounting by 4 screws M4

    current path (for measuring the motor current)

    2CDC

    342014

    F0003

    Device construction (continued)

    Terminals, monitoring LEDs and operating elements on the front plate

  • 8/2/2019 2CDC135001D0204

    8/80

    8 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Planning and commissioning

    Guide to an operating installation (Overview)

    Wiring and internal 24 V / 0 V connections

    Hard-wire with switch apparatus and other components referring to the application requirements,

    see Appendix A "Control functions", example "Direct starter".

    Use external supply (SWITCH to EXT), if components are distant to the UMC22-FBP.

    Interfacing with contactors

    Use spark suppression, for larger contactors also interface relays to keep good lifetime of the

    UMC22-FBP internal relays.

    Motor Current = Set current versus wiring

    Have a look at the wiring of the motor to define the correct set currentfor complete motor

    protection.

    External current transformer for higher currents

    Connect external current transformers for higher currents.

    Connection to the fieldbus, addressing

    Use the appropriate FieldBusPlug.

    Change slave address.

    The bus master is normally defined by the control system.

    Configuring the bus master and binding in the UMC22-FBP as slave

    Load slave configuration file into the programming tool.Example: ABB_078F.GSD for UMC22-FBP as PROFIBUS DP slave.

    Create fieldbus configuration together with the application program in the control system.

    For some control systems dedicated function blocks or example programs are available.

    Parameterization of the UMC22-FBP, proceeding

    As default the control function selected in the UMC22-FBP is transparent: The inputs and outputs

    are directly controlled by the fieldbus telegram.

    To control and protect a motor optimal a motor control function e.g. Direct startermust be

    selected. After parameterization and power-on the motor can be started.

    Details see chapter "Data overview, Parameters ...".

    The parameterization tool depends on the fieldbus type and the control system.

    Examples:

    - The slave configuration file (e.g. GSD file for PROFIBUS DP) contains the parameterization

    medias. The parameters can be changed during configuration of the fieldbus and are loaded

    into the UMC22-FBP during power-on.

    - Parameterization as a part of the application program.

    - Parameterization with the Control Panel. Details see Appendix B "Control Panel.

    As a special feature the Control Panel allows the user to read the complete parameter set of an

    UMC22-FBP and to transfer it to another UMC22-FBP, see Appendix B "Control Panel.

    Start Motor with RUN command. See also:

    Switch on / off motor, local control

    Info available on LEDs , Info available on the Control Panel

    bold: sub clause in this chapter

  • 8/2/2019 2CDC135001D0204

    9/80

    UMC22-FBP 9

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    24 V

    0 V

    690 / 400 V

    UMC22

    FieldBus

    Plug

    11

    24

    V

    24

    V

    12 13 14 15

    DI

    2

    16 17 18

    DI

    4

    DI

    5

    DI

    0

    DI

    1

    DI

    3

    EXT

    INT

    SWITCH

    0V 24V 24V

    24 V0 V

    24 V0 V

    10

    0

    V

    DI1 DI2 DI3 DI4 DI5

    230 V DO1

    DO

    C

    5 6

    DO

    C

    DO

    0

    7

    DO

    2

    9

    DO

    1

    8

    K1K1

    DO2N

    K1

    max.

    70 mA

    Planning and commissioning (continued)

    Wiring and internal 24 V / 0 V connections

    Example: Direct starter

    With the parameter 'Control function' = 3 ('Direct starter')the relay output DO0 is used to control the main contactor

    Free outputs, commandsdirect from fieldbus

    With the parameter 'Check-back' = 1 ('Auxiliary

    contacts') the digital input DI0 is used to survey

    the contactor (default: 2 ('Motor current'))

    Free outputs, monitoring

    signals directly to the fieldbus

    Important:

    Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. Inthis case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests

    urgently this kind of supply.

    If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -

    the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).

    if EXT

    supply

    to supply

    inputs

    Fig. 4: UMC22-FBP:Direct starter (example)

    2CDC

    342060F00

    03

  • 8/2/2019 2CDC135001D0204

    10/80

    10 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    24 V

    0 V

    UMC22

    11

    24

    V

    24

    V

    12 13 14 15

    DI

    2

    16 17 18

    DI

    4

    DI

    5

    DI

    0

    DI

    1

    DI

    3

    EXT

    INT

    SWITCH

    10

    0

    V

    DO

    C

    5 6

    DO

    C

    DO

    0

    7

    DO

    2

    9

    DO

    1

    8

    max.

    70 mA

    0 V 24 V 24 V

    K1

    K2

    K1

    K2

    K1

    690 / 400 V AC230 V N

    Planning andcCommissioning (continued)

    Interfacing of contactors

    (For info about contactors refer to the actual main catalogue)

    Spark suppression

    Spark suppression is always necessary to avoid early failure of the relay contacts.

    Contactor type connected to the UMC22-FBP Type B6, B7 A9 to A40

    Appropriate suppressor for 230 V AC VDR RV-BC 6/250 RV 5/250

    Appropriate suppressor for 24 V AC / DC VDR RV-BC 6/60 RV 5/50

    Contactor type: A45 and larger

    Spark suppression

    For check-back the auxiliary contact of the main contactor has to be used!

    if EXT supply output

    Fig. 5: UMC22-FBP: Connecting contactors with peak current > 0.5 A: Types A45 and larger2CDC

    342061F0003

  • 8/2/2019 2CDC135001D0204

    11/80

    UMC22-FBP 11

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    1

    2

    3

    690 / 400 V AC+ 24 V DC -

    K1ON

    OFF-N

    COM

    230 V AC

    DO

    C

    5 6

    DO

    C

    DO

    0

    7

    DO

    2

    9

    DO

    1

    8

    UMC22

    Planning and commissioning (continued)

    Overview of available ABB contactors (examples)

    Contactor type Inrush current [A] Holding current [A] Inrush power [VA] Holding power [VA]

    BC6-30-10-2.4 0.015 0.015 3.5 3.5

    A9, A12, A16 0.30 0.03 70 8

    A26, A30, A40 0.52 0.05 120 12

    A45, A50, A63, A75 0.78 0.08 120 12

    A95, A110 1.52 0.10 180 18

    A145, A185 2.39 0.15 550 35

    A210, A260, A300 5.87 0.26 1350 60

    The contactor BC6-30-10-2.4 is recommended as interface contactor due to internal spark suppression.

    Contactors A145 to A300 also with electronic interface available (AF145 etc.), larger contactors only with

    electronic interface.

    Lifetime UMC22-FBP mechanical 500 000 switching cycles

    relays (see chapter 0.50 100 000 switiching cycles

    "Technical data") 1.00 50 000 swiching cycles

    Remark:

    Slide switch on the leftside to position "PLC" (up)

    Fig. 6: UMC22-FBP: Connecting larger contactors with electronic interface (AF 145 and larger)2CDC

    342062F0003

  • 8/2/2019 2CDC135001D0204

    12/80

    12 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    U2W2 V2

    V1 W1U1

    690 V

    UMC 22

    ISC=IP

    IP

    U2W2 V2

    V1 W1U1

    400 V / 690 V4.9 A / 2.8 A

    IP=2.8A / ISC=2.8A

    = 2.80

    W2

    U1

    U2

    V1 W1

    V2

    400 V

    UMC 22

    ISC=IP

    U2W2 V2

    V1 W1U1

    IP

    400 V / 690 V4.9 A / 2.8 A

    IP=4.9A / ISC=4.9A

    = 4.90

    V1 W1U1

    W2 U2 V2

    400 V

    UMC 22

    IP

    U2W2 V2

    V1 W1U1

    ISC=0.577*IP

    400 V / 690 V4.9 A / 2.8 A

    IP=4.9A / ISC=2.8 A

    = 2.80

    Planning and commissioning (continued)

    Motor current = Set current versus wiring

    Fig. 7: UMC22-FBP: Motor current = Set current versus wiring2CDC

    342063F0003

    The Delta 3 circuitry is normally used for larger motors to reduce the current transformer size. Theparameter 'Set current' is the nominal motor current devided by 3.

    Terminal boxTerminal box Terminal box

    Motor rating plateMotor rating plate Motor rating plate

    Example for motor:Example for motor: Example for motor:

    StarPower line:

    Delta 1Power line:

    Delta3Power line:

    ParameterParameter Parameter

    'Set current' 'Set current' 'Set current'

  • 8/2/2019 2CDC135001D0204

    13/80

    UMC22-FBP 13

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Accuracy class: actual / nominal current 5 % 20 % 100 % 120 % 500 %

    accuracy class 3 1.5 1 1 5

    Remark:

    For Delta 3 circuitry - normally used for larger motors - the parameter 'Set current' is the nominal motorcurrent devided by 3, see preceeding chapter.

    Type / Current range Recom- Second. Hole Cables Link kit (bar) type*Star, mended current area (E/EN for contactor

    Delta 1 range range W x H 60204) (order code see

    [A] [A] [A] [mm] [mm2] "Technical data")

    UMC22-FBP without 0.24 ... 63 0.24 ... 63 - 11 max. 252 -current transformer **

    KORC 4L185 46 ... 185 60 ... 185 1.3 ... 4 22 x 28 1 x 702 DT450 / A185

    AF145 - AF185

    KORC 4L310 80 ... 310 180 ... 310 2.3 ... 4 22 x 28 2 x 702 DT450 / A300

    AF260 - AF300

    KORC 5L500 125 ... 500 300 ... 500 2.4 ... 4 41 x 22 3 x 702 DT500 / AF460S*

    AF400 - AF460

    KORC 5L850 213 ... 850 500 ... 850 2.4 ... 4 41 x 22 - DT500 / AF750S* AF580 - AF750

    * Link kits for Star-delta starter. (Others see catalogue.)

    ** max. cable diameter with insulation 11 mm

    Fig. 8: UMC22-FBP: External current transformer for higher currents2CDC

    342064F0003

    Planning and commissioning (continued)

    External current transformer for higher currents

    All types of protection current transformers class 5P10 referring the Standard EN 60044 can be used.The selection should be made based on the requirements:

    - secondary current range (= current in the UMC22-FBP) about 5 A (recommended current

    transformers have 4A)

    - through-hole area if single cores are used,- accuracy in the measuring range (50 - 150%) should be class 1, because the inaccuracy is added to

    the inaccuracy of the UMC22-FBP,

    - max. burden 60 m (UMC22-FBP: 30 m , conductor 2x2 m 2.5 mm2: 30 m)

    The pass through sense of the strands does not affect the operation.

    For the current range up to 850 A space saving combinations are recommended.

    max. length 2 x 2 m, cross section 2.5 mm2

  • 8/2/2019 2CDC135001D0204

    14/80

    14 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Planning and commissioning (continued)

    Interfacing to the fieldbus, addressing

    The normal requirement is that the slave address corresponds with the motor. That means: The slaveaddress shall be adjusted and saved in the connected UMC22-FBP. This is possible for all fieldbuses

    except the AS-Interface fieldbus (actual integrated AS-Interface circuits do not allow).

    To adjust the address the Control Panel can be used. Immediately when mounted or when the

    combination is switched on, the address is monitored. Details see Appendix B "Control Panel".

    The UMC22-FBP does not contain a valid address.

    (A000 is a valid address but could be reserved de-pending on the type of the fieldbus). The status

    "no valid address" can be restored setting A999.

    The slave does not start on the bus without a

    valid address.

    CPU coupler,

    bus master

    Fig. 9: UMC22-FBP: Adressing2CDC

    342015F0003

    An other way to adjust the address in the FieldBusPlug is to use the "Addressing Set" CAS21-FBP.0

    (Interface unit + PC with addressing SW). See technical description 2CDC 190 012 D02--.

  • 8/2/2019 2CDC135001D0204

    15/80

    UMC22-FBP 15

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Planning and commissioning (continued)

    Interfacing to the fieldbus, addressing (continued)

    When switching on the combination UMC22-FBP FieldBusPlug, both or one or none of them cancontain a fieldbus address.

    The behaviour in these cases depends on the parameter 'Address check', see chapter "Data overview,

    Parameters, Description".

    'Address check' = 'Off' (= 0) (default):

    1. Neither the UMC22-FBP nor the FieldBusPlug contains a valid address:

    - The UMC22-FBP does not start to operate and to communicate.

    2. Only the UMC22-FBP contains a valid address:- The FieldBusPlug gets the address and saves it. Operation and communication starts.

    3. Only the FieldBusPlug contains a valid address:

    - The UMC22-FBP gets the address and saves it. Operation and communication starts.

    4. The UMC22-FBP and the FieldBusPlug contain the same address:

    - Operation and communication starts.

    5. The UMC22-FBP and the FieldBusPlug contain different addresses:

    - The FieldBusPlug stores the address received from the UMC22-FBP. Operation and

    communication starts.

    'Address check' = 'On' (= 1). Mainly used for draw-out design.

    This parameter can only be set via bus master and fieldbus.

    1. Neither the UMC22-FBP nor the FieldBusPlug contains a valid address:

    - The UMC22-FBP does not start to operate and to communicate.

    2. Only the UMC22-FBP contains a valid address:- The FieldBusPlug gets the address and saves it. Operation and communication starts.

    3. Only the FieldBusPlug contains a valid address:

    - The UMC22-FBP gets the address and saves it. Operation and communication starts.

    4. The UMC22-FBP and the FieldBusPlug contain the same address:- Operation and communication starts.

    5. The UMC22-FBP and the FieldBusPlug contain different addresses:

    - Neither the operation nor the communication starts.

    - The Control Panel displays alternating (3 seconds each):

    Address of UMC22-FBP:

    Address of the FieldBusPlug:

    - Communication fault (F003) is set.- With the Control Panel the menu 2.3 'Change address' has to be selected and the desired

    address must be adjusted. Details see Appendix B "Control Panel".

    - After leaving this menu operation and communication starts immediately. Both the FieldBusPlug

    and the UMC22-FBP store the adjusted address.

    Remark: If the adjusted FieldBusPlug address is not configured in the fieldbus master the

    communication does not start and the red LED on the FieldBusPlug displays fault.

  • 8/2/2019 2CDC135001D0204

    16/80

    16 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    R.....Hardware-Configuration

    07 KT 97-DPM (DP-Master)

    Hardware-Configuration

    07 KT 97-DPM [DP-Master]

    ABB FBP 2003-03-13 [DP-Slave]

    Planning and commissioning (continued)

    Configuring the bus master and binding in the UMC22-FBP as slave

    The control systems, programming tools and the fieldbus types are totally different.

    This means: There is no common rule to configure the fieldbus master and to bind in

    FieldBusPlug slaves into the application program.

    Example

    UMC22-FBP connected to an ABB CPU type 07 KT 97 via PROFIBUS DP

    Preparation of the programming tool 907AC1131:

    Before starting the programming tool 907AC1131 the file - ABB_078F.GSD must be copied into the

    programming SW subdirectory, normally into: ...\AC1131\Library\PLCConf.

    The appropriate ABB_078F.GSD has the version 1.3 (2003-11-09):

    2CDC

    342082F0003

    Binding in the slave:

    - :

    place pointer, click right mouse key twice2CDC

    342083F0003

    - Select , , to transfer into the column right

    - Select , table to change station (=slave) address

    - Select , table ,, to transfer into the column right

    place pointer, click right mouse key twice

    Configuration of the bus master:

    - Start programming SW 9 07AC1131- Select in the main menu (left side, below, R....)

    - Change and - under Bus parameters - if desired.

    - Set - under Standard parameters = on

    - Now the bus master is defined:

    2CDC

    342088F0003

  • 8/2/2019 2CDC135001D0204

    17/80

    UMC22-FBP 17

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    LAN

    CPU

    PROFIBUS DP (/V0)

    --> Master Class 1

    PROFIBUS DP/V1

    --> Master Class 2

    DeviceNet:

    (EDS = Electronic Data Sheet)

    Planning and commissioning (continued)

    Configuring the bus master and binding in the UMC22-FBP as slave (continued)

    I/O addresses are allocated automatically if is selected during bus masterconfiguration: Allocation of the I/Os based of the slave address follow the rule:

    S = 6 Input %IW1.8 %IB1.16 %IX1..8.0 ...1.8.7 RUN REVERSE*

    Slave to PLC %IB1.17 %IX1..8.8 ...1.8.15 not used*

    address (Monitorings) %IW1.9 %IB1.19 %IX1..9.0 ...1.9.7 motor current, high byte

    %IB1.20 %IX1..9.8 ...1.9.15 motor current, low byte

    Output %QW1.8 %QB1.16 %QX1.8.0 ...1.8.7 RUN REVERSE*from PLC %QB1.17 %QX1.8.8 ...1.8.15 not used*

    (Commands) %QW1.9 %QB1.19 %QX1.9.0 ...1.9.7 not used*

    %QB1.20 %QX1.9.8 ...1.9.15 not used*

    * only lowest bit shown

    (S-2) x 2

    coupler slot 1 x 2

    Parameterization of the UMC22-FBP, proceeding

    Some parameters define the application circuit diagram, others are used for current setting and overload

    features etc. This requests and means: The UMC22-FBP starts operation only after receiving valid

    parameters. Details see chapter "Data overview, Parameters, Description".

    The possibility to write and to read parameters depends definitely on the fieldbus and the control system.

    Examples:

    The transfer of parameters

    between the control station

    and the automation station

    Write parameters with

    GSD file during power-on.

    Read not possible. Configuration file:

    ABB_078F.GSD

    Write and read parameters

    whenever desired.

    Write and read parameters

    whenever desired. Configuration file:

    ABB_UMC22-FBP-ESD

    fieldbus

    coupler

    Fig. 10: UMC22-FBP: Write and read parameters2CDC

    342065F0003

  • 8/2/2019 2CDC135001D0204

    18/80

    18 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Planning and commissioning (continued)

    Parameterization of the UMC22-FBP, proceeding (continued)

    Additional: The parameterization can be done with the Control Panel. Details see Appendix B"Control Panel".

    Special feature of the Control Panel: It can be used to read the complete parameter set of aparametrized UMC22-FBP and to transfer it to another UMC22-FBP, see Appendix B "Control

    Panel".

    Example continued

    Configuring the UMC22-FBP as slave connected to the 07 KT 97 via PROFIBUS DP

    - Select on table when UMC22-FBP is present in the column rightNow the parameters can be changed (left then right mouse key).

    The procedure, however, can be more or less different for other control systems and fieldbuses .

    2CDC

    342089F0003

  • 8/2/2019 2CDC135001D0204

    19/80

    UMC22-FBP 19

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    CPU

    In an operating installation, the motor contactors are switched On and Off normally by the control system

    with the commands RUN FORWARD, RUN REVERSE and OFF.

    Switching On (Run) and Off is possible when the UMC22-FBP is parameterized with one of the motor

    controlling Control functions e.g. 'Direct starter, 'Star-delta starter' etc. The exceptions are 'Transparent'

    and 'Overload relay'. Switching On (Run) and Off can be done:

    via control system via Control Panel via digital inputs

    Motor control:

    via Control Panel

    via control system

    via digital inputs

    Fig. 11: UMC22-FBP: Motor control2CDC

    342066F0003

    Planning and commissioning (continued)

    Switch on / off motor, local control

  • 8/2/2019 2CDC135001D0204

    20/80

    20 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Planning and commissioning (continued)

    Switch on / off motor, local control (continued)

    Table of conditions:

    always possible

    control system

    Control Panel

    digital inputs

    control system sends to the

    UMC22-FBP the command:

    control system

    Control Panel

    digital inputs

    if menu

    'Local control'is activated*

    if parameter

    'Local control viadigital inputs' = 'On'

    OFF

    AUTO MODE = 1

    if not blocked by

    local control

    via Control Panel

    AUTO MODE = 1

    (blocked if

    AUTO MODE = 0*)

    RUN

    FORWARD

    / REVERSE

    (after OFF

    0-1transition

    necessary)

    dominating

    if menu

    'Local control' isactivated**

    if not locked by

    local control via

    Control Panel

    if parameter

    'Local control via

    digital inputs' = 'On'

    AUTO MODE = 0

    (blocked if

    AUTO MODE = 1)*

    alternatively:

    connection to

    control station

    interrupted

    AUTO MODE = 0

    dominating

    dominating

    * AUTO MODE = 1: UMC22-FBP ignores RUN from digital inputs, monitors LOCAL CONTROL = 0,

    AUTO MODE = 0: UMC22-FBP ignores RUN from control station, monitors LOCAL CONTROL = 1.

    ** When local control is entered the UMC22-FBP monitors LOCAL CONTROL to the control system.

    local control is immediately stopped when Control Panel is removed or menu 'Local control' is left.The status of the outputs is not changed when entering or leaving local control.

    2CDC

    342087F0003

  • 8/2/2019 2CDC135001D0204

    21/80

    UMC22-FBP 21

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    READY

    MOT.ON

    FAULT

    INT

    EXT

    SWITCH

    55 6

    DODODODODOC C 0 1 2

    7 8 9

    EXT

    5 6 7 8 91 2 3 4

    ABB UMC22

    24 DI DI DI DI DI DI0 24V V 0 1 2 3 4 5V

    12 13 14 15 16 17 1810 11

    Connection to the fieldbus:

    Caused by the definitions of the

    fieldbus type the meaning can

    differ slightly.

    green = on, red = off: normal data exchange

    green = off, red = off:

    check power supply

    one of the LEDs flashing:

    no connection to the bus-master or configuration error

    or parameters not valid

    For more info see approriate

    FieldBusPlug description.

    Connection to the device:

    green = on, red = off:

    normal data exchange

    green = off, red = off:

    check power supply

    both LEDs flashing:

    self test

    one of the LEDs flashing:

    no connection to UMC22-FBP.

    For more info see approriate

    FieldBusPlug description.

    Planning and commissioning (continued)

    Info available on LEDs

    green: ready for operation

    yellow: motor running(overload, check-

    back fault, blocking

    stops the motor)

    red: Fault (overload, other

    failure)

    If no LED is on, check whetherpower is on and the switch

    (above the FieldBusPlug

    socket) is in the appropriate

    position: EXT if supplied via

    terminals, INT if supplied via

    FieldBusPlug.

    Info available on the Control Panel

    The Control Pannel can be mounted on the front of the UMC22FBP and offers access to:

    - Slave address

    - Status of the motor (running, off) and status of the UMC22-FBP inputs and outputs,

    - Actual current and 'Set current',

    - Detailed diagnosis information,

    - Service data- All important parameters

    In addition the Control Panel allows to start and stop the motor (local control)

    The access is arranged in three levels:

    - Monitoring: Offers only to check, not to modify values and parameters

    - Edit 1: Needs password and allows to change parameters during commissioning and also

    local control

    - Edit 2: Accessible via Edit 1, to change parameters that are used mainly associated with the

    circuitry.

    2CDC

    342090F0003

  • 8/2/2019 2CDC135001D0204

    22/80

    22 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    MENU

    ENTER

    Edit 2

    e.g.

    - passwordchange

    - control function

    e.g. Y- ,

    - fault input

    - behaviour if

    bus fails

    - ...

    Edit 1

    e.g.

    - password

    check

    - local control

    - address

    adjust- current

    - trip class

    - ...

    Monitoring,

    e.g..

    - address

    - I/O-signals

    - Current

    - fault incl..

    acknowledge

    - ...

    S

    t

    a

    r

    t

    LOC REM

    MENU

    ENTER

    LOC

    REM

    FAULT Cprm

    kHz%

    mAVs

    OUTPUT PAR SET MENU FWD REV

    Planning and commissioning (continued)

    Info available on the Control Panel

    Overview of the levels

    2CDC

    342091F0003

    For details see Appendix B "Control Panel.

    Remarks:

    Most of the changed parameters are taken over after motor off. Some parameters are taken over during power-on.

    Remark: Some control systems overwrite the parameters on principle during power-on. This can lead

    to the opinion that the parameterizing via Control Panel is not effective.

  • 8/2/2019 2CDC135001D0204

    23/80

    UMC22-FBP 23

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    2CDC

    342016F0003

    Maintenance

    Replacement of an UMC22-FBP in an operating installation

    The UMC22-FBP can be disconnected from the FieldBusPlug without disturbing the fieldbus and theother slaves. The FieldBusPlug is supplied via the voltage conducted together with the bus lines.

    The FieldBusPlug keeps stored the actual slave address and informs the control system that the

    connected device is lost.

    After mounting and connecting a new UMC22-FBP, the control system will be informed that the missing

    slave is complete again (supposed that the new UMC22-FBP contains an invalid address A - - -).

    This allows the control system to download the former parameters and to start up the new UMC22-FBP

    again with correct parameters.

    Replacement of the controller unit only

    Replace only the controller:

    The complete wiring,

    particularly the power lines, can

    be left unchanged.

    The parameters remainstored in the current

    transformer unit.

    The new controller reads theparameters during power-on *.

    current

    transformer

    unit

    controller out of order new controller

    Fig. 12: UMC22-FBP: Replacing the controller unit

    * In addition the parameters can be stored also in the control system and downloaded after power-on.

  • 8/2/2019 2CDC135001D0204

    24/80

    24 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Data overview

    Device inputs and outputs

    The function of the hardware inputs and outputs is fixed by parameterization. Refer parameters Controlfunction and Attached control functions.

    Example (1)

    Control function 'Transparent'

    All Inputs and outputs are directly connected to the Fieldbus as monitoring signals and commands.

    Terminal 13 14 15 16 17 18

    Device DI0 DI1 DI2 DI3 DI4 DI5

    Input to bus to bus to bus to bus to bus to bus

    Terminal 7 8 9

    Device DO0 DO1 DO2

    Output from bus from bus from bus

    Example (2)

    Control function 'Direct starter'

    One output is used to control the contactor coil. Access via fieldbus is not possible.The other inputs and

    outputs are still transparent to the fieldbus

    Terminal 13 14 15 16 17 18

    DeviceDI0 DI1 DI2 DI3 DI4 DI5Input to bus to bus to bus to bus to bus to bus

    Terminal 7 8 9

    Device Contactor DO1 DO2

    Output coil from bus from bus

    Example (3)

    Control function 'Direct starter' withAttached control function 'Local control via digital inputs'

    Additional inputs are used to allow local control. Details see Appendix B "Control Functions".

    Terminal 13 14 15 16 17 18

    Device DI0 DI1 DI2 DI3Local control Local control

    Input to bus to bus to bus to busRun Fwd. Off

    DI4 to bus DI5 to bus

    Terminal 7 8 9

    Device Contactor DO1 DO2

    Output coil from bus from bus

  • 8/2/2019 2CDC135001D0204

    25/80

    UMC22-FBP 25

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Data overview (continued)

    Monitored signals / Commands

    Monitored signals are sent from the UMC22-FBP to the control station,commands are received by the UMC22-FBP from the control station.

    The commands and monitored signals depend on the Control function and the Attached controlfunctions'.

    Complete overview on all signals

    Bit No. 7 6 5 4 3 2 1 0

    Monitor LOCALREVERSING

    RUN RUN

    Byte 0WARNING FAULT

    CONTROLLOCK-OUT -

    FORWARDOFF

    REVERSE*TIME*

    Monitor DI5 DI4 DI3 DI2 DI1 DI0 - -Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)

    MonitorMOTOR CURRENT (% of Set current)

    Byte 2/3

    Command-

    FAULT AUTO- -

    RUNOFF

    RUN

    Byte 0 RESET MODE FORWARD REVERSE

    Command DO2* DO1* DO0*- - - - -

    Byte 1 (UMC output) (UMC output) (UMC output)

    * used depending on the control function

    Example

    Control function 'Direct starter' with

    Attached control function 'Local control via digital inputs'

    Bit No. 7 6 5 4 3 2 1 0

    Monitor LOCAL RUN

    Byte 0WARNING FAULT

    CONTROL- -

    FORWARDOFF -

    MonitorLocal control Local control

    DI3 DI2 DI1 DI0

    Byte 0OFF RUN FOR.

    (UMC input) (UMC input) (UMC input) (UMC input)- -

    DI5 to bus DI4 to bus

    MonitorMOTOR CURRENT (% of Set current)

    Byte 2/3

    Command-

    FAULT AUTO- -

    RUNOFF -

    Byte 0 RESET MODE FORWARD

    Command DO2 DO1*** - - - - -

    Byte 1 (UMC output) (UMC output)

    *** corresponding UMC22-FBP output is used to control the motor contactor coil

  • 8/2/2019 2CDC135001D0204

    26/80

    26 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Data overview (continued)

    Monitored signals (description)

    RUN REVERSE 1:motor running reverse AND check-back (current/contact) = 1

    OFF 1: motor stopped AND no current is flowing AND no RUN command is active

    0:RUN command is active OR current is still flowing after off command

    RUN FORWARD 1:motor running forward AND check-back (current/contact) = 1

    LOCK-OUT TIME 1:Lock-out time running. Only for r eversing starter/ Starts with OFF command.

    The command of the opposite direction is accepted only when reversing lock-

    out time is over.

    LOCAL CONTROL 1:Local control is activated via Control Panel or digital inputs. RUN commandsof the control system are ignored.

    0:The control system can switch on with RUN commands. Details see chapter

    "Planning and commissioning, Switch on / off motor, local control".

    FAULT 1:A fault condition exists: Overload, no check-back when started, etc.

    See Diagnosis, Fault Bytes 0 and 1. Can be acknowledged via fieldbuscommand FAULT RESET or with Control Panel.

    WARNING A warning exists. See Diagnosis, Warning Byte 2

    UMC input DI0...DI5 Reads UMC22-FBP digital inputs DI0 ...DI5, independent of the parameterizing

    Motor current Motor current of the highest loaded phase as a % of set current

    Commands (description)

    RUN REVERSE 0-1 transit ion: Motor starts running reverse

    OFF 1: Motor stops as long as this signal is 1. OFF dominates RUN commands.

    RUN FORWARD 0-1 transition: Motor starts running forward or with speed 1.

    Remark:

    To start the opposite direction or the other speed:

    OFF command is necessary, starts immediately the reverse lock-out time.When

    the reverse lock-out time has elapsed, the motor can be started with the 0-1

    transition of the opposite / different RUN command.

    AUTO MODE 0:Enables start of the motor (RUN) via digital inputs on the UMC22-FBP,

    supposed the parameter 'Local control via digital inputs' is set. UMC22-FBP

    ignores RUN command from control station. Off is always possible.

    Details see chapter "Planning and commissioning, Switch on / off motor, local

    control".

    1:Run via digital inputs is blocked. Off is always possible.

    FAULT RESET 0-1-transition: Resets all resettable faults (overload fault, check-back fault, etc.)

    UMC output DO0...2 Transparent control of UMC22-FBP digital output DO..., if not used by anyControl function different from Transparent.

  • 8/2/2019 2CDC135001D0204

    27/80

    UMC22-FBP 27

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Data overview (continued)

    Diagnosis

    Bit No. 7 6 5 4 3 2 1 0

    Fault Self-testFault

    Byte 0-

    failedinput - - - - -

    signal

    Fault Overload Motor Commu- Parameter Current Relay 2 Relay 1 Relay 0

    Byte 1 (trip) fault blocked*nication out of check-back check-back check-back check-back

    fault range fault* fault* fault* fault*

    WarningMotor Motor Cooling Lock-out

    Byte 2current high current low - time time - - -

    threshold* threshold* running running*

    Fault Parameter numberByte 3 (refers to Byte 1, Bit 4)

    * if activated by appropriate control funtion

    Fault (Byte 0, Byte 1 and Byte 3), description

    Fault input signal 1: Input gets fault signal from external module, e.g. thermistor module.

    DI2 = 1: no external fault,

    DI2 = 0 sets Internal fault signal.

    See 'Attached control functions' - 'Fault input'.

    Self-test failed 1:Self-test during power-on has failed.

    Relay 0 check-back fault 1:no signal from auxiliary contact 1 signal within 100 ms afterswitching on contactor with output DO0.

    See 'Attached control functions' - 'Check-back'.

    Relay 1 check-back fault 1:ditto, contactor on DO1

    Relay 2 check-back fault 1:ditto, contactor on DO2

    Current check-back fault 1:no motor current within 100 ms after switching on contactor

    Parameter out of range 1:Received parameter exeeds high or low limit (the accompanying

    parameter number is shown in Byte 3).

    Communication fault 1:UMC22-FBP does not receive valid telegramms (control system,

    fieldbus or FieldBusPlug is out of order or interrupted).

    Remark:

    Is sent to the control system after reconnection.

    Motor blocked 1: Motor current over blocking current threshold.

    See 'Overload protection parameter '- 'Blocking current threshold'.

    Overload (trip) fault 1:Trip due to thermal protection or phase loss.

    Parameter number #:Number of the parameter which exeeds the high or low limit

    Warnings (Byte 2), description

    Lock-out time running 1: (Reversing) Lock-out time is running.

    Cooling time running 1: Cooling time is running.

    Motor current high threshold 1:Motor current is above the high threshold current.

    See 'Overload protection parameter' - 'High current threshold'.

    Motor current low threshold 1:Motor current is below the low threshold current.

    See 'Overload protection parameter' - 'Low current threshold'.

  • 8/2/2019 2CDC135001D0204

    28/80

    28 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Data overview (continued)

    Parameters, Overview

    The parameters are arranged into groups that apply for:

    Application circuit diagram:- Control function:

    'Transparent', 'Direct starter', 'Star-delta starter', etc.:

    (Descriptions with wiring etc. referring to the particular 'Control function see Appendix A).

    - Attached control functions:

    'Local control via digital inputs',

    'Check-Back' via: 'Motor current', 'Auxiliary contacts', 'Simulation', etc.

    (see chapters "Data overview, Parameters, ..." and Appendix A and B).

    Current setting:

    - 'Set current 1',

    - 'Set current 2' (two-speed),

    Overload protection:- 'Trip class' (5, 10, 20, 30)

    - 'Cooling time' (seconds)

    - 'Blocking current threshold', ...

    - etc.

    Communication:

    - 'Communication fault reaction' (reaction on loss of communication to control system)

    no parameters, but service supporting data: Other Info:

    - 'Operating hours'

    - 'Number of starts'- 'Number of trips'

    To load parameters into the UMC22-FBP, different ways are possible depending on the fieldbus

    and the control system:

    The slave configuration file (e.g. GSD file for PROFIBUS-DP) contains the parameters. The

    parameters can be changed during configuration of the fieldbus and are loaded in the UMC22-FBP

    during switching on.

    The parameterization is done via application program of the control system.

    The parameterization can be done with the Control Panel. Details see Appendix B "Control Panel".

    As a special feature the Control Panel can be used to read the complete parameter set of a

    parameterized UMC22-FBP and to transfer it to another UMC22-FBP, see Appendix B "Control

    Panel".

    Remark:

    Some parameters are taken over with power-on, others during motor off.

    Refer to chapters "Data overview, Parameters, Description".

  • 8/2/2019 2CDC135001D0204

    29/80

    UMC22-FBP 29

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Data overview (continued)

    Parameters, Some changed parameters are taken over after motor off, others during power-on.

    Description Some control systems or fieldbuses overwrite the parameters during power-on of theUMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

    0100 Control functions co.Fu power-on

    0101 Transparent 1 1 Direct access to DIs / DOs via fieldbus

    0101 Overload relay 2 Similar to overload relayAttention: Normal signal on output DO0 is On,connected contactor starts the motor.

    0101 Direct starter 3 Direct starter with check-back

    0101 Reversing starter 4 Reversing starter with check-back

    0101 Star-delta starter 1 5 Star-delta starter via 2 DOs, with check-back

    0101 Pole-changing starter 1 6 Pole-changing starter with check-back

    0200 Attached control functions

    0201 Local control L.c t r motor off via digital Off 0 0 No control via digital inputs

    inputs On 1 Digital inputs prepared to control RUN /

    OFF locally

    For conditions see chapter "Planning and

    commissioning, Switch on / off motor, local

    control".

    0202 Check-back bA.ch motor off

    Auxiliary contacts 1 OK when auxiliary contacts are closed

    100 ms after start

    Motor current 2 2 OK when current >40% ofset currentispresent 100 ms after start

    Simulation 3 Simulated check-back (e.g. for test without

    motor).

    Simulation is recommended only to be set via

    Control Panel. The control system must only

    setAuxiliary contacts orMotor currentto

    guarantee for an operating check-back afternext power-on.

    0203 Fault input F.i nP UMC22-BP input DI2: Closed-circuit signal. motor off

    Off 0 0 Fault input is not activated

    On 1 0 sets internal Fault signal ,1-signal = OK

    0204 Fault output F.out motor off

    Off 0 0 DO2 is not used as Fault outputOn 1 Digital output DO2 used to monitor the

    fault signal

    0205 Reversing 0.2 - 3600 s t i.r L 2s t Only for Reversing starter! motor off

    lock-out time step 0.1 s Starts with OFF (OFF is necessarry

    between FORWARD and REVERSE) RUN Command in other direction is not

    accepted while lock-out time is running

    0206 Star-delta Sd.ch t Only for Star-delta starter. motor off

    changeover Time 0 Change star delta, when star-delta

    mode starting time is over

    Current 1 1 Change star delta, when motor current 0,9 x set current

    Remark: Fault is generated if the star-deltastarting time has elapsed before switching to

    delta.

    Para. Group Parameter value Select. De- Description / remark take-over

    No. Parameter No. fault after

  • 8/2/2019 2CDC135001D0204

    30/80

    30 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    0207 Star-delta 1 - 3600 s Sd.St 60 s t Star-delta starter only! motor off starting time step 0.1 s Starts running with the RUN command

    0300 Current

    Settings

    0301 Set current 1 0.24...63 A Cur 1 0.5 A Important: The UMC22-FBP measures the motor off

    step 10 mA currents of the lines in the bushing holes. The

    current ih the coming lines can be different de-

    pending on the connection circuit.More details see chapter "Planning and Com-

    missioning, Motor current = Set current

    versus wiring"

    0302 Set current 2 0.24 - 63 A Cur 2 0.5 A t Pole-changing and Dahlander starter only! motor off

    step 10 mA Used for overload calculation

    0400 OverloadProtection

    0401 Trip class t r i P Overload calculation (thermal motor image) motor off

    Trip class 5 5

    Trip class 10 10 10

    Trip class 20 20

    Trip class 30 30

    0402 Phase loss Current of one phase: < 40% of other phases motor off

    protection (condition: other phases > 70% of set current)

    Off 0 Phase loss protection is not activated

    On 1 1 Phase loss protection is activated

    0403 Cooling time 30 - 3600 s t i .co 120 s Cooling time simulates the cooling behaviour motor off

    step 0.1 s of the inoperating motor after switching off.While cooling time is running RUN is not

    accepted and WARNING is monitored.

    0404 Automatic ArES motor off

    fault reset Off 0 0 Acknowledgment is necessary to reset Fault.

    To switch on cooling time must be elapsed.

    On 1 Only foroverload relay!Due to safety considerations: Automatic

    reset of fault when fault condition is off and

    cooling time has elapsed. Fault is not

    monitored.

    0405 Start-up time 0 - 600 s 120 s Suppresses some signals / trips until motor is motor off

    step 0.1 s in normal running status (Blocking, High/ Lowcurrent threshold)

    0406 Blocking 0 - 800% x set current 800% Fault signal when current is above threshold motor off

    current step 5% for > 1 s and start-up time has elapsed.

    threshold (800% means: Blocking protection is inactive).

    Remark: Blocking sets the internal fault signal

    and the monitoring telegram Bit OVERLOADand displays FAULT on the Control Panel but

    cooling time is not started.

    0407 Low current 30 - 100% x set current 50% Warning when below threshold and start-up motor off

    threshold step 5% time has elapsed

    0408 High current 100 - 800% x set current 150% Warning when above threshold and start-up motor off

    threshold step 5% time has elapsed

    Para. Group Definition / Range Select. De- UMC behaviour: description take-over

    No. No. fault after

    Data overview (continued)

    Parameters, Some changed parameters are taken over after motor off, others during power-on.

    Description Some control systems or fieldbuses overwrite the parameters during power-on ofthe

    (continued) UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

  • 8/2/2019 2CDC135001D0204

    31/80

    UMC22-FBP 31

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    0500 Communication

    5001 Communi- bu.co All cases when UMC22-FBP does not receive motor off

    cation fault valid telegrams, either when control system or

    reaction fieldbus or FieldBusPlug is out of order or

    interrupted.

    Relays off 0 0 Relay outputs of UMC22-FBP are switched

    offRelays retain status 1 Relay outputs of UMC22-FBP retain status

    0502 Address power-oncheck Off 0 0 UMC22-FBP address is valid on the fieldbus

    On 1 0 If the UMC22-FBP and the FieldBusPlug

    contain different addresses, the user must

    decide.

    Details see chapter "Planning and Commis-

    sioning, connection to the fieldbus,

    addressing.

    0600 Other Info

    0601 Operating 0 - 99.999 oP ho 0 All operating hours are counted but the unit

    hours step 1 h place is not displayed on the Control Panel.The displayd range 00.00-99.99 corresponds

    with real 00.000 to 99.999.The control system can only read the value

    (depending on the type of fieldbus)! Via Control

    Panel the value can be presetted e.g. to zero.

    0602 Number of 0 - 1.000.000 n o St 0 All starts are counted but the three lower

    starts step 1 places are not displayed on the Control Panel.The displayed range 0000-1000 corresponds

    with real 0.000.000 to 1.000.000.

    The control system can only read the value

    (depending on the type of fieldbus)! Via Control

    Panel the value can be presetted e.g. to zero.

    0603 Number of 0 - 255 n o t r 0 All trips are counted and shown on the Controltrips step 1 Panel in a range of 0-255.

    The control system can only read the value

    (depending on the type of fieldbus)! Via Control

    Panel the value can be presetted e.g. to zero.

    0700 other info, LOCAL only

    0701 Address see Appendix B "Control A___ see Appendix B "Control Panel" power-on

    Panel

    0702 Bus Set / reset possible only via Control Panel. power-on

    connection Allows to use the UMC22-FBP without Field-

    (not a para- BusPlug, e.g. as overload relay.

    meter, only Off 0 Stand alone, without FieldBusPlug / fieldbus

    for stand On 1 1 Connection to FieldBusPlug / fieldbus

    alone)

    Para. Group Definition / Range Select. De- UMC behaviour: description take-over

    No. No. fault after

    Data overview (continued)

    Parameters, Some changed parameters are taken over after motor off, others during power-on.

    Description Some control systems or fieldbuses overwrite the parameters during power-on ofthe

    (continued) UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

  • 8/2/2019 2CDC135001D0204

    32/80

    32 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    |

    Technical data

    Main power lines

    Voltage (three-phase systems) max. 690 V AC, 50 or 60 Hz

    Conductor holes in the current transformers 11 mm

    Set current range for overload protection 0.24 A ... 63 A

    Three-phase motors complete overload protection

    Phase loss detection: If current of ... one phase: < 40% of other phases

    other condition: phases > 70% of set current

    Trip classes, selectable by parameter 5, 10, 20, 30

    Tripping diagram

    Currents higher than 10 x set current evaluated as about 10 x set currentcooling time simulation After trip the internal thermal motor model calculates

    the reduction of the motor temperature (independent

    of the parametercooling time)

    Cooling time cnstant ca. 20 min

    If UMC22-FBP is no longer supplied calculation continues for some minutes (typ. 20 min)

    Accuracy class

    Factory adjustment Class 1.5

    any combination of current transformer Class 2.5

    set and control unit

    Burden per phase 30 mHigher currents with current transformer, see chapter "Planning and

    commissioning, external current transformer for

    higher currents'. External current transformercauses additional inaccuracy.

    Frequency range 48 - 62 Hz

    Short-circuit protection separate fuses on line side

    cold Class 30

    Class 20

    Class 10

    warm

    Current related to set current

    Triptime

    seco

    nds

    minutes

    2CDC

    342068F0003

  • 8/2/2019 2CDC135001D0204

    33/80

    UMC22-FBP 33

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Technical data (continued)

    Control unit

    Supply voltage mode Internal or external(see chapter ''Planning and commissioning, Wiring

    and internal 24 V / 0 V connections'')

    Supply voltage 19.2 ... 31.2 VDC including ripple

    Supply current incl. inputs, relays activated max. 130 mA (at 18 ... 30 V DC)

    Total device dissipation max. 3.1 W (at 24 V DC)

    Reverse polarity protection yes

    Number of digital inputs 6 (DI0 ... DI5)

    Number of relay outputs 3 (DO0 ... DO2)

    Number of bus interfaces 1 (for connecting an ABB FieldBusPlug)

    Number of Control Panel interfaces 1 (to mount Control Panel ACS100-PAN)Internal signal processing of control Selectable by parameters

    function and other properties (see chapter "Data overview, Parameters, ..." and

    Appendix A and B)

    Parameter setting via Fieldbus, via Control Panel, see Appendix A / B

    LEDs on front 1, green: Device ready for operation

    1, red: Fault (trip, device fault etc.)

    1, yellow: Motor current > 33% ofset current

    Diagnosis See chapter "Data overview, Diagnosis"

    Digital Inputs

    Number of digital inputs 6 (DI0 ... DI5)

    Supply for digital inputs (terminal 12) Internal or external

    (see chapter ''Planning and commissioning, Wiring

    and internal 24 V / 0 V connections'')

    Supply output current for inputs (terminal 12) max. 70 mA

    Voltage when standard contacts are used min.18 V

    Isolation no (see chapter ''Planning and commissioning,

    Wiring and internal 24 V / 0 V connections'')

    Input signal bounce suppression typ. 4 ms

    1-Signal range including ripple -31.2 V ... +5 V

    0-Signal range including ripple +13 V ... +31.2 V

    Input current per channel (24 V DC) typ. 6.0 mA

    Input resistor to 0V 3.9 k

    Line length unshielded max. 600 m

    Line length shielded max. 1000 m

    Conductor size (solide or stranded) 0.2-1.5 mm2 / AWG 15-24

    Tightening torque 0.4 Nm

    Digital 0utputs

    Number of digital outputs 3 (DO0 ... DO2)

    Type of digital outputs Relay contacts

    Grouping of contacts 3 contacts with 1 common

    Voltage range of contacts 12 ... 250 V AC

    Lowest switched power for correct signals 1 W or 1 VA

  • 8/2/2019 2CDC135001D0204

    34/80

    34 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Technical data (continued)

    Digital outputs (continued)

    Switching capacity per relay contact240 V AC (AC15 / EN 60947-5-1) max. 1.5 A (AC15: electromagnetic load)

    120 V AC (AC15 / EN 60947-5-1) max. 3 A (AC15: electromagnetic load)

    250 V DC (DC13 / EN60947-5-1) max. 0.11 A (DC13, electromagnetic load)

    125 V DC (DC13 / EN60947-5-1) max. 0.22 A (DC13, electromagnetic load)24 V DC (DC13 / EN60947-5-1) max. 1 A (DC13, electromagnetic load)

    Total current all contacts (terminal 5 or 6) max. 4 A (thermal limit)

    Short circuit protection 6 A gL / gG

    Switching of inductive power Inductive loads need additional measures for spark suppression. Diodes for DC voltage andvaristors / RC elements for AC voltage aresuitable. Some DC coil contactors contain

    rectifiers which suppress sparks optimal.

    Relay contact lifetime, mechanical 500 000 switching cycles

    Lifetime 250 V AC / 0.5 A 100 000 switching cycles

    Lifetime 250 V AC / 1.5 A 50 000 switching cycles

    Internal clearance and creepage distances > 5.5 mm (safety insulation up to 250 V AC)

    relay contacts to 24 V circuits (EN60947-1, Pollution degree 2)

    FieldBusPlug connection

    Mounting Plug connection, fastening with supplied screw

    Tightening torque of the fixing screw 0.8 Nm + rotation 90 degree

    Suitable ABB FieldBusPlug types PDP22-FBP (PROFIBUS-DP)

    DNP22-FBP (DeviceNet)

    MRP21-FBP (MODBUS) in preparation

    COP21-FBP (CANopen) in preparation

    Environment and mechanical data

    Mounting on DIN rail (EN 50022-35) or with 4 screws M4

    (refer to chapter "Technical data, Dimensions")

    Dimensions W x H x D 70 x 105 x 110 mm

    (incl. FieldBusPlug and Control Panel)

    Net. weight (current transformer + control unit) 0.39 kg

    Terminals: Conductor cross section max. 2.5 mm or max. 2 x 1.5 mm

    Current transformer bushing holes 11 mm (25 mm)

    Degree of protection IP 20

    Storage temperature range -25 ... +70 C

    Operation temperature range 0 ... +55 C

    Approvals CE

    Approvals (pending) UL, CSA, GL, BV, LRS, ATEX

    MTBF

  • 8/2/2019 2CDC135001D0204

    35/80

    UMC22-FBP 35

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Technical data (continued)

    Ordering data

    Universal Motor Controller UMC22-FBP Order code: 1SAJ 510 000 R0100

    Control Panel

    Control Panel ACS100-PAN Order code: 1SAJ 510 001 R0001

    (not in scope of delivery, to order separately)

    Control Panel Extension Cable ACS100-CAB Order code: 1SAJ 510 002 R0001

    (not in scope of delivery, to order separately)

    FieldBusPlugs

    PDP22-FBP (PROFIBUS DP)

    Cable length: 0.25 m Order code: 1SAJ 240 000 R0003Cable length: 0.50 m Order code: 1SAJ 240 000 R0005

    Cable length: 1.00 m Order code: 1SAJ 240 000 R0010

    Cable length: 2.00 m Order code: 1SAJ 240 000 R0020Cable length: 5.00 m Order code: 1SAJ 240 000 R0050

    DNP22-FBP (DeviceNet)

    Cable length: 0.25 m Order code: 1SAJ 230 000 R0003Cable length: 0.50 m Order code: 1SAJ 230 000 R0005

    Cable length: 1.00 m Order code: 1SAJ 230 000 R0010

    Cable length: 5.00 m Order code: 1SAJ 230 000 R0050

    MRP-21-FBP (MODBUS) in preparation

    COP21-FBP (CANopen) in preparation

    External current transformers

    Type (recommended current range)

    KORC 4L185 R/4 (63 -185 A) Order code: 1SCA 022 193 R7830KORC 4L310 R/4 (185 - 310 A) Order code: 1SCA 022 181 R0760

    KORC 5L500 R/4 (310 - 500 A) Order code: 1SCA 022 208 R1010

    KORC 5L850 R/4 (500 - 850 A) Order code: 1SCA 022 208 R1440

    Link kit (bar)

    Type (for contactor type)

    DT450/A185 (AF145 - AF185) Order code: 1SAZ 501 901R1001

    DT450/A300 (AF260 - AF300) Order code: 1SAZ 501 902R1001

    DT500/AL460S (AF400, AF460)* Order code: 1SAZ 701 902R1011

    DT500/AL750S (AF580, AF750)* Order code: 1SAZ 801 902R1011(*Link kits for Star-delta starter. Others see catalogue)

  • 8/2/2019 2CDC135001D0204

    36/80

    36 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description

    FieldBusPlug / Issue: 10.2003

    V 6

    Technical data (continued)

    Dimensions

    Fig. 13: UMC22-FBP: Dimensions 2CDC

    342031F0003

  • 8/2/2019 2CDC135001D0204

    37/80

    UMC22-FBP Apendix A-1

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    690 / 400 V230 V N DO1 DO2

    K1K1

    UMC22

    EXT

    SWITCH

    10

    0

    V11

    24

    V

    24

    V12 13 14 15

    DI

    216 17 18

    DI

    4

    DI

    5

    DI

    0

    DI

    1

    DI

    3

    DO

    C

    5 6

    DO

    C

    DO

    0

    7

    DO

    2

    9

    DO

    1

    8

    INTFieldBus

    Plug

    0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5

    2

    CDC3

    42070

    F0003

    Fig. A-1: UMC22-FBP: Control function 'Direct starter' (example)

    Contents Page

    Control function .......................................................................................................................................A-1

    Transparent.........................................................................................................................................A-2

    Overload relay .....................................................................................................................................A-4

    Direct starter .......................................................................................................................................A-8

    Reversing starter ..............................................................................................................................A-13

    Star-delta starter 1 ............................................................................................................................A-19

    Pole-changing starter 1 ....................................................................................................................A-25

    Appendix A: Control FunctionsCircuit arrangement, description, data and parameters, timing diagrams

    if EXT

    supply

    to supply

    inputs

  • 8/2/2019 2CDC135001D0204

    38/80

    Appendix A-2 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    DI1 DI2 DI3 DI4 DI5

    DO0 DO1 DO2 690 / 400 V230 V

    UMC22

    FieldBus

    Plug EXT

    INT

    SWITCH

    DI00 V 24 V 24 V

    DO

    C

    5 6

    DO

    C

    DO

    0

    7

    DO

    2

    9

    DO

    1

    8

    10

    0

    V

    11

    24

    V

    24

    V

    12 13 14 15

    DI

    2

    16 17 18

    DI

    4

    DI

    5

    DI

    0

    DI

    1

    DI

    3

    Transparent

    The UMC22-FBP parameterized with the 'Control function' = 'Transparent' (default) behaves like an I/O-

    module with an integrated overload check. The outputs DO0 ... DO2 and the inputs DI0 ... DI5 are

    directly connected to the fieldbus and are independent of the overload status.

    The only possible exception: DO2 outputs the internal fault signal, if the parameter 'Fault output' is set to

    'On'. Default is 'Off', in this case the output is controlled directly via the fieldbus.

    All kinds of faults set the internal fault bit. Following the monitoring signal FAULT is sent to the fieldbus,

    the red LED lights on and the FAULT signal on the Control Panel flashes.

    If a motor overload is the cause of the fault signal, the cooling time is started additionally. The cooling

    time is a parameter and can be adjusted.

    More detailed information are monitored in the diagnosis telegram and on the Control Panel.

    All faults must be acknowledged via f ieldbus or via Control Panel.

    The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the

    Control Panel or with a separate Addressing Set. Details see general part chapter ''Planning and

    commissioning, Interfacing to the fieldbus, addressing''.

    Circuit diagram (Basis circuit)

    Parameters to be changed (based on default)

    Control function = Transparent(default) Address via Control Panel or Addressing Set if

    Set current 1, overload protection parameters connected to bus

    if EXTsupply

    to supplyinputs

    Fig. A-2: UMC22-FBP: Control function 'Transparent' (Basis circuit)2CDC3

    42071

    F0003

    Fault

  • 8/2/2019 2CDC135001D0204

    39/80

    UMC22-FBP Apendix A-3

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    Important:

    Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. Inthis case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests

    urgently this kind of supply.

    If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -

    the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).

    Details see general part chapter ''Planning and commissioning, Wiring and internal 24 V / 0 Vconnections''.

    Interface and data overview

    Device inputs / outputs

    Terminal 13 14 15 16 17 18

    Device DI0 DI1 DI2 DI3 DI4 DI5Input to bus to bus to bus to bus to bus to bus

    Terminal 7 8 9

    Device DO0 DO1 DO2*

    Outputs from bus from bus (fault output)

    Fieldbus telegram: Monitoring signals / Command

    Bit No. 7 6 5 4 3 2 1 0

    Monitor

    Byte 0WARNING FAULT - - - - - -

    Monitor DI5 DI4 DI3 DI2 DI1 DI0- -

    Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)

    MonitorMOTOR CURRENT (% ofset current)

    Byte 2/3

    Command-

    FAULT- - - - - -

    Byte 0 RESET

    Command DO2* DO1 DO0- - - - -

    Byte 1 (UMC output)(UMC output) (UMC output)

    Fieldbus telegram: Diagnosis

    Bit No. 7 6 5 4 3 2 1 0

    Fault Self-test

    Byte 0-

    failed- - - - - -

    Fault Overload Motor Commu- Parameter

    Byte 1 (trip) fault blocked*nication out of - - - -

    fault range

    WarningMotor Motor Cooling

    Byte 2current high current low - time - - - -

    threshold* threshold* running

    Fault Parameter number

    Byte 3 (refers to Byte 1, Bit 4)

    Details see general part chapter "Data overview" * depending on parameterization

    Transparent (continued)

  • 8/2/2019 2CDC135001D0204

    40/80

    Appendix A-4 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    UMC22

    EXT

    INT

    SWITCHDO

    C

    5 6

    DO

    C

    DO

    0

    7

    DO

    2

    9

    DO

    1

    8

    10

    0

    V

    11

    24

    V

    24

    V

    12 13 14 15

    DI

    2

    16 17 18

    DI

    4

    DI

    5

    DI

    0

    DI

    1

    DI

    3

    FieldBus

    Plug

    690 / 400 V230 V DO2tripN

    K1K1

    ON

    OFF

    0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5

    Overload relay

    The UMC22-FBP parameterized with the 'Control function' = 'Overload relay' provides excellent

    protection of a motor. Dedicated to replace a standard overload relay, stand-alone operation can be

    selected via Control Panel setting the parameter 'Bus connection' = 'Off'.

    Circuit diagram (Basis circuit)

    Main features

    Motor contactor K1 at output DO0

    Parameters to be changed (based on default)

    Control function = Overload relay Set current 1, overload protection parameters

    Bus connection = Off(used without Fieldbus) Address if connected to the fieldbus, via Control

    (to be selected by Control Pane)l Panel or Addressing Set

    if EXT

    supply

    to supply

    inputs

    Fig. A-3: UMC22-FBP: Control function 'Overload relay' (Basis circuit)2CDC3

    42072F0003

    Fault

  • 8/2/2019 2CDC135001D0204

    41/80

    UMC22-FBP Apendix A-5

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    Overload relay (continued)

    Description

    After parameterizing 'Control function' = 'Overload relay' and 'Bus connection = Off' power-on is necessa-ry to start the operation. Immediately contact DO0 opens, contact DO1 closes. If ' Bus connection' = 'On',

    the active connection to the control system is an additional condition to start the operation.

    Attached control functions

    With 'Fault output' = 'On', also the output contact DO2 operates similar to DO0.

    Remark: If 'Fault output' = 'Off', output contact DO2 can be controlled via fieldbus.

    Fault behaviour

    All kinds of detected external and internal faults set the internal fault bit. In the following:

    contact DO0 (and DO2 if parameterized) closes,

    DO1 opens,

    the monitoring signal FAULT is sent to the fieldbus,

    the red LED on the UMC22-FBP lights on and the FAULT signal on the Control Panel display flashes.

    If a motor overload is the cause of the fault signal, the cooling time'is started additionally . The cooling

    time is a parameter and can be adjusted.

    All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be

    elapsed to allow to restart the motor.

    Exception: If the parameter 'Automatic fault reset' = 'On', the contacts DO0 (and DO2) closes and DO1

    opens immediately when the cooling time is over (only available with overload relay).

    Addressing

    The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the

    Control Panel or with a separate Addressing Set. Details see general part chapter ''Planning and com-

    missioning, Interfacing to the fieldbus, addressing''.

    Important:

    When connected to a fieldbus via FieldBusPlug:

    Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In

    this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requestsurgently this kind of supply.

    If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -

    the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).

    Details see general part chapter ''Planning and commissioning, Wiring and internal 24 V / 0 V

    connections''.

  • 8/2/2019 2CDC135001D0204

    42/80

    Appendix A-6 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    Overload relay (continued)

    Interface and data overview

    Device inputs / outputs

    Terminal 13 14 15 16 17 18

    Device DI0 DI1 DI2 DI3 DI4 DI5Input to bus to bus to bus to bus to bus to bus

    Terminal 7 8 9

    Devicetrip

    trip DO2*Outputs inverted from bus

    Fieldbus telegram: Monitoring signals / Command

    Bit No. 7 6 5 4 3 2 1 0

    Monitor

    Byte 0WARNING FAULT - - - - - -

    Monitor DI5 DI4 DI3 DI2 DI1 DI0- -

    Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)

    MonitorMOTOR CURRENT (% ofset current)

    Byte 2/3

    Command-

    FAULT- -

    SELF-- - -

    Byte 0 RESET TEST

    Command DO2*- - - - - - -

    Byte 1 (UMC output)

    Fieldbus telegram: Diagnosis

    Bit No. 7 6 5 4 3 2 1 0

    Fault Self-test

    Byte 0-

    failed- - - - - -

    Fault Overload Motor Commu- Parameter

    Byte 1 (trip) fault blocked*nication out of - - - -

    fault range

    WarningMotor Motor Cooling

    Byte 2current high current low - time - - - -

    threshold* threshold* running

    Fault Parameter numberByte 3 (refers to Byte 1, Bit 4)

    Details see general part chapter "Data overview" * depending on parameterization

  • 8/2/2019 2CDC135001D0204

    43/80

    UMC22-FBP Apendix A-7

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    Overload relay (continued)

    Timing diagram: Overload

    FAULT

    (trip)

    FAULT RESET

    via fieldbus or

    Control Panel

    end of

    cooling

    time

    FAULT

    FAULT RESET

    (/trip) DO0

    (trip) DO1

    FAULT

    WARNING

    Cooling time running

    Overload (trip) fault

    red LED (Fault LED)

    UMC internal

    Command(received telegram)

    UMC outputs

    Monitoring signals(telegram)

    Diagnosis

    LEDs

    Fig. A-4: UMC22-FBP: Control function 'Overload relay' - Timing diagram 'Overload'

    2CDC3

    42

    069F0003

  • 8/2/2019 2CDC135001D0204

    44/80

    Appendix A-8 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    690 / 400 V230 V N DO1 DO2

    K1K1

    UMC22

    EXT

    SWITCH

    10

    0

    V

    11

    24

    V

    24

    V

    12 13 14 15

    DI

    2

    16 17 18

    DI

    4

    DI

    5

    DI

    0

    DI

    1

    DI

    3

    DO

    C

    5 6

    DO

    C

    DO

    0

    7

    DO

    2

    9

    DO

    1

    8

    INTFieldBus

    Plug

    0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5

    Direct starter

    The UMC22-FBP parameterized with the 'Control function' = 'Direct starter' provides excellent protection

    and control of a motor for one direction of rotation. The connection to a fieldbus is made via the appropri-

    ate type of the FieldBusPlug.

    Circuit diagram (Basis circuit)

    Main features

    Contactor K1 at DO0 Check-back by motor current

    Parameters to be changed (based on default)

    Control function = Direct starter Set current 1, overload protection parameters

    Address via Control Panel or Addressing Set

    if EXT

    supply

    to supply

    inputs

    Fig. A-5: UMC22-FBP: Control function 'Direct starter' (Basis circuit)2CDC3

    42

    07

    0F0003

  • 8/2/2019 2CDC135001D0204

    45/80

    UMC22-FBP Apendix A-9

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    DI10 V 24 V 24 V

    K1

    PTC DI3 Fwd Off

    690 / 400 V230 V N

    K1K1

    DO1

    UMC22

    EX

    T

    IN

    T

    SWITCH

    0

    V

    24

    V

    24

    V

    DI

    2

    DI

    4

    DI

    5

    DI

    0

    DI

    1

    DI

    3

    DO

    C

    DO

    1

    8

    DO

    0

    7

    DO

    2

    9

    DO

    C

    10 11 12 13 14 15 16 17 18

    5 6

    FieldBus

    Plug

    Direct starter (continued)

    Circuit diagram (Extended circuit)

    Main features

    Contactor K1 at output DO0 Fault lamp at output DO2 Check-back by auxiliary contacts at input DI0 Fault input (closed circuit) at DI2

    Local operation via inputs DI4 and DI5

    Parameters to be changed (based on default)

    Control function = Direct starter Set current 1, overload protection parameters Fault output signal= On Check-back=Auxiliary contact

    Fault input= On Local operation via digital inputs = On

    Address via Control Panel or Addressing Set

    if EXT

    supply

    to supply

    inputs

    Fig. A-6: UMC22-FBP: Control function 'Direct starter' (Extended circuit)2CDC3

    42

    085F0003

    transparent

    to bus

    Local operation via

    digital inputs 2),3)

    thermistor

    switch 1)

    Fault

    1) Fault input: Closed circuit signal: 1 = no fault2) Fwd: Momentary-contact switch3) Off: Closed circuit signal: 0 = dominating Off

  • 8/2/2019 2CDC135001D0204

    46/80

    Appendix A-10 UMC22-FBP

    Universal Motor Controller

    UMC22-FBP

    Technical Description - Appendix A

    FieldBusPlug / Issue: 10.2003

    V 6

    Direct starter (continued)

    Description

    The UMC22-FBP parameterized with the 'Control function' = 'Direct starter' provides excellent protectionand control of a motor for one direction of rotation. The connection to a fieldbus is made via the appropri-

    ate type of the FieldBusPlug.

    With direct starterthe output DO0 is defined to drive the motor contactor coil.

    Attached control functions

    The parameter set 'Attached control functions' prepares the direct starterto support different circuitarrangements including the use of inputs and outputs for particular use.

    Examples:

    'Fault output'= 'On': The output contact DO2 closes if a fault appears.

    'Fault input' = 'On': A closed circuit signal (24 V) on input DI2 corresponds to the fault-free status.

    Remark: Only remaining outputs can be controlled but all inputs are monitored via fieldbus.

    Other parameters define the protection behaviour and additional functions. Refer also general partchapter ''Data overview, Parameters ...''.

    Starting

    After setting the parameter 'Direct starter', power-on is necessary to activate and to allow to start the

    motor with the bus command RUN FORWARD or via local control. All other parameters are activated

    with motor on.

    Check-back

    When the motor is started, the check-backstatus is expected within 100 ms, otherwise a fault is de-