Page 4: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Comparison of FM200 system against room volume

Room Volume

Cylinder c/w its associated accessories (such as valve, solenoid, pressure sw. & etc…) HKD

Detection equipment (such as panel, detector, safety barrier & etc…) HKD

Installation HKD

100 cu m 35,000 12,000 23,000

150 cu m 43,000 12,000 23,000

200 cu m 51,000 12,000 28,000

250 cu m 59,000 12,000 28,000

300 cu m 67,000 16,000 32,000

350 cu m 74,000 16,000 35,000

400 cu m 81,000 16,000 38,000

4

Page 5: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Suppression Solutions

• The latest technology in suppression system suitable for Hospital BuildingSelection criteriaTypes of productDesign and installationMaintenanceQuality

Page 6: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Selection criteria

• Physical dimensions

• Occupant

• Weight / space limitations

• Fire fighting performance

• Environmental

• Life cycle cost

Page 7: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Types of product

• Fixed gaseous fire suppression systemChemical gasesInert gasesCarbon Dioxide

• Fixed water systemWater mistSprinklerWater spay system

Page 8: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Fixed gaseous fire suppression systems

• Chemical gases

Designation Chemical formula Chemical name Trade Name

HFC 23 CHF3Trifloromethane FE-13

HFC 125 CF3CHF2Pentafloroethane FE-25

HFC 227ea CF3CHFCF3Heptafluoropropane FM200 ,

FE-227

FK-5-1-12mmy2 CF3CF2C(0)CF(CF3)2Dodecafluro-2-methylpentan-2-one

Novec 1230

Page 9: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Fixed gaseous fire suppression systems

• Inert gases

Designation Gas blend Trade name

IG-01 100% argon Various

IG-100 100% nitrogen Various

IG-55 50% nitrogen , 50% argon Argonite

IG-541 50% nitrogen , 42 % argon , 8% carbon dioxide

Inergen

Page 10: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Fluid Safety and Use Concentration Comparison

Properties NOVEC 1230

Halon 1301

HFC-125 HFC-227ea

Inert Gas Carbon dioxide

Temperature to change from Liquid to gas form

49.2 -57.8 -48.5 -16.4 -196 Sublimes at low temps

Use Concentration

4-6% 5% 8.7-12.1%

7.5-8.7%

38-40% 30-75%

NOAEL 10% 5% 7.5% 9% 43% NA

Safety Margin

67-150%

Nil Nil 3-20% 7-13% Lethal at Use

Conc.

Page 11: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Fire Protection Fluid Environmental Properties Comparison

Properties NOVEC 1230 (FK-

5-1-12)

Halon 1301

HFC-125 IG-55 (Argonite

)

IG-541 (Inergen)

HFC-227ea

Ozone Deletion Potential (ODP)

0.0 12 0.0 0.0 0.0 0.0

Globe Warming Potential - IPCC

1 6900 3400 0.0 0.0 3500

Atmospheric Lifetime (years)

0.014 65 29 0.0 0.0 33

SNAP Yes N/A Yes Yes Yes Yes

Page 12: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Fixed gaseous fire suppression systems

• Carbon dioxideOver eighty yearsExtinguishes the fire primarily by reducer the oxygen

concentration and provides localized coolingLocal application and total flooding application

Page 13: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Fixed water system

• Water mist90% droplets less than 1 mm in diameter To cool the fire source by removing the heat and

suppressing the fireDisplaces oxygen in the atmosphere

Page 14: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Design and installation

• Complex and various of size

• Type of fuel

• High value asset

• Temperature

• Downtown

• Integration

• Safety

Page 15: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Maintenance

• Regular maintenance by competent , third party certified person

• Manufacturer instruction

• Charges to protection area

• Enclosure integrity

• Nozzles position

Page 16: 2012 Lik Kai Pacific Sense March 2012. PACIFIC SENSE Company Intro

Quality

• Design : Factory trained and certified engineer

• Component : US DOT , EU TPEP and PED

• System : UL , FM Global , LPCB and Vds

• Installation : NFPA 2001 , ISO 14520 and the manufacturer instruction