20 protection and substation control ev-s_v13_17.07.00- 1 line differential relay 7sd52 line...
TRANSCRIPT
Protection and Substation Control EV-S_V13_17.07.00- 1
Line differential relay 7SD52
Line differential relay for HV andUHV lines/cables with a serial communication interface
7SD52
Protection and Substation Control EV-S_V13_17.07.00- 2
Protection and communication join togetherThree benefits of the 7SD52
Differential protection for the universal use with easy to handle settings Two up to six line ends , for serial and parallel compensated lines, handles transformers and compensation coils within the protection zone, tripping time approx. 15 ms with fast high set element
Additional functions for very long overhead lines and cables Considation of local CT errors, charge current compensation (step 2), increased setpoint during switching-on conditions
Direct and modular connection to fibre optic and digital communication
networks
Protection and Substation Control EV-S_V13_17.07.00- 3
Application for a three terminal configuration
SDHcomms-network
X21G703.1
820 nm
max.3 km
eoPCM
multi-plexer
Monomode fibre optic cable up to 35 km with 1300 nm interface
Distance relay7SA52
Mon
omod
e fib
re o
ptic
cab
le u
p to
10
km
(13
00 n
m m
odul
)
PCMmulti-plexero
eoe
Comms-converterG703.1: 64 kBitX21: N*64 kBit (1N8)
Option:
I-REGB
timesynchronisation
Protection and Substation Control EV-S_V13_17.07.00- 4
Scope of functions / Hardware options
Scope of functions
- Fast high set element with charge comparision- Sensitive normal trip stage with vector summation principle- Autoreclosure 1/3 pole- Communication features- Commissioning aid- Overload protection- Backup-/emergency overcurrent- Multiterminal extention- Switch on to fault protection- 4 remote commands 24 remote signals
Relay Hardware
O
O 1300 nm
10 kmmonomode
O 1300 nm35 kmmonomode
OE
ElectricalX21G703.1interface
Options for the Protection Interface
½*19´´
internal
internal
internal
1*19´´External converter
16 binary inputs24 contacts
24 binary inputs32 contacts
Option: 5 fast trip contacts
820 nm1,5 / 3 kmmultimode
820 nm1,5 kmST-connectors
3Iph, and IE 4 U 8 binary inputs16 contacts 1 - 2 protection interfaces System interfacePC-interfaceTime synchronisation
ST-connector
ST-connector
FC-connector
Protection and Substation Control EV-S_V13_17.07.00- 5
Hardware option of the comms interfaces
Protection interface 2Port E
Synchronous N x 64kB/sec7SD52
Protection interface 1Port D
Synchronous N x 64kB/sec
Serial time sync. input GPS-receiver
Interfacemodul 1RS485 or FOor RS232
service-interface DIGSI 4; also for modem connection
and Browser
local-PCinterface
DIGSIlocal
Browser
Substation controlcommunication modules
FO (Fibre optic) or RS485or RS232Available ProtocolsIEC - standard
Interfacemodul 2RS485 or FO
Subst. control interface
Plug in modules
Remote line end 2
Remote line end 1
Protection and Substation Control EV-S_V13_17.07.00- 6
Main processor board of the relay
Sockets for the communicationmodules
Main board of the relay with it´s Communication - Interfaces
Protection and Substation Control EV-S_V13_17.07.00- 7
Main protection functionFeatures of the differential function
Phase selective multiend differential protection(2 - 6 ends). Tripping time 15 ms with fast charge comparison protection.
Fundamental vector comparison for the sensitive
trip stage.
Dynamic increase of differential setpoint during switch-on of long lines / cables (settable time)
CT saturation detector (only 5 ms saturation free time due to external faults necessary)
Phase selective intertrip within 15 ms
Settable delay time for single phasefaults (feature for inductive compensated networks)
Option: Inrush 2nd harmonic restraint with vector group adaption. Undelayed trip for high fault currents
Optional Lockout function
Protection and Substation Control EV-S_V13_17.07.00- 8
Adaptive differential relayingConsideration of CT- errors and comms-errors
IDiff
IN
I IN
I1 I2
I3
IDiff = I1 + I2 + I3Phasor summation:
Error summation:
IDiff>
I1
I2 I3
I1
I = IDiff> + Linear CT-error ( + Syncronization errorIK)
Trip, if diff.current exceeds the max. permissible error
Restraint area
Tripping area
Protection and Substation Control EV-S_V13_17.07.00- 9
To complete the 7SD52Additional functions
3 stage backup- or emergency O/C protection(Can be activated automatically if the communication with the remote end is >50 ms interrupted)
Overload function (Thermal replica with IOperation)
User definable logic and control functions(AND, OR, NOT, Timer, Flip-Flop)
4 remote commands via binary input or logic inputs (destination is adressable), 24 remote signals
Operational values: currents, voltages, power,delay time, differential current - remote end refresh 2 s
Fault recorder with voltages, currents, binary traces and differential and restraint current per phase
Fast monitoring functions(Fast broken wire supervision, Current symmetry)
Switch On to Fault protection
Option: Three pole and single pole AR (Single pole AR during 2pole fault without earth possible, adaptive AR)
Protection and Substation Control EV-S_V13_17.07.00- 10
Synchronous data transmission by HDLC- protocol
Permanent supervision of the data transmission
Measurement and compensation of signal transmission time (max. 20 ms)
Counts number of invalid telegrams Blocking the diff.protection if transmission failure rate is too high
Settings for the data transmission (N*64 kBit/s, N settable from 1 - 8, synchronous HDLC-protocol)
Communication device addresses (Protection devices are clearly assigned to a defined protection section)
Detection of reflected data in the loops in comms- network
Step 2: Microsecond exact time synchronisation via satellite (civil - IRIG-B) (If signal transmission time depends on the transmission direction, Online high resolution fault recorder)
Familiar with digital communication networks Features of the relay to relay communication
Protection and Substation Control EV-S_V13_17.07.00- 11
Ring and Chain topologie
Closed ring Partial current summation
I3
I2
I1
side 1
side 2
side 3
I3
I2
I1
side 1
side 2
side 3
I3+I1 I2
I1+I2 I3
I3+I1
I1+I2
Connection to
other diff. relays
Automatic change fromclosed ring to chain, if one connection is lostor not available
Protection and Substation Control EV-S_V13_17.07.00- 12
Topologies: Chain topology for max. 6 line ends
1 32
46 5
PI - Protection Interface
PI1 PI1 PI2 PI1
PI2
PI1
PI2PI1PI2PI1
Protection and Substation Control EV-S_V13_17.07.00- 13
Topologies: Ring topology, 6 line ends
31 2
46 5
PI1
PI2
PI1
PI2PI1PI2PI1
PI2
PI1
PI2 PI1 PI2
PI - Protection Interface
Protection and Substation Control EV-S_V13_17.07.00- 14
IL1_1
IL3_1
IL2_1
IL1_2
IL2_2
IL3_2
Phi1->2
Signal transmission timeMean value of transmit and receive direction
Generation of signals for switching test loopsSending of defined telegram patterns looped back to the receive input of the transmitting relay
Absolute value and phase measurement of currentsLocal measurement of angle between IL1, IL2, IL3
,Angle between currents of each phase from remote
CB test trip
Counting of faulty telegrams in % per minute and hour
Activation of binary inputs and outputs by operating software DIGSI 4.
Display of the status of binary inputs
Test telegrams to the substation control system
Automatic Switchover from 3 line to 2 line end configuration (while commissioning 3rd line end)
Complete commissioning support with DIGSI 4 andbrowser based PC-software
Plug and Protect Commissiong helps and test features
Protection and Substation Control EV-S_V13_17.07.00- 16
Comprehensive fault analysis with DIGRA 4
iEe iL1 iL2 iL3 t/s-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075 0,100 0,125I/A-2,00-1,50-1,00-0,50-0,000,501,001,50
uL1 uL2 uL3 t/s-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075 0,100 0,125U/V-80-60-40-20020406080