LOCATION
Nimoda, Undal, Motipura,
Singharia and Devri villages of
Tehsil Jhalarapatan,
Distt. Jhalawar
LAND
The GOR has alloted 842 bigha Government land and aquired 1388
bigha private khatedari land for
the thermal project.
WATER
The state irrigation department has
alloted 1200 mcft water for the project
from proposed Kalisindh dam
COAL
Ministry of coal, Govt. of India
has alloted ‘Paras east and Kanta basin ‘ coal blocks to
RVUN in Chhatisgarh state. under
joined venture with M/s. Adani
Enterprises
.
BUS BAR
LIGHTING ARRESTER
CIRCUIT BREAKER
ISOLATOR
CURRENT TRANSFORMER
CAPCITIVE VOLTAGE TRANSFORMER
WAVE TRAPER
The whole switchyard is grounded with MAT Grounding.
In MAT grounding,5 Conductors are placed Horizontally & 8 Conductors are Placed Vertically.
All Switchyard equipment are grounded by two Earthing Connection.
In switchyard grounding,32mm earthing conductor is used & 75/2 GI earth Sheet is used.
All switchyard are gravelled to make the tower footing resistance high.
BUSBAR SCHEME
GT feeder
Line feeder
2000A
2000A
IPS tube of minimum 4.5 inch size
IPS tube of minimum 4.5 inch size
LIGHTNING ARRESTORS
• These are equipments designed to protect
insulators of power lines and electrical installations from lightening surges by diverting the surge to earth and instantly restoring the circuit insulation to its normal strength with respect to earth.
CIRCUIT BREAKER A circuit breaker is an automatically
operated electric switch designed to
protect an electrical circuit from
damage caused by overload or short
circuit.
Its basic function is to detect a fault
condition and, by interrupting
continuity, to immediately discontinue
electrical flow.
Unlike a fuse, which operates once
and then has to be replaced, a circuit
breaker can be reset (either manually
or automatically) to resume normal
operation.
SYSTEM ISOLATORS
• 400KV, 2000A, 40KA for 3.0 sec isolators for GT, lines, ICT
bays shall be provided.
The Isolator used in this plant is of two types.
Single pole double break isolator.
Double pole single break isolator.
CURRENT TRANSFORMERS
When current in a circuit is too high to directly apply to measuring
instruments, a current transformer produces a reduced current
accurately proportional to the current in the circuit, which can be
conveniently connected to measuring and recording instruments
400KV oil filled live tank type hermetically sealed single phase
current transformers will be used.
Multi-ratio CT tapping shall be provided on the secondary side to
obtain different ratios in order to different ratios In order to permit
different ratios on each core, as desired.
C
V
T
capacitor voltage transformer (CVT) is a transformer used to step down extra high voltage signals and provide a low voltage signal, for measurement or to operate a protective relay.
Nominal/highest system voltage 400/420 KV Rated primary voltage 400 KV/1.732 Rated secondary voltage 110 V/1.732
• An electronic filtering device designed to exclude unwanted
signals or interference.
• It blocks the high frequency carrier waves (24 kHz to 500 kHz)
and let power waves (50 Hz - 60 Hz) to pass through. It is basically an inductor of rating in milli henry.
• Purpose of ICT is simply interconnection between 400KV and 220KV Switchyard.
• 315MVA,400/220/33 KV
ONAN ONAF ODAF
HV 189 252 315
LV 189 252 315
TV 63 84 109
KaTPP
SWITCHYARD
400KV
BTAWDA
400KV
BTAWADA
220KV JHALAWAR
220KV
JHALAWAR
GENERATOR BAY
24
Grid Incomer Bay
25
Bus PT Bay
26
Bus Coupler Bay
Bus Sectionaliser Bay.
ST back charging Bay
27
CLEARANCES
Interlocks When Circuit breaker is ON, Isolator should not
operate. When Isolator is CLOSE, Earth switch should be OPEN. When Both the Bus are charged, Bus coupler should
not become CLOSE. When DC supply if not available, alarm should be
raised. When gas pressure inside the Breaker is reduced to
5Kg/cm2,the alarm should be raised.
28
When the oil pressure inside the current transformer is low , then alarm should be raised.
When the Nitrogen gas pressure is low at the Current Transformer , then alarm should be raised.