10. overcurrent coordination basics conductors
TRANSCRIPT
-
7/27/2019 10. Overcurrent Coordination Basics Conductors
1/7
Frequently Asked Questions Application Guides Power Systems Study Specs Tech Support
PTW Tutorial Videos
Overcurrent Coordination Basics Conductors
The information presented in this application guide is for review, approval, interpretation andapplication by a registered professional engineer only. SKM disclaims any responsibility andliability resulting from the use and interpretation of this information.
Reproduction of this material is permitted provided proper acknowledgement is given to SKM
Systems Analysis Inc.
Purpose
The purpose of this guide is to provide a basic overcurrent protection philosophy for conductors.
Cable Overcurrent ProtectionTime-current curve (TCC) landmarks (figure 1)
Ampacity located in the upper decade Emergency overload curve located in the upper 2 decades, typically not shown
Short circuit damage curve located in the bottom 3 decades
TCC regions (figure 2)
Equipment operating region located at and to the left of the ampacity
Equipment damage region located to the right and above the damage curves
Protective device operating region located between the equipment operating anddamage regions
Suggested overcurrent protection (figure 3)
Set device long time pickup (LTPU) function at or below the ampacity Set all other device functions at or below the damage curves
Comments
If current penetrates the limits of the thermal overload curve, cable insulation life isreduced.
If the maximum through-fault current penetrates the limits of the short circuit damagecurve, cable insulation will be damaged. The through-fault current is defined as themaximum current that can flow for a fault at the load-side terminals of the feeder.
-
7/27/2019 10. Overcurrent Coordination Basics Conductors
2/7
Fig. 1 Cable TCC landmarks
-
7/27/2019 10. Overcurrent Coordination Basics Conductors
3/7
Fig. 2 Cable TCC regions
-
7/27/2019 10. Overcurrent Coordination Basics Conductors
4/7
Fig. 3 Cable overcurrent protection
OH Conductor Overcurrent Protection
TCC landmarks (figure 4)
Ampacity located in the upper decade Short Circuit Damage Curve located in the bottom 3 decades
TCC regions (figure 5)
Equipment operating region located at and to the left of the ampacity
Equipment damage region located to the right and above the damage curve
Protective device operating region located between the equipment operating anddamage regions
Suggested overcurrent protection (figure 6)
Set device long time pickup (LTPU) function at or below the ampacity Set all other device functions below the damage region
Comments
If the maximum through-fault current penetrates the limits of the short circuit damagecurve, conductor damage will occur. The through-fault current is defined as themaximum current that can flow for a fault at the load-side terminals of the conductor.
-
7/27/2019 10. Overcurrent Coordination Basics Conductors
5/7
Fig. 4 OH conductor TCC landmarks
-
7/27/2019 10. Overcurrent Coordination Basics Conductors
6/7
Fig. 5 OH conductor TCC regions
-
7/27/2019 10. Overcurrent Coordination Basics Conductors
7/7
Fig. 6 OH conductor overcurrent protection
References
Other Application Guides offered by SKM Systems Analysis at www.skm.com Aluminum Electrical Conductor Handbook, The Aluminum Association Inc., Washington,
D.C., 3rd edition, 1989 Electrical Transmission and Distribution Reference Book, ABB Power T&D Company,
Raleigh, North Carolina, 1997 Protective Relaying Theory and Applications, 2nd Edition, Marcel Dekker, New York, 2004
The latest revision of:
IEEE Std 242, IEEE Recommended Practice for Protection and Coordination of Industrialand Commercial Power Systems (IEEE Buff Book)
IEEE Std C37.113, IEEE Guide for Protective Relay Applications to Transmission Lines
back to Application guides
products support contact us distributors Copyright SKM 2010