1 the promus pump a new direction in prominent metering pumps
TRANSCRIPT
2 Experts in Chem-Feed and Water Treatment
ProMus Training Sections Bridging the Gap Technical Review Sales Review
3 Experts in Chem-Feed and Water Treatment
Bridging the Gap Pumps Needed for Heavy Industrial
Applications Sigma’s Not Always Suitable Hydro and Makro Only Partial Solution Need Higher Pressure Orlita is too Large and Specialized Need for API 675 General Compliance
4 Experts in Chem-Feed and Water Treatment
API 675 Key Points Removable Check Valves
• Spool pieces acceptable if proposed
Adjustable Over Turndown While Running Rated for 110% of Maximum Specified Flow Steady State Flow of 1% Over 10:1 Turndown Flow Repeatability of +/-3% Connection Sizes ½” Through 1-½” (Really!) Double Check Valves When Specified
5 Experts in Chem-Feed and Water Treatment
API 675 Key Points Diaphragms
• Provisions to prevent excess flexure (Contour Plates?)• Double Diaphragms when spec’d
Internal Relief Valve Set at 10% or 25 psig Over Rated Pressure, Whichever is Higher
Packed Plunger Pumps Require Ext. PRV Stroke Adjustment – Manual or Auto
• Visual indication of Stroke Setting for both• Locking Device
6 Experts in Chem-Feed and Water Treatment
API 675 Key Points Special Tools (upon request) Hydrotest to 1.5x MAWP (Maximum
Allowable Working Pressure) Repeatability and Linearity Test
• 100, 75, 50, 25, 10 Percent Up and Down (10 Point)
Data and Documentation Requirements
7 Experts in Chem-Feed and Water Treatment
API 675 Specs You Don’t See Cast Iron Drive Case Stroke Speed Limitations Hydraulically Actuated Diaphragm Mechanically Actuated Diaphragm Restrictions on Lost Motion Control of Flow
8 Experts in Chem-Feed and Water Treatment
Technical Specifications Hydraulically Actuated Diaphragm Pump Capable of 0.61 gph to 101 gph Capable of Pressures to 3500 psig Mechanical Lost Motion
9 Experts in Chem-Feed and Water Treatment
Technical – ProMus Features Materials – 316ss
• Alloy 20, Hast C – future development Modular Design – Maximum Interchangeability
• 5 Gear Ratios• 8 Plunger Sizes• 3 Head Sizes (17, 30 & 40)• 1 Drive Size
Internal Pressure Relief (Adjustable) Mechanically Actuated Hydraulic Refill Valve Automatic Hydraulic Air Bleed Valve
10 Experts in Chem-Feed and Water Treatment
Technical – ProMus Features 10 Turn Micrometer Stroke Adjustment
• 10:1 Turndown Ratio on Stroke Nema 4 and Nema 7 Stroke Actuators Avail. Can Utilize Variable Speed Drives* Double Ball Check Options (17 & 30 Heads) Visual Indication of Relief Valve and Air
Bleed Valve Operation
11 Experts in Chem-Feed and Water Treatment
Technical – ProMus Specifications Minimum Backpressure – 22 psig Maximum Suction Pressure – 50 psig Maximum Viscosity – 200 cps (500 cps w/ spring) Oil Quantity – 1.5 quarts Oil Type – Mobilube 1 SHC 70W-90 or equal Priming Lift – 5 ft Suction Lift – 7.5 ft Weight – approx. 50-72 lb w/o motor
12 Experts in Chem-Feed and Water Treatment
Technical – ProMus Specifications Operating Temp. Range – 15 to 105 F Maximum Process Fluid Temp
• Continuous – 195 F• Intermittent – 250 F
Permissible Humidity – 95% Non-Condensing
13 Experts in Chem-Feed and Water Treatment
Technical – Motors Need to Know Class, Division & Group
• Class – Gas, Vapor, Liquid or Dust• Division – When Combustible is Present• Group – Type of Combustible Material
Explosion Proof Motors• Class 1, Division 1• Class 1, Division 2 if Single Phase Power• Be aware of Group required for motor
14 Experts in Chem-Feed and Water Treatment
Sales – ProMus vs mRoy Newer Pump Design
• Incorporates newer hydraulic refill technologies• Will not fail on starved suction conditions
Modular• Simple to modify in field
Easy to Hydraulically Prime Repairable Check Valves Very Price Competitive!!!!
15 Experts in Chem-Feed and Water Treatment
Sales – Applications Chemical Plants
•Catalysts for Process•Additives for Plastics•Defoamers
Oil & Gas Refineries•Oil or Fuel Additives
Power Plants•Water Treatment•Boiler Feed
Boiler Feed Applications•O2 Scavengers•Anti-scalants•Amines•Phosphates•pH Control
LNG Plants•Odorant (Mercaptan)