1 ge consumer & industrial multilin protection fundamentals by craig wester, john levine

90
1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

Upload: angelique-strudwick

Post on 29-Mar-2015

336 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

1GE Consumer & Industrial

Multilin

Protection Fundamentals

ByCraig Wester, John Levine

Page 2: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

2GE Consumer & Industrial

Multilin

Outline• Introductions

• Tools – Enervista Launchpad – On – Line Store – Demo Relays at ISO / Levine

• Discussion of future classes

• Protection Fundamentals

• ANSI number handout, Training CD’s

Page 3: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

3GE Consumer & Industrial

Multilin

Introduction

• Speakers:– Craig Wester – GE Multilin Regional Manager– John Levine – GE Multilin Account Manager

Page 4: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

4GE Consumer & Industrial

Multilin

Objective

• We are here to help make your job easier. This is very informal and designed around ISO Applications. Please ask question. We are not here to “preach” to you.

• The knowledge base on GE Multilin Relays varies greatly at ISO. If you have a question, there is a good chance there are 3 or 4 other people that have the same question. Please ask it.

Page 5: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

5GE Consumer & Industrial

Multilin

Tools

Page 6: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

6GE Consumer & Industrial

Multilin

Page 7: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

7GE Consumer & Industrial

Multilin

Page 8: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

8GE Consumer & Industrial

Multilin

Demo Relays with Ethernet

• Working with James McRoy and Dave Curtis

• SR 489

• SR 750

• G30

• MIF II

• Training CD’s

Page 9: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

9GE Consumer & Industrial

Multilin

Demo Relays at L-3

Page 10: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

10GE Consumer & Industrial

Multilin

Future Classes• GE Multilin Training will be the 2nd Friday of

every month. We will cover:– March – Basics, Enervista Launchpad, ANSI number

and what they represent, Uploading, downloading, Training CD’s, etc.

– April – 489 Relay– May – MIF II relay– June - 750 Relay– July - UR relay basic including Enervista Engineer– August – UR F60 and F35 relays– September – G30 and G60 including Transformer and

Generator in same zone– October – Communications and security– November -  Neutral Grounding Resistors– December – Ct’s and PT’s

Page 11: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

11GE Consumer & Industrial

Multilin

Protection Fundamentals

Page 12: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

12GE Consumer & Industrial

Multilin

Desirable Protection Attributes

• Reliability: System operate properly– Security: Don’t trip when you shouldn’t– Dependability: Trip when you should

• Selectivity: Trip the minimal amount to clear the fault or abnormal operating condition

• Speed: Usually the faster the better in terms of minimizing equipment damage and maintaining system integrity

• Simplicity: KISS

• Economics: Don’t break the bank

Page 13: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

13GE Consumer & Industrial

Multilin

Selection of protective relays requires compromises:

• Maximum and Reliable protection at minimum equipment cost

• High Sensitivity to faults and insensitivity to maximum load currents

• High-speed fault clearance with correct selectivity

• Selectivity in isolating small faulty area

• Ability to operate correctly under all predictable power system conditions

Art & Science of ProtectionArt & Science of Protection

Page 14: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

14GE Consumer & Industrial

Multilin

• Cost of protective relays should be balanced against risks involved if protection is not sufficient and not enough redundancy.

• Primary objectives is to have faulted zone’s primary protection operate first, but if there are protective relays failures, some form of backup protection is provided.

• Backup protection is local (if local primary protection fails to clear fault) and remote (if remote protection fails to operate to clear fault)

Art & Science of ProtectionArt & Science of Protection

Page 15: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

15GE Consumer & Industrial

Multilin

Primary Equipment & ComponentsPrimary Equipment & Components• Transformers - to step up or step down voltage level

• Breakers - to energize equipment and interrupt fault current

to isolate faulted equipment

• Insulators - to insulate equipment from ground and other

phases

• Isolators (switches) - to create a visible and permanent

isolation of primary equipment for maintenance purposes

and route power flow over certain buses.

• Bus - to allow multiple connections (feeders) to the same

source of power (transformer).

Page 16: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

16GE Consumer & Industrial

Multilin

Primary Equipment & ComponentsPrimary Equipment & Components• Grounding - to operate and maintain equipment safely

• Arrester - to protect primary equipment of sudden

overvoltage (lightning strike).

• Switchgear – integrated components to switch, protect,

meter and control power flow

• Reactors - to limit fault current (series) or compensate for

charge current (shunt)

• VT and CT - to measure primary current and voltage and

supply scaled down values to P&C, metering, SCADA, etc.

• Regulators - voltage, current, VAR, phase angle, etc.

Page 17: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

17GE Consumer & Industrial

Multilin

Types of ProtectionOvercurrent• Uses current to determine magnitude of fault– Simple– May employ definite time or inverse time curves– May be slow– Selectivity at the cost of speed (coordination stacks)– Inexpensive– May use various polarizing voltages or ground current

for directionality– Communication aided schemes make more selective

Page 18: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

18GE Consumer & Industrial

Multilin

Instantaneous Overcurrent Protection (IOC) & Definite Time Overcurrent

t

I

CTI

50+2

50+2

CTI • Relay closest to fault operates first

• Relays closer to source operate slower

• Time between operating for same current is called CTI (Clearing Time Interval)

Distribution Substation

Page 19: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

19GE Consumer & Industrial

Multilin

(TOC) Coordination

t

I

CTI

• Relay closest to fault operates first

• Relays closer to source operate slower

• Time between operating for same current is called CTI

Distribution Substation

Page 20: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

20GE Consumer & Industrial

Multilin

• Selection of the curves uses what is termed as a “ time multiplier” or “time dial” to effectively shift the curve up or down on the time axis

• Operate region lies above selected curve, while no-operate region lies below it

• Inverse curves can approximate fuse curve shapes

Time Overcurrent Protection (TOC)

Page 21: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

21GE Consumer & Industrial

Multilin

Multiples of pick-up

Time Overcurrent Protection(51, 51N, 51G)

Page 22: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

23GE Consumer & Industrial

Multilin

Types of Protection

Differential– current in = current out– Simple– Very fast– Very defined clearing area– Expensive– Practical distance limitations

• Line differential systems overcome this using digital communications

Page 23: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

24GE Consumer & Industrial

Multilin

Differential

• Note CT polarity dots

• This is a through-current representation

• Perfect waveforms, no saturation

I P

I S

I R-X

I P

I S

I R-Y

Relay

CT-X CT-Y

1 + (-1) = 0

+1

-1

0

Cur

rent

, pu

DIFF CURRENT

1 pu

Page 24: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

25GE Consumer & Industrial

Multilin

Differential

• Note CT polarity dots

• This is an internal fault representation

• Perfect waveforms, no saturation

FaultI P

I S

I R-X

I P

I S

I R-Y

Relay

2 + (+2) = 4

+2

-2

0

Cu

rre

nt,

puX

2 pu 2 pu

CT-X CT-Y

DIFF CURRENT

Page 25: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

26GE Consumer & Industrial

Multilin

Types of ProtectionVoltage• Uses voltage to infer fault or abnormal condition• May employ definite time or inverse time curves• May also be used for undervoltage load shedding

– Simple– May be slow– Selectivity at the cost of speed (coordination stacks)– Inexpensive

Page 26: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

27GE Consumer & Industrial

Multilin

Types of ProtectionFrequency• Uses frequency of voltage to detect power

balance condition• May employ definite time or inverse time

curves• Used for load shedding & machinery

under/overspeed protection– Simple– May be slow– Selectivity at the cost of speed can be expensive

Page 27: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

28GE Consumer & Industrial

Multilin

Types of ProtectionPower• Uses voltage and current to determine

power flow magnitude and direction• Typically definite time

– Complex– May be slow– Accuracy important for many applications – Can be expensive

Page 28: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

29GE Consumer & Industrial

Multilin

Types of ProtectionDistance (Impedance)– Uses voltage and current to determine impedance of fault– Set on impedance [R-X] plane– Uses definite time – Impedance related to distance from relay– Complicated– Fast– Somewhat defined clearing area with reasonable

accuracy– Expensive– Communication aided schemes make more selective

Page 29: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

30GE Consumer & Industrial

Multilin

Impedance• Relay in Zone 1 operates first• Time between Zones is called

CTI

Source

A B

21 21

T1

T2

ZA

ZB

R

X ZL

Page 30: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

Generation-typically at 4-20kV

Transmission-typically at 230-765kV

Subtransmission-typically at 69-161kV

Receives power from transmission system and transforms into subtransmission level

Receives power from subtransmission system and transforms into primary feeder voltage

Distribution network-typically 2.4-69kV

Low voltage (service)-typically 120-600V

TypicalBulk

Power System

TypicalBulk

Power System

33GE Consumer & Industrial

Multilin

Page 31: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

34GE Consumer & Industrial

Multilin

1. Generator or Generator-Transformer Units

2. Transformers

3. Buses

4. Lines (transmission and distribution)

5. Utilization equipment (motors, static loads, etc.)

6. Capacitor or reactor (when separately protected)

Unit Generator-Tx zoneBus zone

Line zone

Bus zone

Transformer zoneTransformer zone

Bus zone

Generator

~

XFMR Bus Line Bus XFMR Bus Motor

Motor zone

Protection Zones Protection Zones

Page 32: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

35GE Consumer & Industrial

Multilin

1. Overlap is accomplished by the locations of CTs, the key source for protective relays.

2. In some cases a fault might involve a CT or a circuit breaker itself, which means it can not be cleared until adjacent breakers (local or remote) are opened.

Zone A Zone B

Relay Zone A

Relay Zone B

CTs are located at both sides of CB-fault between CTs is cleared from both remote sides

Zone A Zone B

Relay Zone A

Relay Zone B

CTs are located at one side of CB-fault between CTs is sensed by both relays, remote right side

operate only.

Zone OverlapZone Overlap

Page 33: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

40GE Consumer & Industrial

Multilin

1. One-line diagram of the system or area involved

2. Impedances and connections of power equipment, system frequency, voltage level and phase sequence

3. Existing schemes

4. Operating procedures and practices affecting protection

5. Importance of protection required and maximum allowed clearance times

6. System fault studies

7. Maximum load and system swing limits

8. CTs and VTs locations, connections and ratios

9. Future expansion expectance

10.Any special considerations for application.

What Info is Required to Apply ProtectionWhat Info is Required to Apply Protection

Page 34: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

C37.2: Device

Numbers

• Partial listing

41GE Consumer & Industrial

Multilin

Page 35: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

42GE Consumer & Industrial

Multilin

One Line Diagram

• Non-dimensioned diagram showing how pieces of electrical equipment are connected

• Simplification of actual system

• Equipment is shown as boxes, circles and other simple graphic symbols

• Symbols should follow ANSI or IEC conventions

Page 36: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

43GE Consumer & Industrial

Multilin

1-Line Symbols [1]

Page 37: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

44GE Consumer & Industrial

Multilin

1-Line Symbols [2]

Page 38: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

45GE Consumer & Industrial

Multilin

1-Line Symbols [3]

Page 39: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

46GE Consumer & Industrial

Multilin

1-Line Symbols [4]

Page 40: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

47GE Consumer & Industrial

Multilin

1-Line [1]

Page 41: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

1-Line [2]

Page 42: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

49GE Consumer & Industrial

Multilin

3-Line

Page 43: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

52GE Consumer & Industrial

Multilin

CB Trip Circuit (Simplified)

Page 44: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

55GE Consumer & Industrial

Multilin

Lock Out Relay

86b

PR

86b

Shown in RESET position

86TC 86a

Page 45: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

56GE Consumer & Industrial

Multilin

CB Coil Circuit Monitoring:T with CB Closed; C with CB Opened

Coil Monitor Input

Trip/Close Contact

+

T/CCoil

-

52/aor

52/b

Breaker

Relay

52/a for trip circuit52/b for close circuit

Page 46: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

57GE Consumer & Industrial

Multilin

CB Coil Circuit Monitoring:Both T&C Regardless of CB state

Breaker

Relay

Breaker

Relay

Page 47: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

58GE Consumer & Industrial

Multilin

• Current transformers are used to step primary system currents to values usable by relays, meters, SCADA, transducers, etc.

• CT ratios are expressed as primary to secondary; 2000:5, 1200:5, 600:5, 300:5

• A 2000:5 CT has a “CTR” of 400

Current Transformers

Page 48: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

59GE Consumer & Industrial

Multilin

• IEEE relay class is defined in terms of the voltage a CT can deliver at 20 times the nominal current rating without exceeding a 10% composite ratio error.

For example, a relay class of C100 on a 1200:5 CT means that the CT can develop 100 volts at 24,000 primary amps (1200*20) without exceeding a 10% ratio error. Maximum burden = 1 ohm.

100 V = 20 * 5 * (1ohm)

200 V = 20 * 5 * (2 ohms)

400 V = 20 * 5 * (4 ohms)

800 V = 20 * 5 * (8 ohms)

Standard IEEE CT Relay Accuracy

Page 49: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

61GE Consumer & Industrial

Multilin

Application Burden Designation

Impedance (Ohms)

VA @ 5 amps

Power Factor

Metering B0.1 0.1 2.5 0.9B0.2 0.2 5 0.9B0.5 0.5 12.5 0.9B0.9 0.9 22.5 0.9B1.8 1.8 45 0.9

Relaying B1 1 25 0.5B2 2 50 0.5B4 4 100 0.5B8 8 200 0.5

Standard IEEE CT Burdens (5 Amp) (Per IEEE Std. C57.13-1993)

Page 50: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

62GE Consumer & Industrial

Multilin

Current into the Dot, Out of the DotCurrent out of the dot, in to the dot

Forward Power

I P

I S

I R

Relayor Meter

Forward Power

I P

I S

I R

Relayor Meter

Page 51: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

63GE Consumer & Industrial

Multilin

VVPP

VVSS

Relay

• Voltage (potential) transformers are used to isolate and step down and accurately reproduce the scaled voltage for the protective device or relay

• VT ratios are typically expressed as primary to secondary; 14400:120, 7200:120

• A 4160:120 VT has a “VTR” of 34.66

Voltage Transformers

Page 52: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

64GE Consumer & Industrial

Multilin

Typical CT/VT Circuits

Courtesy of Blackburn, Protective Relay: Principles and Applications

Page 53: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

65GE Consumer & Industrial

Multilin

CT/VT Circuit vs. Casing Ground

• Case ground made at IT location• Secondary circuit ground made at first point of

use

Case

Secondary Circuit

Page 54: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

66GE Consumer & Industrial

Multilin

Equipment Grounding

– Prevents shock exposure of personnel– Provides current carrying capability for the

ground-fault current– Grounding includes design and construction of

substation ground mat and CT and VT safety grounding

Page 55: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

67GE Consumer & Industrial

Multilin

System Grounding

– Limits overvoltages– Limits difference in electric potential through local

area conducting objects– Several methods

• Ungrounded• Reactance Coil Grounded • High Z Grounded• Low Z Grounded• Solidly Grounded

Page 56: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

68GE Consumer & Industrial

Multilin

1. Ungrounded: There is no intentional ground applied to the system-however it’s grounded through natural capacitance. Found in 2.4-15kV systems.

2. Reactance Grounded: Total system capacitance is cancelled by equal inductance. This decreases the current at the fault and limits voltage across the arc at the fault to decrease damage.

X0 <= 10 * X1

System Grounding

Page 57: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

69GE Consumer & Industrial

Multilin

3. High Resistance Grounded: Limits ground fault current to 10A-20A. Used to limit transient overvoltages due to arcing ground faults.

R0 <= X0C/3, X0C is capacitive zero sequence reactance

4. Low Resistance Grounded: To limit current to 25-400A

R0 >= 2X0

System Grounding

Page 58: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

70GE Consumer & Industrial

Multilin

5. Solidly Grounded: There is a connection of transformer or generator neutral directly to station ground.

Effectively Grounded: R0 <= X1, X0 <= 3X1, where R is the system fault resistance

System Grounding

Page 59: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

76GE Consumer & Industrial

Multilin

Basic Current Connections:How System is Grounded

Determines How Ground Fault is Detected

Medium/High Resistance

Ground

Low/No Resistance

Ground

Page 60: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

77GE Consumer & Industrial

Multilin

Substation TypesSubstation Types

•Single Supply

•Multiple Supply

•Mobile Substations for emergencies

•Types are defined by number of

transformers, buses, breakers to

provide adequate service for

application

Page 61: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

78GE Consumer & Industrial

Multilin

Industrial Substation Arrangements(Typical)

Page 62: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

79GE Consumer & Industrial

Multilin

Industrial Substation Arrangements(Typical)

Page 63: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

80GE Consumer & Industrial

Multilin

Utility Substation ArrangementsUtility Substation Arrangements

Single Bus, 1 Tx, Dual supply Single Bus, 2 Tx, Dual Supply

2-sections Bus with HS Tie-Breaker, 2 Tx, Dual Supply

(Typical)

Page 64: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

81GE Consumer & Industrial

Multilin

Breaker-and-a-half –allows reduction of equipment cost by using 3 breakers for each 2 circuits. For load transfer and operation is simple, but relaying is complex as middle breaker is responsible to both circuits

Utility Substation ArrangementsUtility Substation Arrangements

Bus 1

Bus 2

Ring bus –advantage that one breaker per circuit. Also each outgoing circuit (Tx) has 2 sources of supply. Any breaker can be taken from service without disrupting others.

(Typical)

Page 65: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

82GE Consumer & Industrial

Multilin

Double Bus: Upper Main and Transfer, bottom Double Main bus

Main bus

Aux. bus

Bus 1

Bus 2

Tie

b

rea

ker

Utility Substation ArrangementsUtility Substation ArrangementsUtility Substation ArrangementsUtility Substation Arrangements

Main

Reserve

Transfer

Main-Reserved and Transfer Bus: Allows maintenance of any bus and any breaker

(Typical)

Page 66: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

83GE Consumer & Industrial

Multilin

Switchgear Defined• Assemblies containing electrical switching,

protection, metering and management devices• Used in three-phase, high-power industrial,

commercial and utility applications• Covers a variety of actual uses, including motor

control, distribution panels and outdoor switchyards

• The term "switchgear" is plural, even when referring to a single switchgear assembly (never say, "switchgears")

• May be a described in terms of use:– "the generator switchgear" – "the stamping line switchgear"

Page 67: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

91GE Consumer & Industrial

Multilin

A Good Day in System Protection……

– CTs and VTs bring electrical info to relays– Relays sense current and voltage and declare

fault– Relays send signals through control circuits to

circuit breakers– Circuit breaker(s) correctly trip

What Could Go Wrong Here????

Page 68: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

92GE Consumer & Industrial

Multilin

A Bad Day in System Protection……

– CTs or VTs are shorted, opened, or their wiring is– Relays do not declare fault due to setting errors,

faulty relay, CT saturation– Control wires cut or batteries dead so no signal is

sent from relay to circuit breaker– Circuit breakers do not have power, burnt trip coil

or otherwise fail to trip

Protection Systems Typically are Designed for N-1

Page 69: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

93GE Consumer & Industrial

Multilin

Protection Performance Statistics

• Correct and desired: 92.2%

• Correct but undesired: 5.3%

• Incorrect: 2.1%

• Fail to trip: 0.4%

Page 70: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

94GE Consumer & Industrial

Multilin

Contribution to Faults

Page 71: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

95GE Consumer & Industrial

Multilin

Fault Types (Shunt)

Page 72: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

99GE Consumer & Industrial

Multilin

AC & DC Current Components of Fault Current

Page 73: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

100GE Consumer & Industrial

Multilin

Variation of current with time during a fault

Page 74: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

102GE Consumer & Industrial

Multilin

Useful Conversions

Page 75: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

103GE Consumer & Industrial

Multilin

Per Unit System

Establish two base quantities:

Standard practice is to define– Base power – 3 phase– Base voltage – line to line

Other quantities derived with basic power equations

Page 76: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

104GE Consumer & Industrial

Multilin

Per Unit Basics

Page 77: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

105GE Consumer & Industrial

Multilin

Short Circuit CalculationsPer Unit System

Per Unit Value = Actual Quantity Base Quantity

Vpu = Vactual

Vbase

Ipu = Iactual

Ibase

Zpu = Zactual

Zbase

Page 78: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

106GE Consumer & Industrial

Multilin

Short Circuit CalculationsPer Unit System

3 x kV L-L base

I base =x 1000MVAbase

Z base =kV2

L-L base

MVAbase

Page 79: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

107GE Consumer & Industrial

Multilin

Short Circuit CalculationsPer Unit System – Base Conversion

Zpu = Zactual

Zbase Zbase = kV 2

base

MVAbase

Zpu1 = MVAbase1

kV 2base1

X Zactual

Zpu2 = MVAbase2

kV 2base2

X Zactual

Zpu2 =Zpu1 x kV 2base1 x MVAbase2

kV 2base2 MVAbase1

Page 80: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

120GE Consumer & Industrial

Multilin

A Study of a Fault…….

Page 81: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

Fault Interruption and Arcing

121GE Consumer & Industrial

Multilin

Page 82: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

122GE Consumer & Industrial

Multilin

Arc Flash Hazard

Page 83: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

123GE Consumer & Industrial

Multilin

Arc Flash Mitigation:Problem Description

– An electric arc flash can occur if a conductive object gets too close to a high-amp current source or by equipment failure (ex., while opening or closing disconnects, racking out)• The arc can heat the air to temperatures as high as 35,000 F, and

vaporize metal in equipment • The arc flash can cause severe skin burns by direct heat exposure

and by igniting clothing• The heating of the air and vaporization of metal creates a pressure

wave (arc blast) that can damage hearing and cause memory loss (from concussion) and other injuries.

• Flying metal parts are also a hazard.

Page 84: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

124GE Consumer & Industrial

Multilin

Methods to Reduce Arc Flash Hazard

– Arc flash energy may be expressed in I2t terms, so you can decrease the I or decrease the t to lessen the energy

– Protective relays can help lessen the t by optimizing sensitivity and decreasing clearing time• Protective Relay Techniques

– Other means can lessen the I by limiting fault current• “Non-Protective Relay Techniques”

Page 85: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

125GE Consumer & Industrial

Multilin

Non-Protective Relaying Methods of Reducing Arc Flash Hazard

– System design modifications increase power transformer impedance• Addition of phase reactors• Faster operating breakers• Splitting of buses

– Current limiting fuses (provides partial protection only for a limited current range)

– Electronic current limiters (these devices sense overcurrent and interrupt very high currents with replaceable conductor links (explosive charge)

– Arc-resistant switchgear (this really doesn't reduce arc flash energy; it deflects the energy away from personnel)

– Optical arc flash protection via fiber sensors

– Optical arc flash protection via lens sensors

Page 86: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

126GE Consumer & Industrial

Multilin

Protective Relaying Methods of Reducing Arc Flash Hazard

– Bus differential protection (this reduces the arc flash energy by reducing the clearing time

– Zone interlock schemes where bus relay selectively is allowed to trip or block depending on location of faults as identified from feeder relays

– Temporary setting changes to reduce clearing time during maintenance • Sacrifices coordination

– FlexCurve for improved coordination opportunities

– Employ 51VC/VR on feeders fed from small generation to improve sensitivity and coordination

– Employ UV light detectors with current disturbance detectors for selective gear tripping

Page 87: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

Arc Flash Hazards

128GE Consumer & Industrial

Multilin

Page 88: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

Arc Pressure Wave

129GE Consumer & Industrial

Multilin

Page 89: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

133GE Consumer & Industrial

Multilin

Copy of this presentation are at:

www.L-3.com\private\Levine

Page 90: 1 GE Consumer & Industrial Multilin Protection Fundamentals By Craig Wester, John Levine

134GE Consumer & Industrial

Multilin

Protection Fundamentals

QUESTIONS?