05 2wc flat spray nozzle
DESCRIPTION
spray nozzleTRANSCRIPT
-
FLAT SPRAY NOZZLE(For Tank Cooling)05 WC15B (brass) or 05 WC15S (316SS)05 WC20B (brass) or 05 WC20S (316SS)
Progard Flat Spray Nozzle distributes water in awide angle flat spray pattern with mediumimpact to prevent fire/heat penetration. Theyproduce a uniform spray distribution of mediumsized droplets.
When installed in a upright (or pendent)position, the nozzle acts a a window spraynozzle to protect windows, interior wall andother openings in a building which are affectedby fire.
The nozzle can also be installed in a horizontalposition with the flow towards the ground, toproduce a flat water curtain for cooling ofexterior tank walls and roofs. The water flow tothese nozzles is normally controlled either by amanual operated block valve or by means of anautomatically operated deluge valve system.
These nozzles are available with different orificesizes. The minimum pressure to achieve areasonable spray pattern is 1.4 bar (20 psi). Allspray patterns shown are based on tests carriedin a closed environments (indoor). The windvelocity must be taken into consideration whendesigning these nozzles for outdoor systems.
Technical DataMaterial : Brass or 316 SSS
Working Pressure : 12.3 bar (175 psi) max
Working Pressure : 1.40 bar (20 psi) min
Finish : Brass or Nickel-Chromed for Model 05 WC15 and 05 WC15SNatural finish for Model 05 WC20 and 05 WC20S
End connection : 05 WC15 BSPT (or NPT)05 WC15S BSPT (or NPT)05 WC20 BSPT (or NPT)05 WC20S BSPT (or NPT)
Nozzle Selection
18K140
15.5K120
14K98
316SS05 WC20S
18K140
15.5K120
14K98
Brass05 WC20B
12K-72
10K-53
9K-45
8K-37
7K-30
6K-23
316SS05 WC15S
12K-72
10K-53
9K-45
8K-37
7K-30
150
6K-23
Brass05 WC15B
Spray Angle(Degree)
OrificeSize(mm)
NozzleK-FactorMaterialProduct Code
Dimensions
46 mm BSPT05 WC15B /PGN-WC15S42 mm BSPT05 WC15B /PGN-WC15SLengthInlet SizeNozzle Model
Horizontal Spray Distance in METRES (approx.)
5.54.515.114.6K1405.44.41514.4K1205.24.214.414K984.84.414.213.8K723.63.313.313.8K532.42.21212.2K452.42.21211k372.21.81111K302.21.81110K23DCBAK-factor
Recommended distance between nozzles is 2.5 metres (max).The above figures shown are indicative trajectory (max) with nospecific density applied
05 WC15S05 WC15B
-
FLAT SPRAY NOZZLE(For Tank Cooling)05 WC15B (brass) or 05 WC15S (316SS)05 WC20B (brass) or 05 WC20S (316SS)
Pendent Spray Distance in METRES(approximate)
6.86.6K140
6.56.4K120
6.36.2K98
6.25.9K72
65.5K53
5.85.3K45
5.85.3k37
5.55K30
5.55K23
BANozzle K-factor
Ordering InformationThe following details should be specified when placing orders:
1) Product code2) K-Factor3) Spray angle4) Material and Finish