2
FLAT SPRAY NOZZLE(For Tank Cooling) 05 WC15B (brass) or 05 WC15S (316SS) 05 WC20B (brass) or 05 WC20S (316SS) Progard Flat Spray Nozzle distributes water in a wide angle flat spray pattern with medium impact to prevent fire/heat penetration. They produce a uniform spray distribution of medium sized droplets. When installed in a upright (or pendent) position, the nozzle acts a a window spray nozzle to protect windows, interior wall and other openings in a building which are affected by fire. The nozzle can also be installed in a horizontal position with the flow towards the ground, to produce a flat water curtain for cooling of exterior tank walls and roofs. The water flow to these nozzles is normally controlled either by a manual operated block valve or by means of an automatically operated deluge valve system. These nozzles are available with different orifice sizes. The minimum pressure to achieve a reasonable spray pattern is 1.4 bar (20 psi). All spray patterns shown are based on tests carried in a closed environments (indoor). The wind velocity must be taken into consideration when designing these nozzles for outdoor systems. Technical Data Material : Brass or 316 SSS Working Pressure : 12.3 bar (175 psi) max Working Pressure : 1.40 bar (20 psi) min Finish : Brass or Nickel-Chromed for Model 05 WC15 and 05 WC15S Natural finish for Model 05 WC20 and 05 WC20S End connection : 05 WC15 ½” BSPT (or NPT) 05 WC15S ½” BSPT (or NPT) 05 WC20 ¾” BSPT (or NPT) 05 WC20S ¾” BSPT (or NPT) Nozzle Selection 18 K140 15.5 K120 14 K98 316SS 05 WC20S 18 K140 15.5 K120 14 K98 Brass 05 WC20B 12 K-72 10 K-53 9 K-45 8 K-37 7 K-30 6 K-23 316SS 05 WC15S 12 K-72 10 K-53 9 K-45 8 K-37 7 K-30 150 6 K-23 Brass 05 WC15B Spray Angle (Degree) Orifice Size (mm) Nozzle K-Factor Material Product Code Dimensions 46 mm ¾” BSPT 05 WC15B /PGN-WC15S 42 mm ½” BSPT 05 WC15B /PGN-WC15S Length Inlet Size Nozzle Model Horizontal Spray Distance in METRES (approx.) 5.5 4.5 15.1 14.6 K140 5.4 4.4 15 14.4 K120 5.2 4.2 14.4 14 K98 4.8 4.4 14.2 13.8 K72 3.6 3.3 13.3 13.8 K53 2.4 2.2 12 12.2 K45 2.4 2.2 12 11 k37 2.2 1.8 11 11 K30 2.2 1.8 11 10 K23 D C B A K-factor Recommended distance between nozzles is 2.5 metres (max). The above figures shown are indicative trajectory (max) with no specific density applied 05 WC15S 05 WC15B

Upload: sam-low

Post on 08-Nov-2015

216 views

Category:

Documents


0 download

DESCRIPTION

spray nozzle

TRANSCRIPT

  • FLAT SPRAY NOZZLE(For Tank Cooling)05 WC15B (brass) or 05 WC15S (316SS)05 WC20B (brass) or 05 WC20S (316SS)

    Progard Flat Spray Nozzle distributes water in awide angle flat spray pattern with mediumimpact to prevent fire/heat penetration. Theyproduce a uniform spray distribution of mediumsized droplets.

    When installed in a upright (or pendent)position, the nozzle acts a a window spraynozzle to protect windows, interior wall andother openings in a building which are affectedby fire.

    The nozzle can also be installed in a horizontalposition with the flow towards the ground, toproduce a flat water curtain for cooling ofexterior tank walls and roofs. The water flow tothese nozzles is normally controlled either by amanual operated block valve or by means of anautomatically operated deluge valve system.

    These nozzles are available with different orificesizes. The minimum pressure to achieve areasonable spray pattern is 1.4 bar (20 psi). Allspray patterns shown are based on tests carriedin a closed environments (indoor). The windvelocity must be taken into consideration whendesigning these nozzles for outdoor systems.

    Technical DataMaterial : Brass or 316 SSS

    Working Pressure : 12.3 bar (175 psi) max

    Working Pressure : 1.40 bar (20 psi) min

    Finish : Brass or Nickel-Chromed for Model 05 WC15 and 05 WC15SNatural finish for Model 05 WC20 and 05 WC20S

    End connection : 05 WC15 BSPT (or NPT)05 WC15S BSPT (or NPT)05 WC20 BSPT (or NPT)05 WC20S BSPT (or NPT)

    Nozzle Selection

    18K140

    15.5K120

    14K98

    316SS05 WC20S

    18K140

    15.5K120

    14K98

    Brass05 WC20B

    12K-72

    10K-53

    9K-45

    8K-37

    7K-30

    6K-23

    316SS05 WC15S

    12K-72

    10K-53

    9K-45

    8K-37

    7K-30

    150

    6K-23

    Brass05 WC15B

    Spray Angle(Degree)

    OrificeSize(mm)

    NozzleK-FactorMaterialProduct Code

    Dimensions

    46 mm BSPT05 WC15B /PGN-WC15S42 mm BSPT05 WC15B /PGN-WC15SLengthInlet SizeNozzle Model

    Horizontal Spray Distance in METRES (approx.)

    5.54.515.114.6K1405.44.41514.4K1205.24.214.414K984.84.414.213.8K723.63.313.313.8K532.42.21212.2K452.42.21211k372.21.81111K302.21.81110K23DCBAK-factor

    Recommended distance between nozzles is 2.5 metres (max).The above figures shown are indicative trajectory (max) with nospecific density applied

    05 WC15S05 WC15B

  • FLAT SPRAY NOZZLE(For Tank Cooling)05 WC15B (brass) or 05 WC15S (316SS)05 WC20B (brass) or 05 WC20S (316SS)

    Pendent Spray Distance in METRES(approximate)

    6.86.6K140

    6.56.4K120

    6.36.2K98

    6.25.9K72

    65.5K53

    5.85.3K45

    5.85.3k37

    5.55K30

    5.55K23

    BANozzle K-factor

    Ordering InformationThe following details should be specified when placing orders:

    1) Product code2) K-Factor3) Spray angle4) Material and Finish