    USERS MANUAL

    All VRF Indoor Units

    0150511194-A

    Read this manual before installation and operation

    Make sure that it is well kept for later reference

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    2/28

    Your air conditioner may be subject to any change owing to the improvement of JCI products.

    VRF series multiple air conditioning systems adopt the consistent running mode, by which, all

    indoor units can only be heating or refrigerating operation at the same time.

    To protect the compressor, the air conditioning unit should be powered on for over 12 hours

    before using it.All indoor units of the same refrigerating system should use the unied power switch to ensure

    that all indoor units are in the state of being powered on at the same time during the operation

    of air conditioner.

    Operating Range of Air Condtioner(except Fresh Air Unit)

    Cooling

    dry

    indoormax. DB:32 WB:23

    min. DB:18 WB:14

    outdoormax. DB:52 WB:26

    min. DB:-5

    Heating

    indoormax. DB:27 WB:23

    min. DB:15 WB:14

    outdoormax. DB:21 WB:15

    min. DB:-15

    Operating Range of Air Condtioner(Fresh Air Unit)

    Cooling

    dry

    indoormax. DB:52 WB:32

    min. DB:21 WB:15

    outdoormax. DB:52 WB:32

    min. DB:21

    Heating

    indoormax. DB:15

    min. DB:-5outdoor

    max. DB:15

    min. DB:-5

    User Manual

    CONTENT

    Parts and Functions.................................................................................................................. 1

    Safety ..................................................................................................................................... 13Maintenance ........................................................................................................................... 15

    Fault Checkup ....................................................................................................................... 24

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    3/28

    1

    Parts and Functions

    Remote Controller & Wired Controller

    Indoor Type Standard Optional

    4-Way Cassette Type

    Wired controller

    Wired controller

    2-Way Cassette Type

    Wired controller

    High Wall

    Remote controller

    Remote controller

    Wired controller

    Floor Ceiling

    Wired controller

    Wired controller

    Slim Duct-Low static

    Duct-Low static

    Duct-medium static

    Duct-high static

    Console

    Fresh air unit

    Wired controller

    Wired controller

    Remote controller

    Wired controller

    NOTE:1.means optional controller not available.2. For controller instructions please refer to the corresponding controller user manual.

    Remote controller

    Remote controller

    Remote controller

    Remote controller

    Remote controller

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    4/28

    2

    Parts and Functions

    Indoor Units

    YVKVXH028WAR--GX

    YVKVXH036WAR--GX

    YVKVXH045WAR--GX

    YVKVXH056WAR--GX

    YVKVXH071WAR--GX

    YVKVXH080WAR--GX

    YVKVXH090WAR--GX

    YVKVXH112WAR--GX

    YVKVXH140WAR--GX

    Functions:

    1. Controller do not memory the wind direction function. When the unit power on, the louver do

    not swing.

    If you need the function of louver swing, please follow the controller user manual to operate.

    2. When swing, the 4 louvers will swing together, cannot be controlled single.

    3. The unit congure takeup pump of condensing water in standard.

    4. Lamp instruction:

    "Compressor" lamp: It lights up when the compressor is operating.

    "Operation" lamp: Indoor unit receive the ON signal.

    "POWER" lamp: It lights up when the Indoor Unit is powered.

    "TIMER" lamp: It lights up when "TIMER" function is activated for programmed start/stop.The timer lamp ashing when the unit have some malfunction happens, ashing times stands

    for corresponding number, detailed information see the malfunction sheet.

    4-Way Cassette Type

    LAMPS ON INDOOR UNIT

    electrical cabinetwind deector

    control panelThe lamp will not ash

    when wired controller

    is used

    inlet grid

    air cleaner (in inlet grid)

    Emergency operation switch

    Operation indicator

    Compressor indicator

    Power indicator

    Timer indicator

    Receiving window for remote control

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    5/28

    3

    YV8VXH022WAR--GX

    YV8VXH028WAR--GX

    YV8VXH036WAR--GXYV8VXH045WAR--GX

    YV8VXH056WAR--GX

    If you choose the optional remote controller, you can follow this function instruction below:

    Functions:

    1. This series units congure without outlet grill , so it cannot implement swing function.

    2. Unit system do not congure takeup pump of condensing water.

    3. Lamp instruction:

    "Compressor" lamp: It lights up when the compressor is operating.

    "Operation" lamp: Indoor unit receive the ON signal.

    "TIMER" lamp: It lights up when "TIMER" function is activated for programmed start/stop.The timer lamp ashing when the unit have some malfunction happens, ashing times stands

    for corresponding number, detailed information see the malfunction sheet.

    Parts and Functions

    2-Way Cassette Type

    drainpipe

    wind deector

    (regulate wind direction)

    air cleaner (in inlet grid)

    inlet grid

    Receiving window for remote

    control

    Compressor indicator Operation indicator

    Timer indicator

    Emergency operation switch

    Control panel

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    6/28

    4

    Functions:

    1. Controller do not memory the wind direction function. When the unit power on, the louver

    swing to the standard setting position.

    If you need the function of louver swing, please follow the controller user manual to operate.

    2. The louver standard setting position: cooling mode is horizontal blowing estate and heating

    mode is blowing downwards estate.

    3. When the unit power off, the louver's position is closed.

    YVHVXH022WAR--FX

    YVHVXH028WAR--FX

    YVHVXH036WAR--FXYVHVXH045WAR--FX

    YVHVXH056WAR--FX

    YVHVXH071WAR--FX

    Parts and Functions

    High wall type

    Inlet

    Inlet grille

    Outlet

    Vertical blade

    (adjust left and right air ow)

    Display board

    Emergency Switch

    Air Purifying Filter

    (inside)

    Horizontal ap

    (adjust up and down air ow.Don't adjust it manually)

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    7/28

    5

    YVFVXH080WAR--GX

    YVFVXH090WAR--GX

    YVFVXH112WAR--GX

    YVFVXH140WAR--GX

    Functions:

    1. Controller do not memory the wind direction function. When the unit power on, the louver

    swing to the standard setting position.

    If you need the function of louver swing, please follow the controller user manual to operate.

    2. When the unit power off, the louver*s position is closed.

    3. Lamp instruction:

    "Compressor" lamp: It lights up when the compressor is operating.

    "Operation"lamp: Indoor unit receive the ON signal.

    "POWER" lamp: It lights up when the Indoor Unit is powered.

    "TIMER" lamp: It lights up when "TIMER"function is activated for programmed start/stop.The timer lamp ashing when the unit have some malfunction happens, ashing times stands

    for corresponding number, detailed information see the malfunction sheet.

    YVFVXH028WAR--GX

    YVFVXH036WAR--GX

    YVFVXH045WAR--GXYVFVXH056WAR--GX

    YVFVXH071WAR--GX

    Parts and Functions

    Floor ceiling type

    Control Panel

    Emergency Operation Switch

    Remote Control Signal Window Receiver

    Power Indicator Operation Indicator Air Inlet

    Timer indicator Outlet Guide Plate

    Compressor indicator Outlet Flap

    The lamp will not ash

    when wired controller is

    used.

    The lamp will not ash when wired

    controller is used.

    Air Inlet

    Front Panel

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    8/28

    6

    If you choose the optional remote controller, you can follow this function instruction below:

    Functions:

    1. This series units congure without outlet grill , so it cannot implement swing function.

    2. Unit system do not congure takeup pump of condensing water.

    3. Lamp instruction:

    "Compressor" lamp: It lights up when the compressor is operating.

    "Operation" lamp: Indoor unit receive the ON signal.

    "TIMER" lamp: It lights up when "TIMER" function is activated for programmed start/stop.

    The timer lamp ashing when the unit have some malfunction happens, ashing times stands

    for corresponding number, detailed information see the malfunction sheet.

    YV3VXH022WAR--GX

    YV3VXH028WAR--GX

    YV3VXH036WAR--GXYV3VXH045WAR--GX

    YV3VXH056WAR--GX

    YV3VXH071WAR--GX

    Parts and Functions

    Slim Duct-Low static

    Receiving window for remote

    control

    Compressor indicator Operation indicator

    Timer indicator

    Emergency operation switch

    Control panel

    Evaporator

    Air outlet port

    liquid pipe

    Drainage pipeElectric box

    Drainage pipe

    (pump)

    suspending bolt

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    9/28

    7

    YVDVXH022WAR--GX

    YVDVXH028WAR--GX

    YVDVXH036WAR--GXYVDVXH045WAR--GX

    YVDVXH056WAR--GX

    YVDVXH071WAR--GX

    Parts and Functions

    Duct type-Low static

    If you choose the optional remote controller, you can follow this function instruction below:

    Functions:

    1. This series units congure without outlet grill , so it cannot implement swing function.

    2. Unit system do not congure takeup pump of condensing water.

    3. Lamp instruction:

    "Compressor" lamp: It lights up when the compressor is operating.

    "Operation" lamp: Indoor unit receive the ON signal.

    "TIMER" lamp: It lights up when "TIMER" function is activated for programmed start/stop.

    The timer lamp ashing when the unit have some malfunction happens, ashing times stands

    for corresponding number, detailed information see the malfunction sheet.

    Receiving window for remote

    control

    Compressor indicator Operation indicator

    Timer indicator

    Emergency operation switch

    Control panel

    Evaporator

    Cabinet of electric appliance

    Condensated water pan

    Air outlet frame

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    10/28

    8

    YVEVXH090WAR--GX

    YVEVXH112WAR--GX

    YVEVXH140WAR--GX

    YVEVXH056WAR--GX

    YVEVXH071WAR--GX

    YVEVXH080WAR--GX

    Parts and Functions

    Duct type-medium static

    air outlet port

    air inlet port

    air inlet port

    duct

    esh air inlet port

    drainage holeair outlet port

    Up

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    11/28

    9

    If you choose the optional remote controller, you can follow this function instruction below:

    Functions:

    1. This series units congure without outlet grill , so it cannot implement swing function.

    2.This series units are middle static. They should install wind pipe. If the wind pipe is too short or

    missing, it will make big noise when running.

    3. 56~80 unit system congure takeup pump of condensing water , 90~140 unit system do not

    congure it.

    4. Lamp instruction:

    "Compressor" lamp: It lights up when the compressor is operating.

    "Operation" lamp: Indoor unit receive the ON signal.

    "TIMER" lamp: It lights up when "TIMER" function is activated for programmed start/stop.

    The timer lamp ashing when the unit have some malfunction happens, ashing times stands

    for corresponding number, detailed information see the malfunction sheet.

    Parts and Functions

    Receiving window for remote

    control

    Compressor indicator Operation indicator

    Timer indicator

    Emergency operation switch

    Control panel

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    12/28

    10

    If you choose the optional remote controller, you can follow this function instruction below:

    Functions:

    1. This series units congure without outlet grill , so it cannot implement swing function.

    2. This series units are middle static. They should install wind pipe. If the wind pipe is too short

    or missing, it will make big noise when running.

    3. Unit system do not congure takeup pump of condensing water.

    4. Lamp instruction

    "Compressor"lamp: It lights up when the compressor is operating.

    "Operation" lamp: Indoor unit receive the ON signal.

    "TIMER" lamp: It lights up when "TIMER" function is activated for programmed start/stop.The timer lamp ashing when the unit have some malfunction happens, ashing times stands

    for corresponding number, detailed information see the malfunction sheet.

    YVGVXH056WAR--GX

    YVGVXH071WAR--GX

    YVGVXH080WAR--GXYVGVXH090WAR--GX

    YVGVXH112WAR--GX

    YVGVXH140WAR--GX

    YVGVXH226WAR--GX

    YVGVXH280WAR--GX

    Parts and Functions

    Duct type-high static

    Receiving window for remotecontrol

    Compressor indicator Operation indicator

    Timer indicator

    Emergency operation switch

    Control panel

    air outlet port

    air inlet port

    ue

    ue

    drainage pipe

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    13/28

    11

    Functions:

    1. Controller do not memory the wind direction function. When the unit power on, the louver

    swing to the standard setting position.

    If you need the function of louver swing, please follow the controller user manual to operate.

    2. The louver standard setting position :cooling mode is horizontal blowing estate and heatingmode is blowing downwards estate.

    3. When the unit power off, the louver*s position is closed.

    4. Single & double fan motor changeover:

    Use remote controller setting single /double fan motor operation condition. In airflow mode,

    press the sleep button 6 times within 10 seconds, if the buzzer short ring twice stands for

    double fan motor condition; if only ring one time, stands for enter single fan motor mode.

    5. Lamp instruction:

    "POWER" lamp: It lights up when the Indoor Unit is powered.

    "TIMER" lamp: It lights up when "TIMER" function is activated for programmed start/stop.

    The timer lamp ashing when the unit have some malfunction happens, ashing times standsfor corresponding number, detailed information see the malfunction sheet.

    "RUN" lamp: Indoor unit receive the ON signal.

    YV5VXH022WAR--FX

    YV5VXH028WAR--FX

    YV5VXH036WAR--FXYV5VXH056WAR--FX

    Parts and Functions

    Console type

    LAMPS ON INDOOR UNIT

    LED panel and IR Receive

    Upper air outlet

    LED Panel and

    IR Receiver

    Lower air outlet

    Inlet grille

    Remote controller's infrared receiver

    Emergency and Test Switch

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    14/28

    12

    Function instruction:

    1. Fresh air unit can control the outlet temperature but cannot control the room temperature.

    2. In cooling mode, when air inlet temperature is lower than 19 , the unit run in fan mode; when

    air inlet temperature is higher than 43 , the unit will try the best to run, but for protecting the

    unit, it may stop running.

    3. In heating mode, when air inlet temperature is higher than 18 , the unit run in fan mode;

    when air inlet temperature is lower than -5 , the unit will try the best to run, but for protecting

    the unit, it may stop running.

    YV4VXH140WAR--GX

    YV4VXH226WAR--GX

    YV4VXH280WAR--GX

    Parts and Functions

    Fresh air unit

    air outlet port

    air inlet port

    ue

    ue

    drainage pipe

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    15/28

    13

    Safety

    This manual should always be accessible and close to this air condition equipmet.

    There are two types of indications, " WARNING"and " CAUTION" The indication

    preventing from death or heavy injury is lister as " WARNING".Even the indication listed as

    " CAUTION" may also cause serious accident. Both of them are related to safety, and

    should be strictly follwed. After installation and start-up commissioning, please handover the manual to the user. The

    manual should be well kept in safe place and close to the unit.

    The installation or the maintenance should be pertormed by an authorized agency. The worng

    operation of this air condition equipment may cause water leakage, electric shock or re.

    Please install the unit on the top of a solid founfation or structure which is strong enough to

    support the unit.

    The installation of this condition equipment should follow local construction codes.

    Use the right cable size, secure the terminal rmly, organize the cables well and make sure notension is added on cables. Cable insulation should not be damaged. The incorrect installation

    may lead to overheat or re.

    When installing or moving the unit, the refrigerant system should be vacuumed and recharged

    with R-410A refrigerant. If any other gas enters the system, it may lead to abnormal high

    pressure which may cause damage or injury.

    Please use the proper manifolds or branches during the system installation. The wrong parts

    may cause refrigerant leakage.

    Keep the drain pipe away from toxic gas vents to prevent possible pollution of indoor

    environment.

    During or after the installation, please check whether there is refrigerant leakage. If any

    leakage, please take any measures for ventilation. The refrigerant may be toxic at some

    concentration levels.

    The unit is not explosion-proof. Please keep it away from ammable gases.

    The drain pipe should be installde per this manual to ensure proper drainage. The pipe should

    be well insulated to avoid condensation. Wrong installation may lead to water leakage.

    Both liquid pipe and the gas pipe should be also well insulated. Not enough insulation may

    lead to system performance deterioration or humidity formation.

    This air condition equipment is not intended to be operated by persons with lack of experience

    and training, unless they have supervision or instruction concerning use of this air condition

    equipment.

    Please keep children away from this air condition equipment.

    Grounding wire should be connected with the grounding bar. The grounding wire can not be

    connected to the gas pipe, water pipe, lightening rod or the telephone grounding wire.

    Improper grounding may cause electric shock.

    The Circuit Breaker should be installed.If not, it may cause electric shocks.

    After installation, the air condition equipment should be powered on and passed the electric

    leakage current lest.

    WARNING

    Attention

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    16/28

    14

    Safety

    Noticesdurin

    gOperation

    Attention

    Do not put any heating apparatus

    under the indoor units. The heat may

    cause distortion of the units.

    Pay attention to the

    ventilation to avoid

    anoxic injury.

    Do not put burning apparatus in the

    place which the unit blows directly.

    There is risk of re or anoxic injury.

    Ensure the installation area does

    not deteriorate with age. If the base

    collapses, the unit may fall and cause

    damage, product failure, personal

    injury or death.

    Do not use the unit for special

    purposes such as preserving foods,

    works of art etc. It is an air conditioner

    for comfort cooling / heating, not a

    precision refrigeration system.

    Use the correctly rated breaker or

    fuse. Improper breaker or fuse may

    lead to re, electric shock, explosion,

    personal injury or death.

    Do not permit water or steam to enter

    the unit and the wired controller.

    There is risk of unit failure, re,

    electric shock, personal injuryor death.

    Turn on the power at least 6 hours

    before operation begins. Starting

    operation immediately after power

    on can result in severe damage to

    internal parts.

    Turn off the power to save energy if

    the unit will be not used for a long

    period. If the unit is not powered off,it will consume power.

    3-minutes protection

    To protect the unit, compressor can be

    actuated with at least 3-minutes delay after

    stopping.

    Close the window to avoid outdoor air

    getting in.Curtains or

    window shutters can

    be put down to avoid

    the sunshine.

    Do not touch the power switch with

    the wet hand to avoid power shock.

    Stop running and switch off the manual

    power switch when cleaning the

    unit.

    During the unit operation, don't switch off

    the manual power switch.

    Do not press the liquid crystal zone of

    controller to prevent damage.

    Do not clean the unit with water spray.

    There is risk of unit failure, re, electric

    shock, personal injury or death.

    Keep ammable gas or combustibles

    away from the unit.There is risk of productfailure, re, personal injury or death.

    The unit is not intended to be operated

    by persons with lack of experience and

    training, unless they have supervision

    or instruction concerning use of this air

    condition equipment.

    Please keep children away from this air

    condition equipment.

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    17/28

    15

    Maintenance

    Repair can only be performed by professional personnel.

    Before touching the connection line, all power supplies should be switched off. Only after

    switching off the power supply can the operator clean the air conditioner as to avoid electricshock or injury.

    When cleaning the air cleaner, make sure to use a stable platform; don't ush the air

    conditioner with water, or the electric shock might be caused.

    Daily Maintenance - 4-Way Cassette type

    2.Dismantle the gauze: press the outer frame of the air inlet grid by the thumb, and draw the

    base angle of gauze by the forenger and pull it out as to make the gauze disengage the

    locks and dismantle the gauze (as shown in Fig. 3).

    Remove and install the lter

    1.Remove the air inlet grid as shown in the gure: press down the two locks on the grid (as

    shown in Fig. 1) to move it close to the nearby grid, gently lift it 45 degree (as shown in Fig. 2),

    and then remove the air inlet grid.

    Installing air cleaner and air inlet grid:

    1. Mounting the gauze: opposite to the ways of

    dismantling the gauze (as shown in Fig. 3 above).

    2. Mounting the air inlet grid: as shown in the right

    figure, nip the locks on the grid as directed by

    arrows, put the side with the lock device into the

    lock port, and then put the side with locks into the

    panel frame. Release the locks to position the grid

    after determining that the grid is abutting upon the

    bottom of the panel frame.

    Attention

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    18/28

    16

    Cleaning the air outlet port and the shell:

    Maintenance

    Daily Maintenance

    Clean the air cleaner & air inlet grid.

    Don't dismantle the air cleaner if not cleaning, or faults might be caused.

    When the air conditioner operates in the environment with too much dust, clean the air

    conditioner more times (generally once every two weeks).

    Attention

    Don't use gasoline, benzene, diluents, polishing powder or liquid insecticide to clean them.

    Do not clean them with hot water of above 50to avoid fading or distorting.

    Wipe them with soft dry cloth.

    Water or neutral dry cleanser is recommended if the dust cannot be removed.

    The Wind Deector can be dismantled to clean (as below).

    Do not wipe the wind deector with water forcibly to avoid falling off.

    Wipe dust with water or dust collector.

    (A) Wipe dust with dust collector. (B) Clean it with soft bush in mild detergent

    if there is too much dust on it

    (C) Throw off the water and airing it in the

    cool dry condition.

    Before Operating Season: 1. Please make the following checkup. If abnormal condition occurs, consult the after-service

    personnel.

    There is no blockage in inlet port and outlet port of outdoor and indoor units.

    The ground line and the wiring are in the proper state

    2. After cleaning, the air cleaner must be mounted.

    3. Switch on to the power.

    After Operating Season:

    1. In sunny days, blowing operation can be performed for half a day to make the inside of

    machine dry.

    2. Electrical power should be cut down to economize electricity, or the machine will stillconsume power.Air cleaner and shell must be mounted after cleaning.

    Cleaning Wind Deector:

    Cleaning Air Cleaner:

    Attention

    Don't rinse the air cleaner with hot water of above 50to avoid fading and distorting.

    Don't put the air cleaner on the re to dry to avoid catching re.

    Maintenance before and after Operating Season

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    19/28

    17

    Maintenance

    Daily Maintenance - 2-Way Cassette type

    Daily Maintenance:

    Wipe them with soft dry cloth.

    Water or neutral dry cleanser is recommended if the dust cannot be removed.

    The Wind Deector can be dismantled to clean (as below).

    Repair can only be performed by professional personnel.

    Before touching the connection line, all power supplies should be switched off. Only afterswitching off the power supply can the operator clean the air conditioner as to avoid electric

    shock or injury.

    When cleaning the air cleaner, make sure to use a stable platform; don't ush the air

    conditioner with water, or the electric shock might be caused.

    Attention

    Don't dismantle the air cleaner if not cleaning, or faults might be caused.

    When the air conditioner operates in the environment with too much dust, clean the airconditioner more times (generally once every two weeks).

    Take up the panel then pull forward, draw out from the bottom slowly. (The panel only can

    move to left or right, please take down it after conformation.)

    Unfasten the thread against the both of ends falling off.

    Pull the air lter downward and take it out.

    Clean the air cleaner & air inlet grid

    Cleaning the air outlet port and the shell:

    Attention

    Don't use gasoline, benzene, diluents, polishing powder or liquid insecticide to clean them. Do not clean them with hot water of above 50to avoid fading or distorting.

    Do not wipe the wind deector with water forcibly to avoid falling off.

    Cleaning Wind Deector:

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    20/28

    18

    Maintenance before and after Operating Season

    Before Operating Season:

    1. Please make the following checkup. If abnormal condition occurs, consult the after-

    service personnel. There is no blockage in inlet port and outlet port of outdoor and indoor units.

    The ground line and the wiring are in the proper state

    2. After cleaning, the air cleaner must be mounted.

    3. Switch on to the power.

    After Operating Season:

    1. In sunny days, blowing operation can be performed for half a day to make the inside of

    machine dry.

    2. Electrical power should be cut down to economize electricity, or the machine will still

    consume power.3. Air cleaner and shell must be mounted after cleaning.

    Maintenance

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    21/28

    19

    Replacement of Air Purifying Filter

    1.Open the lnlet Grille

    Prop up the inlet grille by using a small device named grille-support

    which located in the right side of the indoor unit.

    2.Detach the standard air lter Slide the knob slightly upward to release

    the lter, then withdraw it.

    3.Attach Air Purifying Filter

    Put air purifying lter appliances into the right and left

    lter frames.

    4.Attach the standard air lter

    (Necessary installation)

    ATTENTION:

    The white side of the photocatalyst air purifying lter face outside,and the black side face the

    unit The green side of the bacteria-killing medium air purifying lter face outside,and the white

    side face the unit.

    5.Close the Inlet Grille

    Close the Grille surely

    Note - The lter medium mentioned below is optional:

    The photocatalyst air purifying lter will be solarized in xed time. In normal family, it will

    besolarized every 6 months.

    The bacteria-killing medium air purifying lter will be used for a long time,no need for

    replacement. But in the period of using them ,you should remove the dust frequently by

    using vacuum cleaner or apping them lightly, otherwise, its performance will be affected.

    Please keep the bacteria-killing medium air purifying lter in the cool and dry conditions

    avoid long time directly sunshine when you stop using it,or its ability of sterilization will bereduced.

    MaintenanceDaily Maintenance - High wall type

    Clean the machine.

    Turn off the air conditioner before cleaning.

    Do not touch the machine if the hands are wet.Neither hot water nor solvent should be used in cleaning.

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    22/28

    20

    Maintenance

    Daily Maintenanc

    Clean the air cleaner & air inlet grid.

    Don't dismantle the air cleaner if not cleaning, or faults might be caused.

    When the air conditioner operates in the environment with too much dust, clean the air

    conditioner more times (generally once every two weeks).

    Cleaning the air outlet port and the shell:

    Attention Don't use gasoline, benzene, diluents, polishing powder or liquid insecticide to clean them.

    Do not clean them with hot water of above50to avoid fading or distorting.

    Wipe them with soft dry cloth.

    Water or neutral dry cleanser is recommended if the dust cannot be removed.

    The Wind Deector can be dismantled to clean (as below).

    Do not wipe the wind deector with water forcibly to avoid falling off.

    Cleaning Wind Deector:

    Wipe dust with water or dust collector.

    (A) Wipe dust with dust collector. (B) Clean it with soft bush in mild detergent

    if there is too much dust on it

    (C) Throw off the water and airing it in the

    cool dry condition.

    Cleaning Air Cleaner:

    Attention

    Don't rinse the air cleaner with hot water of above 50to avoid fading and distorting.

    Don't put the air cleaner on the re to dry to avoid catching re.

    Before Operating Season:1. Please make the following checkup. If abnormal condition occurs, consult the after-service

    personnel.

    There is no blockage in inlet port and outlet port of outdoor and indoor units.

    The ground line and the wiring are in the proper state

    2. After cleaning, the air cleaner must be mounted.

    3. Switch on to the power.

    After Operating Season:

    1. In sunny days, blowing operation can be performed for half a day to make the inside of

    machine dry.

    2. Electrical power should be cut down to economize electricity, or the machine will still

    consume power.Air cleaner and shell must be mounted after cleaning.

    Maintenance before and after Operating Season

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    23/28

    21

    Maintenance

    Daily Maintenance - Floor ceiling type

    Only when the air cleaner is switched off and disconnected to the power supply can it be

    cleaned, or electric shock and injury may appear.

    Cleaning the air outlet port and the shell:

    Attention Don't use gasoline, benzene, diluents, polishing powder or liquid insecticide to clean them.

    Do not clean them with hot water of above50to avoid fading or distorting.

    Wipe them with soft dry cloth.

    Water or neutral dry cleanser is recommended if the dust cannot be removed.

    The Wind Deector can be dismantled to clean (as below).

    Do not wipe the wind deector with water forcibly to avoid falling off.

    Cleaning Wind Deector:

    Pull the air screen forward to the front

    side of the unit to remove it. Clean up air screens according to their

    different types. For more information,

    please make contact with

    after service staff.

    Wipe dust with water or dust collector.

    (A) Wipe dust with dust collector.

    (B) Clean it with soft bush in mild detergent

    if there is too much dust on it

    (C)Throw off the water and airing it

    in the cool dry condition.

    Cleaning Air Cleaner:

    Attention

    Don't rinse the air cleaner with hot water of above 50to avoid fading and distorting.

    Don't put the air cleaner on the re to dry to avoid catching re.

    Before Operating Season:

    1. Please make the following checkup. If abnormal condition occurs, consult the after-

    service personnel.

    There is no blockage in inlet port and outlet port of outdoor and indoor units.

    The ground line and the wiring are in the proper state

    2. After cleaning, the air cleaner must be mounted.

    3. Switch on to the power.

    After Operating Season:

    1. In sunny days, blowing operation can be performed for half a day to make the inside of

    machine dry.

    2. Electrical power should be cut down to economize electricity, or the machine will stillconsume power.Air cleaner and shell must be mounted after cleaning.

    Maintenance before and after Operating Season

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    24/28

    22

    Maintenance

    Cleaning the air outlet port and the shell:

    Attention

    Don't use gasoline, benzene, diluents, polishing powder or liquid insecticide to clean them.

    Do not clean them with hot water of above50to avoid fading or distorting.

    Wipe them with soft dry cloth.

    Water or neutral dry cleanser is recommended if the dust cannot be removed.

    The Wind Deector can be dismantled to clean (as below).

    Do not wipe the wind deector with water forcibly to avoid falling off.

    Cleaning Wind Deector:

    Wipe dust with water or dust collector.

    (A) Wipe dust with dust collector.(B) Clean it with soft bush in mild detergent

    if there is too much dust on it

    (C)Throw off the water and airing it

    in the cool dry condition.

    Cleaning Air Cleaner:

    Attention

    Don't rinse the air cleaner with hot water of above 50to avoid fading and distorting.

    Don't put the air cleaner on the re to dry to avoid catching re.

    Before Operating Season:

    1. Please make the following checkup. If abnormal condition occurs, consult the after-service

    personnel.

    There is no blockage in inlet port and outlet port of outdoor and indoor units.

    The ground line and the wiring are in the proper state

    2. After cleaning, the air cleaner must be mounted.

    3. Switch on to the power.

    After Operating Season:

    1. In sunny days, blowing operation can be performed for half a day to make the inside of

    machine dry.

    2. Electrical power should be cut down to economize electricity, or the machine will stillconsume power.Air cleaner and shell must be mounted after cleaning.

    Maintenance before and after Operating Season

    Daily Maintenance - Duct type

    Clean the air cleaner & air inlet grid.

    Don't dismantle the air cleaner if not cleaning, or faults might be caused.

    When the air conditioner operates in the environment with too much dust, clean the air

    conditioner more times (generally once every two weeks).

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    25/28

    23

    Daily Maintenance - Console type

    Cleaning of the unit

    Maintenance

    Take off the air inlet grill Do not touch with wet handDo not clean with hot water

    or solvent

    Take off the air inlet grill

    First switch off the power supply,take off the screw cap,loosen the screw with cross screwdriver

    Clean the lter

    Use water or vacuum cleaner to remove dust.If it is too dirt, clean with detergent or neutral

    soap water. Rinsing with fresh water, dry the

    lter and re-assemble.

    Caution:

    Do not wash f i l ter in hot water above

    40 ,which will damage the lter.

    Do carefully wipe the lter.

    Clean the indoor(outdoor) unit

    Clean with warm cloth or neutral

    detergent,then wipe away moisture with

    dry cloth. Do not use too hot water(above

    40 ),which will cause discoloration or

    deformation. Do not use pesticide or other

    chemical detergents.

    Maintenance at the end of application season

    On a fine day, unit shall be started and operate in FAN mode for

    about half a day until the inside of the unit becomes thoroughly dry.

    Turn off the unit operation switch and power on/off.

    Otherwise,there will be some electricity consumption

    even the unit is in stop status.

    Clean the lter and indoor,cover the units well.

    Maintenance before beginning of application season

    Check there are no obstacles in the air inlet and outlet to avoid impairing of working efciency.

    Please do attach the air filter to ensure the electrostatic filters not soiled.Otherwise,dirt will

    come into and damage the unit or bring failures.

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    26/28

    24

    Fault CheckupPlease check the following when consigning repair service:

    Symptoms Reasons

    Allt

    hesearenotproblems

    Water ow sound

    Water ow sound can be heard when starting operation,during operation or immediately after stopping operation.

    When it starts to work for 2-3 minutes, the sound maybecome louder, which is the owing sound of refrigerant orthe draining sound of condensed water.

    Cracking sound

    During operation, the air conditioner may make thecracking sound, which is caused from the temperaturechanges or the slight dilation of heat exchanger.

    Terrible smell in outlet air

    Flashing operating

    indicator

    When switching it on again after power failure, turn on themanual power switch and the operating indicator ashes.

    Awaiting indication

    It displays the awaiting indication as it fails to performrefrigerating operation while other indoor units arein heating operation. When the operator set it to therefrigerating or heating mode and the operation is oppositeto the setting, it displays the awaiting indication.

    Sound in

    shutdown indoor

    unit or white

    steam or cold air

    To prevent oil and refrigerant from blocking the shutdownindoor units, refrigerant ows in the short time and makethe sounds of refrigerant owing. Otherwise, when otherindoor units performs heating operation, white steam mayoccur; during refrigerating operation, cold air may appear.

    When the conditioner is powered on, the sound is madedue to the resetting of the expansion valve.

    Check if it is in the state of Timer-ON and Timer-OFF.

    Failure to work Check if there is a power failure.Check if the manual power switch is turned off.Check if the supply fuse and breaker are disconnected.Check if the protective unit is working.Check if refrigerating and heating functions are selectedsimultaneously with the awaiting indication on line control.

    Bad cooling & heating

    effects

    Check if air intake port and air outlet port of outdoor units areblocked.Check if the door and windows are open.Check if the ltering screen of air cleaner is blocked withsludge or dust.Check if the setting of wind quantity is at low wind.Check if the setting of operation is at the Fan Operation state.Check if the temperature setting is proper.

    During operation, the air conditioner may make the crackingsound, which is caused from the temperature changes orthe slight dilation of heat exchanger.

    Under the following circumstances, immediately stop the operation, disconnect the manual

    supply switch and contact the after-service personnel.

    When buttons are inexible actuated;

    When there are foreign objects and water in the refrigerator; When it cannot still be operated after removing the operation of protective unit;

    When other abnormal conditions occur.

    Pleasemake

    anothercheck.

    Clicking sound whenswitching the air conditionon

    Start or stop workingautomatically

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    27/28

  • 8/9/2019 0150511194-A-130708 All Indoor User Manual

    28/28

    Johnson Controls reserve the right to change product features without prior notice