![Page 1: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/1.jpg)
Your reliable partner in UPS
for information technologyWhenever wherever wattever
Industry - IT - Telecoms - Transportation - Services
A company of
![Page 2: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/2.jpg)
Rely on Saft Power Systems for end-to-end solutions worldwide. Bringing
together three internationally-renowned brands (AEG Power Supply Systems,
Harmer+Simmons, Saft Power Systems), proven through decades of experience,
Saft Power Systems offers a unique, comprehensive range of power systems
and solutions.
Commitment to excellence From world class systems to turnkey technology and high reliability, we deliver competitive, cost-effective,customer-driven solutions. Committed to excellence, our 250 engineers and project managers offer a wide range of R&D and application engineering skillsand have registered more than 70 active patents in power conversion.
You deserve the best power solutions for your equipmentand infrastructure, coupled with comprehensive expertservice. To that end the Saft Power Systems team hasmore than 150 experts, ready to provide support andtraining worldwide.
Combined AC and DC power solutionsSaft Power Systems designs, engineers and installscombined solutions for a broad variety of customers to help keep their businesses running smoothly.
Modular telecom power systems Leading-edge technology combined with a unique rangeof versatile system elements yield proven benefits for fixed line and wireless operators, ISPs, CATV operators and equipment manufacturers.
Industrial chargersand DC power systemsReady to meet the toughest challenges in oil and gas,utilities, and transport applications, our robust rangefeatures built-in communications for cost-effectivenetwork integration and remote monitoring.
Traction chargersCustomization, innovation and partnership with majorOEMs help Saft Power Systems serve the motive powerindustry.
2
Your efficient power protection
AEG Power Supply Systems is fully ISO accredited, with ISO
certified suppliers and manufacturing locations worldwide.
![Page 3: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/3.jpg)
AC/DC and DC/DC custom and standard convertersSaft Power Systems has custom and standard powerconversion solutions for single, distributed (centralised)or point of load (localised) configurations.
Power controllers and Soft starters Precision-engineered to switch, control and regulate, the AEG Power Supply Systems Tyro-Family is made for heavy industrial applications in ovens, automotive,glass and chemical industry applications, steel production, conveyor lines, cooling equipment, and pumps.
Railway power supply systems Our groundbreaking high-density on-board switch modepower supply systems meet railway industry needs.
UPS systems AEG-branded UPS solutions provide up to 99.9999%availability for mission-critical equipment in data centers,co-location centers, local networks and industry.
against power failure starts here3
WhereverFor Home Office and small business
• Home computing: PC, MAC, storage,
peripherals (scanner, printer, etc)
• Multimedia applications
• Telecommunication systems
Data Centres
• Servers: Web, Storage, Backup
• Networks: hubs, switches
• Gateways
Enterprise Systems
• Engineering, cabling, installation, operation
• on – site service
• you need power supply safety, we can
provide the total solution.
WheneverWe support you long-term with first-class
service throughout the product life cycle.
WatteverWith solutions available to satisfy home
office, small business, data centres or
enterprise networks requirements all
customers and partners can rely on AEG
Power Supply Systems as a single source of
complete UPS solutions.
Milestones2005 Saft Power Systems group, 1,437 employees worldwide
1998 Acquisition of AEG SVS Power Supply Systems GmbH (Germany).
1995 Acquisition of Harmer+Simmons Ltd (United Kingdom)
1947 Establishment of Saft Power Systems when Saft (founded in 1917) leverages its recognized expertise in battery technology to introduce a range of innovative battery chargers and power systems.
![Page 4: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/4.jpg)
4
The right UPS for any applica
PROTECT PROTECT A. PROTECT B. PROTECT C. / C.RHOME.
PAGE 6 8 10 12
POWER (kVA) 0.6 0.5-1.4 0.7-3 1-10
TECHNOLOGY to IEC 62040-3 VFD (Offline) VI (Line - Interactive) VI (Line - Interactive) VFI (Double-conversion)
INPUT/OUTPUT 1ph~/1ph~ 1ph~/1ph~ 1ph~/1ph~ 1ph~/1ph~
PARALLEL OPERATION no no no yes
AUTONOMY TIME (MIN) 3 3 5-75 5-60
Also available with reinforced charging rec
Product Overview
600 VA.Protection for satellite TV,phones, faxes or modems as well as USB and serial connections for communicationwith your PC.
500 up to 1400 VA.Security for PCs,workstations and telephone systems.
750 up to 3000 VA.Uninterruptible securitywith sine wave output for server and network components.
1 up to 10 kVA.High performance UPS-system for IT and electronic data processingin medium-sized companies.
COMPACT UPS
HOME OFF
AEG Power Supply Systems supplies customer-focused solutions for protectionagainst power fluctuations and failures, thus preventing data loss and expensive downtime.
Plug and Play FacilityWe have over 30 Uninterruptible Power Supply models in our Compact UPSproduct range including tower, rack mountable, and hot swappable modularunits that all provide a “Plug and Play” facility for UPS systems up to 24 kVA.
![Page 5: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/5.jpg)
tion5
PROTECT 1. PROTECT 1.M PROTECT 2. PROTECT 3. PROTECT 4. PROTECT 5.
14 16 22 22 23 23
10-20 4-24 10-40 10-120 160-1000 10-120
VFI (Double-conversion) VFI (Double-conversion) VFI (Double-conversion) VFI (Double-conversion) VFI (Double-conversion) VFI (Double-conversion)
3ph~/1ph~ 1ph~/1ph~ or 3ph~/1ph~ 3ph~/3ph~ 3ph~/1ph~ and 3ph~/3ph~ 3ph~/3ph~ 3ph~/1ph~ and 3ph~/3ph~
yes yes yes yes yes yes
9-80 10-90 10-90 5-xxx (extern) 5-xxx (extern) 5-xxx (extern)
ctifier for transitionary periods lasting hours
10 up to 20 kVA.Online UPS Systems for networks and computercenters 10 - 20 kVA.
4 up to 24 kVA.Modular high performanceUPS system for IT environments.
10 up to 40 kVA.For building control,telecommunication,data processing centres,webhosting.
10 up to 120 kVA.For data processing centres,banks and insurance companies, process control.
160 up to 1000 kVA.Highest availability for data processing centres,building control, industry.
10 up to 120 kVA.For power stations,life-saving facilities,flight security, industry.
MEDIUM HIGH POWER UPS
ICE IT DATA CENTER, INDUSTRIY
Solutions to satisfy each market and each applicationWith solutions available to satisfy home office, smallbusiness, data centres or enterprise networks, all customers and partners can rely on AEG Power SupplySystems as a single source of complete UPS solutions.
Experience and Consistency AEG Power Supply Systems has been providing reliablepower solutions for mission critical applications for over60 years and will continue to set industry standards forthe future.
Product SupportThe performance, quality and value of UPS Systemssupplied by AEG Power Supply Systems is continuallysupported by our highly specialised technical team.
1972 Development of first 5/25 switching power supply
1969 Development of power controller
1965 Development of three-phase thyristor a.c. converter
1961 Development of single-phase thyristor a.c. converter
1951 Direct current supply for “Deutsche Bundespost”
1945 Foundation of AEG factory in Warstein-Belecke with 25 employees
The History of AEG in Warstein2005 Ripplewood Holding acquires the Saft Power Systems Group
1998 SAFT takes over AEG SVS Power Supply Systems GmbH in Belecke
1995 First UPS in the world with 100% digital control: PROTECT 3
1988 Development of UPS with IBGT transistors (one- and three-phase)
1985 First Profitec S rectifier with microprocessor
![Page 6: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/6.jpg)
6
Protection against data loss through uninterrupted powerprotection with a size from 600 VA, the PROTECT HOME.offers professional and economical protection againstpower outages, surges and sags.
Practical ProtectionEspecially for multi-media applications, the PROTECTHOME. offers data line protection for telephones, faxesand modems as well as surge protection for satellite TV.Connections are made directly to the UPS outlets.
PROTECT HOME. proves itself in critical situations with its high availability due to a sturdy overload and excess voltage protection. With user friendly batterydesign, PROTECT HOME. offers a truly economicalsolution.
Simple OperationThe “One-Board-Design” as well as LED notificationprovides clear information about the unit’s most importantoperating conditions. And an acoustic alarm makesoperation even simpler.
USB and RS232 Connectionsfor Simple ControlThe PROTECT HOME. is quickly connected to a USB or RS232 interface. The included special AEG"CompuWatch" software enables you to control the mostimportant functions while providing for automaticshutdown during extended power outages.
Protection against Power Outagesand dangerous Power Spikes• Microprocessor controlled, robust UPS
technology for power outages and dangerouspower spikes
• Complete CompuWatch “plug-and-play“ Software
• USB and RS232 interface for overview andcontrol from a PC
• Overvoltage protection for satellite TV’s as wellas dataline protection for telephones, faxesand modems
• User friendly battery design
• 24 month warranty with pre-exchange service
PROTECT HOME.
Uninterrupted Protection
for PCs and Multimedia
Excellent Provisions: all around protectionfor satellite TV, phones, Faxes or modems as well as USBand serial connections for communication with your PC
Surge protection TV portSAT-TV / SAT-Receiver
Surge protection phone,fax, modem
Input breakerMains line
Status LED indicator
USB
RS232
![Page 7: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/7.jpg)
7
CLASSIFICATION VFD SY 322 to IEC 62040-3 PROTECT HOME.Type power 600 VA / 300 W
UPS-InputInput voltage 230 Vac
Frequency 50 Hz
Current consumption (max.) 3.0 A
UPS-OutputRated output voltage 230 Vac
Rated output voltage in battery mode ± 10%
Frequency in battery mode 50 Hz ± 1 Hz
Output current 2.6 A
Transfer time at mains outage 2 - 6 ms (typical)
Voltage waveform Modified sinewave
Overload / Short Circuit Protection yes
BATTERYType Sealed, maintenance free, A-Brand
Autonomy time for 1 PC with 17'' TFT ~ 10 min.
Overload / deep discharge protection yes
Recharge time (to 90 % of rated capacity) 8 h
COMMUNICATIONInterfaces USB and RS232 for status and measurement levels
Shutdown software (on CD) Included for all typical operating systems (e.g. Windows, Linux, Mac)
Failure indicators (acoustical/optical) Mains failure, overload, battery low, fault
GENERAL DATAAudible noise (1 m distance) < 40 dB(A)
Operating temperature range 0 - 40°C
Humidity 20 - 90%
EMC immunity Surge protection RJ11 (Phone, Fax, Modem), F-Connector for Satellite TV
Operation altitude Up to 1000m at nominal load
Outlets 4 Sockets (German version)
(3 x with UPS-protection / 1 x with surge protection)
Equipment colour Black line
Size appr.W x H x D 125 mm x 85 mm x 300 mm
Weight appr. 3.5 kg
Shipment Mains-cord, USB and RS232 communication cable,
management software „CompuWatch“ (CD), user-manual
Certification CE
Specification
![Page 8: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/8.jpg)
8
PROTECT A.
Uninterruptible security
for PCs, workstations
and telephone systems
Software CompuWatch
Rear panel A. 1000 / A. 1400
Includes a CD with CompuWatchshutdown and reboot software,compatible with most major operatingsystems, such as Windows, Mac OSand Linux.
Protection against power failureand voltage fluctuations• Modern VI (line-interactive) technology
against power failure and dangerous excessvoltage
• Automatic voltage pre-regulation againstvoltage fluctuation (AVR)
• Double network filter against power surges
• Simple installation with the cables suppliedand optimal operation
• Hot-swappable battery design
• USB connection and RS232 interface
• Data line protection for phone, fax and modem
• 24 month warranty with pre-exchangeservice
RS232
UPS-output
UPS-input
Surge protection phone,fax, modem or network
USB
Input breaker
![Page 9: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/9.jpg)
9
Specification
CLASSIFICATION VI SY 322 to IEC 62040-3 A. 500 A. 700 A. 1000 A. 1400Type power 500 VA 700 VA 1000 VA 1400 VA
300 W 420 W 600 W 840 W
UPS-InputInput voltage 220 Vac / 230 Vac / 240 Vac
Input voltage range without battery mode 150 - 280 Vac 170 - 280 Vac
Frequency (auto selection) 50 Hz / 60 Hz ± 5 Hz
Current consumption (max.) 3.3 A 4.6 A 6.6 A 9.2 A
UPS-OutputRated output voltage /AVR-technology 220 Vac / 230 Vac / 240 Vac
Rated output voltage in battery mode ± 10%
Frequency in battery mode 50 Hz / 60 Hz ± 1 Hz
Output current (at 230 Vac) 2.2 A 3.0 A 4.3 A 6.1 A
Transfer time at mains outage 2-6 ms (typical)
Voltage waveform Modified sinewave
Overload protection yes yes yes yes
BATTERYType Sealed, maintenance free, hot swappable, A-Brand
Autonomy time for 1 PC with 17'' TFT ~ 15 min ~ 20 min ~ 30 min ~ 40 min
Overload / deep discharge protection yes yes yes yes
Recharge time (to 90 % of rated capacity) 8 h
COMMUNICATIONInterfaces USB and RS232 for status and measurement levels
Shutdown software (on CD) Included for all typical operating systems (e.g. Windows, Linux, Mac)
Failure indicators (acoustical / optical) Mains failure, overload, battery discharge, battery replace, failure
LED bar graph for
UPS load / battery capacity
GENERAL DATAAudible noise (1 m distance) < 40 dB (A) < 45 dB (A)
Operating temperature range 0° - 40°C
Humidity 0 - 90% (non condensing)
Number of outlets 3 x IEC 320 4 x IEC 320
Equipment colour Black line
Size approse W x H x D (mm) 100 x 140 x 330 140 x 180 x 370
Weight approse (kg) 6 kg 6.5 kg 14 kg 14.5 kg
Shipment Mains-cord, 2 load-cords,
USB and RS232 communication cable,
management software “CompuWatch” (CD), user-manual
Certification CE
![Page 10: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/10.jpg)
10
PROTECT B.
Uninterruptible security
with sine wave output
for server and network
components
Set-up options
PROTECT B. 1500 & B. 2000 • rear panel
PROTECT B. operating panel
PROTECT B. 3000 • front and rear panel
AC output distribution box
Battery level indicator Load level indicatorLine mode
Battery modeOperating mode
Power switch
Error LED indicator
Output voltage mode
ConfigureEnter
UPS-input
RS232
Emergency shutdown / EPO
Communication slot for expansion cards
UPS-outputs Surge protection data interface, phone, fax,modem
UPS-input
Height= 2 U
USB Connection for externalbattery module Output breaker
UPS-output module
Emergency shutdown / EPOUSB
RS232
High level flexibility,intelligent functionality• Modern VI (line-interactive)
protection technology with sine wave output voltage
• Compact construction/flexibleuse due to combinationtower/rack design
• Robust design: overloadcapability and short circuitprotection
• Intelligent monitoring systemwith USB and RS232 interfaces
• User-friendly battery design in hot-swappable version (from 1500 VA)
• Operator friendly display foroptimal readability/configuration
• Over voltage protection (RJ11 / RJ45) for fax, modemand network
• Expansion slot for extensioncards, e.g. SNMP (from 1500 VA)
UPS test/ silence
communication slot for optional expansion cards
Connection for external battery moduleOverload protection data interface,
phone, modem or network
![Page 11: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/11.jpg)
11
CLASSIFICATION VI SS 211 to IEC 62040-3 B. 750 B. 1000 B. 1500 B. 2000 B. 3000Type power 750 VA 1,000 VA 1,500 VA 2,000 VA 3,000 VA
500 W 700 W 1,050 W 1,340 W 2,100 W
UPS-InputInput voltage 220 Vac / 230 Vac / 240 Vac
Input voltage range without battery mode 161 / 184 - 276 Vac (adjustable)
Frequency (auto selection) 50 Hz / 60 Hz ± 5 Hz (> 40 Hz generator operation)
Current consumption (max.) 5 A 8 A 10 A 10 A 16 A
UPS-OutputRated output voltage / AVR-technology 220 Vac / 230 Vac / 240 Vac
Rated output voltage in battery mode ± 5%
Frequency in battery mode 50 Hz / 60 Hz ± 0.1 Hz
Output current (at 230 Vac) 3.2 A 4.3 A 6.5 A 8.7 A 13.0 A
Transfer time at mains outage 2-4 ms (typical), 6 ms max.
Voltage waveform Sinusoidal
Overload response at mains operation 110% for 3 min / 150% for 200 ms
Overheat and short-circuit protection yes yes yes yes yes
BATTERYType Sealed, maintenance free; hot swappable (from 1500 VA)
Rated voltage 24 Vdc 48 Vdc 96 Vdc
Autonomy time at rated load 5 min 5 min 5 min 5 min 5 min
- - Runtime extension with scalable ext. battery packs
Overload / deep discharge protection yes yes yes yes yes
Recharge time (to 90% of rated capacity) 3 h 3 h 3 h 3 h 3 h
COMMUNICATIONInterfaces USB and RS232 for status and measurement levels
Slot for enhanced communications (SNMP) EPO port for emergency power off
Configuration panel for voltage preselection and setting of operating mode
Shutdown software (on CD) Included for all typical operating systems (e.g. Windows, Linux, Mac)
Failure indicators (acoustical / optical) Separate LED bar graphs for UPS load and battery capacity,
indicators for mains failure, overload, battery discharge,
battery replace, failure
GENERAL DATA B. 750 B. 1000 B. 1500 B. 2000 B. 3000
Audible noise (1 m distance) < 45 dB(A)
Operating temperature range 0° - 35°C
EMC stability EN 61000-4 Teile 2 to 5
EMC emitted interference EN 61000-6-3 Klasse A
Data lines protection RJ11 (Telefon, Fax, Modem) / RJ45 (Ethernet 10 Mbit/s / 100 Mbit/s)
Humidity 0 - 90% (non condensing)
Installation height Up to 1000 m, at nominal load
Number of outlets 4 x IEC 320-10A 6 x IEC 320-10A 8 x IEC 320-10A
Removable module 1 x IEC 320-16A
Equipment colour Black line
Size appr.W x H x D (mm) 235 x 88 x 383 (2 x 217) x 88 x 414 438 x 88 x 582
Rack- / Tower Design / optional 19'' kit
Weight appr. (kg) 8.5 kg 9.5 kg 6.5 kg + 12 kg 31.5 kg
Shipment Mains-cord, 2 load-cords IEC 320-10A,
USB and RS232 communication cable, management software
“CompuWatch” (CD), user-manual
Certification CE
Specification
![Page 12: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/12.jpg)
12
PROTECT C.
High performance
UPS system for IT
and electronic data
processing in medium-sized
companies
UPS PROTECT C.autonomy time (full load / half load) [ min. ]
1000VA 2000VA 3000VA 6000VA 10000VA
integrated battery 6/20 10/30 5/16 8/25 5/15
1 additional battery 37/95 50/125 30/80 25/70 15/40
2 additional batteries 75/165 90/190 60/125 45/105 25/65
3 additional batteries - - - 60/135 33/80
PROTECT C. 10kVA rear panel
PROTECT C. Autonomy time
Terminal
Manual bypass switch
Input breaker
Intelligent functions, high level protection• VFI-topology (double-conversion): Protects
against all mains power disturbances
• Microprocessor control / DSP guaranteeshighest availability
• Sine wave shaped current consumption(High frequency PWM with IGBTs)
• Automatic bypass, additional integratedservice bypass at 6 and 10 kVA (tower)
• Redundancy due to N+X configuration at 6 and 10 kVA; increase in power output/ safety and availability
• Expansion slot for extension cards SNMP / volt free contacts
PROTECT C. 6000 in parallel operation
Distribution field for parallel operation
Single phase input
External battery
Parallel port
Communication slot forexpansion cards SNMP,AS 400
RS232
Fan
UPS PROTECT C.Rautonomy time (full load / half load) [ min. ]
1000VA 2000VA 3000VA 6000VA
integrated battery 6/20 - - -
1 additional battery 37/95 10/30 5/16 8/25
2 additional batteries 75/165 30/80 17/48 25/70
3 additional batteries - 50/125 30/80 45/105
4 additional batteries - 75/165 48/110 60/135
5 additional batteries - 90/90 60/125 -
![Page 13: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/13.jpg)
13
CLASSIFICATION VFI SS 211 to IEC 62040-3 C. 1000 C. 2000 C. 3000CLASSIFICATION VFI SS 111 to IEC 62040-3 C. 6000 C. 10000Type power 1000 VA 2000 VA 3000 VA 6000 VA 10000 VA
700 W 1400 W 2100 W 4200 W 7000 W
Parallel operations (n+x)
UPS-InputInput voltage 220 Vac / 230 Vac / 240 Vac
Input voltage range without battery mode 160 – 300 Vac 176 – 276 Vac
Frequency (Automatic recognition) 50 Hz / 60 Hz ± 4 Hz
Power factor (System perturbation factor) λ ≥ 0.96 λ ≥ 0.98
Current consumption (max.) 7 A 10 A 16 A 31 A 50 A
UPS-OutputRated output voltage 220 Vac / 230 Vac / 240 Vac ± 2% ± 1%
Frequency in battery mode 50 Hz / 60 Hz ± 0.2% ± 0.1%
Output current (at 230 Vac) 4.3 A 8.7 A 13 A 26 A 43.4 A
Transfer time at mains outage 0 ms (zero transfer)
Voltage waveform Sinusoidal, THD < 4%
Overload response (online mode) 140% 30 s / 150% 300 ms 125% 10 min / 130% 1 s
subsequent, transfer to bypass mode
Crest factor 3
Short-circuit response Short-circuit-proof
BATTERYType Sealed, maintenance free, A-Brand
Rated voltage 36 Vdc 96 Vdc 240 Vdc
Autonomy time (full load / half load) 6 / 20 min. 10 / 30 min. 5 / 16 min. 8 / 25 min. 5 / 15 min.
Runtime extension with scalable external battery packs
Overload / deep discharge protection yes yes yes yes yes
Recharge time (to 90 % of rated capacity) 5 h 5 h 5 h 5 h 7 h
COMMUNICATIONInterfaces RS232 for UPS configuration,
status and measurement levels
Shutdown software (on CD) Included for all typical operating systems
(e.g. Windows, Mac, Linux, Unix, Sun, etc)
Failure indicators (acoustical / optical) LED bar graph for UPS load and battery capacity,
indicators for mains failure, overload, battery discharge,
battery replace, failure
GENERAL DATA C. 1000 C. 2000 C. 3000 C. 6000 C. 10000
Efficiency total (at full load) ≥ 85% ≥ 88% > 88%
Audible noise (1 m distance) < 45 dB (A) < 50 dB (A) < 55 dB (A)
Operating temperature range 0° – 40°C
EMC stability EN 61000-4 Teile 2 to 5
EMC emitted interference EN 61000-6-3 Classe B EN 61000-6-3 > 25A
Data lines protection RJ11 (Phone, Fax, Modem) / RJ45 (Ethernet 10 Mbit/s / 100 Mbit/s)
Humidity 0 - 90% (non condensing)
Installation height Up to 1000 m, at nominal load
Number of outlets Tower 4 x IEC 320-10A 6 x IEC 320-10A 4 x IEC 320-10A Terminal block
+ 1 x IEC 320-16A permanent connection)
Rack 4 x IEC 320-10A 1 x IEC 320-10A Terminal block
+ 1 x IEC 320-16 A permanent connection)
Equipment colour Black line
Size appr. W x H x D (mm) Tower 145 x 220 x 400 192 x 340 x 460 260 x 717 x 570
Battery integrated integrated integrated
Rack 482.6 x 88 x 450 482.6 x 88 x 450 482.6 x 132 x 600 -
Battery integrated 482.6 x 88 x 450 482.6 x 132 x 600 -
Weight appr. (kg) Tower 15 kg 34 kg 35 kg 90 kg 93 kg
Rack 16.5 kg 10 kg + 29 kg 11 kg + 29 kg 18 kg + 64 kg -
Shipment Mains-Cord, 3 load-cords (type C.1000, C.2000, C.3000), communication cable,
management software “CompuWatch” (CD), user-manual
Certification CE
Specification
![Page 14: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/14.jpg)
14
• True online UPS including static bypass(double- / duration conversion VFI -technology)
• Power range 10,15, 20 kVA, space-savingdesign
• n + x technology (DSP controlled)to increase output power and/ or for redundancy
• State-of-the-art: High reliability and efficiency by digital signalprocessing (DSP), CAN bus system, and high frequency IGBT technology.
• Uses battery systems with up to three yearsbattery service life, according to EUROBAT
• Communication via RS232, expansion slotfor e.g. SNMP and AS400
PROTECT 1.
Online UPS Systems
for networks and computer
centers 10 - 20 kVA
Views PROTECT 1.200
Combined autonomy time ( full load / half load ) [ min. ]
battery modules PROTECT 1.100 PROTECT 1.150 PROTECT 1.200
1 x PROTECT 1.100 BP 15/35 - -
2 x PROTECT 1.100 BP 35/75 - -
3 x PROTECT 1.100 BP 55/120 - -
1 x PROTECT 1. BP 28 30/75 16/45 9/30
2 x PROTECT 1. BP 28 75/180 45/110 30/75
1 x PROTECT 1. BP 42 50/115 26/75 15/50
2 x PROTECT 1. BP 42 120/250 75/170 50/115
3 x PROTECT 1. BP 42 180/360 120/250 80/180
PROTECT 1. Autonomy time
N e w i n 2 0 0 7
Manual bypass switch
Parallel port
Terminal
Input breaker
RS232
Fan
Communication slot for expansion cards SNMP, AS 400
![Page 15: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/15.jpg)
15
CLASSIFICATION VFI SS acc. 111 to IEC 62040-3 PROTECT 1.100 PROTECT 1.150 PROTECT 1.200n + x Technologie skalierbar (Parallelschaltfähigkeit von bis zu 3 Einheiten)
Type power 10 kVA 15 kVA 20 kVA
7 kW 10.5 kW 14 kW
UPS-InputVoltage 400 / 230 Vac ( 3 / N / PE~ )
Voltage range without battery mode 304 - 478 Vac ( Bypass: 176 - 261 Vac )
Frequency (automatic selection) 50 Hz / 60 Hz ± 4Hz
Power factor λ > 0.95
Current consumption maximum 13 A / 46 A (Bypass) 19 A / 68 A (Bypass) 25 A / 91 A (Bypass)
UPS-OutputVoltage 220 Vac / 230 Vac / 240 Vac ± 1%
Frequency in battery mode 50 Hz ± 0.5 Hz (synchronisation range 1Hz/s)
Current (at 230 Vac) 43.4 A 65.2 A 86.9 A
Transfer time at mains failure 0 ms (zero transfer)
Waveform sinusoidal, THD ≤ 2% (linear load) THD ≤ 6% (load 100% non-linear load)
Überlastverhalten 130% for 10 min / >130% for 1s
automatic transfer to bypassmode (zero transfer)
Crest Ratio 3
Short Circuit Reaction short circuit proof
BATTERYNominal voltage 240 Vdc
Load characteristic IU - characteristic curve (charging voltage 274 Vdc/ charging current max. 4,2 Adc)
Autonomy time runtime extension with scalable external battery packs
Overload/ deep discharge protection yes
COMMUNICATIONInterface RS232 with status message and measured values
Communication-Slot (for volt free contacts / SNMP)
Shutdown-Software (als CD) included for common Operating Systems (Windows, Linux, Mac)
single seat licence CompuWatch with a 5 fold network licence
Alarms (audible/ optical) LED bar graph showing UPS load, battery capacity, several measured values,
Indicators for mains failure, overload, battery low, battery replacement, fault
GENERAL DATAPower Factor AC-AC/ DC-AC (at full load) > 88%
Noise level (1m distance) < 55 dB (A) < 60 dB (A)
Operation temperature 0 - 40°C
Installation height up to 1000 m above sea level at nominal load
EMC stability EN 61000-4-2 Level 4 / EN 61000-4-3 Level 3 / EN 61000-4-4 Level 4 / EN 61000-4-5 Level 4
EMC emitted interference EC 62040-2
Humidity 0 - 95% (non condensing)
Equipment colour black line
Size appr. W x H x D (mm) 260 x 720 x 570
Weight appr. (kg) 39 kg 55 kg
Certification CE
Specification
![Page 16: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/16.jpg)
16
PROTECT 1.M
Modular high performance
UPS system
for IT-environments
PROTECT 1.M provides RS232, RS485 connectorsand an expansion slot e.g. for AS400 and SNMP.
• Higher reliability• Easy to increaseoverall capacity• Modules hot-swappablewithout any interruption
Advantagesof n+x technology
“Dual monitoring” interface
NUMBER OF UPS MODULESLoad 1 module 2 modules 3 modules 4 modules 5 modules 6 modules4 kVA no n+1 n+2 n+3 n+4 n+5
redundancy (4kVA) (8kVA) (12kVA) (16kVA) (20kVA)
8 kVA no n+1 n+2 n+3 n+4redundancy (4kVA) (8kVA) (12kVA) (16kVA)
12 kVA no n+1 n+2 n+3redundancy (4kVA) (8kVA) (12kVA)
16 kVA no n+1 n+2redundancy (4kVA) (8kVA)
20 kVA no n+1redundancy (4kVA)
24 kVA noredundancy
CLASSIFICATION OF BATTERY RACKS AVAILABLE FROM STOCK - IN PROTECT 1.M DESIGN10 min. 20 min. 30 min. 40 min. 50 min. 60 min. 90 min.
4 kVA – – – – – – 1x 1.M BP24 1x 1.M BP38 – – – 1x 1.M BP48 1x 1.M BP65
8 kVA 1x 1.M BP38 1x 1.M BP65 1x 1.M BP76 – – – – – – 2x 1.M BP65
12 kVA 1x 1.M BP48 1x 1.M BP65 1x 1.M BP72 – – – 2x 1.M BP65 2x 1.M BP76 3x 1.M BP65
16 kVA 1x 1.M BP65 1x 1.M BP72 2x 1.M BP65 2x 1.M BP72 3x 1.M BP65 – – –
20 kVA 1x 1.M BP72 2x 1.M BP76 – – – 3x 1.M BP65 3x 1.M BP76 – – –
24 kVA 1x 1.M BP72 2x 1.M BP65 2x 1.M BP72 3x 1.M BP76 – – – – – – – – –
n+x scalable technology Redundancy Capacity
Load
Load
ExpansionsslotRS485RS232RS485RS485
• High power reserves through max. 24 KVA total power
• High security stock through n+x technology
• Integrated electronic switch unit and malfunction-safemaintenance bypass
• 3-phase or 1-phase connection to the complete system; 1-phase output
• Long periods of autonomy in case of power outage
• Use of standard battery, irrespective of manufacturer
• Intelligent battery management
• Easy substitution of modules through hot-swappabletechnique during operation
• Modular construction in plug-in form in compact tower,19” installable
• Communication module with LCD display, dual monitoringinterface with expansion slot
• “CompuWatch” software on CD
Conceived for all IT applicationsthat require high availability and safetyreserves but have to stay flexible at thesame time.
other types on request
![Page 17: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/17.jpg)
17
CLASSIFICATION VFI SS 111 to IEC 62040-3 1.M UPS 1.M SYSTEMMODULE 1.040 MAX. (6 x 1.040)
Type power 4 kVA 24 kVA
2.8 kW 16.8 kW
n+x scalable technology
UPS-InputInput voltage (auto. detection) 230 Vac (1/N/PE~) or 400 / 230 Vac (3/N/PE~)
Input voltage range without battery mode 160 - 300 Vac (1 ph~) or 277 - 520 Vac (3 ph~)
Frequency 50 Hz / 60 Hz ± 4 Hz
Current consumption (max.) 22 A (1ph~) bzw. / 7.3 A (3ph~) 132 A (1ph~) bzw. / 44 A (3ph~)
Power factor λ ≥ 0.98
UPS-OutputRated output voltage 220 Vac / 230 Vac / 240 Vac ± 2% (adjustable)
Frequency in battery mode 50 Hz / 60 Hz ± 0.2 Hz
Output current 17.4 A 104.4 A
Transfer time at mains outage 0 ms (zero transfer)
Voltage waveform Sinusoidal THD < 3%
Overload response (online mode) 125% for 30 s / 130% for 2 s
subsequent, transfer to bypass mode (zero transfer)
Crest factor 3
BATTERYNominal voltage 120 Vdc
Autonomy time IU characteristic curve (charging voltage 274 Vdc/ charging current max. 4,2 Adc)
Overload / deep discharge protection Arbitrary and expandable with external battery modules
(standard available modules with 24, 38 or 65 AH)
Service life: 10 years to EUROBAT
Overload / deep discharge protection yes
COMMUNICATIONInterfaces (dual monitoring) RS232 / RS485 for status and measurement levels,
communication slot (for pot.-free contacts / SNMP)
Shutdown software (on CD) Included for all typical operating systems
(e.g. Windows, Mac, Linux, Unix, FreeBSD, Novell, Sun, etc.)
Failure indicators (acoustic / optical) LCD with digital information of input
and output parameters (voltage, frequency, power etc.),
battery parameter incl. failure diagnosis by password
protected level, LED for status and main failures
GENERAL DATAEfficency total > 89% > 88%
Audible noise (1 m distance) < 55 dB (A) < 62 dB (A)
Operating temperature range 0° - 40°C
EMC Immunity: EN 61000-4 Part 2 to 5
Emission: EN 61000-6-3 Class A
Humidity 20% – 90%
Installation height Up to 1500 m, at nominal load
Equipment colour Black line
Size appr. W x H x D (mm) 442 x 965 x 700 (chassis) / Module: 405 x 87 x 530
Weight appr. (kg) 75 kg (chassis) + 15 kg each module
Certification CE
Specification
![Page 18: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/18.jpg)
18
SOFTWARE &HARDWAREOPTIONS
CompuWatch – the shutdown and UPS management software...for automation in data processing.
Features:• Software in client/server technology
• Integration as background process or service inoperating systems
• Supports RS232, USB and network interfaces in UPSequipment
• User-friendly easy software installation andconfiguration
• Supports multi-server shutdown in heterogeneousand homogeneous networks
• Programmable system campaigns operates through adata planner
• Password-protected control functions for UPS system
• User-friendly graphical front-end to supervise UPSequipment, local and remote using the network
• Selectable bar graphs for data
• Automatic shutdown of operating systems
• Supports wake-up on LAN function for sequentialreboot
• User-adjustable batch files and scripts for shutdownprocedure
• Alerting of events through network switches, emails,short message services
• Configurable events manager
• Saves all events from UPS and EDP, logged by dateand time
• Supports many operating systems on differentprocessors:
- MS Windows solutions
- Novell Netware solutions
- Linux solutions
- MAC OS solutions
- IBM AIX solutions
- SUN Solaris solutions
- DEC VMS
- IBM OS400
- … and many other Unix derivatives (more information at www.aegpss.com)
Network management software for UPS equipment...solution for intelligent network management.
Features:• Web-based remote supervision of power supply
systems in network
• Simple operation of complex power supply management
• Alerting of events through network switches, e-mails,short message services
• Saves all events in a logbook
• Graphics for statistical analysis
• Customer-specific representations with backgroundgraphics possible
A basic version of this software for up to nine UPSsystems is available free of charge on the CompuWatchCD-ROM.
![Page 19: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/19.jpg)
19
Manual bypassThe external manual bypass unit serves to connect the UPS, e.g. for maintenance purposeswith simultaneous continued uninterruptible supply for the connected consumers. As well aspure bypass operation, it is also possible to set an additional switch for UPS trial operation.
MBS10 / MBS16 for series
PROTECT B., C. / C.R up to 3000 VA
- Universal design for tower and 19” rack models in solid metal casing
- High quality cam-operated switch with advanced contacts
MBS32 for PROTECT C. 6000 R
- Design in solid 19” metal casing with just 2 HE
- High quality cam-operated switch with overlapping contacts
- Optical signal of different operating conditions
- Integrated output distribution (4 fused output electric circuits), additional output on terminal to feed external UV
PDB box (parallel control panel, distribution, bypass)To increase availability (active redundancy) or even increase the UPS performance, the compactparallel control panel allows the possibility of coupling up to 3 UPS systems. An integrated feedand output field offers unlimited potential to expand without converting the existing low-voltagemain distribution board. For maintenance purposes, there is also an integrated manual bypassunit available.
The parallel control panel is available for the following product types:
- PROTECT C. 6000 - PROTECT C. 10000 - PROTECT 1. 100 - PROTECT 1. 150 - PROTECT 1. 200
Relay cardThe relay card in slot-in design for the UPS series PROTECT B./C./1./1.M displays collective faultsignals through volt free contacts, including power fail, WR and bypass operation.
SNMP (PRO) adapterThe SNMP adapter allows UPS systems to be supervised via Web or WAP.
A graduated shutdown of all relevant servers on the network is possible if necessary.
Through the Wake-up-on-LAN, the server can also be restarted.
This means that automatic SHUTDOWN and REBOOT of the system is possible.
As well as these features on the adapter, the UPS can also be supervised through integratedSNMP agent by network management software, such as HP-OpenView, SunNetManger oranother NMS. The PRO variation of the SNMP adapter also allows incorporation of the accesscontrol of the room, air conditioning and a smoke and fire alarm. In addition, temperatures and air humidity can be measured by using a special environment manager and be processed in the SNMP PRO adapter.
Load switchThis compact module as a supplement to the SNMP PRO adapter allows intelligent loadmanagement through the UPS monitor, web browser or network management software for UPS systems.
Temperature sensorThe digital temperature sensor is directly connected to the SNMP PRO adapter.The sensor is mainly used in server cabinets or to supervise rooms.The installation and configuration are both user-friendly.
![Page 20: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/20.jpg)
“Only a professionally maintained UPS offers the highest availability
with effective cost control”
2. Pro-Check 3. Pro-Repair
20
Services Pro-Check Pro-Check Pro-Check Pro-CheckBasic Comfort Deluxe Deluxe
on-site*Pro-Check x x - -
24-hour Hotline x x x x
Loaned goods - x - -
Exchange - - x x
5-year warranty - - x x
* For PROTECT C., PROTECT 1., PROTECT 1.M
The Pro-Check packet includes:
• Software update• Basic cleaning• Battery test• Ventilator test• Extensive function inspections of all parameters• Power failure and concurrent tests of different network
failures• Long-term test with load and full-load inspection• VDE safety check
In addition, with Pro-Check Deluxe:• New battery• New ventilator
The exchange takes place after 3 years.
*On acquisition of a Deluxe Service packet within 6 months of the date of purchase of the UPS system.
Services Pro-Repair Pro-Repair Pro-Repair Pro-RepairBasic Comfort Deluxe Deluxe
on-sitePro-Repair x x - -
24-hour Hotline x x x x
Loaned goods - x - -
Exchange - - x x
5-year warranty - - x x
The Pro-Repair packet includes:
• Repair• Software update• Basic cleaning• Battery test• Ventilator test• Extensive function inspections of all parameters• Power failure and concurrent tests of different network
failures• Long-term test with load and full-load inspection• VDE safety check• Short repair report
With Pro-Repair Deluxe, an exchange is made in the caseof warranty.
On the basis of our high standards and decades of experience, we also provide cost-effective, efficientand rapid service in terms of maintenance.
During the first 24 months of your purchase, we guaranteecomprehensive preliminary exchange on all systems and batteries in the compact UPS range.
A large spectrum of service packages, which take all requirements into account, are available alongside the acquisition of your UPS and guarantee optimal costcontrol over a period of up to 60 months.
AEG Power Supply Systems -Your power partner for service
Up to 5 years warranty*
1. Extended WarrantyWarranty extensions up to 36 months are available for allcompact UPS systems during the first 6 months ofownership.
Thefollowingservicesareavailable:
![Page 21: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/21.jpg)
IT• IBM• MOTOROLA• SUN MICRO SYSTEMS• UNIDATA
Telecommunication• British Telecom• Deutsche Telekom• E-Plus• DORNIER SATELLITs• Vodafone• ARCOR• KPN-TELECOM• POST LUXEMBURG• Telephone Organisation
of Singapore• Telecon Italy (WIND)
Internet• Accenture New Office• ALCATEL CABLE• ARGE Network• AT&T UK• Cable & Wireless• CARRIER• City reach• COLT Telecommunications• DETE Immobilien• Dutchtone• Easynet UK• Etesca, Cuba• EX-CELL-O• Exchange Quays UK• Global Crossing• Hutchinson• LambdaNet• Level 3 Communications
• Marconi Communications• MCI Worldcom• Motorola• Nortel Networks• Orange UK Completel• O2
• PsiNet• Quest• Redbus Interhouse• TELECITY• TELEGLOBE• Telectron• Telestet• VIAG IntercomVodafone• WORLDCOM VERSATEL• World Online• 360 Networks
Oil & Gas / Chemicals• ABB-Lumus• BAYER AG• British Gas• Norsk Hydro• Shell NL + UK• WACKER Chemie AG
Power plants• KKW OSKARSHAMN• KW NEU ISENBURG• WINGAS
Infrastructure /Transportation• Airport Budapest• Airport WARSCHAU • BMW LONDON• BMW R&D Center München• Volkswagen ( VW)• POLIZEI HAMBURG
• DORNIER GMBH• Deutsche Flugsicherung• DYNAMIC STOCK• Finance Ministry of HUNGARY • Stadt HANNOVER • STUDIO HH• TOYOTA
General Industry • ARTRONIC LTD.• HYDRO AGRI• KRAUSS MAFFEI• MAN Turbomaschinen AG• N.G. BAILEY• MARKS & SPENCER• Procter & Gamble• Tecstiplik
Banking / Insurance• ALLIANCE &LEICESTER• BANK AUSTRIA• Bank für Gemeinwirtschaft• National BANK Hungary• COMMERZBANK• EXCHANGE HOUSE• GIRO BANK• EXCHANGE QUAYS• LLOYDS / TSB BANK• SCHMIDT BANK• SCHROEDER BANK• YAPI Kredi Bank
21
References
![Page 22: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/22.jpg)
Operational Areas:Data centres, telecommunication, internet hubs, banking and insurance, building services mengineering, process management, etc.
Brief description:Future proof, the new PROTECT 2. UPS draws pure sine wavecurrent well below existing IEC/EN 61000-3-12 limits. Due to itsproven double conversion technology (true online technology) thePROTECT 2. output voltage tolerances have a triple first-classrating: VFI SS 111. The active rectifier reduces power consumption by 20%. Lessinstallation and cabling and smaller GenSet units reduce requiredspace by 40%, with easy-to-maintain construction.
Specifications (power):PROTECT 2.33 10 kVA – 40 kVA
Main characteristics:• Integrated battery• Active rectifier with sine wave input current, better than IEC / EN
61000-3-12• Low operating costs, 20% lower input power• Battery test with feedback to the mains
Operational Areas:Host computers, file servers, workstations, computing centresand their integration into complex networks in manufacturingand service industries
Brief description:Ready to use UPS with genuine online technology (DoubleConversion). Market leading product with unique technology,highest availability through internal redundancy and redundantparallel operation of up to 8 units. Robust overload response and short circuit resistance. The immunity of PROTECT 3.against electronic noise is 2 to 3 times higher than required by UPS standards.
Specifications (power):PROTECT 3.31 10 kVA - 60 kVAPROTECT 3.33 10 kVA - 120 kVA
Main characteristics:• Low operating costs
• Excellent dynamic response
• Separate microprocessors for rectifier, inverter and SBS unit
• VT100 emulation for IBM users
• Ergonomic full graphical display for ease of operation (full text in 17 languages)
22
The PROTECT series – A comof the most reliable systems
PROTECT 2. PROTECT 3.
![Page 23: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/23.jpg)
mplete UPS portfolio in all performance classes
23
Operational Areas:Data centres, telecommunications, internet hubs, banking and insurance, building services engineering, facilities and systemsfor air traffic control. Appropriate for all critical.
Brief description:This UPS is the first such unit that provides 1000 kVA in a compact, ready to use unit with online technology. Highest availability through internal redundancy and redundantparallel operation of up to 8 units (8 MVA!). The UPS is controlledby 3 microprocessors – offering 100% digital control UPStechnology.
Specifications (power):PROTECT 4.33 160 kVA - 1000 kVA
Main characteristics:• Expansion up to 8 MVA possible (redundant parallel operation)
• 94 % efficiency (also in partial load operation)
• 12 pulse rectifier with low current THD
• Control via 3 microprocessors
• Intelligent battery management
• Multilingual interface in 16 languages
Operational Areas:Process control technology in power plants, life support equipmentin hospitals, industrial facilities, transformer stations, control and supervision equipment in chemical and petrochemicalindustries, process computers, etc
Brief description:Robust and safe! The PROTECT 5. series guarantees a stablepower supply for all connected loads through exceptional onlinetechnology. The short duration overload protection is rated at 500%.At short circuit currents, facilities and processes are highlyprotected by reliable stability and a high crest factor.
Specifications (power):PROTECT 5.31 10 kVA - 120 kVAPROTECT 5.33 25 kVA - 120 kVA
Main characteristics:• Potential free 220 V battery voltage for connection to an existing
DC source
• Isolating transformer in the rectifier and inverter
• Designed for operation in extremely critical areas, including lifesupport facilities
• Extremely flexible in regards to mechanical and electricalrequirements
PROTECT 4. PROTECT 5.
![Page 24: Your reliable partner in UPS for information technology · 2008-08-28 · conversion solutions for single, distributed (centralised) or point of load (localised) configurations. Power](https://reader034.vdocuments.site/reader034/viewer/2022042113/5e8f680bb993850208430dc8/html5/thumbnails/24.jpg)
Da
wir
unse
re P
rodu
kte
stän
dig
wei
tere
ntw
icke
ln, k
önne
n di
e in
die
sem
Dok
umen
t au
fgef
ührt
en D
aten
ohn
e Vo
rank
ündi
gung
geä
nder
t w
erde
n un
d w
erde
n er
st n
ach
schr
iftlic
her
Bes
tätig
ung
verb
indl
ich.
Fot
os: G
etty
Imag
es
Power SystemsWhenever wherever wattever
AMERICA• Canada
Saft Power Systems
125, Nantucket BlvdScarborough - Ontario MIP 2N8Tel: +1 416 757 51 51Fax:+1 416 752 45 14• USA
Saft Power Systems
800 Klein Road - Suite 400Plano, TX 75074 TexasTel: +1 469 229 9600Fax:+1 469 229 9650
ASIA• China
Harmer + Simmons
No. 10 Factory of KangSheng Industrial Park,No. 11 Kang Ding Street,YiZhuang development Zone,Beijing,100176 P.R. ChinaTel : +86 10 6780 3466Fax : +86 10 6780 3819Saft Power Systems
(Hong Kong Branch)
Unit 2106-07, 21/F., Saxon Tower,7 Cheung Shun Street, Lai Chi KokKowloon, Hong KongTel: +852 2969 4488Fax:+852 2969 4400Harmer + Simmons
Suite I, 27th Floor Times Square500 Zhangyang Road Pudong200122 ShanghaiTel: +86 21 3887 0601Fax:+86 21 3887 0448Harmer + Simmons
Suite 925 The garden Hotel368 Huanshi Dong Lu510064 Guangzhou ChinaTel: +86 20 8376 7261Fax:+86 20 8376 7361• Singapore
Saft Power Systems
54 Genting Lane#03-01 Ruby Land Complex Block IISingapore 349562Tel: +65 6846 5700Fax:+65 6743 1037
• Malaysia
Saft Power Systems
14th Floor Menara SafuanN°80 Jalan Ampang50450 Kuala LumpurTel: +6 3 2078 8996Fax:+6 3 2078 8995Harmer + Simmons
Plot 19 Tingat Perusahaan 6, Fasa IVKawasan Perusahaan Prai13600 PraiSeberang Prai Pulau PinangTel: +60 4 507 0542Fax: +60 4 506 3105• Thailand
Saft Power Systems
Suite 4126 Level 43 United Centre323 Silom RoadBangrakBangkok 10500Tel: +66 2 231 1571Fax: +66 2 231 1611• India
Harmer + Simmons PSS (India)
Pvt. Ltd.,
No. 2923/E 30, 1st Floor,East of Chord Road,2nd Stage, Vijayanagar,Bangalore – 560 040Tel: +91 80 41229127 / 9128Fax: +91 80 412291276
EUROPE• Czech Republic
AEG PSS UPS Systémy spol.s.r.o
Na Vlastni Pude 6/136810200 Praha 15 HostivarTel: +420 274 773 273Fax:+420 274 773 265• France
Saft Power Systems
HeadquartersImmeuble "Défense Avenue 2"93/95, rue des Trois Fontanot BP40492004 NanterreTel: +33 (0) 1 55 51 10 79Fax: +33 (0) 1 55 51 10 73
Saft Power Systems
ZI 10 rue Jean Perrin37173 Chambray-lès-ToursTel: +33 (0) 2 47 80 88 60Fax: +33 (0) 2 47 28 07 19Harmer + Simmons
4, rue Louis de Broglie22300 LannionTel: +33 (0) 2 96 04 77 39Fax: +33 (0) 2 96 04 71 66• Germany
AEG Power Supply Systems
Emil-SiepmannStr.32D-59581 Warstein/BeleckeTel: +49 2902 763 0Fax: +49 2902 763 680• Hungary
AEG SVS Aramellatasi Kft.
H-1507 Budapest, P.O.B 30Kondorfa utca 10H-1116 BudapestTel: +36 1 209 9550Fax:+36 1 209 9555• Italy
Saft Power Systems
Via Trento 3020059 Vimercate – MilanTel: +39 0 39 686 1Fax:+39 0 39 686 3847• Romania
Saft Power Systems S.R.L.
Str. Gh Lazar Nr. 9300081 TimisoaraTel: +40 256 303 149Fax: +40 256 490 326Saft Power Systems S.R.L.
Bd. D. Pompei nr. 10AConect Business ParkEtJ. 1, sect. 2,020337 Bucuresti,Tel: +40 213 114 077Fax: +40 213 114 077• Russia
Harmer+Simmons
Petrovka str., 13/15 build.5.Russia, 107031, MoscowTel: +7(495) 795-07-44Fax: +7(495) 795-07-43
•
Spain
Saft Power Systems
Parque Tecnologico de AlavaC/Albert Einstein 31 01510 Minano – AlavaTel: +34 945 21 41 10Fax:+34 945 21 41 11• The Netherlands
Saft Power Systems
Weerenweg 101161 AH ZwanenburgTel: +31 20 4077 800Fax: +31 20 4077 801• UK
Saft Power Systems
97-101 Peregrine road, Hainault, IlfordEssex IG6 3XJTel: +44 (0)208 500 12 11Fax: +44 (0)208 500 9365
MIDDLE-EAST• Cyprus
Saft Power Systems
P O BOX 56646 - 5th floorArchbishop Makarios III Ave No 171LimassolTel:+357 258 20055Fax:+357 257 48417• Dubaï
Saft Power Systems