You Can Measure the Benefits…
Training Course
MonoScan Setup & Configuration
You Can Measure the Benefits…
MonoScan supplied with preprogrammed default settings, making it ready for immediate
use.
Main setting-up steps 0 – 5 Pr 00 – Flow measurement
(MonoScan O)This program enables you to
selectpreset weir/flumes.Note: this function will be
available only for Open Channel unit.
Setup
MonoScan 2 wires
You Can Measure the Benefits…
Pr 01 – Reset reset the unit (keeps the last parameters), same as on/off
Pr 02 – Tank height enter the correct height (from sensor to bottom)
MonoScan 2 wires
Setup
You Can Measure the Benefits…
Pr 03 – Defining interfering
signals (Scan Distance process)
“Static interference” is a well
known phenomenon in ultrasound
technology.
Use Scan Distance function to
“map” your tank from these
obstacles and to memorize the
interfering signals.
MonoScan 2 wires
Setup
You Can Measure the Benefits…
MonoScan can locate and store up to 7 obstructions.
After storing 7 interference signals the memory act as FIFO (first in first out), the 7th signal will erase the first signal and so on.
Note: Each obstruction will extend
the calculation time. Defining interfering signals
is done while the tank is empty.
MonoScan 2 wires
Setup
You Can Measure the Benefits…
Clear stored interferences When entering Pr.03, you
can either select Search to locate acoustic interferences, or Clear to delete stored interferences.
MonoScan 2 wires
Setup
You Can Measure the Benefits…
Pr 04 - 4 mA Pr 05 - 20 mA
The 4mA can be defined for Level, Distance or Flow measurements. This definition will be applicable for 20mA values, in Pr.05.
MonoScan 2 wires
Setup
You Can Measure the Benefits…
When setting 4mA and 20mA for Level measurements, Pr.04 and Pr.05 will be configured for level values.
When setting 4mA and 20mA for Distance or Flow the values will be in Distance or Flow).
MonoScan 2 wires
Setup
You Can Measure the Benefits…
MonoScan 2 wires
Extra Features
Pr 06 Low / High dynamic Define whether high or low reading speed :
SE 0 - 80cm/minute (low dynamic)SE 1 - 1.5m/minute (high
dynamic)SE 2 – rapid changes (fast
dynamic 2m/min)Note: Pro 06 is available in models L/O, while S uses low dynamic as default.
Setup
You Can Measure the Benefits…
Pr 08To select whether to display distance (from surface) or the level (of the surface) d000 represents
distance reading L000 represents level
reading
MonoScan 2 wires
Setup
You Can Measure the Benefits…
MonoScan 2 wires
Setup
Pr.09 – Gas Compensation. This program enables you to
compensate for sound velocity in different types of gasses, provided the sound velocity is fixed.
You can enter the appropriate factor for each type of gas listed on the ‘Gas Table’ in the User Manual.
For example the sound velocity in air is 331.6 m/sec and for Ethanol (C2H3OH) 235.4 m/sec, therefore a factor of 235.4 /331.6= 0.71 .
Note: Since there are several gases in the tank, air density must be calculated
You Can Measure the Benefits…
MonoScan 2 wires
Setup
Gas Compensation – Volume calculation This program enables the user to calculate volume in a linear
tank (cylindrical etc). PR09 factor is multiplied with the measurement value giving a volume up to 1500 (maximum displayed value).
For example tank height = 1.5m Volume factor = 3 Maximum volume = max T.H. X Volume factor = 1.5 X 3 = 4500
Maximum Gas factor = 10 Volume is calculated linear.
You Can Measure the Benefits…
MonoScan 2 wires
Setup
Pr.10 – Clear
Restore default parameters, as set
by manufacturer.
You Can Measure the Benefits…
22mA Error Signal Indications
“F.F.F.F” - Whenever the level reaches up to 10cm inside dead zone or overflow occurred, “F.F.F.F” will appear on the MonoScan’s display.
“E.E.E.E” - Whenever the echo is not received by the transducer because of empty tank or when the measured distance is greater than permitted, “E.E.E.E” will appear on the MonoScan’s display.
MonoScan 2 wires Setup
You Can Measure the Benefits…
Enable/Disable 22mA error signal indications, such as: Near Zone (F.F.F.F) and Lost Echo or empty (E.E.E.E).
Default value is disable. In order to enable it, Enter
0016 in Pr.02.
MonoScan 2 wires
Setup
You Can Measure the Benefits…
Device’s version.
Enter 0017 in Pr 02. After entering this code, the
screen Addr (Version) will be displayed.
Enter 0013 in Pr 02. After entering this code, the
screen Addr (sub Version) will be displayed.
MonoScan 2 wires
Setup
You Can Measure the Benefits…
Shift Blocking Distance (SBD)
This function enables you to enlarge the Dead Zone and is applicable for installations requiring extension pipes or nuzzles positioned above the application level.
SBD is limited to 1.5m/4.9ft. In order to access this
function, enter 0001 in Pr 02.
MonoScan 2 wires
Setup
You Can Measure the Benefits…
Pr 00 – Flow measurement (MonoScan O)Includes 17 types of Flume/Weirs, each of them is offered at several Sizes.The measured units can be displayed as either GPM or M3 Per hour.The methodology used when setting up open channel:X – Particular flume/weir typeE/U – European/American standardYY- Specific flume/weir dimensions
Setup
MonoScan 2 wires
You Can Measure the Benefits…
EC11 – Noise 5544 – Sensor
disconnected Contact manufacturer for further instructions
E555 – Power supply problem Make sure your power supply corresponds to Solid specification. If problem persists, replace the power supply
MonoScan 2 wires
Troubleshooting
You Can Measure the Benefits…
A combination of three 8 and one 1 may occurred either due to shortage or when two pads pushed simultaneously.
8188 Back 8818 Next 8881 Enter 1888 Escape
Check for any visual damage on Pads.
MonoScan 2 wires
Troubleshooting
You Can Measure the Benefits…
8888 will appear for a few seconds after restart. If it last more than a few seconds it may be due to the following reasons: Power supply’s voltage is
too low “Load Resistor”
resistance is too high or not necessary at all
Random Impulse which cause automatically self restart
MonoScan 2 wires
Troubleshooting