wind energy and protection - aventri

114
Wind Energy and Protection Roy Moxley Thanks to Reigh Walling, Walling Energy Systems Consulting LLC

Upload: others

Post on 15-Oct-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Wind Energy and Protection - Aventri

Wind Energy and Protection

Roy Moxley

Thanks to Reigh Walling, Walling Energy Systems Consulting LLC

Page 2: Wind Energy and Protection - Aventri

You See Wind Machines Everywhere (30 miles North of Pullman)

82 GW Capacity in the US as of January 2017

Page 3: Wind Energy and Protection - Aventri

Wind Turbines

Self Protecting

Size Increasing (today up to 8 MW)

No Zero Sequence

No (Presently) Negative Sequence

Page 4: Wind Energy and Protection - Aventri

Type 1 and type 2 induction generator wind turbines Basic operation of type 1 and 2 – typical configuration

Page 5: Wind Energy and Protection - Aventri

Type 1 and 2 IG wind turbines

Advantages/disadvantages

Page 6: Wind Energy and Protection - Aventri

Type 3 – Doubly-fed induction generator (DFIG)

Basic operation of DFIG – typical configuration

Page 7: Wind Energy and Protection - Aventri

Type 3 – Doubly-fed induction generator (DFIG)

Advantages/disadvantages

Page 8: Wind Energy and Protection - Aventri

Full-Converter (type 4) system

Page 9: Wind Energy and Protection - Aventri

What are the advantages of the Full

Converter system?

Page 10: Wind Energy and Protection - Aventri

Type 4 Variable-speed, full-converter wind

turbine-generator Advantages/disadvantages

Page 11: Wind Energy and Protection - Aventri

Comparison of WTG Designs to Comply with

Interconnection Requirements

Page 12: Wind Energy and Protection - Aventri

Comparison of Type 4 with Synchronous

(conventional) generation

Page 13: Wind Energy and Protection - Aventri

Advantages and Disadvantages of

Conventional generation

Page 14: Wind Energy and Protection - Aventri

Reactive capability characteristic

of synchronous generator

Page 15: Wind Energy and Protection - Aventri

Modeling Full Converter Machines –

Reactive Capability

Page 16: Wind Energy and Protection - Aventri

Reactive capability characteristic of

full-converter wind turbine

Page 17: Wind Energy and Protection - Aventri

Reactive capability characteristic of full-

converter wind turbine

Page 18: Wind Energy and Protection - Aventri

Reactive capability characteristic of full-

converter wind turbine

Page 19: Wind Energy and Protection - Aventri

Reactive capability characteristic of full-

converter wind turbine

Page 20: Wind Energy and Protection - Aventri

Reactive capability characteristic of full-

converter wind turbine

Page 21: Wind Energy and Protection - Aventri

Reactive capability characteristic of full-

converter wind turbine

Page 22: Wind Energy and Protection - Aventri

Reactive capability characteristic of full-

converter wind turbine

Page 23: Wind Energy and Protection - Aventri

Reactive capability characteristic of full-

converter wind turbine

Page 24: Wind Energy and Protection - Aventri

Curves for different terminal voltages

(example)

Page 25: Wind Energy and Protection - Aventri

Curves for different terminal voltages

(example)

Page 26: Wind Energy and Protection - Aventri

Curves for different terminal voltages

(example)

Page 27: Wind Energy and Protection - Aventri

Curves for different terminal voltages

(example)

Page 28: Wind Energy and Protection - Aventri

Curves for different terminal voltages

(example)

Page 29: Wind Energy and Protection - Aventri

Curves for different terminal voltages

(example)

Page 30: Wind Energy and Protection - Aventri

Curves for different terminal voltages

(example)

Page 31: Wind Energy and Protection - Aventri

Curves for different terminal voltages

(example)

Page 32: Wind Energy and Protection - Aventri

Existing:

Voltage Regulation

Reactive Power Control (constant Q)

Power Factor Control (constant ratio of

Q to P)

Reactive Control without Active Power

Production

Voltage Regulation (adjustment of

reactive power to satisfy voltage regulation

schedule)

Reactive Power Control All are

capabilities currently provided on a routine

basis by synchronous generators, except

reactive power control without active power

production (“synchronous condenser

operation”), which typically requires extra

equipment.

What Are Common Reactive Control

Requirements ?

Page 33: Wind Energy and Protection - Aventri

Wind Plant Reactive Power and

Voltage Control

Page 34: Wind Energy and Protection - Aventri

Typical Droop of 1% to 5%

Option for Voltage Deadband

Wind Plant Voltage Control – Reactive Droop

Page 35: Wind Energy and Protection - Aventri

Exercise – Draw Rough Sketch:

How does a full-converter wind park compare with a

synchronous generator for steady-state voltage control?

Page 36: Wind Energy and Protection - Aventri
Page 37: Wind Energy and Protection - Aventri
Page 38: Wind Energy and Protection - Aventri
Page 39: Wind Energy and Protection - Aventri
Page 40: Wind Energy and Protection - Aventri

Voltage control: Fast response to change in

reference

Wind plant response very comparable to synchronous generator response.

WTG response very similar to excitation system response.

Page 41: Wind Energy and Protection - Aventri

Summary – How Full-Converter WTGs provide

Reactive Power Control

Page 42: Wind Energy and Protection - Aventri

Existing:

• Power Output (Curtailment) Control

• Ramp Rate Control

• Curtailments

• Start-up

• Regulation Up for Underfrequency

• Adjustable Droop

• Regulation Down for Overfrequency

• Adjustable Droop

• Low Voltage Ride Through

• High Wind Ride-Through

• Rate Variation Control

What Are Common Active Power Control

Requirements

Page 43: Wind Energy and Protection - Aventri

Ramp rate control - smooth, controlled

transition from one output level to another

Page 44: Wind Energy and Protection - Aventri

Frequency Droop Control - Primary

Frequency Response

Page 45: Wind Energy and Protection - Aventri

Frequency response – Simulations calibrated with

test in Electric Reliability Council of Texas (ERCOT)

Much faster than fossil

response, which may require

over a minute to fully

respond.

Page 46: Wind Energy and Protection - Aventri

Low-voltage ride-through (LVRT)

Page 47: Wind Energy and Protection - Aventri

Rate Variation Control

Page 48: Wind Energy and Protection - Aventri

Transient underfrequency response (“inertial

response”)

Page 49: Wind Energy and Protection - Aventri

Delta control – operate with a constant delta below

maximum output

Page 50: Wind Energy and Protection - Aventri
Page 51: Wind Energy and Protection - Aventri

High Wind Ride Through (HWRT)

High wind speeds (above 25 m/s) caused widespread tripping in the past;

Page 52: Wind Energy and Protection - Aventri

Summary – How FC WTGs provide Power

Control (existing and anticipated)

Page 53: Wind Energy and Protection - Aventri

Modeling for power system analysis

Page 54: Wind Energy and Protection - Aventri

Type 3 WTG Fault Performance

Page 55: Wind Energy and Protection - Aventri

Type 3 WTG Performance During

Crowbar Activation

Page 56: Wind Energy and Protection - Aventri
Page 57: Wind Energy and Protection - Aventri
Page 58: Wind Energy and Protection - Aventri

Model Limitations

Page 59: Wind Energy and Protection - Aventri

Comparison of FC WTG with Synchronous Generation

to Comply with Interconnection Requirements

Page 60: Wind Energy and Protection - Aventri

• Weak grid controls for sustained stable operation in

systems with SCR < 3 (SCR = 3-phase short circuit MVA at

regulation point / aggregate turbine MW)

• Power oscillation damping for inter-area power

oscillations.

• Sub-synchronous resonance damping for series

compensated systems

• Isochronous operation – standalone operation These are

capabilities that can presently be provided by synchronous

generators.

Future Developments (Present Weaknessess)

Page 61: Wind Energy and Protection - Aventri

Protection Design Excercise

230 kV Line 75 miles long

Assumptions:

$200,000 per installed 230 kV breaker

$100,000 + $10,000/MVA for installed transformer

$25,000 per installed 34.5 kV breaker

$150,000 per mile 34.5 kV line

$10,000 per mile for fiber

$50,000 per microwave link

$20,000 per installed relay

25 mi. 25 mi. 25 mi.

2 mi. 2 mi.

Page 62: Wind Energy and Protection - Aventri

Protection Design Excercise

230 kV Line 75 miles long

25 mi. 25 mi. 25 mi.

2 mi. 2 mi.

25 – 3 MW

Type 4 machines 25 – 3 MW

Type 4 machines

10kA fault duty 5kA fault duty

1000A load →

Page 63: Wind Energy and Protection - Aventri
Page 64: Wind Energy and Protection - Aventri
Page 65: Wind Energy and Protection - Aventri

Considerations

230 kV Line 75 miles long

10kA fault duty 5kA fault duty

1000A load →

• Distance Relays have been shown to have unreliable reach if wind

machines are radial due to SubSynchronous factors

• Line Current Differential can go up to 6 terminals

• Infeed is unreliable from wind farms (overcurrent complications,

distance reach trouble)

• How much added fault “exposure” is being added, compared to the

total line length?

Page 66: Wind Energy and Protection - Aventri

Each generator has its

advantages and

disadvantages, but

Full Converter WTGs

generally have many

advantages and few

major disadvantages.

If we could only

control the wind…

Page 67: Wind Energy and Protection - Aventri

Protection Considerations

Page 68: Wind Energy and Protection - Aventri

Distance Relay with Inverter Current

IZ-Vop

Vpol

Page 69: Wind Energy and Protection - Aventri

Slide 69

Current Differential

AI

AI

BIBI IRe

IImeach I is the summation of:

Ii = ICT-Err.+ ISignal-Err.+ISync-Err.

DiffI

BI

AI

AI BII

Res_minRes III

min_Re sI Trip if differential current exceeds sum of

measurement errors

added by safety margin IRes_min

Page 72: Wind Energy and Protection - Aventri

Slide 72

Let’s Calculate the Business Case of Tap versus Substation

$750,000 -

$1,500,000 for 3

installed 230 kV

breakers +

buswork,

switches…

Plus –

New Line Relays

New Bus Relay

New Feeder Relay

Buswork

Construction Time

Page 73: Wind Energy and Protection - Aventri

Slide 73

Look at Business Case of Tap –vs- Substation

What does a

Splice Cost ?

Page 74: Wind Energy and Protection - Aventri

Up to 6 Terminals, 64kbps Channels to Each Relay

Wind Farm

Tapped Loads

Major Industrials

Provisos, Limitations, Exclusions…

Photo Voltaic

Page 75: Wind Energy and Protection - Aventri

Relay 1

Relay 6

Relay 2

Relay 5

Relay 3

Relay 4

Apply Built-in Distance for Backup

Page 76: Wind Energy and Protection - Aventri

Relay 1

Relay 6

Relay 2

Relay 5

Relay 3

Relay 4

Set Reach to Inside Line With Maximum Infeed –

But What About Faults Beyond That ?

Page 77: Wind Energy and Protection - Aventri

Relay 1

Relay 6

Relay 2

Relay 5

Relay 3

Relay 4

Sequential Tripping Clears Strongest Source

First – Best Stability Response

Note: Shape shows reach, not

characteristic of the relay

Page 78: Wind Energy and Protection - Aventri

Slide 78

Power Swing Detection

Typical impedance trajectory

X

R

Z(ϑ = 0°)

Z(ϑ = 40°)

Z(ϑ = 120°) Z(ϑ = 180°)

φ

ϑ = 40°

normal load condition

ϑ = 120°

dangerous for

distance protection

ϑ = 180°

unstable power swing

out of step tripping

Zone Z1

Page 79: Wind Energy and Protection - Aventri

Traditional Power Swing

Blocking and Tripping

X

R

Z(ϑ = 0°)

Z(ϑ = 120°) Z(ϑ = 180°)

φ

Zone Z1

Blinder Blinder

Page 80: Wind Energy and Protection - Aventri

Slide 80

Impedance trajectories of

3-machine power-swings

Page 81: Wind Energy and Protection - Aventri

Slide 81

Zero Setting Power Swing

Detection

impedance in

power swing area

OR

monotony

continuity

smoothness

power swing

detectedAND

Page 82: Wind Energy and Protection - Aventri

Slide 82

Measure Power Swings Like a

Human Would

X

R

power swing if

ΔR1 and ΔR2 and

ΔX1 and ΔX2

have same direction power swing if

ΔR1 and ΔR2 or

ΔX1 and ΔX2

have same directions

ΔR1

ΔX1

ΔX2

ΔR2

ΔR1

ΔX1 ΔX2

ΔR2 ΔR1

ΔX1

ΔX2

ΔR2

no power swing if

ΔR1 and ΔR2 and

ΔX1 and ΔX2 have

different directions

Page 83: Wind Energy and Protection - Aventri

Swing

Center

Voltage

Method

Page 84: Wind Energy and Protection - Aventri

Out of Step Blocking 180°System

Separation

Page 85: Wind Energy and Protection - Aventri

Quick Quiz

180°System

Separation

What will the voltage across the

breaker contacts be if tripped on

the line between ZS and ZR ?

Page 86: Wind Energy and Protection - Aventri

Quick Quiz

180°System

Separation

What will the voltage across the

breaker contacts be if tripped on

the line between ZS and ZR ?

A. 2 X L-L Voltage

Page 87: Wind Energy and Protection - Aventri

Quick Quiz pt 2

180°System

Separation

What would you expect to

happen when the breaker tries

to open at 2 X L-L Voltage?

Page 88: Wind Energy and Protection - Aventri

Quick Quiz pt 2

180°System

Separation

What would you expect to

happen when the breaker tries

to open at 2 X L-L Voltage?

A. Restrike !!

Page 89: Wind Energy and Protection - Aventri

Quick Quiz pt 3

180°System

Separation

What would Generators (type 1

or 2 wind machines) during a

restrike ?

Page 90: Wind Energy and Protection - Aventri

Quick Quiz pt 3

180°System

Separation

What would Generators (type 1

or 2 wind machines) during a

restrike ? A. Serious

Damage Possible

Page 91: Wind Energy and Protection - Aventri

Quick Quiz pt 4

180°System

Separation

What would happen to capacitor

banks energized by a restriking

breaker ?

Page 92: Wind Energy and Protection - Aventri

Quick Quiz pt 4

180°System

Separation

What would happen to capacitor

banks energized by a restriking

breaker ? A.

Failure…Explosion

…Fire…

Page 93: Wind Energy and Protection - Aventri
Page 94: Wind Energy and Protection - Aventri
Page 95: Wind Energy and Protection - Aventri

Replacing Nuclear with Wind

High Availability

High Inertia

Dynamic Voltage Support

Significant Fault Contribution

Non-Dispatchable

Low Inertia

No Dynamic Voltage Support

Minimal Fault Contribution

Page 95

Page 96: Wind Energy and Protection - Aventri

Massive

Wind Farms

Installed and

Planned for

the North Sea

8 GW Installed and 2.9

Awaiting Installation

Page 97: Wind Energy and Protection - Aventri

Loss of Northern Power Plant

Loss of 80%

Power

Transfer

Power

Oscillation

Page 97

P=V1V2sinΘ/X

Page 98: Wind Energy and Protection - Aventri

System Impact of a Line Trip

Loss of 50 MW Power Transfer

Loss of 13 MVar

Page 98

Page 99: Wind Energy and Protection - Aventri

Power Plant Trip in Southern Area

Loss of about 600 MW

Page 99

Page 100: Wind Energy and Protection - Aventri

Impact of System Changes

On Protection Settings

Fault Duty – Overcurrent Pickup

Critical Clearing Time, Breaker Failure

Load Changes – Load Encroachment

Overcurrent Coordination

Load Balance – Islanding Considerations

Power Swing Settings

Page 101: Wind Energy and Protection - Aventri

Adaptive Protection ?

• How Are Settings Changed ?

• What is Protection Impact during setting

changes?

Page 102: Wind Energy and Protection - Aventri

Real – World Distribution Example

Page 103: Wind Energy and Protection - Aventri

Provide Overcurrent Settings for Breaker B

Page 104: Wind Energy and Protection - Aventri

Settings if Breaker B knew Status of Breaker C ??

Page 105: Wind Energy and Protection - Aventri

Headlines Impact

System Stability

Note the Concentration of

Nuclear Plants along the West

Edge and the SouthWest

Page 106: Wind Energy and Protection - Aventri

Current Account Balance

2013 2023

Page 107: Wind Energy and Protection - Aventri

Bulk Power Flows

Page 108: Wind Energy and Protection - Aventri

Adjusting to Dynamic Load Limits

Page 109: Wind Energy and Protection - Aventri

Changing Setting Groups and Files

Page 110: Wind Energy and Protection - Aventri

In Service Application Considerations

Setting Groups and Setting Files

Loss of Protection during Group Change ?

Time Required for Setting File Input ?

Security of File Transfer

Time Required

Control Center Calculations

Data Transmission

Time inside relay

Page 111: Wind Energy and Protection - Aventri

In Service Results

• Setting Groups and Setting Files

No Loss of Protection during Group Change

Security of File Transfer

Time to Transfer and Implement New Settings File

10 Seconds for Control Center Calculations and transmission

1 second within the relay

Security

Encrypted files to Station and to Relay

Backup / Fallback Settings Always in Place

Page 112: Wind Energy and Protection - Aventri

Wind is Here to Stay

Page 113: Wind Energy and Protection - Aventri

Protection Considerations

• Fault Response

• System Response

• Out of Step Impacts

• Coordination Impacts

• Connection Costs

Page 114: Wind Energy and Protection - Aventri

Questions ?