what is distributed generation
TRANSCRIPT
![Page 1: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/1.jpg)
SEMINOR ON DG(distribution generation) PLACEMENT IN DISTRIBUTION NETWORK
PRESENTED BY AJAY PRAKASH SINGH PSE 152603 EEE NIT WARANGAL Under the guidance of SREE B. Nagu
2
![Page 2: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/2.jpg)
2
REFRENCE IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 1 Voltage Stability Based DG Placement in Distribution Networks BY H. Ghasemi , S. Vaez Zadeh (senior member ,IEEE)
![Page 3: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/3.jpg)
content1. What is DG?2. Why DG?3. Earlier used techniques4. Techniques used in this paper5. Case study6. Application7. Conclusion
1
![Page 4: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/4.jpg)
What is Distributed Generation? The small energy-generation units which are connected to
distribution system are referred to as "Distributed Generation”.
The best definition for DG is, "the source of electrical energy is connected to distribution networks or directly to the consumer side".
2
![Page 5: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/5.jpg)
POWER SYSTEM WITHOUT DG
3
![Page 6: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/6.jpg)
Distributed Generation Diagram
4
![Page 7: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/7.jpg)
POWER SYSTEM WITH DG
5
![Page 8: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/8.jpg)
WHY DG ? System Security
Reliability
Efficiency
Quality
Active Management of distribution network
6
![Page 9: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/9.jpg)
earlier use technique’s ,How too select best location for dg voltage stability index – most sensitive bus too voltage collapse in radial distribution system Problem – an equivalent two bus system is used for the analysis of voltage stability bus indices – for considering the effect of aggregated dg in voltage security of transmission grid are developed
7
![Page 10: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/10.jpg)
New techniques for dg placement Voltage stability technique – • Modal analysis • Continuous power flow Ranking method – priority list for dg location for compensating reactive power
8
![Page 11: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/11.jpg)
Modal Analysis for Voltage Stability Evaluation A system is voltage unstable if for at least one bus in the system
bus voltage magnitude decreases as the reactive power injection at the same bus is increased.
other words, a system is voltage stable if V-Q sensitivity is positive or every bus and unstable if V-Q sensitivity is negative for at least one bus.
9
![Page 12: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/12.jpg)
Reduced Jacobian Matrix The linearized steady state system power voltage equations are
given by-
∆P = incremental change in bus real power.∆Q=incremental change in bus reactive power injection.∆θ = incremental change in bus voltage angle.∆V= incremental change in bus voltage magnitude.
10
![Page 13: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/13.jpg)
at each operating point we keep P constant and evaluate voltage stability by considering the incremental relationship between Q and V. To reduce the above equations we assume ∆P= ∆P=0.
JR is called the reduced Jacobian matrix of the system. JR is the matrix which directly relates the bus voltage magnitude and bus reactive power injection.
11
![Page 14: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/14.jpg)
The ith mode of the Q-V response is defined by the ith eigenvalue , and the corresponding right and left eigenvectors.Since Using this in ∆V, we get
By defining v=η∆V vector of modal voltage variationq= η∆Q vector of modal reactive power variation
We can write uncoupled first order equation as-
12
![Page 15: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/15.jpg)
Thus for ith mode voltage variation is - Vi=1/ λi * qi
If λi >0 , the ith modal voltage and the ith modal reactive power variations move in the same direction, indicating voltage stability of the system.
whereas λi <0 refers to instability of the system.
13
![Page 16: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/16.jpg)
The relative contribution of the power at bus k in mode i isgiven by the bus participation factorPki= ki*ℰ η kiParticipation factors determine the most critical areas which lead the system to instability. Higher the magnitude bus participation factor
better be the remedial action taken too stabilize the mode.
13
![Page 17: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/17.jpg)
Continuous power flow methodology Determination of max loading is one of the most important problem in voltage stability analysis that can’t be calculated by model analysis.This uses successive solution, to compute the voltage profile up too the collapse point there jacobian become singular to determine voltage security margin
14
![Page 18: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/18.jpg)
Dg placement ALGORITHMDG Placement ProcessThe DG placement problem is solved here by using modal analysis and the CPF method by an objective of voltage security margin enhancement and loss reduction.
14
![Page 19: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/19.jpg)
15
![Page 20: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/20.jpg)
Dg placement evaluation indices ALR – active loss reduction RLR – reactive loss reduction higher values indicate better performanceVI index – lower value better the performance of dg units
16
![Page 21: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/21.jpg)
SHORT TERM REACTIVE POWER RANKING
17
![Page 22: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/22.jpg)
CASE STUDYApplication of DG placement AlgorithmApplication of the placement method and the corresponding indices are examined on the well-known 33-bus radial distribution network.The system total apparent load is 4.3694 MVA and DG penetration in all cases is considered to be 40% (i.e., 1.7477 MVA).
18
![Page 23: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/23.jpg)
MODIFIED EQUIVALENT REACTIVE POWER COMPENSATION METHOD (MERC) Uses (QLI) – to determine priority list of dg to compensate reactive power shortagesIt will not seek VSM
19
![Page 24: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/24.jpg)
APPLICATION OF PLACEMENT ALGORITHM
20
![Page 25: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/25.jpg)
System active and reactive losses for different placement scenarios when DGs active power is limited to 0.4 total load and no voltage regulation is performed by DGs.
21
![Page 26: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/26.jpg)
VOLTAGE PROFILE FOR DIFFERENT PLACEMENT SCENARIOS
. osk
22
![Page 27: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/27.jpg)
The proposed placement algorithm is implementable in different DG penetration scenarios
23
![Page 28: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/28.jpg)
Due to the radial nature of distribution networks, the buses of each network branch, from the tail to the main feeder, usually have participation factors in a descending order for a specific mode.
the 33-bus radial networks participation factors for mode 1 in descending order when DG at bus 18
24
![Page 29: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/29.jpg)
APPLICATION OF RANKING METHOD .
Application of the ranking method is examined on all candidate buses obtained from the placement algorithm, bus 28 is the best site for reactive power compensation in the case of shortage.
25
![Page 30: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/30.jpg)
The places are ranked using an MERC method, which determines a priority list of DG locations for reactive power compensation during occasions of reactive power shortage.
The placement algorithm is executed and remedial effect of DGs, both in loss reduction and voltage profile improvement in normal operation, and enhancement of the loading parameter in the case of voltage instability
The ranking method is executed over the obtained candidates to provide a priority list from the view point of reactive power compensation in the case of shortage.
26
![Page 31: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/31.jpg)
CONCLUSIONDG placement is different from the best location for reactive power compensation and VSM in the presence of a voltage-stability problem.Long-term DG placement problem can be solved by CPF and modal analysis while the short-term reactive power issues can be addressed by the ranking method
27
![Page 32: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/32.jpg)
REFRENCES R. Cossent, T. Gomez, and P. Fras, “Towards a future with large penetration of distributed generation: Is the current regulation of electricitydistribution ready? Regulatory recommendations under a European perspective,” Int. J. Energy Policy, vol. 37, pp. 1145–1155, 2009.
. Chakravorty and D. Das, “Voltage stability analysis of radialdistribution networks,
M. E. Baran and F. F. Wu, “Network recon figuration in distributionsystems for loss reduction and load balancing,” IEEE Trans. Power
H. A. Gil, M. E. Chehaly, G. Joos, and C. A. Caizares, “Bus-basedindices for assessing the contribution of DG to the voltage securitymargin of the transmission grid,” presented at the IEEE Power Energy
28
![Page 33: What is Distributed Generation](https://reader036.vdocuments.site/reader036/viewer/2022062522/58d08ebf1a28ab012d8b6fa1/html5/thumbnails/33.jpg)
33