west coast power cerus catalog

46
INDUSTRIAL The Pursuit of Excellence in Motor Controls

Upload: group-bbi

Post on 08-Mar-2016

341 views

Category:

Documents


8 download

DESCRIPTION

Authorized Dealer of Cerus Products

TRANSCRIPT

Page 1: West Coast Power Cerus Catalog

INDUSTRIALThe Pursuit of Excellence in Motor Controls

Page 2: West Coast Power Cerus Catalog

SAFETY FIRST! As with all electrical equipment, only qualified, expert personnel should perform maintenance and installation. Comply with all applicable local and national codes and laws that regulate the installation and operation of equipment and read manuals thoroughly. Use only installation manuals and not this sales brochure for installation procedures. It is up to the installer to determine product suitability for a given application.

©��Product�improvement�is�a�continual�process;�pricing�and�specifications�subject�to�change�without�notice.�Marketing�materials�should�not�be�relied�upon�for�technical�specification.�Cerus,�Mira,�Orion,�Titan�and�associated�logos�are�trademarks�of�Cerus�Industrial,�Inc.�All�sales�subject�to�Cerus�Terms�and�Conditions.

Contactors, Overloads and Accessories 5-15Mira Contactors and Overloads 5

Orion Contactors and Overloads 11

CONTENTS pg. 5

pg. 26

pg. 60

Contactors

Starters

VFDs

Additional Components 72-88Line Reactors 72

Pressure Sensors 74

Soft Starts 76

Panel Components 80

Variable Frequency Drives 60-68Micro-Single Phase C-Series VFD 60

Compact GS Series VFD 62

P-Series VFD 64

Resistors & Braking units 67

Pump Controls 44-59 Industrial and Pump Starter 44

Standard Pump Starter 48

Duplex Alternating Pump Starter 50

Enclosed VFD Pump Package 54

Industrial Enclosed Starters 34-43Enclosed Starters 36

Industrial Start Stop 38

Industrial Starters 42

Mira Molded Case Circuit Breakers 26-33TD/TS Series Circuit Breakers & Accessories 28

Enclosed Manual Motor Starters 33

Relays, Overloads, Mini Contactors/Overloads 22-25Digital Motor Protection Relays 22

Electronic Overloads 23

Mini Contactors, Overloads & Relays 24

Manual Motor Starters and Accessories 16-21Manual Motor Starters 16

Manual Motor Starter Accessories 20

Page 3: West Coast Power Cerus Catalog

MIRA Contactors and Overloads Installs�in�Minutes,�Lasts�a�Lifetime

� 9~95 Amp Rated Models � Integrated Lugs - Easy to Wire Without

Additional Hardware � DIN Rail Compatible � Complete Line of Accessories and Adapters

For Clean and Effective Installation � Industry Leading 5-Year Warranty

Quality DesignCerus MIRA contactors and overloads have been designed and tested to the world’s highest standards. Utilizing the Power Test and Technology Institute for rigorous testing, we have produced one of the world’s top performing and most durable UL listed contactor. The complete MIRA line of motor control components boasts one of the highest UL ratings attainable for interruption capacity when paired with our manual motor starters – as high as 100,000 amps interrupting.

Performance & ReliabilityOur advanced design sets MIRA apart as one of the industry’s most durable line of motor controls. The combination of unique contact alloys and control of the electrical arc within the contactor extends the useful life to as many as 2.5 million electrical operations. MIRA is manufactured to ISO certified quality standards and backed by an industry leading 5-Year warranty.

Easy Mounting AccessoriesThe MIRA line includes accessories that offer easy installation, space savings and reduce overall cost. MIRA Bus bars, reversing kits, mating plates and DIN rail mounting hardware allow for comprehensive and highly flexible motor control solutions.

Page 4: West Coast Power Cerus Catalog

6

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 7

Frame Size 32AF 63AF 95AF

Type

Model MRC-9 MRC-12 MRC-18 MRC-25 MRC-32 MRC-35 MRC-40 MRC-50 MRC-63 MRC-65 MRC-75 MRC-85 MRC-95

Screw clamp terminals • • • • • • • • • • • • •

Lug terminals - - - - - • • • • • • • •

Number of poles 3 3 3

Rated operational voltage, Ue 690V 690V 690V

Rated insulation voltage, Ui

Conforming to IEC947-4-1 1000V 1000V 1000V

Conforming to UL, CSA 600V 600V 600V

Rated impulse withstand voltage, Uimp 8kV 8kV 8kV

Degree of pollution (IEC60529) IP20 IP20 IP20

Rated operational current Ie (θ≤ 55 °C)AC-1AC-3

Ue max 690V [A] 25 25 40 40 50 55 60 70 75 100 110 135 140

200/240V [A] 11 13 18 25 32 35 40 55 63 65 75 85 95

380/400V [A] 9 12 18 25 32 35 40 50 63 65 75 85 95

415V [A] 9 12 18 25 32 35 40 50 63 65 75 85 95

440V [A] 9 12 18 25 32 35 40 50 63 65 75 85 95

500V [A] 7 12 13 22 28 30 32 43 45 60 64 75 85

690V [A] 5 9 9 18 20 21 23 28 30 35 42 45 50

UL 508

NEMA size 00 - 0 - 1 - 1P 2 - - - 3 -

Rated thermal current (Ith) [A] 25 25 40 40 50 55 65 70 75 100 110 135 140

Single Phase

115V [HP] 1/2 3/4 1 2 2 2 3 3 5 5 5 7.5 10

230V [HP] 1.5 2 3 3 5 5 7.5 10 10 15 15 15 20

Three Phase

200V [HP] 2 3 5 7.5 7.5 10 15 20 20 25 25 30 30

230V [HP] 3 5 7.5 10 10 15 20 25 25 30 30 40 40

460V [HP] 5 7.5 10 15 20 25 30 40 40 50 50 60 75

575V [HP] 7.5 10 15 20 25 30 40 50 50 60 60 75 75

IEC947-4-1

Rated making capacity AC-3 250 250 250

Rated breaking capacity AC-3 200 200 200

Mechanical durability (M of cycles) 15 15 15 15 15 12 12 12 12 12 12 12 12

Electrical life for Ie/AC-3 max (M of cycles) 2.5 2.5 2.5 2.5 2.5 2 2 2 2 2 2 2 2

Maximum cycles per hour 1800 1800 1800 1800 1800 1200 1200 1200 1200 1200 1200 1200 1200

AC control coil voltage operated contactors

Weight [lbs] 0.99 2.07 4.00

Dimensions (W x H x D) [in] 1.77 x 3.27 x 3.66 2.17 X 4.17 X 4.80 2.76 X 5.51 X 5.39

Coil ConsumptionInrush [VA] 80 120 220

Holding [VA] 9 7 16

DC control coil voltage operated contactors

Weight [lbs] 1.39 2.64 5.94

Dimensions (W x H x D) [in] 1.77 x 3.27 x 4.65 2.17 X 4.17 X 6.32 2.76 X 5.51 X 6.79

Coil ConsumptionInrush [VA] 7 9 18

Holding [VA] 7 9 18

MIRAContactor Specifications3-Pole, 9~95 Amp ContactorsAC or DC Coil Voltages NEMA Sized

Relay type MTK-32 MTK-63 MTK-95

Tripping class (IEC 60947-4-1) 10 10 10 10 10

Number of poles 3 3 3 3 3

Rated operational voltage (Ue) Up to 690V Up to 690V Up to 690V Up to 690V Up to 690V

Rated insulation voltage (Ui) 690V 690V 690V 690V 690V

Rated impulse voltage (Uimp) 6kV 6kV 6kV 6kV 6kV

Temperature compensation °C -5 ~ 40 -5 ~ 40 -5 ~ 40 -5 ~ 40 -5 ~ 40

Dimensions (W x H x D) [in] 2.1 x 1.8 x 3.4 2.8 x 2.2 x 3.8 3.3 x 2.8 x 4.2

Weight (kg) 0.17 0.31 0.31 0.48 0.48

Functions

Differential, Phase Failure • • • • •

Trip Indicating • • • • •

Stop • • • • •

Test • • • • •

Manual/Automatic Reset • • • • •

Terminal type Screw clamp Screw Lug Screw Lug

MIRA

ALLEN BRADLEY

Electric Life

2.5 Million Up to 95A

Up to 63A 1.3 Million

1.5 Million

Standards

Safety Cover

Auxilary Contacts

Spring Loaded Screw Terminals

Matching UL Type F MMS

Spring Loaded Screw Terminals

5 Year Warranty

5 Year Warranty

5 Year Warranty

Matching UL Type F MMS

Up to 63A Matching UL Type F MMS

Auxilary Contacts

Spring Loaded Screw Terminals

Auxilary Contacts

Safety Cover

Safety Cover

Electric Life

Standards

Electric Life

Standards

*These�comparisons�are�based�on�published�marketing�information�from�manufacturers.��If�any�company�or�their�representative�notices�a�factual�discrepancy,�please�contact�Cerus�to�ensure�accuracy�and�timely�correction.��Allen-Bradley�and�Square�D�are�trademarks�of�their�respective�companies�and�these�companies�are�not�affiliates�of�Cerus�Industrial.��

TM

TM

TM

Overload Specifications9~95 Amp OverloadsDifferential Class 10

CONTACTORS & OVERLOADS

NEMA Sized

NEMA Sized

NEMA Sized

Page 5: West Coast Power Cerus Catalog

8

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 9

MIRA Contactors & Overload Relays Contactors 32AF 63AF 95AF Motor Voltage Horsepower Horsepower Horsepower

Single Phase

115V 1/2 3/4 1 2 2 2 3 3 5 5 5 7.5 10

230V 1.5 2 3 3 5 5 7.5 10 10 15 15 15 20

Three Phase

200V 2 3 5 7.5 7.5 10 15 20 20 25 25 30 30

230V 3 5 7.5 10 10 15 20 25 25 30 30 40 40

460V 5 7.5 10 15 20 25 30 40 40 50 50 60 75

575V 7.5 10 15 20 25 30 40 50 50 60 60 75 75

NEMA Size 00 0 - 1 - - 2 - - - 3 -

AC Contactors MRC-9 MRC-12 MRC-18 MRC-25 MRC-32 MRC-35L MRC-40L MRC-50L MRC-63L MRC-65L MRC-75L MRC-85L MRC-95L

DC Contactors MRD-9 MRD-12 MRD-18 MRD-25 MRD-32 MRD-35L MRD-40L MRD-50L MRD-63L MRD-65L MRD-75L MRD-85L MRD-95L

Reversing Kits MR-02 MR-02 MR-02 MR-02 MR-02 MR-02 MR-02 MR-02 MR-02 MR-02 MR-02 MR-02 MR-02

UW-32 UW-32 UW-32 UW-32 UW-32 UW-63 UW-63 UW-63 UW-63 UW-95 UW-95 UW-95 UW-95

Overload Relays 32AF 63AF 95AFSetting Range Part Number Setting Range Part Number Relay Setting Range Part Number

0.1~0.16 MTK-32/3-0.16 4~6 MTK-63/3-6L 7~10 MTK-95/3-10L

0.1~0.25 MTK-32/3-0.25 5~8 MTK-63/3-8L 9~13 MTK-95/3-13L

0.25~0.4 MTK-32/3-0.4 6~9 MTK-63/3-9L 12~18 MTK-95/3-18L

0.4~0.63 MTK-32/3-0.63 7~10 MTK-63/3-10L 16~22 MTK-95/3-22L

0.63~1 MTK-32/3-1 9~13 MTK-63/3-13L 18~25 MTK-95/3-25L

1~1.6 MTK-32/-3-1.6 12~18 MTK-63/3-18L 24~36 MTK-95/3-36L

1.6~2.5 MTK-32/3-2.5 16~22 MTK-63/3-22L 28~40 MTK-95/3-40L

2.5~4 MTK-32//3-4 18~25 MTK-63/3-25L 34~50 MTK-95/3-50L

4~6 MTK-32/3-6 24~36 MTK-63/3-36L 45~65 MTK-95/3-65L

5~8 MTK-32/3-8 28~40 MTK-63/3-40L 54~75 MTK-95/3-75L

6~9 MTK-32/3-9 34~50 MTK-63/3-50L 63~85 MTK-95/3-85L

7~10 MTK-32/3-10 45~65 MTK-63/3-65L 70~95 MTK-95/3-95L

12~18 MTK-32/3-18

16~22 MTK-32/3-22

18~25 MTK-32/3-25

22~32 MTK-32/3-32

Coil Voltage Options

AC Coil VoltagesVoltage 24VAC 120VAC 208VAC 220VAC 240VAC 277VAC 380VAC 480VAC 600VAC

Frequency 50/60Hz 50/60Hz 60Hz 50/60Hz 50/60Hz 60Hz 50/60Hz 60Hz 60Hz

DC Coil Voltages Voltage 12VDC 24VDC 48VDC 110VDC

� Finger safe terminals � Interchangeable replacement coils � Standard 1NO/1NC auxiliary contacts

� Mounts directly to MIRA contactors � Differential thermal protection detects phase loss � Adjustable current setting, Hand or Auto reset

Auxiliary ContactsDescription Part Number

Side mount MA-1 (1NO�&�1NC)

Top mount CA-2 (Specify�2NO,�2NC,�or�1NO�&�1NC)

Top mount CA-4 (Specify�4NO,�4NC,�2NO�&�2NC,�3NO�&�1NC,�or�1NO�&�3NC)

CONTACTORS & OVERLOADS

Page 6: West Coast Power Cerus Catalog

10 www.westcoastpower.com 1-866-955-0888

Replacement AC Contactor CoilsFrame Size Coil Voltage Part Number

9-32

24VAC MC9-32 24V 50/60HZ

48VAC MC9-32 48V 50/60HZ

120VAC MC9-32 120V 50/60HZ

208VAC MC9-32 208V 60HZ

220VAC MC9-32 220V 50/60HZ

240VAC MC9-32 240V 50/60HZ

277VAC MC9-32 277V 60HZ

380VAC MC9-32 380V 50/60HZ

480VAC MC9-32 480V 60HZ

600VAC MC9-32 600V 60HZ

35-63

24VAC MC35-63 24V 50/60HZ

48VAC MC35-63 48V 50/60HZ

120VAC MC35-63120V 50/60HZ

208VAC MC35-63 208V 60HZ

220VAC MC35-63 220V 50/60HZ

240VAC MC35-63 240V 50/60HZ

277VAC MC35-63 277V 60HZ

380VAC MC35-63 380V 50/60HZ

480VAC MC35-63 480V 60HZ

600VAC MC35-63 600V 60HZ

65-95

24VAC MC65-95 24V 50/60HZ

48VAC MC65-95 48V 50/60HZ

120VAC MC65-95 120V 50/60HZ

208VAC MC65-95 208V 60HZ

220VAC MC65-95 220V 50/60HZ

240VAC MC65-95 240V 50/60HZ

277VAC MC65-95 277V 60HZ

380VAC MC65-95 380V 50/60HZ

480VAC MC65-95 480V 60HZ

600VAC MC65-95 600V 60HZ

Replacement DC Contactor CoilsFrame Size Coil Voltage Part Number

9-32

12VDC MC9-32 12VDC

24VDC MC9-32 24VDC

48VDC MC9-32 48VDC

110VDC MC9-32 110VDC

35-63

12VDC MC35-63 12VDC

24VDC MC35-63 24VDC

48VDC MC35-63 48VDC

110VDC MC35-63 110VDC

65-95

12VDC MC65-95 12VDC

24VDC MC65-95 24VDC

48VDC MC65-95 48VDC

110VDC MC65-95 110VDC

Mechanical and Electrical InterlockFrame Size Part Number

32AF~95AF MR-02

Capacitor Auxiliary UnitsFrame Size Part Number

32AF~63AF AC-9

95AF AC-50

AC/DC Surge SuppressorVoltage Part Number

24-48VAC MS-1

100-125VAC MS-2

200-240VAC MS-3

24-48VDC MS-4

100-125VDC MS-5

200-220VDC MS-6

24-48VAC/VDC MS-11

100-125VAC/VDC MS-12

200-240VAC/VDC MS-13

380-440VAC/VDC MS-14

Mechanical Latch UnitVoltage Part Number

AC Operated Units 100~127V 50/60Hz AL-9 100VAC

200~240V 50/60Hz AL-9 200VAC

460~500V 50/60Hz AL-9 500VAC

100~127V 50/60Hz AL-50 100VAC

200~240V 50/60Hz AL-50 200VAC

460~500V 50/60Hz AL-50 500VAC

DC Operated UnitsDC24V AL-9 24VDC

DC24V AL-50 24VDC

DIN Rail AdaptersFrame Size Part Number

32AF UZ-32

63AF UZ-63/L

63AF UZ-63/S

95AF UZ-95/L

95AF UZ-95/S

MIRAAccessories

INDUSTRIAL CATALOG

Installs�in�Minutes,�Lasts�a�Lifetime � 100~800 Amp Rated Models � High Reliability: Up to 25 Million Cycles � Superior Value � Our Contactors Are Among the Highest

Rated in the Industry for UL Sizes. � 5-Year Warranty

ORION Contactors and Overloads

“We like the flexibility of Orion contactors. Their universal coils are unique because they accept a wide range of voltages – I don’t have to stock a bunch of different sized coils.”

Page 7: West Coast Power Cerus Catalog

12

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 13

Quiet, Reliable Switching For Tough Applications � Long-term reliability thanks to large contact surface areas, advanced metallurgy and oversized magnetics � Among the highest current ratings in the industry for UL sizes � Heavy -duty construction eliminates buzzing and poor switching � Electronic coil reduces in-rush and holding current, integrates protective surge suppression and prevents

coil failures due to mechanical faults.

Reduced Inventory Carrying Costs � Pre-installed auxiliary contacts included standard with each contactor (2NO & 2NC) � Wide voltage range AC/DC coil reduces inventory and offers flexible installation solutions

Frame Size 100AF 150AF 220AF 400AF 600AF

Model CRC-100 CRC-125 CRC-150 CRC-180 CRC-220 CRC-300 CRC-400 CRC-600 CRC-800

Number of poles 3 3 3 3 3

Rated operational voltage, Ue 690V 690V 690V 690V 690V

Rated operational current Ie (θ≤ 55 °C)

AC-1AC-3

Ue max 690V [A] 150 150 200 230 260 350 420 660 900

200/240V [A] 105 125 150 180 250 300 400 630 800

380/440V [A] 105 120 150 180 250 300 400 630 800

500V/550V [A] 85 90 140 180 200 250 350 500 720

690V [A] 65 70 100 120 150 220 300 420 630

UL 508

NEMA size - - 4 - - 5 - 6 -

Rated thermal current (Ith) [A] 160 160 210 230 275 350 450 660 900

Single Phase

115V [HP] 7.5 10 15 15 15 - - - -

230V [HP] 15 20 25 30 40 - - - -

Three Phase

200V [HP] 30 40 40 60 60 100 125 150 250

230V [HP] 30 40 50 60 75 100 150 200 300

460V [HP] 60 75 100 125 150 200 300 400 600

575V [HP] 60 75 100 125 150 200 300 400 600

AC/DC control coil voltage operated contactors

Weight [lbs] 6.7 7.9 13.5 22 52

Dimensions (W x H x D) [in] 3.9 x 6.5 x 5.8 4.7 x 6.9 x 6.2 5.4 x 8.0 x 7.1 6.4 x 9.6 x 7.8 11.2 x 12.3 x 9.5

Coil ConsumptionInrush [VA] 220 393 1000

Holding [VA] 9.1 14 17

Contactor Specifications100~800 Amp ContactorsWide Range, Common Coils (AC & DC)

ORION

NEMA Sized

Thermal Overload Options � Mounts directly to contactor or standalone (screw mount) � Overload includes NO & NC trip contacts � Differential phase failure protection � Ambient compensated (-5º to 40ºC)

Easy Installation � Thermal overload relays matched for simple, direct connection with busbars � Standard 1NO & 1NC auxiliary contacts on each overload relay � Optional finger-proof safety covers

Frame Size CTK-100 CTK-150 CTK-220 CTK-400 CTK-600

Tripping class (IEC 60947-4-1) 10 10 10 10 10

Number of poles 3 3 3 3 3

Rated operational voltage (Ue) Up to 690V Up to 690V Up to 690V Up to 690V Up to 690V

Rated insulation voltage (Ui) 690V 690V 690V 690V 690V

Rated impulse voltage (Uimp) 6kV 6kV 6kV 6kV 6kV

Temperature compensation °C -5 ~ 40 -5 ~ 40 -5 ~ 40 -5 ~ 40 -5 ~ 40

Weight [lbs] 1.4 1.8 5.9 7 30

Functions

Differential, Phase Failure • • • • •

Trip Indicating • • • • •

Stop • • • • •

Test • • • • •

Manual/Automatic Reset • • • • •

Terminal type Screw Screw Screw Screw Screw

Overload Specifications100~800 Amp OverloadsDifferential Class 10

ORION

CONTACTORS & OVERLOADS

Page 8: West Coast Power Cerus Catalog

14

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 15

ORION Contactors & Overload RelaysContactors 100AF 150AF 220AF 400AF 800AF

Motor Voltage HP HP HP HP HP

Single Phase

115V 7.5 10 15 15 16 - - - -230V 15 20 25 30 40 - - - -

Three Phase

200V 30 40 40 60 60 100 125 150 200230V 30 40 50 60 75 100 150 200 300460V 60 75 100 125 150 200 300 400 600575V 60 75 100 125 150 200 300 400 600

NEMA Size 4 5 6AC/DC Contactors CRC-100 CRC-125 CRC-150 CRC-180 CRC-220 CRC-300 CRC-400 CRC-600 CRC-800

Contactor Lug Kits* AJ-125 AJ-125 AJ-150 AJ-220 AJ-220 AJ-400 AJ-400 AJ-600 AJ-600

Reversing Kits* AR-100 AR-100 AR-100 AR-180 AR-180 AR-180 AR-180 AR-600 AR-600

CRC-100R CRC-100R CRC-150R CRC-220R CRC-220R CRC-400R CRC-400R - -

Overload Relays 100AF 150AF 220AF 400AF 800AF

Setting Range Part Number

34-50 CTK-100/3-50 CTK-150/3-50

39-57 CTK-100/3-57 CTK-150/3-57

43-65 CTK-100/3-65 CTK-150/3-65

54-80 CTK-100/3-80 CTK-150/3-80

65-100 CTK-100/3-100 CTK-150/3-100 CTK-220/3-100

85-125 CTK-100/3-125 CTK-150/3-125 CTK-220/3-125 CTK-400/3-125

100-150 CTK-150/3-150 - -

100-160 CTK-220/3-160 CTK-400/3-160

120-180 CTK-220/3-180 CTK-400/3-180

160-240 CTK-220/3-240 CTK-400/3-240

220-300 CTK-400/3-300

260-400 CTK-400/3-400

200-300 CTK-600/3-300

260-400 CTK-600/3-400

400-600 CTK-600/3-600

520-800 CTK-600/3-800

Reversing�assemblies�are�easy�with�the�Orion�Series�Reversing�Kit�which��includes�adapter�plate�and�mechanical�interlock.

*Products�ship�disassembled.‡For�4-Pole�configurations�consult�factory.

Replacement Contactor CoilsVoltage Frame Size Part Number

24-25V 100AF & 150AF CRC150C-24V

100-240V 100AF & 150AF CRC150C-100-200V

440-575V 100AF & 150AF CRC150C-500V*

24-25V 220AF CRC220C-24V

100-240V 220AF CRC220C-100-200V

440-575V 220AF CRC220C-500V*

100-240V 400AF CRC400C-100-200V

440-575V 400AF CRC400C-500V*

100-127V 600AF CRC800C-100V

200-240V 600AF CRC800C-200V

440-575V 600AF CRC800C-500V*

Latching Units AC Coil Operated Units

Voltage Frame Size Part Number

100~127V 50/60Hz 100AF AL-100 100VAC

200~240V 50/60Hz 100AF AL-100 200VAC

460~550V 50/60Hz 100AF AL-100 500VAC

100~127V 50/60Hz 150AF AL-150 100VAC

200~240V 50/60Hz 150AF AL-150 200VAC

460~550V 50/60Hz 150AF AL-150 500VAC

100~127V 50/60Hz 220AF AL-180 100VAC

200~240V 50/60Hz 220AF AL-180 200VAC

460~550V 50/60Hz 220AF AL-180 500VAC

100~127V 50/60Hz 400AF AL-400 100VAC

200~240V 50/60Hz 400AF AL-400 200VAC

460~550V 50/60Hz 400AF AL-400 500VAC

DC Coil Operated UnitsVoltage Frame Size Part Number

DC24V 100AF AL-100 24VDC

DC24V 150AF AL-150 24VDC

DC24V 220AF AL-180 24VDC

DC24V 400AF AL-400 24VDC

Terminal Cover Units Frame Size Part Number

100AF AP-100/125

150AF AP-150

220AF AP-180/220

400AF AP-300/400

600AF AP-600/800

100AF APT-100

150AF APT-150

220AF APT-220

400AF APT-400

600AF APT-600

*AC�Coil�Voltage�only�

Surge Suppressors Voltage Part Number

0~48VAC/DC AS-11

48~120VAC/DC AS-12

120~240VAC/DC AS-13

AccessoriesORION

The�Orion�contactor’s��standard�electronic�coil�accepts�either�AC�or�DC�voltages.

CONTACTORS & OVERLOADS

Page 9: West Coast Power Cerus Catalog

MIRA Manual Motor Starters � Compact Design � High Interruption Capacity � Reduces Overall Installed Cost � 32~100 Amp Frame Sizes

The�OEM�Solution�for�Motor�Controls�

The�Cerus�MMS�insulated�busbar�system�allows�you�to�feed�several�modular�circuit�breakers�on�a�standard�mounting�rail.�

Quality Design Carefully engineered to improve reliability, the advanced flexibility of MIRA components allow for seamless integration with Cerus’ Manual Motor Starters (MMS) and accessories. With coordinated ratings as a combination starter meeting both UL and IEC Type 2 standards, the MIRA design provides an unbeatable combination reducing installation costs and saving valuable panel space.

High Reliability Only contactors and breakers tested to UL standards as a unit can achieve the highest coordinated interrupt ratings. Cerus MMS carry UL Type E and F ratings when paired with MIRA contactors meeting standards for both group motor protection and self-protection when used as a combination starter.

Easy Mounting Accessories Cerus MMS have a full range of optional accessories including base plates, auxiliary contacts, alarm switches, shunts and under voltage releases. The simplified mounting of the Cerus MMS allows for fast and easy integration with bus bars and MIRA contactors.

� Up to 100,000 Amps Short Circuit Interrupting Current Rating � Available in Standard & High-Break Versions � Lockable Handle Operator and Finger Safe Terminals � Exceeds UL Standards for Group and Combination Motor Applications

(UL Type E & F Ratings with Cerus MIRA Contactors) � Universal Accessories Reduce Inventory � Optional Waterproof Enclosure

“We saved money and space by installing Cerus Manual Motor Starters which eliminated costly fuse blocks for branch protection in our multi-motor control panels.”

Page 10: West Coast Power Cerus Catalog

18

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 19

Rated Operational Current (A)

Thermal Release

Adjustment Range (A)

Magnetic Release

Operating Current (A)

Horsepower Standard Trip‡ High Break Trip Magnetic Trip Only

Single Phase Three Phase SCIC (kA)*Part Number

SCIC (kA)Part Number Part Number

115V 230V 200V 230V 460V 575V 240V kA 480V kA 600V kA 240V kA 480V kA 600V kA

32 AF Manual Motor Starters0.16 0.1-0.16 2.1 - - - - - - 100 50 10 CMS-32S-0.16 100 65 25 CMS-32H-0.16 CMS-32HI-0.160.25 0.16-0.25 3.3 - - - - - - 100 50 10 CMS-32S-0.25 100 65 25 CMS-32H-0.25 CMS-32HI-0.250.4 0.25-0.4 5.2 - - - - - - 100 50 10 CMS-32S-0.4 100 65 25 CMS-32H-0.4 CMS-32HI-0.4

0.63 0.4-0.63 8.2 - - - - - - 100 50 10 CMS-32S-0.63 100 65 25 CMS-32H-0.63 CMS-32HI-0.631 0.63-1 13 - - - - - 1/2 100 50 10 CMS-32S-1 100 65 25 CMS-32H-1 CMS-32HI-1

1.6 1-1.6 20.8 - 1/10 - - 3/4 3/4 100 50 10 CMS-32S-1.6 100 65 25 CMS-32H-1.6 CMS-32HI-1.62.5 1.6-2.5 32.5 - 1/6 1/2 1/2 1 1.5 100 50 10 CMS-32S-2.5 100 65 25 CMS-32H-2.5 CMS-32HI-2.54 2.5-4 52 1/8 1/3 3/4 3/4 2 3 100 50 5 CMS-32S-4 100 65 25 CMS-32H-4 CMS-32HI-46 4-6 78 1/4 1/2 1 1.5 3 5 100 25 5 CMS-32S-6 100 65 25 CMS-32H-6 CMS-32HI-68 5-8 104 1/3 1 2 2 5 5 100 25 5 CMS-32S-8 100 65 25 CMS-32H-8 CMS-32HI-8

10 6-10 130 1/2 1.5 2 3 5 7.5 50 10 5 CMS-32S-10 100 65 25 CMS-32H-10 CMS-32HI-1013 9-13 169 1/2 2 3 3 7.5 10 50 10 5 CMS-32S-13 100 65 25 CMS-32H-13 CMS-32HI-1317 11-17 221 1 3 3 5 10 15 40 10 5 CMS-32S-17 100 30 10 CMS-32H-17 CMS-32HI-1722 14-22 286 1.5 3 5 7.5 15 20 30 10 5 CMS-32S-22 100 30 10 CMS-32H-22 CMS-32HI-2226 18-26 338 2 3 7.5 7.5 15 20 30 7.5 5 CMS-32S-26 100 30 10 CMS-32H-26 CMS-32HI-2632 22-32 416 2 5 7.5 10 20 30 20 7.5 5 CMS-32S-32 100 30 10 CMS-32H-32 CMS-32HI-32

63 AF Manual Motor Starters10 6-10 130 1/2 1.5 2 3 5 7.5 100 50 10 CMS-63S-10 100 65 25 CMS-63H-10 CMS-63HI-1013 9-13 169 1/2 2 3 3 7.5 10 100 50 10 CMS-63S-13 100 65 25 CMS-63H-13 CMS-63HI-1317 11-17 221 1 3 3 5 10 15 100 40 10 CMS-63S-17 100 50 10 CMS-63H-17 CMS-63HI-1722 14-22 286 1.5 3 5 7.5 15 20 100 40 10 CMS-63S-22 100 50 10 CMS-63H-22 CMS-63HI-2226 18-26 338 2 3 7.5 7.5 15 20 100 40 10 CMS-63S-26 100 50 10 CMS-63H-26 CMS-63HI-2632 22-32 416 2 5 7.5 10 20 30 100 40 10 CMS-63S-32 100 50 10 CMS-63H-32 CMS-63HI-3240 28-40 520 3 7.5 10 10 30 30 100 40 10 CMS-63S-40 100 50 10 CMS-63H-40 CMS-63HI-4050 34-50 650 3 10 15 15 30 40 100 40 10 CMS-63S-50 100 50 10 CMS-63H-50 CMS-63HI-5063 45-63 819 5 10 20 20 40 60 100 40 10 CMS-63S-63 100 50 10 CMS-63H-63 CMS-63HI-63

100 AF Manual Motor Starters17 11-17 221 1 3 3 5 10 15 100 50 10 CMS-100S-17 100 65 25 CMS-100H-17 CMS-100HI-1722 14-22 286 1.5 3 5 7.5 15 20 100 50 10 CMS-100S-22 100 65 20 CMS-100H-22 CMS-100HI-2226 18-26 338 2 3 7.5 7.5 15 20 100 50 10 CMS-100S-26 100 65 20 CMS-100H-26 CMS-100HI-2632 22-32 416 2 5 7.5 10 20 30 100 50 10 CMS-100S-32 100 65 20 CMS-100H-32 CMS-100HI-3240 28-40 520 3 7.5 10 10 30 30 100 50 10 CMS-100S-40 100 65 20 CMS-100H-40 CMS-100HI-4050 34-50 650 3 10 15 15 30 40 100 50 10 CMS-100S-50 100 65 20 CMS-100H-50 CMS-100HI-5063 45-63 819 5 10 20 20 40 60 100 40 10 CMS-100S-63 100 50 10 CMS-100H-63 CMS-100HI-6375 55-75 975 5 15 20 25 50 60 100 40 10 CMS-100S-75 100 50 10 CMS-100H-75 CMS-100HI-7590 70-90 1170 7.5 20 25 30 60 75 100 40 10 CMS-100S-90 100 50 10 CMS-100H-90 CMS-100HI-90

100 80-100 1300 10 20 30 30 75 100 100 40 10 CMS-100S-100 100 50 10 CMS-100H-100 CMS-100HI-100

*�UL�ratings�for�combination�manual�motor�controller�with�Cerus�Mira�contactors.‡ CMS-32S�are�UL�listed�as�a�manual�motor�controller�only,�and�are�not�UL�Type�E,�manual�self-protected�combination�motor�controller.

H=3.70”

D=2.95”

W=1.77”

CMS-32S

H=3.70”

D=3.90”

W=1.77”

CMS-32H

H=5.51”

D=5.69”

W=2.17”

CMS-63HManual Motor Starters32~100 Amp Frame SizesStandard & High BreakAdjustable Thermal or Magnetic Trip

� Differential Class 10 Thermal Overload � Phase Failure Protection � Ambient Temperature Compensation

H=6.50”

D=6.73”

W=2.76”

CMS-100H

MANUAL MOTOR STARTERS

Page 11: West Coast Power Cerus Catalog

20

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 21

Side Auxiliary Switch & Magnetic Trip Alarm Switch

� Side mounting on the left � 2-pole (1NO, 1NC) � One side mounting module

per circuit breaker (Always directly fitted to the circuit breaker except using with Any Trip Alarm Switch)

Front Auxiliary Switch � Front mounting � 2-pole (1NO, 1NC) � One front mounting module per

circuit breaker

Shunt Release & Undervoltage Release with Auxiliary (2NO)

� Side mounting on the right � One side mounting module per

circuit breaker (Always directly fitted to the circuit breaker)

Manual Motor StarterAccessories

MMS Auxiliaries Description Part Number

Front Auxiliary Switch FX-1NO-1NC

Side Auxiliary Switch LX-1NO-1NC

Magnetic Trip Alarm Switch LAM-1NO-1NC

Any Trip Alarm Switch LA-1NO-1NC (32AF�size�only)

Shunt Release RS-(specify�voltage�rating�using�chart�below)�

Undervoltage Release RU-(specify�voltage�rating�using�chart�below)�

Undervoltage Release with Auxiliary (2NO) RUX-(specify�voltage�rating�using�chart�below)�

AC Voltage 28VAC 120VAC 260VAC 480VAC

Frequency/ Range

24V @ 50Hz 28V @ 60Hz

110-127V @ 50Hz 120V @ 60Hz

220-230V @ 50Hz240-260V @ 60Hz

415-440V @ 50Hz460-480V @ 60Hz

IP65 Enclosure (NEMA 4X)Frame Size Part Number

32AF CI-EPH32-65S

� Insulated bus-bar system � Feed several modular circuit

breakers on standard mounting rails

� Rugged, heavy-duty impact-resistant plastic case � Rotary switch includes lockable handle for up to 3 padlocks � Convenient standard knockouts for easy installation � Incorporates neutral and ground busbars for easy wiring

Through the Door OperatorFrame Size Shaft Length Part Number

32AF 115 CI-MEH-32/115

63AF 115 CI-MEH-63/115

95AF 115 CI-MEH-100/115

32AF 315 CI-MEH-32/315

63AF 315 CI-MEH-63/315

95AF 315 CI-MEH-100/315

� Door interlocking mechanism (defeatable) � Accommodates up to 3 padlocks for lockout � Available in 115mm & 315mm shaft lengths

Phase Bus DevicesFrame Size Description Part Number

32AF 2-Position CPB-322

63AF 2-Position CPB-632

32AF 3-Position CPB-323

63AF 3-Position CPB-633

32AF Plastic Cover CPBPC-32

63AF Plastic Cover CPBPC-63

� Direct Adapter and Mounting Unit allow complete integration of Manual Motor Starter and Contactor

� Reduce labor associated with wiring and mounting components

MMS Direct Adapters & Mounting UnitsFrame Size Part Number

AC Operated Units 32AF DA-32SA

32AF DA-32HA

63AF DA-63A

95AF DA-95A

Frame Size Part Number

DC Operated Units 32AF DA-32SD

32AF DA-32HD

63AF DA-63D

95AF DA-95D

Frame Size Part Number

Mounting Units 32AF MU-45

63AF MU-55

95AF MU-70

� Reduce wiring and feed multiple manual motor starters

� Space saving, easy installation

Manual Motor StarterAccessories

MANUAL MOTOR STARTERS

Page 12: West Coast Power Cerus Catalog

22

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 23

Digital Motor Protection Relays & AccessoriesSetting Range Connection Part Number*

0.5-6A Screw Terminals CDP06-S

5-60A Screw Terminals CDP60-S

0.5-6A Tunnel CDP06-T

5-60A Tunnel CDP60-T

SpecificationsWiring Connection Screw or tunnel

Mounting 35mm DIN or screw mount Panel Mount Display On unit or with cable extension

Trip time curve Inverse curve/Definite timeReset Manual Reset

Display LED & Bar-graphAlarm Variable (60-110% of the setting current)

Current setting ranges 0.5-6A, 5-60AInsulation resistance Over DC 500V 100Ω

Surge impulse voltage (IEC1000-4-5) 1.2 x 50μs 6kV (apply standard wave form)Trip Class Inverse trip delay Class 1-60

ProtectiveFunctions

Overcurrent AdjustableUndercurrent 3 secondsPhase Failure 3 seconds

Phase Unbalance 5 secondsPhase Reversal Within 0.1 seconds

Stall 5 secondsLocked rotor Within 0.5 secondsGround fault 0.05~1 second

Definite Time Settings

Start delay 0-60 secondsOperating delay 0-30 seconds

ToleranceCurrent ±5%

Time ±5% (or ±0.5 sec.)

Operating Power

Voltage AC 110-120VFrequency 60Hz (50Hz)

Auxiliary Contacts

Overload (2-SPST) 3A/250VAC resistive loadAlarm (SPST) 3A/250VAC resistive load

Operating Environment

Operating Temperature -25° ~ 60°CStorage Temperature -30° ~ 70°C

Humidity 30-90% Relative Humidity (non-condensing)

Complete Motor Protection & Monitoring � Excellent motor protection against under/over-current,

stall, phase failure, phase unbalance and phase reversal � Ground fault and instantaneous short circuit options � Inverse time or definite time limit selection for precise

control of trip characteristics � LED display indicates fault type

Digital Motor Protection Relays0.5~60AAdjustable Class 1-60LED Display

Under current Reverse phase

Phase fall Ground fault

Stall Short circuit

Lock

Fault�conditions�are�clearly�displayed�on�the�DMPR’s�7-segment�LED�interface.

Versatile Installation � Removable terminal base allows integrated display

to be door-mounted with cable extension � Screw or tunnel-type models available

DMPR AccessoriesDescription Part Number*

Ground Fault Current Sensor

ZCT D30 (30mm opening)

ZCT D50 (50mm opening)

ZCT D65 (65mm opening)

ZCT D80 (80mm opening)

Remote Mounting

Cable

CDP-CABLE-1M (1 meter)

CDP-CABLE-2M (2 meter)

CDP-CABLE-3M (3 meter)

*�For�ground�fault�detection,�part�number�is�followed�with�“Z”�and�requires�a�current�sensor�selected�from�table�above.

RELAYS, OVERLOADS, MINI CONTACTORS

Phase Protection � Phase current unbalance: trips within 5 seconds

when the phase current unbalance exceeds 50% � Phase loss/phase failure: trips within 3 seconds

when phase current is 70% unbalanced � Phase reversal: trips within 1 second in the event

of reverse phase current or mis-wiring � Wide range current adjustment

and Class1-30 adjustment fits any application

Easy Installation � Mounts to 35mm DIN-Rail through screw

terminals and tunnel type terminal in single unit

Fully Adjustable Overload Relay � Three models cover ¼ HP to 60 HP for reduced

stocking and flexibility � 1-5A range can be used with external CTs to

cover applications over 80A � Built-in stall protection provides maximum

protection to the motor (trips at 170% of full load amps at 3 seconds)

Electronic Overloads0.3~80AAdjustable Class 1-30Microprocessor Based

SpecificationsWiring Connection Screw, tunnel or pin

Mounting 35mm DIN, screw or directTrip time curve Inverse curve

Reset Manual Reset

Display Trip LED indicator

Current setting ranges 0.3-80A, Model specificTrip Class Inverse trip delay Class 1-30

ProtectiveFunctions

Overcurrent AdjustablePhase Failure 3 seconds

Phase Unbalance 5 secondsPhase Reversal Optional

Stall 5 seconds

ToleranceCurrent ±5%

Time ±5% (or ±0.5 sec.)

Operating Power

Voltage AC 100-260VFrequency 50Hz/60Hz

Auxiliary Contacts

Contact 2 SPDT (when power applied)Ratings 3A/250VAC resistive load

Operation 1 N.O. & 1 N.C.

Operating Environment

Operating Temperature -25° ~ 60°CStorage Temperature -30° ~ 70°C

Humidity 30-90% Relative Humidity (non-condensing)

Electronic OverloadsConnections Mounting Part Number Setting Range

Pin Direct CRP22-3P- 0.3-1.5A1-5A

4.4-22AScrew DIN/Screw CRP22-3S-

Tunnel DIN/Screw CRP22-3T-

Pin Direct CRP40-3P-4-20A 8-40AScrew DIN/Screw CRP40-3S-

Tunnel DIN/Screw CRP40-3T-

Screw Direct/DIN/Screw CRP80-3S- 16-80A

LED Indicator

Status Indication- Normal- Overload- Phase Unbalance

Fault Indication- Overcurrent- Phase loss- Reverse phase

Current Setting- Amp range varies based on model selected

Test/Reset Button

Trip Class Setting- 1 to 30 seconds

Page 13: West Coast Power Cerus Catalog

24

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 25

6A~12A Mini-Contactors6A 9A 12A

Rated Thermal Current 20 20 20

Motor Voltage115V 1/2 1/2 1230V 1/3 1.5 2200V 1/4 3 3230V 1/5 3 3460V 1/6 5 7.5575V 1/7 10 15

AC Contactors CMC-6M CMC-9M CMC-12MDC Contactors CMD-6M CMD-9M CMD-12M

AC Reversing CMC-6MR CMC-9MR CMC-12MRDC Reversing CMD-6MR CMD-9MR CMD-12MR

Setting Range Part Number

Overload Relays

0.1~0.16 CTK-12M/3-0.160.16~0.25 CTK-12M/ 3-0.250.25~0.4 CTK-12M/ 3-0.40.4~0.63 CTK-12M/ 3-0.630.63~1 CTK-12M/ 3-11~1.6 CTK-12M/ 3-1.6

1.6~2.5 CTK-12M/ 3-2.52.5~4 CTK-12M/ 3-44~6 CTK-12M/ 3-65~8 CTK-12M/ 3-86~9 CTK-12M/ 3-9

7~10 CTK-12M/ 3-109~13 CTK-12M/ 3-13

12~16 CTK-12M/ 3-16

� PLC compatible coils with lower holding current for cool operation

� Available thermal overloads attach without brackets � Standard mounting wither with screws or on 35mm

DIN rail � Pre-assembled and wired reversing

Economical, Compact & Reliable - The Perfect OEM Solution!

Coil Voltage Options

AC VoltagesVoltage 24VAC 120VAC 240VAC 480VAC

Frequency 50/60Hz 50/60Hz 60Hz 60Hz

DC Voltages Voltage 12V 24V 48V

Mini-Contactors & Overloads6~12A, 3-PoleStandard & Reversing35mm DIN or Screw Mount

Auxiliary ContactsDescription Part Number

2-Pole Auxiliaries (Top Mount)

CA-2M (1NO, 1NC)

CA-2M (2NO)

CA-2M (2NC)

4-Pole Auxiliaries (Top Mount)

CA-4M (2NO, 2NC)

CA-4M (3NO, 1NC)

CA-4M (4NO)

CA-4M (4NC)

� Economical open starter package pre-wired for contactor coil operation

� Wide selection of coil voltages

Expandable up to 8-Pole � Select DPDT, 3PDT or 4PDT variations � 44mm wide � Finger proof design

Specifications

Contact RatingsRated Current Making/Braking Current

Inductive Load Resistive Load Inductive Load Resistive Load

AC Duty

120V 6A 10A 66A 66A

240V 3A 8A 33A 33A

480V 1.5A 5A 16.5A 16.5A

600V 2A 5A 13.2A 13.2A

DC Duty

125V 1.1A 5A 3.7A -

250V 0.55A 3A 1.8A -

440V 0.31A 2.5A 1.4A -

600V 0.2A 1A 0.7A -

Continuous Current, Ith 16A

Performance

Operation cycle 1800 operations/hour

Endurance

Mechanical Durability 20 M operations

Electrical Life

AC15 duty220V 0.5 M operations

440V 0.5 M operations

AC12 duty220V 0.25 M operations

440V 0.25 M operations

DC13, 12 duty 24~220V 0.5 M operations

Mini-Contactor Control RelaysDescription Part Number

4-Pole AC Coil Relay CMC-6M/4 (2NO, 2NC)

4-Pole DC Coil Relay CMD-6M/4 (2NO, 2NC)

Additional Contacts

6-Pole

CA-2M (1NO, 1NC)

CA-2M (2NO)

CA-2M (2NC)

8-Pole

CA-4M (1NO, 3NC)

CA-4M (2NO, 2NC)

CA-4M (3NO, 1NC)

CA-4M (4NO)

CA-4M (4NC)

Mini-Contactor Control Relays4, 6 & 8-Pole Units16 Amp RatedStandard 44mm Size

� 16A continuous current, Ith

� DIN rail or screw mountable � AC/DC control voltage

Mini-contactor�relays�shown�with�additional�contacts�configured�for�multi-pole�operation.

RELAYS, OVERLOADS, MINI CONTACTORS

Page 14: West Coast Power Cerus Catalog

MIRA Breakers Low�voltage�circuit�breakers��

� High Breaking Capacity � Optimum Coordination Technique � Superior Overload Protection � Guaranteed Short Circuit Current Ratings � Wide Range of Optimized Auxiliaries and Accessories

“I have made a conscious effort to change all my breakers to the MIRA line. The solid protection and high interrupting ratings make Cerus our choice.”

Mechanism Unit � Optimum cam curve provides consistent

contact force during closing and opening of the breaker resulting in excellent current limiting and superior de-bounce for longer contact life.

High Interrupting Capacity � Up to 65KA on high interrupting

models at 480VAC. � UL489 Rated � IEC Listed

Arc-extinguishing Unit � Patented puffer assisted self-quenching arc chamber � Greatly reduces arc voltage compared to traditional

arc quenching technologies for higher interrupting performance.

High Performance

Page 15: West Coast Power Cerus Catalog

28

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 29

Superior Technology Results in High Performance � Cerus TD and TS circuit breakers provide superior performance in a compact package,

with adjustable thermal trip settings and magnetic trip settings for ultimate flexibility � Advanced arc quenching technology ensures excellent trip performance and long life � Standardized internal accessories are interchangeable on all models and are field or factory installed � Accessories mount on right or left side to simplify panel wiring

High Interrupting Capacity � Up to 65KA on high interrupting models at 480VAC

Simplified Range � Common mounting depths between frames 125A~800A � Four frame sizes from 40A~800A

Variety of Trip Units Available � FTU - Fixed thermal & magnetic � FMU- Adjustable thermal (0.8~1.0), fixed magnetic � ATU - Adjustable thermal (0.8~1.0) & magnetic (0.5~1.0)

Variable Accessories � Electrical auxiliaries � Extended rotary handle � Flange handle � Locking devices

High Interrupting capacity

TS800HU TS800NU

TS250HU

TS400NUTS400HU

TD125HU TD125NU

TS250NU

TD/TS Series Circuit Breakers3-Pole, 40~800 Amp RatedUL 489 Standards

TD/TS Series Circuit Breakers

Frame Size

Amp Rating

Thermal Trip

Setting

Magnetic Trip Setting

HU Series(High Interrupting)*

NU Series(Normal Interrupting)

125AF

40A 32-40A

10X

TD125HU FMU 125 40A TD125NU FMU 125 40A

50A 40-50A TD125HU FMU 125 50A TD125NU FMU 125 50A

60A 48-60A TD125HU FMU 125 60A TD125NU FMU 125 60A

80A 64-80A TD125HU FMU 125 80A TD125NU FMU 125 80A

100A 80-100A TD125HU FMU 125 100A TD125NU FMU 125 100A

125A 100-125A TD125HU FMU 125 125A TD125NU FMU 125 125A

250AF

160A 125-160A

5-10X

TS250HU ATU 250 160A TS250NU ATU 250 160A

200A 160-200A TS250HU ATU 250 200A TS250NU ATU 250 200A

250A 200-250A TS250HU ATU 250 250A TS250NU ATU 250 250A

400AF300A 250-300A

5-10XTS400HU ATU 400 300A TS400NU ATU 400 300A

400A 300-400A TS400HU ATU 400 400A TS400NU ATU 400 400A

800AF

500A 400-500A

5-10X

TS800HU ATU 800 500A TS800NU ATU 800 500A

600A 500-600A TS800HU ATU 800 600A TS800NU ATU 800 600A

800A 600-800A TS800HU ATU 800 800A TS800NU ATU 800 800A

SpecificationsTD125 TS250 TS400 TS800

Frame size (AF) 125 250 400 800

Rated current (A) 40,50,60,80,100,125 160,200,250 300,400 500,600,800

No. of Poles 3 3 3 3

Rated operational voltage, Ue AC (V) 600 600 600 600

UL interrupting rating (kA) NU HU NU HU NU HU NU HU

AC 50/60Hz

240V 50 100 50 100 50 100 50 100

480V 35 65 35 65 35 65 35 65

600V 10 14 10 14 14 20 18 14

Reference standard UL 489 UL 489 UL 489 UL 489

Trip unit (Thermal-Magnetic)

• Fixed-thermal, Fixed-magnetic (FTU) - - - -

• Adjustable-thermal, Fixed-magnetic (FMU • - - -

• Adjustable-thermal, Adjustable-magnetic, 3-Pole (ATU) - • • •

• Molded Case Switch (MCS) - - - -

Accessories

AX • • • •

AL • • • •

SHT • • • •

UVT • • • •

Extended rotary handle • • • •

Flange handle • • • •

Mechanical life (operations) 4,000 5,000 5,000 5,000

Electrical life @ 600V AC (operations) 4,000 1,000 1,000 500

Weight [lbs] 1.2 1.9 5.7 13.6

Dimensions (W x H x D) [in] 3.5 x 6.5 x 3.4 4.1 x 7.0 x 3.4 5.5 x 11.5 x 4.3 8.3 x 16.9 x 5.3

CIRCUIT BREAKERS

Page 16: West Coast Power Cerus Catalog

30

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 31

MIRA CIRCUIT BREAKERS

Alarm Switch (AL) � Output for audio or visual indication of a tripped breaker due to

overload, short-circuit, operation of shunt trip, or undervoltage trip conditions, operation of pushbutton.

� Useful in automated plants where operators must be signaled about changes in the electrical distribution system.

� Closed contact when the circuit breaker is tripped automatically. � Does not function when the breaker is opened manually. � Contact is open when the circuit breaker is reset.

Auxiliary Switch (AX) � For applications requiring remote “ON” and “OFF” indication � Contains two contacts having a common connection; one

open, one closed.

Undervoltage Trip (UVT) � Automatically opens a circuit breaker when the voltage

drops to a value ranging between 35% - 75% of the line voltage. � The operation is instantaneous - the circuit breaker

cannot be reclosed until the voltage returns to 85% of line voltage.

� Continuously energized, the undervoltage trip must be operating before the circuit breaker can be closed.

� Range of tripping voltage: 0.35 ~ 0.7Vn � MCCB re-closing is possible when voltage: 0.85Vn is exceeded.

� Frequency (only AC): 45Hz ~ 65Hz

Shunt Trip (SHT) � Opens the mechanism in response to an externally applied

voltage signal. � Includes coil clearing contacts that automatically clear the

signal circuit when the mechanism has tripped, to prevent coil overheating.

SimplicityAll�TD�&�TS�accessories�fit�all�frame�sizes�of�circuit�breakers.��Cassette�style,�each�accessory�fits�into�a�unique�slot�in�each�breaker�for�an�easy,�trouble�free,�installation.�

Optimize Your Circuit Breaker Functionality

Electrical�Auxiliaries

Alarm & Auxiliary Switches

Part Number Description

AL-TD/TS Alarm switch for TD/TS series MCCB

AX-TD/TS Auxiliary switch for TD/TS series MCCB

Shunt Trip, SHT

Part Number Control VoltagePower Consumption

AC (VA) DC (W) mA

SHT-12VDC DC 12V - 0.36 30

SHT-24V AC/DC 24V 0.58 0.58 24

SHT-48V AC/DC 48V 1.22 1.23 25

SHT-120V AC/DC 110 ~ 130V 1.36 1.37 10.5

SHT-230V AC/DC 220 ~ 240V/DC250V 1.80 1.88 7.5

SHT-480V AC/DC 380 ~ 500V 1.15 - 2.3

Maximum opening time (ms) 50

Undervoltage Trip, UVT

Part Number Control VoltagePower Consumption

AC (VA) DC (W) mA

UVT-24V AC/DC 24V 0.64 0.65 27

UVT-48V AC/DC 48V 1.09 1.10 23

UVT-120V AC/DC 110 ~ 130V 0.73 0.75 5.8

UVT-230V AC/DC 200 ~ 240V/DC 250V 1.21 1.35 5.4

UVT-400V AC/DC 380 ~ 440V 1.67 - 3.8

UVT-480V AC/DC 440 ~ 480V 1.68 - 3.5

Maximum opening time (ms) 50

Transformer operating voltage (V) - Drop (Circuit breaker trips) - Rise (Circuit breaker can be switched on)

0.7 ~ 1.35Vn~0.85Vn

TD/TS Series Accessories

Alarm Switch Auxiliary Switch

CIRCUIT BREAKERS

Page 17: West Coast Power Cerus Catalog

32

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 33

MIRA CIRCUIT BREAKERS

Extension HandlesRotary Handles

UL Type Degree of Protection Circuit Breaker Part Number

12/3R Rain, dripping water, dust

TD125 EHU-1

TS250 EHU-2

TS400 EHU-3

TS800 EHU-4

4XTotally protected against ingress of dust and water jets from any

direction

TD125 EHU-1X

TS250 EHU-2X

TS400 EHU-3X

TS800 EHU-4X

Flange HandlesUL Type Degree of Protection Circuit Breaker Part Number

12/3R Rain, dripping water, dust

TD125 FH-1

TS250 FH-2

TS400 FH-3

TS800 FH-4

4XTotally protected against ingress of dust and water jets from any

direction

TD125 FH-1X

TS250 FH-2X

TS400 FH-3X

TS800 FH-4X

Circuit�breaker�with�cover�frame�and�rotary�extended�handle

A Full Range of Accessories1. Circuit Breaker 2. Flange handle 3. Extended rotary handle 4. Locking devices (Removable, Fixed) 5. Mechanical interlock device

1.

2. 3.

5.

4.

Guaranteed Breaker Isolation � Removable locking device is available for all TD & TS circuit breakers. � The locking device is designed to be easily attached to the circuit-breaker. � This device allows the handle to be locked in the “OFF” position. � Locking in the “OFF” position guarantees isolation according to IEC 60947-2. � A maximum of three (3) padlocks with shackle diameters ranging from 5 to 8mm may be used. � Padlocks are not supplied

Removable Locking DeviceMCCB Function Part Number

TD125 “OFF” position PL1

TS250 “OFF” position PL2

TS400 “OFF” position PL3

TS800 “OFF” position PL4

Mechanical InterlockFrame Size Part Number

TD125 MIT13

TS250 MIT23

TS400 MIT33

TS800 MIT43

� Mechanical interlock is applied to the front of two breakers mounted side-by-side � Prevents simultaneous closing of the two breakers � Mounts directly on the cover of the breakers � Interlocking plate allows user to lock both breakers in the OFF position or only one

breaker in the OFF position � A simple and effective interlock for bypass or other power transfer systems

Circuit Breaker Interlocks

Provide Security and Safety with Cerus BreakersSupports Up to 3 Padlocks

� Available for all TD & TS circuit breakers � Allows the handle to be locked in the “ON” and “OFF” position � Locking in the OFF position guarantees isolation according to IEC 60947-2 � Accommodates up to three padlocks with shackle diameters no larger than 5/16” � Padlocks are not supplied

Fixed Locking DeviceMCCB Function Part Number

TD125 Lock in “OFF” or “ON” position PHL1

TS250 Lock in “OFF” or “ON” position PHL2

TS400 Lock in “OFF” or “ON” position PHL3

TS800 Lock in “OFF” or “ON” position PHL4

CIRCUIT BREAKERS

Page 18: West Coast Power Cerus Catalog

MIRA CIRCUIT BREAKERS

Exceeding�the�Industrial�Standard � Optimize System Reliability � Fast Installation � Higher Reliability

“Cerus makes sure that I get the right starter for my application. They deliver when I need it and comes ready to install. Talk about service.”

Economy Starters MMS: Enclosed Manual Motor Starters

ISS: IndustrialStart/Stop

IPS: Industrial & Pump Starter

��Ranges

HP�ranges* 3/4�HP�-�50HP 3/4�HP�-�20HP 1HP�-�300HP 1HP�-�300HP

Amperage�ranges 0.1A�-�85A 0.1A�-�32A 0.1A�-�400A 0.1A�-�400A

��Starter�Type Non-reversing Non-reversing� Non-reversing�(standard),�or�Combination��

Non-reversing�(standard)�or�Combination�

��Protective�Options Bi-metallic�Thermal�Overload(Class�10)�

Bi-metallic�Thermal�Overload(Class�10)

Electronic�Overload(9~95A�Models)

Bi-metallic�Thermal�Overload�(Class�10)(100~400A�Models)

Electronic�OverloadPhase�Fail�Protection�Stall�Protection�Locked�RotorOver/Under�Voltage�Power�Fail�Options�Anti-Cycling�

��Construction UL�Type�1 UL�Type�4X UL�Type�1,�4,�12,�4X UL�Type�1,�4,�12,�4X

��Operator�Options On/Off�pushbuttons�available - START/STOP�pushbuttonsHOA/Reset�KeypadOptional�START/STOP�pushbuttons

��Automation�System�Interface - - Remote�Operator�Station

Remote�Operator�StationDry/Voltage�Auto�Input�Permissive�Auto�Override�(Fireman’s)120VAC�Control�Power�Transformer�Damper�Control�&�Status

From�1/2�HP�to�300HP,�Cerus�has�your�starter�application�covered.�You�get�time�and�money�saving�features�on�top�of�Cerus’�legendary�quality�and�service�–�all�backed�by�a�5-year�contactor�warranty!�We�don’t�meet�the�specs�–�we�set�them!

*�Horsepower�minimum�&�maximum�ratings�are�based�on�460V�applications

Page 19: West Coast Power Cerus Catalog

36

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 37

*UL�rating�for�manual�motor�controller-group�ratings.��Manual�motor�starter�group�ratings�may�vary�–�visit�www.westcoast-

Enclosed Manual Motor Starter

Rated Operational Current (A)

Thermal Release

Adjustment Range (A)

Magnetic Release

Operating Current (A)

HorsepowerSCIC (kA)

High Break Trip Magnetic Trip OnlySingle Phase Three Phase

115V 230V 230V 460V 575V 240V kA

480V kA

600V kA

1.6 1-1.6 20.8 - 1/10 - 3/4 3/4 100 65 25 CIE-MMS-32H-1.6 CIE-MMS-32HI-1.6

2.5 1.6-2.5 32.5 - 1/6 1/2 1 11/2 100 65 25 CIE-MMS-32H-2.5 CIE-MMS-32HI-2.5

4 2.5-4 52 1/8 1/3 3/4 2 3 100 65 25 CIE-MMS-32H-4 CIE-MMS-32HI-4

6 4-6 78 1/4 1/2 11/2 3 5 100 65 25 CIE-MMS-32H-6 CIE-MMS-32HI-6

8 5-8 104 1/3 1 2 5 5 100 65 25 CIE-MMS-32H-8 CIE-MMS-32HI-8

10 6-10 130 1/2 11/2 3 5 71/2 100 65 25 CIE-MMS-32H-10 CIE-MMS-32HI-10

13 9-13 169 1/2 2 3 71/2 10 100 65 25 CIE-MMS-32H-13 CIE-MMS-32HI-13

17 11-17 221 1 3 5 10 15 100 30 10 CIE-MMS-32H-17 CIE-MMS-32HI-17

22 14-22 286 11/2 3 71/2 15 20 100 30 10 CIE-MMS-32H-22 CIE-MMS-32HI-22

26 18-26 338 2 3 71/2 15 20 100 30 10 CIE-MMS-32H-26 CIE-MMS-32HI-26

32 22-32 416 2 5 10 20 30 100 30 10 CIE-MMS-32H-32 CIE-MMS-32HI-32

Rugged Construction with Standard Handle Lock-out � With a heavy-duty impact-resistant plastic case. IP65 rating. (UL Type 4/4X pending) � Standard rotary switch includes easy provision for padlock/tag-out at no extra charge.

Superior Protection � UL listed manual motor control provides motor overload and motor circuit protection

in one package - no separate circuit breaker or fuses required � Both models are rated up to 100,000 Amps interrupting capacity - ensuring maximum

compatibility and coordination with existing electrical installations. � Meet UL Type E ratings for group motor installation with no additional branch circuit

breaker or fuses required

Enclosed Manual Motor Starter1Ø & 3Ø, 115~600VAC, 1/10~30HPHigh Break Thermal Magnetic or Magnetic Trip OnlyLockable Disconnect

ENCLOSED INDUSTRIAL STARTERS

Magnetic Starters - NEMA1 Plastic Enclosure with Thermal Overload & Start/Stop Pushbuttons

Single Phase Three Phase Part Number Maximum

Overload (A)115V 230V 200V 230V 460V 575V*

– 1/10 - - 3/4 3/4 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 1.6

– 1/8 1/2 1/2 1 1 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 2.5

1/8 1/3 3/4 3/4 2 2 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 4

1/4 1/2 1 1.5 3 3 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 6

1/3 1 2 2 5 5 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 9

1/2 1.5 2 3 5 5 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 10

1/2 2 3 3 7.5 7.5 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 13

1 3 3 5 10 10 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 18

1 .5 3 5 7.5 15 15 CMW-9MB/K- CMW-12MB/K- CMW-18MB/K- CMW-22MB/K- 22

Magnetic Starters - NEMA1 Steel Enclosure with Thermal Overload

Single Phase Three Phase Part Number Start/

Stop BaseMaximum Overload

Amps 115V 230V 200V 230V 460V 575V*

– 1/10 - - 3/4 3/4 CMW-9 CMW-12 CMW-22 B/K /K 1.6

– 1/8 1/2 1/2 1 1 CMW-9 CMW-12 CMW-22 B/K /K 2.5

1/8 1/3 3/4 3/4 2 2 CMW-9 CMW-12 CMW-22 B/K /K 4

1/4 1/2 1 1.5 3 3 CMW-9 CMW-12 CMW-22 CMW-40 B/K /K 6

1/3 1 2 2 5 5 CMW-9 CMW-12 CMW-22 CMW-40 B/K /K 9

1/2 1.5 2 3 5 5 CMW-12 CMW-22 CMW-40 B/K /K 10

1/2 2 3 3 7.5 7.5 CMW-12 CMW-22 CMW-40 B/K /K 13

1 3 3 5 10 10 CMW-12 CMW-22 CMW-40 B/K /K 18

1 .5 3 5 7.5 15 15 CMW-22 CMW-40 CMW-50 CMW-85 B/K /K 22

2 3 7.5 7.5 15 20 CMW-22 CMW-40 CMW-50 CMW-85 B/K /K 26

3 5 7.5 10 20 25 CMW-40 CMW-50 CMW-85 B/K /K 36

3 5 10 10 25 25 CMW-40 CMW-50 CMW-85 B/K /K 40

3 7.5 10 10 30 30 CMW-50 CMW-85 B/K /K 50

3 7.5 15 15 30 40 CMW-50 CMW-85 B/K /K 65

5 10 20 20 40 50 CMW-85 B/K /K 75

7.5 15 20 25 50 60 CMW-85 B/K /K 85

� Thermal overload protection � Differential phase failure protection � Ambient compensated (-5º to 40ºC)

Cost Effective and Reliable � Start/Stop pushbutton options � Metal or plastic enclosures � High reliability up to 2.5 million electrical contactor

cycles at full rated current* (varies by model)

*Visit�www.westcoastpower.com�for�warranty�terms.�Contactor�ratings�vary�by�model.

High Value Enclosed Starter1Ø & 3Ø, 115~600VAC, 1/10~60HPAvailable Start/Stop Pushbutton OptionThermal Motor Overload

Page 20: West Coast Power Cerus Catalog

38

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 39

Everything You Need is Standard � Start/Stop pushbutton control with terminals for remote 3-wire operator station � Multi-tap control power transformer accepts all common motor voltages � Solid-state electronic overload relay (Up to NEMA Size 3) � Lockable cover prevents tampering

Quality Construction � UL 508A Listed � NEMA size rated contactors � 5-Year warranty

Superior Motor Overload Protection � Phase loss and phase imbalance protection � Ambient compensated (-5º to 40ºC) � Manual Reset � Trip-free design

Combination Versions Include Disconnect � Motor Circuit Protector disconnect provides branch and short circuit protection � High interrupting ratings for maximum electrical system compatibility � No fuses or breakers required - save time and money � Lockable through the door handle for safety

Easy Installation with Fewer Call Backs � Flexible sizing makes ordering easy � UL Type 1 enclosure includes top and bottom knock-outs � Mount more starters in less space with our slim line case � High reliability...up to 2.5 million contactor electrical cycles at full

rated current

Wide�range�electronic�overload�eliminates�sizing�call�backs.

Our�lockable�disconnect�provides�superior�protection�without�costly�fuses.

Proven Reliability for Demanding Industrial Applications

Industrial Start/Stop1Ø & 3Ø, 115~600VAC, 1–300HPStart/Stop PushbuttonsSuperior Electronic Motor Protection

ISS

NEMA Sized

Simple�and�clearly�indicated�Start/Stop�operation.

Provided�terminal�blocks�allow�for�connection�to�remote�Start/Stop�station.

SpecificationsStarter Type

Industrial Starter

Standard or Combination

UL Type 1, UL Type 4/12, UL Type 4X (Stainless or Fiberglass)

User Interface

Start / Stop Pushbuttons

Standard Control Operations

3-Wire Terminal block provision for remote Start/Stop

Protective Functions (9~95A Models)

Overload Type Electronic; I2t Thermal Trip Curve

Trip Class Class 1-30

Reset Manual

Phase Unbalanced Trip within 3 seconds @ 70% unbalance

Phase Loss Trip within 3 seconds

Stall Trip within 3 seconds @ 170% FLA

Protective Functions (100~400A Models)

Overload Type Thermal bi-metallic

Trip Class Class 10 (100~800A)

Reset Manual

Phase Loss Differential overload protection

Mechanical

Enclosure types UL Type 1 or UL Type 4/12

Environmental

Ambient Operating Temp -5° to 140° F (-20° to 60° C)

Ambient Storage Temp -5° to 185° F (-20° to 85° C)

Relative Humidity 5% to 95% non-condensing

Compact & Rugged UL Type 1 Model � Ready for indoor installations with conduit knockouts and

mounting flanges � Same-day shipping available up to NEMA Size 1

ENCLOSED INDUSTRIAL STARTERS

Page 21: West Coast Power Cerus Catalog

40

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 41

Standard Magnetic Starters 9~95A - Electronic Overload

Horsepower SCICKAIC

@460VNEMA

Size UL Type 1 UL Type 4/12 UL Type 4XFiberglass

UL Type 4XStainlessSingle Phase Three Phase

115V 230V 200V 230V 460V 575V*

1/6 1/2 1 1.5 3 3 5 00 ISS1-9/J-5 ISS12-9/J-5 ISSXF-9/J-5 ISSXS-9/J-5

1 3 5 5 10 15 5 0 ISS1-18/J-22 ISS12-18/J-22 ISSXF-18/J-22 ISSXS-18/J-22

2 5 7.5 10 20 25 5 1 ISS1-32/J-40 ISS12-32/J-40 ISSXF-32/J-40 ISSXS-32/J-40

3 10 20 20 40 50 5 2 ISS1-50/J-80 ISS12-50/J-80 ISSXF-50/J-80 ISSXS-50/J-80

5 15 30 40 60 60 10 3 - ISS12-85/J-80 ISSXF-85/J-80 ISSXS-85/J-80

Combination Magnetic Starters 9~95A - Electronic Overload

Horsepower *SCIC KAIC

@460VNEMA

Size UL Type 1 UL Type 4/12 UL Type 4X Fiberglass

UL Type 4X StainlessSingle Phase Three Phase

115V 230V 200V 230V 460V 575V*

- 1/10 - - 3/4 3/4 65 00 ISS1-9/ J-G1.6-5 ISS12-9/J-G1.6-5 ISSXF-9/J-G1.6-5 ISSXS-9/J-G1.6-5

- 1/6 1/2 1/2 1 1.5 65 00 ISS1-9/J-G2.5-5 ISS12-9/J-G2.5-5 ISSXF-9/J-G2.5-5 ISSXS-9/J-G2.5-5

1/8 1/3 3/4 3/4 2 3 65 00 ISS1-9/J-G4-5 ISS12-9/J-G4-5 ISSXF-9/J-G4-5 ISSXS-9/J-G4-5

1/6 1/2 1 1.5 3 3 65 00 ISS1-9/J-G6-5 ISS12-9/J-G6-5 ISSXF-9/J-6-5 ISSXS-9/J-6-5

1/3 1 2 2 5 5 65 0 ISS1-18/J-G8-22 ISS12-18/J-G8-22 ISSXF-18/J-G8-22 ISSXS-18/J-G8-22

1/2 1.5 2 3 5 7.5 65 0 ISS1-18/J-G10-22 ISS12-18/J-G10-22 ISSXF-18/J-G10-22 ISSXS-18/J-G10-22

1/2 2 3 3 7.5 10 65 0 ISS1-18/J-G13-22 ISS12-18/J-G13-22 ISSXF-18/J-G13-22 ISSXS-18/J-G13-22

1 3 3 5 10 15 30 0 ISS1-18/J-G17-22 ISS12-18/J-G17-22 ISSXF-18/J-G17-22 ISSXS-18/J-G17-22

1.5 3 5 7.5 15 20 30 1 ISS1-32/J-G22-40 ISS12-32/J-G22-40 ISSXF-32/J-G22-40 ISSXS-32/J-G22-40

2 3 7.5 7.5 15 20 30 1 ISS1-32/J-G26-40 ISS12-32/J-G26-40 ISSXF-32/J-G26-40 ISSXS-32/J-G26-40

2 5 7.5 10 20 25 30 1 ISS1-32/J-G32-40 ISS12-32/J-G32-40 ISSXF-32/J-G32-40 ISSXS-32/J-G32-40

3 7.5 10 10 30 30 50 2 - ISS12-50/J-G40-40 ISSXF-50/J-G40-40 ISSXS-50/J-G40-40

3 10 15 15 40 40 50 2 - ISS12-50/J-G50-80 ISSXF-50/J-G50-80 ISSXS-50/J-G50-80

5 10 20 20 50 50 50 3 - ISS12-85/J-G63-80 ISSXF-85/J-G63-80 ISSXS-85/J-G63-80

5 15 20 25 60 60 50 3 - ISS12-85/J-G75-80 ISSXF-85/J-G75-80 ISSXS-85/J-G75-80

� Standard Start/Stop pushbuttons � Enclosure types for all environments � Provision for remote operator station � Combination version features motor circuit

protector to provide branch and short circuit protection

ISS Ordering and Sizing Information

OptionsPart Number Description

ISS-RST Front Mounted Reset Pushbutton

ISS-TBC Terminal Control Only

ISS-1PH Wiring for Single Phase Motor

Standard Magnetic Starters 100~400A - Thermal Overload

Horsepower SCIC KAIC

@460VNEMA

Size UL Type 4/12 UL Type 4X Fiberglass

UL Type 4X StainlessThree Phase

200V 230V 460V 575V*

40 40 75 75 10 - ISS12-125/K-125 ISSXF-125/K-125 ISSXS-125/K-125

40 50 100 100 10 4 ISS12-150/K-150 ISSXF-150/K-150 ISSXS-150/K-150

60 75 150 150 10 - ISS12-220/K-220 ISSXF-220/K-220 ISSXS-220/K-220

100 100 200 200 18 5 ISS12-300/K-300 ISSXF-300/K-300 ISSXS-300/K-300

125 150 300 300 18 - ISS12-400/K-400 ISSXF-400/K-400 ISSXS-400/K-400

Combination Magnetic Starters 100~400A -Thermal Overload

Horsepower SCIC KAIC

@460VNEMA

Size UL Type 4/12 UL Type 4XFiberglass

UL Type 4X StainlessThree Phase

200V 230V 460V 575V*

40 40 75 75 10 - ISS12-125/K-G-125 ISSXF-125/K-G-125 ISSXS-125/K-G-125

40 50 100 100 10 4 ISS12-150/K-G-150 ISSXF-150/K-G-150 ISSXS-150/K-G-150

60 75 150 150 10 - ISS12-220/K-G-220 ISSXF-220/K-G-220 ISSXS-220/K-G-220

100 100 200 200 18 5 ISS12-300/K-G-300 ISSXF-300/K-G-300 ISSXS-300/K-G-300

125 150 300 300 18 - ISS12-400/K-G-400 ISSXF-400/K-G-400 ISSXS-400/K-G-400

� Standard Start/Stop pushbuttons � Enclosure types for all environments � Provision for remote operator station � Combination version features molded case

circuit breaker to provide branch and short circuit protection

*�For�600V�part�numbers�please�consult�factory.++�For�starters�over�NEMA�Size�3�consult�factory.�

ENCLOSED INDUSTRIAL STARTERS

Page 22: West Coast Power Cerus Catalog

42

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 43

OptionsPart Number Description

STR-RPL Run pilot light�(Red Standard)

STR-RST Door mounted Reset pushbutton

STR-OFF Off pilot light�(Green Standard)

STR-STP Emergency stop pushbutton (40mm, push-pull)

STR-1PH Wiring for Single Phase Motor

Enclosed Wye-Delta, Open TransitionHorsepower

UL Type 4/12 Standard UL Type 4/12 Combination208V 230V 460V

20 20 40 CIE12-50/DW CIE12-50/DW-G

40 40 60 CIE12-85/DW CIE12-85/DW-G

50 50 125 CIE12-125/DW CIE12-125/DW-G

60 60 125 CIE12-150/DW CIE12-150/DW-G

125 125 200 CIE12-220/DW CIE12-220/DW-G

150 150 300 CIE12-300/DW CIE12-300/DW-G

200 200 400 CIE12-400/DW CIE12-400/DW-G

Enclosed Wye-Delta Starters � Standard timer ensures smooth transition between start & run operations � Each starter includes a control power transformer and Hand/Off/Auto switch � Ambient temperature compensated differential bi-metallic thermal overload protection � Terminal block connection for remote operation � Optional molded case circuit breaker disconnect provides branch and short circuit protection � Disconnect features high interrupting ratings for maximum electrical system compatibility � 5-Year contactor warranty

Industrial Starters1Ø & 3Ø, 115~600VAC, 1–200HPWye-Delta & Reversing ModelsOptional Control Features

NEMA Sized

Enclosed Reversing Starters � Each starter includes a control power transformer and terminal block connections � Easily integrate remote user controls such as pendant stations or switch/pushbutton operators � Solid-state electronic overload relay provides phase loss and stall protection � Optional motor circuit protector (MCP) disconnect provides branch and short circuit protection � Disconnect features high interrupting ratings for maximum electrical system compatibility � Options for user selected local control methods � 5-Year contactor warranty

Industrial Reversing Starters 9~95A - Electronic Overload

Horsepower SCICKAIC

@460VNEMA

Size UL Type 4/12 UL Type 4XFiberglass

UL Type 4XStainlessSingle Phase Three Phase

115V 230V 200V 230V 460V 575V*

1/6 1/2 1 1.5 3 3 5 00 CIE12-9/R-5 CIEXF-9/R-5 CIEXS-9/R-5

1 3 5 5 10 15 5 0 CIE12-18/R-22 CIEXF-18/R-22 CIEXS-18/R-22

2 5 7.5 10 20 25 5 1 CIE12-32/R-40 CIEXF-32/R-40 CIEXS-32/R-40

3 10 20 20 40 50 5 2 CIE12-50/R-80 CIEXF-50/R-80 CIEXS-50/R-80

5 15 30 40 60 60 10 3 CIE12-85/R-80 CIEXF-85/R-80 CIEXS-85/R-80

Industrial Combination Reversing Starters 9~95A - Electronic Overload

Horsepower SCIC KAIC

@460VNEMA

Size UL Type 4/12 UL Type 4X Fiberglass

UL Type 4X StainlessSingle Phase Three Phase

115V 230V 200V 230V 460V 575V*

- 1/10 - - 3/4 3/4 65 00 CIE12-9/R-G1.6-5 CIEXF-9/R-G1.6-5 CIEXS-9/R-G1.6-5

- 1/6 1/2 1/2 1 1.5 65 00 CIE12-9/R-G2.5-5 CIEXF-9/R-G2.5-5 CIEXS-9/R-G2.5-5

1/8 1/3 3/4 3/4 2 3 65 00 CIE12-9/R-G4-5 CIEXF-9/R-G4-5 CIEXS-9/R-G4-5

1/6 1/2 1 1.5 3 3 65 00 CIE12-9/R-G6-5 CIEXF-9/R-G6-5 CIEXS-9/R-G6-5

1/3 1 2 2 5 5 65 0 CIE12-18/R-G8-22 CIEXF-18/R-G8-22 CIEXS-18/R-G8-22

1/2 1.5 2 3 5 7.5 65 0 CIE12-18/R-G10-22 CIEXF-18/R-G10-22 CIEXS-18/R-G10-22

1/2 2 3 3 7.5 10 65 0 CIE12-18/R-G13-22 CIEXF-18/R-G13-22 CIEXS-18/R-G13-22

1 3 3 5 10 15 30 0 CIE12-18/R-G17-22 CIEXF-18/R-G17-22 CIEXS-18/R-G17-22

1.5 3 5 7.5 15 20 30 1 CIE12-32/R-G22-40 CIEXF-32/R-G22-40 CIEXS-32/R-G22-40

2 3 7.5 7.5 15 20 30 1 CIE12-32/R-G26-40 CIEXF-32/R-G26-40 CIEXS-32/R-G26-40

2 5 7.5 10 20 25 30 1 CIE12-32/R-G32-40 CIEXF-32/R-G32-40 CIEXS-32/R-G32-40

3 7.5 10 10 30 30 50 2 CIE12-50/R-G40-40 CIEXF-50/R-G40-40 CIEXS-50/R-G40-40

3 10 15 15 40 40 50 2 CIE12-50/R-G50-80 CIEXF-50/R-G50-80 CIEXS-50/R-G50-80

5 10 20 20 50 50 50 3 CIE12-85/R-G63-80 CIEXF-85/R-G63-80 CIEXS-85/R-G63-80

5 15 20 25 60 60 50 3 CIE12-85/R-G75-80 CIEXF-85/R-G75-80 CIEXS-85/R-G75-80

OptionsPart Number Description

STR-RPL Run pilot light�(Red Standard)

STR-RST Door mounted Reset pushbutton

STR-OFF Off pilot light�(Green Standard)

STR-STP Emergency stop pushbutton (40mm, push-pull)

STR-1PH Wiring for Single Phase Motor

*�For�600V�part�numbers�please�consult�factory.++�For�starters�over�NEMA�Size�3�consult�factory.�

ENCLOSED INDUSTRIAL STARTERS

Page 23: West Coast Power Cerus Catalog

44

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 45

Internal HOA Keypad with LCD Display � Door mounted pilot devices � Plain English operation – easy to set up and simple to operate � LEDs indicate Hand/Off/Auto modes, run and fault conditions

Built-in Pump Protection Features � Standard over/undervoltage detection with selectable trip settings � Optional true power measurement detects dry pump and provides alarm output;

preventing dry pump operation to protect motor and pump from potential damage

Power Metering (option)

� 1% ANSI grade metering with pulse/analog output for accurate measurements � kW and kWh data available on LCD display

Voltage & Dry Contact Inputs for PLC Compatibility � Wire directly from a centralized controller to the starter, no interposing

relays necessary � Save on installation costs and increase reliability.

Dual Shut Down Inputs � Manual shut down or automatic high-limit alarm shut down � Accepts either a voltage signal or contact opening

Actuator Control � Interlocks valves with starter ensuring proper sequence of operation � Reduces wiring and saves on installation costs

The�IPS�includes�a�rugged�Hand/Off/Auto�switch.

Industrial & Pump Starter1Ø & 3Ø, 115~600VAC, 1–200HPStart/Stop Pushbuttons or HOASuperior Motor & Pump Protection

IPS

Digital�display�clearly�delivers�instantaneous�&�precise�motor�parameter�data�and�fault�conditions.

NEMA Sized

Our�lockable�disconnect�provides�superior�protection�without�costly�fuses.

24V Actuator Control � Option in lieu of 120VAC standard

Options

Simplex Pump Options � Inputs for float control (5 float inputs maximum) � Dry pump protection

Power Metering � 1% ANSI Accuracy with integrated current transformers � Pulse kWh output, N.O. Contact, max on resistance 8 ohms, max 45V � 4- 20 mA kW output � Includes kW, kWh display

Over/Under Voltage � Protects motors from damage � Adjustable minimum and maximum

voltage thresholds

Ground Fault Protection � Protects motors from damage due to

ground current conditions � UL 1053 Certified

Time Delay � Programmable On/Off delay

Wide Range Class 1-60 Electronic Overload � Prevents ordering confusion and eliminates call backs due to mis-sized heaters. � Advanced protective features including anti-cycling, manual/auto reset, phase

sequence, phase loss, stall and locked rotor protection

Flexible Control Transformer (CPT) � Multi-tap CPT input accepts all common motor voltages � Integrated secondary protection – no fuses required

Combination Versions Include Disconnect � Motor circuit protection disconnect provides branch

and short circuit protection � High interrupting ratings for maximum electrical system compatibility � No fuses required – save time and money � Lockable handle for safety

Our�integrated�CTs�provide�superior�motor�protection�and�metering�accuracy.

PUMP CONTROLS

Page 24: West Coast Power Cerus Catalog

46

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 47

*Programmable On or Off. See owner’s manual for customer selectable settings.

SpecificationsStarter Type

Industrial & Pump Starter

Standard or Combination

UL Type 4/12 Enclosure

User Interface

Internal Display Digital keypad with LEDs

LED pilot lights Hand, Off, Auto, Run, Fault

LCD parameter display 16 character, dual line, backlight

22mm Pilot Devices HOA, Start/Stop Pushbuttons, Reset

Standard Control Operations

Inputs

Voltage Auto Run Apply 10 - 130VAC/DC to energize

Emergency Power Off Apply 10 - 130VAC/DC to energize

Actuator position switch N.O. dry contact closure

Permissive Auto N.O. dry contact closure

Shutdown N.C. dry contact input

Outputs

Proof of flow status relay (adjustable) N.O., 0.3A@125VAC; 1A@24VAC

Fault relay N.O., 0.3A@125VAC; 1A@24VAC

Actuator motor control 120VAC, 0.2A max (24VAC optional)

Operational

Power fail mode Restart last mode, no delay (default)

Restart with delay

Restart Off - LED flashes last mode

On/Off Time Delay Programmable, selectable from 0.1 to 99 seconds

Protective Functions Mechanical

Overload Type Electronic; I2t Thermal Trip Curve Enclosure Types UL Type 1 or UL Type 4/12

Current Setting Range 0.5 - 95A

Trip Class Class 5 - 60

Reset Manual or Automatic Environmental

Phase Unbalance Trip within 1 second at programmed unbalance percentage (75% default)

Ambient Operating Temp -5° to 140° F (-20° to 60° C)

Phase Loss Trip within 1 second (50% default) Ambient Storage Temp -5° to 185° F (-20° to 85° C)

Stall/Locked Rotor* Trip within 0.5 seconds @ 300% FLA Relative Humidity 5% to 95% non-condensing

Cycle Fault* Trip if cycle rate exceeds 1200 starts per hour

Under Power Trip* Trip within 10 seconds @ 50% measured horsepower

Phase Sequence* Trip within 0.1 seconds upon reverse phase detection

Warm Start Provision Delays motor restart if calculated motor temperature exceeds thermal curve

Ground Fault UL1053 Certified (Optional)

Over/Under Voltage Selectable trip within 0.1-99 seconds (Optional)

UL Type 4/12 Outdoor Enclosure Standard Industrial Pump Starter - Electronic Overload

Horsepower SCICKAIC

@460V

NEMASize Part NumberSingle Phase Three Phase

115V 230V 200V 230V 460V 575V*

– 1/2 2 3 5 7.5 5 00 IPS12-9/J-9

1 3 5 7.5 10 15 5 0 IPS12-18/J-18

2 5 7.5 10 20 25 5 1 IPS12-32/J-32

3 10 20 25 40 50 5 2 IPS12-50/J-50

5 15 30 40 60 75 10 3 IPS12-85/J-85

UL Type 4/12 Outdoor Enclosure Combination Industrial Pump Starter - Electronic Overload

Horsepower SCICKAIC

@460V

NEMASize Part NumberSingle Phase Three Phase

115V 230V 200V 230V 460V 575V*

– 1/10 – – 3/4 3/4 65 00 IPS12-9/J-G1.6-9

– 1/6 1/2 1/2 1 1.5 65 00 IPS12-9/J-G2.5-9

1/8 1/3 3/4 3/4 2 3 65 00 IPS12-9/J-G4-9

1/4 1/2 1 1.5 3 5 65 00 IPS12-9/J-G6-9

1/3 1 2 2 5 5 65 0 IPS12-18/J-G8-18

1/2 1.5 2 3 5 7.5 65 0 IPS12-18/J-G10-18

1/2 2 3 3 7.5 10 65 0 IPS12-18/J-G13-18

1 3 3 5 10 15 30 0 IPS12-18/J-G17-18

1.5 3 5 7.5 15 20 30 1 IPS12-32/J-G22-32

2 3 7.5 7.5 15 20 30 1 IPS12-32/J-G26-32

2 5 7.5 10 20 25 30 1 IPS12-32/J-G32-32

3 7.5 10 10 30 30 50 2 IPS12-50/J-G40-50

3 10 15 15 30 40 50 2 IPS12-50/J-G50-50

5 10 20 20 40 60 50 3 IPS12-85/J-G63-85

5 15 20 25 50 60 50 3 IPS12-85/J-G75-85

Ordering and Sizing Information

� UL Type 4/12 for outdoor use � Fully sealed: welded and gasketed for long life � Rugged 16 gauge steel construction � Combination version features motor circuit

protector to provide branch and short circuit protection.

*�For�600V�part�numbers�please�consult�factory.++�For�starters�over�NEMA�Size��3�consult�factory.�

IPSOptionsPart Number Description

IPS-HOA Hand/Off/Auto Control (Door Mounted)

IPS-STSP Start/Stop Pushbutton Control (Door Mounted)

IPS-PMP Pump Option Card (with Dry Pump Protection)

IPS-PWR Power Monitoring with Pulse/Analog output

IPS-DRY Dry Pump Protection

IPS-GFLT Ground Fault Protection

IPS-TMR Programmable On/Off Delay Timer

IPS-24 24V Actuator Control

PUMP CONTROLS

Page 25: West Coast Power Cerus Catalog

48

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 49

SPS

Economical and Functional Pump Starter ControlHeavy Duty HOA Switch with Run Pilot Light

� Simple and functional basic control � Long life LED pilot light

Wide Range Class 1-30 Electronic Overload � Prevents ordering confusion and eliminates call backs due to mis-sized heaters � Advanced protective features including phase loss, phase imbalance,

stall protection & manual reset

Flexible Control Transformer (CPT) � Multi-tap CPT input accepts all common motor voltages � Integrated secondary protection – no fuses required � Standard 120VAC secondary control

Rugged�HOA�switch

Standard Pump Starter1Ø & 3Ø, 115~600VAC, 1–300HPHOA Switch with LED Run Pilot LightElectronic Motor Protection

SpecificationsStarter Type

Standard Pump Starter

Standard or Combination

UL Type 1 or UL Type 4/12 Enclosure

User Interface

HOA Selector switch with Run pilot light

Standard Control Operations

Inputs Protective Functions

Dry Auto Run N.O. dry contact closure to energize starter Overload Type Electronic; I2t Thermal Trip Curve

Mechanical Current Setting Range 0.3 - 1.5A, 1 - 5A, 4.4 - 22A, 8 - 40A, 16 - 80A

Enclosure types UL Type 1 or UL Type 4/12 Trip Class Class 1-30

Environmental Reset Manual

Ambient Operating Temp -5° to 140° F (-20° to 60° C) Phase Unbalanced Trip within 3 seconds @ 70% unbalance

Ambient Storage Temp -5° to 185° F (-20° to 85° C) Phase Loss Trip within 3 seconds

Relative Humidity 5% to 95% non-condensing Stall Condition Trip within 3 seconds @ 170% FLA

Our�lockable�disconnect�provides�superior�protection�without�costly�fuses.

NEMA Sized

Standard Pump Starters - HOA Electronic Overload

Horsepower SCICKAIC

@460VNEMA

Size UL Type 1 UL Type 4Single Phase Three Phase115V 230V 200V 230V 460V 575V*

1/2 1 1.5 3 3 5 00 SPS1-9/J-5 SPS4-9/J-5

1 3 5 5 10 15 5 0 SPS1-18/J-22 SPS4-18/J-22

1.5 3 5 7.5 15 20 5 1 SPS1-32/J-22 SPS4-32/J-22

2 5 7.5 10 20 25 5 1 SPS1-32/J-40 SPS4-32/J-40

3 7.5 10 10 25 30 5 2 SPS1-50/J-40 SPS4-50/J-40

3 10 20 20 40 50 5 2 SPS1-50/J-80 SPS4-50/J-80

5 15 30 40 60 60 10 3 SPS1-85/J-80 SPS4-85/J-80

Combination Pump Starters - HOA Electronic Overload

Horsepower SCICKAIC

@460V

NEMA Size UL Type 1 UL Type 4Single Phase Three Phase

115V 230V 200V 230V 460V 575V*1/10 – – 3/4 3/4 65 00 SPS1-9/J-G1.6-5 SPS4-9/J-G1.6-5

1/6 1/2 1/2 1 1.5 65 00 SPS1-9/J-G2.5-5 SPS4-9/J-G2.5-5

1/8 1/3 3/4 3/4 2 3 65 00 SPS1-9/J-G4-5 SPS4-9/J-G4-5

1/4 1/2 1 1.5 3 3 65 00 SPS1-9/J-G6-5 SPS4-9/J-G6-5

1/3 1 2 2 5 5 65 0 SPS1-18/J-G8-22 SPS4-18/J-G8-22

1/2 1.5 2 3 5 7.5 65 0 SPS1-18/J-G10-22 SPS4-18/J-G10-22

1/2 2 3 3 7.5 10 65 0 SPS1-18/J-G13-22 SPS4-18/J-G13-22

1 3 3 5 10 15 30 0 SPS1-18/J-G17-22 SPS4-18/J-G17-22

1.5 3 5 7.5 15 20 30 1 SPS1-32/J-G22-40 SPS4-32/J-G22-40

2 3 7.5 7.5 15 20 30 1 SPS1-32/J-G26-40 SPS4-32/J-G26-40

2 5 7.5 10 20 25 30 1 SPS1-32/J-G32-40 SPS4-32/J-G32-40

3 7.5 10 10 30 30 50 2 SPS1-50/J-G40-40 SPS4-50/J-G40-40

3 10 15 15 30 40 50 2 SPS1-50/J-G50-80 SPS4-50/J-G50-80

5 10 20 20 40 50 50 3 SPS1-85/J-G63-80 SPS4-85/J-G63-80

5 15 20 25 50 60 50 3 SPS1-85/J-G75-80 SPS4-85/J-G75-80

*�For�600V�part�numbers�please�consult�factory.++�For�starters�over�NEMA�Size�3�consult�factory.�

Ordering and Sizing Information

SPS

Combination Versions Include Disconnect � Motor circuit protection disconnect provides branch

and short circuit protection � High interrupting ratings for maximum electrical system compatibility � No fuses required – save time and money � Lockable handle for safety

OptionsPart Number Description

SPS-RST Front Mounted Reset Pushbutton

SPS-TBC Terminal Control Only

SPS-1PH Wiring for Single Phase Motor

PUMP CONTROLS

Page 26: West Coast Power Cerus Catalog

50

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 51

The�Cerus�Basic�Duplex�pump�starter�provides�alternating�control�between�two�motors.�A�single�HOA�switch�allows�manual�operation�or�the�starter�accepts�a�remote�run�command�input.�Each�starter�includes�a�motor�selector�switch�to�alternate�between�motors.�Additional�alternating�options�include�an�alternating�relay,�24-hour�timer�or�7-day�clock�allowing�maximum�control�flexibility.

Dependable Alternating Control � Single HOA selector switch with Run pilot lights for each pump � Automatically alternates motors in the event of a fault or trip � Manual alternating controlled via selector switch � Optional alternating control by relay, 24-hour timer, or 7-day clock

Wide Range Class 1-30 Electronic Overload � Prevents ordering confusion and eliminates call backs due to mis-sized heaters � Advanced protective features including phase loss, phase imbalance, stall protection & manual reset

Combination Versions Include Disconnect � Motor circuit protection disconnect provides branch and short circuit protection � High interrupting ratings for maximum electrical system compatibility � No fuses required – save time and money � Lockable handle for safety

A Simple & Reliable Solution Designed for Dual Pump Control

Duplex Alternating Pump Starter1Ø & 3Ø, 115~600VAC, 1–200HPStart/Stop Pushbuttons or HOAUL Type 4 Enclosure

NEMA Sized

Basic Duplex Pump Starters - HOA & Electronic Overload

Horsepower SCICKAIC

@460V

NEMA Size UL Type 4 UL Type 4X

FiberglassSingle Phase Three Phase115V 230V 200V 230V 460V 575V*

1/2 1 1.5 3 3 5 00 DPX4-9/J-5 DPXF-9/J-5

1 3 5 5 10 15 5 0 DPX4-18/J-22 DPXF-18/J-22

1.5 3 5 7.5 15 20 5 1 DPX4-32/J-22 DPXF-32/J-22

2 5 7.5 10 20 25 5 1 DPX4-32/J-40 DPXF-32/J-40

3 7.5 10 10 25 30 5 2 DPX4-50/J-40 DPXF-50/J-40

3 10 20 20 40 50 5 2 DPX4-50/J-80 DPXF-50/J-80

5 15 30 40 60 60 10 3 DPX4-85/J-80 DPXF-85/J-80

Basic Combination Duplex Pump Starters - HOA & Electronic Overload

Horsepower SCICKAIC

@460V

NEMA Size UL Type 4 UL Type 4X

FiberglassSingle Phase Three Phase115V 230V 200V 230V 460V 575V*

1/10 – – 3/4 3/4 65 00 DPX4-9/J-G1.6-5 DPXF-9/J-G1.6-5

1/6 1/2 1/2 1 1.5 65 00 DPX4-9/J-G2.5-5 DPXF-9/J-G2.5-5

1/8 1/3 3/4 3/4 2 3 65 00 DPX4-9/J-G4-5 DPXF-9/J-G4-5

1/4 1/2 1 1.5 3 3 65 00 DPX4-9/J-G6-5 DPXF-9/J-G6-5

1/3 1 2 2 5 5 65 0 DPX4-18/J-G8-22 DPXF-18/J-G8-22

1/2 1.5 2 3 5 7.5 65 0 DPX4-18/J-G10-22 DPXF-18/J-G10-22

1/2 2 3 3 7.5 10 65 0 DPX4-18/J-G13-22 DPXF-18/J-G13-22

1 3 3 5 10 15 30 0 DPX4-18/J-G17-22 DPXF-18/J-G17-22

1.5 3 5 7.5 15 20 30 1 DPX4-32/J-G22-40 DPXF-32/J-G22-40

2 3 7.5 7.5 15 20 30 1 DPX4-32/J-G26-40 DPXF-32/J-G26-40

2 5 7.5 10 20 25 30 1 DPX4-32/J-G32-40 DPXF-32/J-G32-40

3 7.5 10 10 30 30 50 2 DPX4-50/J-G40-40 DPXF-50/J-G40-40

3 10 15 15 30 40 50 2 DPX4-50/J-G50-80 DPXF-50/J-G50-80

5 10 20 20 40 50 50 3 DPX4-85/J-G63-80 DPXF-85/J-G63-80

5 15 20 25 50 60 50 3 DPX4-85/J-G75-80 DPXF-85/J-G75-80

OptionsPart Number Description

DPX-ALT Automatic Alternating Relay

DPX-CLK 7-Day Programmable Clock Alternation

DPX-TMR 24-Hour Timer Alternation

DPX-FLT Fault Pilot Lights

Ordering and Sizing Information

*�For�600V�part�numbers�please�consult�factory.++�For�starters�over�NEMA�Size�3�consult�factory.�

PUMP CONTROLS

Page 27: West Coast Power Cerus Catalog

52

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 53

The� Advanced� Duplex� Pump� Starter� is� ideal� for� wastewater� lift� stations� or� other� redundant� pump�systems.�Cerus�designed�the�package�specifically�for�float�switch�controlled�pump�stations�utilizing�lead-lag�and�alternating�control.�Cerus�provides�single�or�dual�pump�automatic�operation�based�on�demand�including�alternating�function.�In�the�event�of�a�lead�pump�failure,�Cerus�increases�system�reliability�by�initiating�lag�pump�start�to�ensure�continued�flow.

� Elapsed-time meter for each pump � Fault lights for each pump � Door-mounted overload reset pushbuttons � Alarm beacon light � Horn or buzzer with silence pushbutton

Advanced Duplex Pump Controller1Ø & 3Ø, 115~600VAC, 1–200HPPLC-Based Lead/Lag & AlternatingFloat Switch Inputs

Engineered for the Most Demanding Pumping Applications

Options

� Integrated controls lead/lag & alternating operation � Door-mounted Alarm pilot light indicates high level alarm

& float switch failure (identifies specific float number) � Optional circuit breaker or service entrance rated MCCB � Flexible control for three, four or five float switch systems � Automatic alternating control

� 120VAC output for external alarm light � Motor seal failure relay for each pump

(Motor should have a resistive float switch or probe)

� Motor overheat relay (motor should have an internal thermostat)

Wide Range Class 1-30 Electronic Overload � Prevents ordering confusion and eliminates call backs due to mis-sized heaters � Advanced protective features including phase loss, phase imbalance, stall protection & manual reset

Combination Versions Include Disconnect � Motor circuit protection disconnect provides branch and short circuit protection � High interrupting ratings for maximum electrical system compatibility � No fuses required – save time and money � Lockable handle for safety

� Hand/Off/Auto switches for independent local or remote operation

� Dual Run pilot lights indicate motor operation � Adjustable time for lag start delay and

alternation settings � Fault and Alarm contact outputs allow

integration with external devices

Time Saving Features & Standard Components

NEMA Sized

Advanced Duplex Pump Starters - HOA & Electronic Overload

Horsepower SCICKAIC

@460V

NEMA Size UL Type 4 UL Type 4X

FiberglassSingle Phase Three Phase115V 230V 200V 230V 460V 575V*

1/2 1 1.5 3 3 5 00 APX4-9/J-5 APXF-9/J-5

1 3 5 5 10 15 5 0 APX4-18/J-22 APXF-18/J-22

1.5 3 5 7.5 15 20 5 1 APX4-32/J-22 APXF-32/J-22

2 5 7.5 10 20 25 5 1 APX4-32/J-40 APXF-32/J-40

3 7.5 10 10 25 30 5 2 APX4-50/J-40 APXF-50/J-40

3 10 20 20 40 50 5 2 APX4-50/J-80 APXF-50/J-80

5 15 30 40 60 60 10 3 APX4-85/J-80 APXF-85/J-80

Advanced Combination Duplex Pump Starters - HOA & Electronic Overload

Horsepower SCICKAIC

@460V

NEMA Size UL Type 4 UL Type 4X

FiberglassSingle Phase Three Phase115V 230V 200V 230V 460V 575V*

1/10 – – 3/4 3/4 65 00 APX4-9/J-G1.6-5 APXF-9/J-G1.6-5

1/6 1/2 1/2 1 1.5 65 00 APX4-9/J-G2.5-5 APXF-9/J-G2.5-5

1/8 1/3 3/4 3/4 2 3 65 00 APX4-9/J-G4-5 APXF-9/J-G4-5

1/4 1/2 1 1.5 3 3 65 00 APX4-9/J-G6-5 APXF-9/J-G6-5

1/3 1 2 2 5 5 65 0 APX4-18/J-G20-22 APXF-18/J-G20-22

1/2 1.5 2 3 5 7.5 65 0 APX4-18/J-G25-22 APXF-18/J-G25-22

1/2 2 3 3 7.5 10 65 0 APX4-18/J-G30-22 APXF-18/J-G30-22

1 3 3 5 10 15 30 0 APX4-18/J-G50-22 APXF-18/J-G50-22

1.5 3 5 7.5 15 20 30 1 APX4-32/J-G60-40 APXF-32/J-G60-40

2 5 7.5 10 20 25 30 1 APX4-32/J-G80-40 APXF-32/J-G80-40

3 7.5 10 10 30 30 50 2 APX4-50/J-G100-40 APXF-50/J-G100-40

3 10 15 15 30 40 50 2 APX4-50/J-G125-80 APXF-50/J-G125-80

5 10 20 20 40 50 50 3 APX4-85/J-G160-80 APXF-85/J-G160-80

5 15 20 25 50 60 50 3 APX4-85/J-G200-80 APXF-85/J-G200-80

OptionsPart Number Description

APX-FLT Fault Pilot Lights

APX-DHM Digital Hour Meter

APX-BCN Alarm Beacon Light

APX-HRN Door Mounted Horn w/ Silence Pushbutton

APX-BZR Door Mounted Buzzer w/ Silence Pushbutton

APX-LSR Leak Seal Relays

Ordering and Sizing Information

*�For�600V�part�numbers�please�consult�factory.++�For�starters�over�NEMA�Size�3�consult�factory.�

PUMP CONTROLS

Page 28: West Coast Power Cerus Catalog

54

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 55

For�pumping�applications�that�require�constant�discharge�pressure,�Cerus�provides�a�package�that�varies�the�flow�rate�to�maintain�a�pressure�set�point.�Gain�increased�energy�savings�from�demand-based�pump�usage�including�Sleep�Mode,�which�continues�to�monitor�system�set�point�while�stopping�VFD�output�during�periods�of�low�demand.

Enclosed VFD Pump Package1Ø & 3Ø Input, 200~230VAC & 480VAC, 1–125HPPhase Conversion CapabilitiesUL Type 3R Enclosure

Designed to Withstand Harsh Pumping Environments � P-Series VFD motor control with additional application-specific protective options

- Lightning/Surge Arrestor - Line Reactors - Load Reactors - dV/dT Filter

� UL Type 3R enclosure reduces thermal absorption with white, solar reflective finish and filtered cooling fans

� Standard enclosed VFD package is rated for 92° F outside temperature, non-direct sunlight � Attain up to 110° F outside temperature, non-direct sunlight by de-rating VFD

Functionality � A single VFD has the capability to control up to four additional pump starters, VFDs, or soft

starters in lead-lag operation, reducing the need for additional controls � Sleep mode reduces energy consumption by stopping pumps during periods of low demand � Flexible sensor inputs accept 0-10VDC and 4-20mA analog signals � VFD provides additional 12VDC and 24VDC power for sensors � Dual PID control with Pre-PID mode and time delay reduces water hammer and cavitation

while providing precise system control

Responsive Control for Demand Driven Pump SystemsUL Type 3R VFD Pump Packages (3-Phase, 200~230V)

1Ø HP* HP FLA Part Number 3% Line Reactor Output Reactor Output Filter

2 5 24 CIE3R-PMP005-P2 VFD-KDRB22L VFD-KDRD1P VFD-V1K16A00

3 7.5 24 CIE3R-PMP007-P2 VFD-KDRB23L VFD-KDRD2P VFD-V1K25A00

5 10 32 CIE3R-PMP010-P2 VFD-KDRD25L VFD-KDRD3P VFD-V1K35A00

7.5 15 46 CIE3R-PMP015-P2 VFD-KDRD24L VFD-KDRC1P VFD-V1K45A00

10 20 60 CIE3R-PMP020-P2 VFD-KDRD26L VFD-KDRF1P VFD-V1K55A00

10 25 74 CIE3R-PMP025-P2 VFD-KDRC22L VFD-KDRF2P VFD-V1K80A00

15 30 88 CIE3R-PMP030-P2 VFD-KDRF24L VFD-KDRF3P VFD-V1K80A00

20 40 115 CIE3R-PMP040-P2 VFD-KDRF25L VFD-KDRH1P VFD-V1K110A00

UL Type 3R VFD Pump Packages (3-Phase, 380~480V)

1Ø HP* HP FLA Part Number 3% Line Reactor Output Reactor Output Filter

2 5 12 CIE3R-PMP005-P4 VFD-KDRA3L VFD-KDRA3P VFD-V1K8A00

3 7.5 12 CIE3R-PMP007-P4 VFD-KDRA4L VFD-KDRA4P VFD-V1K12A00

5 10 16 CIE3R-PMP010-P4 VFD-KDRA5L VFD-KDRB1P VFD-V1K18A00

7.5 15 24 CIE3R-PMP015-P4 VFD-KDRB2L VFD-KDRD1P VFD-V1K21A00

10 20 30 CIE3R-PMP020-P4 VFD-KDRB1L VFD-KDRD2P VFD-V1K27A00

10 25 39 CIE3R-PMP025-P4 VFD-KDRD1L VFD-KDRD3P VFD-V1K35A00

15 30 45 CIE3R-PMP030-P4 VFD-KDRD2L VFD-KDRD4P VFD-V1K45A00

20 40 61 CIE3R-PMP040-P4 VFD-KDRC1L VFD-KDRC1P VFD-V1K55A00

20 50 75 CIE3R-PMP050-P4 VFD-KDRF2L VFD-KDRF1P VFD-V1K80A00

20 60 91 CIE3R-PMP060-P4 VFD-KDRF4L VFD-KDRF2P VFD-V1K80A00

20 75 110 CIE3R-PMP075-P4 VFD-KDRF3L VFD-KDRF3P VFD-V1K110A00

20 100 152 CIE3R-PMP0100-P4 VFD-KDRH3L VFD-KDRH1P VFD-V1K130A00

20 125 183 CIE3R-PMP0125-P4 VFD-KDRH2L VFD-KDRI1P VFD-V1K160A00

OptionsPart Number Description

VFD-RPL/120 Run Pilot Light for Type 12 & 3R (Green Standard)

VFD-FLT/120 Fault Pilot Light for Type 12 & 3R (Red Standard)

VFD-OFF/120 Off Pilot Light for Type 12 & 3R (Red Standard)

VFD-HOA Hand-Off-Auto Switch for Enclosed Drives

VFD-SPD Door Mounted Speed Potentiometer

VFD-LTA Lightning Arrestor

VFD-KPD Door Mounted Keypad

VFD-KPD/4X Door Mounted Keypad with Type 4X Cover

Ordering and Sizing Information

PUMP CONTROLS

*��Maximum�HP�of��3-phase�motor�in�single�phase�power�applications

*��Maximum�HP�of��3-phase�motor�in�single�phase�power�applications

Page 29: West Coast Power Cerus Catalog

56

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 57

Advanced Duplex VFD Pump Package1Ø & 3Ø Input, 200~230VAC & 480VAC, 1–125HPPhase Conversion CapabilitiesUL Type 3R Enclosure

The� Advanced� Duplex� VFD� Pump� package� is� ideal� for� domestic� water� pump� and� booster� pump�systems.�Cerus�designed�the�package�specifically�to�maintain�a�pressure�set�point�based�on�sensor�feedback�using�internal�PID�control.�This�package�provides�the�most�economic��pump�control��solution�by�reducing�both�energy�and�maintenance�costs.

� Run pilot lights � Fault pilot lights � Off pilot lights � Door-mounted potentiometer � Door-mounted keypad � Door-mounted keypad with Type 4X cover

Engineered for the Most Demanding Pumping Applications

Options

� Integrated controls lead/lag & alternating operation � Optional circuit breaker or service entrance rated MCCB � Single pressure transducer provides feedback for both

PID control loops � Automatic alternating control

� Hand/Off/Auto switches for independent local or remote operation

� Adjustable time for lag start delay and alternation settings

� Fault contact output allow integration with external devices

Maintain System Pressure with Single Sensor Feedback

UL Type 3R VFD Pump Packages (3-Phase, 200~230V)

1Ø HP* HP FLA Part Number 3% Line Reactor Output Reactor Output Filter

2 5 24 CIE3R-ADP005-P2 VFD-KDRB22L VFD-KDRD1P VFD-V1K16A00

3 7.5 24 CIE3R-ADP007-P2 VFD-KDRB23L VFD-KDRD2P VFD-V1K25A00

5 10 32 CIE3R-ADP010-P2 VFD-KDRD25L VFD-KDRD3P VFD-V1K35A00

7.5 15 46 CIE3R-ADP015-P2 VFD-KDRD24L VFD-KDRC1P VFD-V1K45A00

10 20 60 CIE3R-ADP020-P2 VFD-KDRD26L VFD-KDRF1P VFD-V1K55A00

10 25 74 CIE3R-ADP025-P2 VFD-KDRC22L VFD-KDRF2P VFD-V1K80A00

15 30 88 CIE3R-ADP030-P2 VFD-KDRF24L VFD-KDRF3P VFD-V1K80A00

20 40 115 CIE3R-ADP040-P2 VFD-KDRF25L VFD-KDRH1P VFD-V1K110A00

UL Type 3R VFD Pump Packages (3-Phase, 380~480V)

1Ø HP* HP FLA Part Number 3% Line Reactor Output Reactor Output Filter

2 5 12 CIE3R-ADP005-P4 VFD-KDRA3L VFD-KDRA3P VFD-V1K8A00

3 7.5 12 CIE3R-ADP007-P4 VFD-KDRA4L VFD-KDRA4P VFD-V1K12A00

5 10 16 CIE3R-ADP010-P4 VFD-KDRA5L VFD-KDRB1P VFD-V1K18A00

7.5 15 24 CIE3R-ADP015-P4 VFD-KDRB2L VFD-KDRD1P VFD-V1K21A00

10 20 30 CIE3R-ADP020-P4 VFD-KDRB1L VFD-KDRD2P VFD-V1K27A00

10 25 39 CIE3R-ADP025-P4 VFD-KDRD1L VFD-KDRD3P VFD-V1K35A00

15 30 45 CIE3R-ADP030-P4 VFD-KDRD2L VFD-KDRD4P VFD-V1K45A00

20 40 61 CIE3R-ADP040-P4 VFD-KDRC1L VFD-KDRC1P VFD-V1K55A00

20 50 75 CIE3R-ADP050-P4 VFD-KDRF2L VFD-KDRF1P VFD-V1K80A00

20 60 91 CIE3R-ADP060-P4 VFD-KDRF4L VFD-KDRF2P VFD-V1K80A00

20 75 110 CIE3R-ADP075-P4 VFD-KDRF3L VFD-KDRF3P VFD-V1K110A00

20 100 152 CIE3R-ADP0100-P4 VFD-KDRH3L VFD-KDRH1P VFD-V1K130A00

20 125 183 CIE3R-ADP0125-P4 VFD-KDRH2L VFD-KDRI1P VFD-V1K160A00

OptionsPart Number Description

VFD-RPL/120 Run Pilot Light for Type 12 & 3R (Green Standard)

VFD-FLT/120 Fault Pilot Light for Type 12 & 3R (Red Standard)

VFD-OFF/120 Off Pilot Light for Type 12 & 3R (Red Standard)

VFD-SPD Door Mounted Speed Potentiometer

VFD-LTA Lightning Arrestor

VFD-KPD Door Mounted Keypad

VFD-KPD/4X Door Mounted Keypad with Type 4X Cover

Ordering and Sizing Information

PUMP CONTROLS

*��Maximum�HP�of��3-phase�motor�in�single�phase�power�applications

*��Maximum�HP�of��3-phase�motor�in�single�phase�power�applications

Page 30: West Coast Power Cerus Catalog

* As compared to typical sinusoidal pulse width modulation

Featuring Space Vector Modulation � Reduced harmonic distortion, torque ripple, and current ripple* � Motors run cooler, smoother with greater torque and efficiency

VARIABLE FREQUENCYDRIVES C Series

Micro-Single Phase GS Series Compact Space Vector VFD

P Series Dual Rated Optimized

Description A�fully�capable�micro�drive�that�accepts�single�phase�input�and�provides�three�phase�space�vector�pulse�width�modulated�output.

An�economical,�compact�and�full-featured�micro�drive�delivers�high�performance�control�through�programmable�inputs,�PID�operation�and�communications.

Dual-rated�for�either�variable�or�constant�torque�applications.�Integrated�communications,�dual�PID�control�and�sleep�mode�maximize�installation�flexibility.

Horsepower Range 1/2~3HP 1/2~5HP 7.5~400HP

Voltage Ratings

Input 1Ø, 200~230V (+10%, -15%) 3Ø, 200~230V (+10%, -15%)3Ø, 380~480V (+10%, -15%)

3Ø, 200~230V (+10%, -15%)3Ø, 380~480V (+10%, -15%)

Output 200~230V 3Ø, 200~230V3Ø, 380~480V

3Ø, 200~230V3Ø, 380~480V

Frequency Ranges

Input 50-60Hz 50-60Hz 50-60Hz

Output 0-400Hz 0-400Hz 0-120Hz

User Interface 3-Character LED Display with 4-Direction Keypad & Potentiometer

4-Character LED Display with 4-Direction Keypad

32-Character Backlit LCD Display with Keypad

Digital Inputs 5 Programmable 8 Programmable 8 Programmable

Analog Inputs 0-10VDC & 4-20mA 0-10VDC & 4-20mA 0-10VDC & 4-20mA

Analog Outputs 0-10VDC 0-10VDC 0-10VDC

Enclosure Open Chassis (IP20) UL Type 1 (Optional) UL Type 1 (Standard)

Page 31: West Coast Power Cerus Catalog

60

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 61

Standard Features � Sensorless & space vector control (Space Vector PWM by IGBT) � 150% torque at 0.5Hz. � 1~400Hz output frequency � Heavy duty: rated at 100% load at 15kHz carrier frequency

Intuitive Interface, Easy to Program � PID control for built-in process applications � Built-in potentiometer � Programmable I/O � PNP/NPN selectable digital inputs � 0~10VDC analog output (PWM) � Optional ModBus communications � Ground fault protection � Built-in RFI filter (Class A)

The�C-Series�interface�features�a�jogwheel�and�LED�display.

Terminal�connections�on�the�C-Series�drive�allow�for�easy�setup.

� Easy user setup � Improved torque at low speed � Optimized motor control � Auto-tuning algorithm simplifies commissioning

Micro-Single Phase C Series VFD0.5–3HPInput 1Ø, 230VAC - Output 3Ø, 230VACSpace Vector Pulse Width Modulation

OptionDescription Part Number

ModBus communication card CI-MB-COM-C

Specifications

Output RatingsVoltage (V) Three phase, 200~230V

Frequency (Hz) 0~400Hz

Input RatingsVoltage (V) Single phase, 200~230V (±10%)

Frequency (Hz) 50~60Hz (±5%)Control method Sensorless vector, V/F control (Space vector PWM)

Frequency setting resolution Digital reference: 0.01Hz (below 99Hz) & 0.1Hz (100Hz and over), Analog reference: 0.03Hz at 50Hz Frequency setting accuracy Digital: 0.01% of maximum output frequency, Analog: 0.1% of maximum output frequency

V/F ratio Linear, Square, User V/FOperation Overload capacity 1 minute at 150%, 30 seconds at 200% (with inverse characteristic proportional to time)

Torque boost Auto, Manual (0~15%)Assigned terminals FX (forward), RX (reverse), BX (inverter stop input), RST (reset), JOG (jog)

Programmable input terminals 5 digital InputsAnalog output 0~10V Linear

Input Signal

Operator control 3 digit LED keypad, Terminals, ModBus communicationFrequency setting Analog: 0~10V, 4~20mA, Digital: Keypad, Communication: ModBus

Start signal Forward, ReverseMulti-step operation Setting up to 8 speeds (using multi-function terminal)

Multi-step accel./decel. time 0.1~6000 seconds. Maximum 8 pre-defined steps using multi-function terminals

Operational functions DC braking, Frequency limit, Frequency jump, Second motor function, Slip compensation, Reverse rotation prevention, Auto restart, PID controls

Emergency stop Interrupting output from inverterJog Jog operation at 10Hz

Fault reset Resets fault signal when protective function is active

Output SignalOperational status Frequency detection, Overload alarm, Stall, Overvoltage, Undervoltage, Inverter overheat, Run, Stop, Constant speed,

Speed search, Fault output (relay and open collector output)

Indicator Output frequency, Output current, Output voltage, DC voltage, RPM

Protective FunctionsTrip Overvoltage, Undervoltage, Overcurrent, Inverter overheat, Motor overheat, I/O phase loss, I/O miss wiring,

Overload, Speed command loss, Hardware fault, Communication errorAlarm Stall; Overload

Operating Environment

Ambient temperature -10°~ 40° CStorage temperature -20°~ 65° C

Humidity 90% Relative Humidity maximum (non-condensing)Altitude & Vibration 1000m max, 5.9m/sec2(0.6g) max.

Application site No corrosive gas, flammable gas, oil mist or dust

Dimensions (H x W x D)

CI-000-C2, CI-001-C2 5.63” x 3.11” x 5.63”CI-002-C2, CI-003-C2 5.63” x 6.14” x 5.63”

Weight (lbs)CI-000-C2, CI-001-C2 2.9 lbsCI-002-C2, CI-003-C2 5.4 lbs

Micro-Single Phase C-Series VFDHP kW Capacity (kVA) FLA Part Number 3% Line Reactor*

1/2 0.4 0.95 2.5 CI-000-C2-1P KDRULA54LE01

1 0.75 1.9 5 CI-001-C2-1P KDRULA25LE01

2 1.5 3 8 CI-002-C2-1P KDRULA27LE01

3 2.2 4.5 12 CI-003-C2-1P KDRULA28LE01

*�Line�Reactors�housed�in�separate�UL�Type�1�Enclosure

VARIABLE FREQUENCY DRIVES

Page 32: West Coast Power Cerus Catalog

62

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 63

Intelligent High Performance � Precise control and high starting torque

(up to 150% at 0.5 Hz (Space Vector PWM by IGBT) � Auto carrier frequency adjusts inversely in relation to temperature of drive

for long term reliability � Ground fault protection of output terminal during run � Quiet operation thanks to fan control coordination

with motor start/stop

Easy To Set Up and Operate � New 4-direction keypad makes parameter settings a snap � Operation algorithm helps prevent nuisance tripping � Auto & manual torque boost � Optimum acceleration and deceleration curves set automatically for

maximum torque - or choose one of three different patterns � 8 preset speeds

Flexible � ModBus & 485 communication for easy integration � Built-in dynamic braking unit (external resistor required) � Remote keypad mounting available for flexible installation options � Built-in fault memory (stores last five fault conditions)

Compact GS Series VFD0.5–5HP200~230VAC, 380~480VAC, 3ØCompact Design, Sensorless & VF Control

With�sensorless�control�the�GS�series�makes�motor�control�easy.

The�easy�to�use�4-direction�keypad�makes�settings�a�snap.

Specifications

Output ratingsVoltage (V) Three phase, 200~230V or Three phase, 380~480V

Frequency (Hz) 0~400Hz

Input ratingsVoltage (V) Three phase, 200~230V (+10%, -15%) or Three phase, 380~480V (+10%, -15%)

Frequency (Hz) 50~60Hz (±5%)

Operation

Control method Sensorless Vector, V/F control (Space vector PWM)Frequency setting resolution Digital reference: 0.01Hz (below 99Hz) & 0.1Hz (100Hz and over); Analog reference: 0.03Hz at 50Hz

Frequency setting accuracy Digital: 0.01% of maximum output frequency; Analog: 0.1% of maximum output frequencyV/F ratio Linear; Square; User V/F

Overload capacity 1 minute at 150%; 30 seconds at 200% (with inverse characteristic proportional to time)Torque boost Auto; Manual (0~15%)

Assigned terminals FX (forward), RX (reverse), BX (inverter gate blocking), RST (reset), JOG (jog)Programmable input 8 digital inputs

Analog output 0~10V linear

Input signal

Operator control 4 digit LED display/keypad, Terminals, ModBus communicationFrequency setting Analog: 0~10V, 4~20mA, Digital: Keypad, Communication: ModBus

Start signal Forward, ReverseMulti-step operation Setting up to 8 speeds (using multi-function terminal)

Multi-step accel./decel. time 0.1~6000 seconds. Maximum 8 pre-defined steps using multi-function terminals

Operational functions DC braking, Frequency limit, Frequency jump, Second motor function, Slip compensation, Reverse rotation prevention Auto restart, PID controls

Emergency stop Interrupting output from inverterJog Jog operation

Fault reset Resets fault signal when protective function is active

Output signalOperational status Frequency detection, Overload alarm, Stall, Overvoltage, Undervoltage, Inverter overheat, Run, Stop, Constant speed,

Speed search, Fault output (relay and open collector output)

Indicator Output frequency, Output current, Output voltage, DC voltage, rpm

Protective functionsTrip Overvoltage, Undervoltage, Overcurrent, Inverter overheat, Motor overheat, I/O phase loss, I/O mis-wiring, Overload,

Speed command loss, Hardware fault, Communication error

Alarm Stall, Overload

Operatingenvironment

Ambient temperature -10°~ 50° CStorage temperature -20°~ 65° C

Humidity 90% Relative Humidity maximum (non-condensing)Altitude & Vibration 1000m max, 5.9m/sec2(0.6g) max.

Application site No corrosive gas, flammable gas, oil mist or dust

Dimensions (H x W x D)

CI-000-GS2/GS4, CI-001-GS2/GS4 5.04” x 2.76” x 5.12” (Height is 6.90” w/ NEMA kit)CI-002-GS2/GS4 5.04” x 3.94” x 5.12” (Height is 6.90” w/ NEMA kit)

CI-003-GS2/GS4, CI-005-GS2/GS4 5.04” x 5.51” x 6.10” (Height is 6.90” w/ NEMA kit)

Weight (lbs)CI-000-GS2/GS4, CI-001-GS2/GS4 1.7 lbs

CI-002-GS2/GS4 2.5 lbsCI-003-GS2/GS4, CI-005-GS2/GS4 4.1 lbs

OptionsDescription Part Number

Remote Keypad Mounting Kit (2 Meter Cable) CI-RKPK-EXT2M-GS

Remote Keypad Mounting Kit (3 Meter Cable) CI-RKPK-EXT3M-GS

Remote Keypad Mounting Kit (5 Meter Cable) CI-RKPK-EXT5M-GS

GS Series VFD (3-Phase, 200~230V)HP kW Capacity (kVA) FLA Part Number NEMA 1 Kit 3% Line Reactor*

1/2 0.4 0.95 2.5 CI-000-GS2 CI-NEMA1-GS/A KDRULA54LE01

1 0.75 1.9 5 CI-001-GS2 CI-NEMA1-GS/A KDRULA25LE01

2 1.5 3 8 CI-002-GS2 CI-NEMA1-GS/B KDRULA27LE01

3 2.2 4.5 12 CI-003-GS2 CI-NEMA1-GS/C KDRULA28LE01

5 3.7 6.1 16 CI-005-GS2 CI-NEMA1-GS/C KDRULB22LE01

GS Series VFD (3-Phase, 380~480V)HP kW Capacity (kVA) FLA Part Number NEMA 1 Kit 3% Line Reactor*

1/2 0.4 0.95 1.25 CI-000-GS4 CI-NEMA1-GS/A KDRULA6LE01

1 0.75 1.9 2.5 CI-001-GS4 CI-NEMA1-GS/A KDRULA8LE01

2 1.5 3 4 CI-002-GS4 CI-NEMA1-GS/B KDRULA1LE01

3 2.2 4.5 6 CI-003-GS4 CI-NEMA1-GS/C KDRULA2LE01

5 3.7 6.1 8 CI-005-GS4 CI-NEMA1-GS/C KDRULA3LE01

*�Line�Reactors�housed�in�separate�UL�Type�1�Enclosure

*�Line�Reactors�housed�in�separate�UL�Type�1�Enclosure

VARIABLE FREQUENCY DRIVES

Page 33: West Coast Power Cerus Catalog

64

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 65

Intuitive Keypad Interface, Easy to Program � E asy-set up thanks to 32 character LCD & simplified parameters � Each drive ships with easy to follow Quick Start guide � Save, download & upload parameter settings to multiple drives

with a single keypad � DriveView software allows VFD to interface with a PC � Displays parameters in plain English

Maximize Energy Savings � Space-vector control for clean sine wave output increasing efficiency and

extending motor life � Sleep-mode conserves energy when demand level falls

below set threshold � Automatic self tuning for maximum energy savings � Quiet, super smooth 15kHz carrier frequency operation

Versatile Features for the Most Demanding Applications � Sensorless vector control for variable load applications � Built-in multi-motor control (for up to 4 additional motors) � Dual PID controls � Torque boost and stall prevention features guarantees smooth motor starts � 8 programmable digital inputs, 2 analog inputs (0-10VDC, 4-20mA) � Optional DC braking units ensure quick, controlled deceleration

P-Series VFD7.5–40HP (200~230VAC), 7.5–400HP (380~480VAC), 3ØDual Rated for Constant & Variable TorqueIntegrated PID Control

The�32-character�backlit�LCD�screen�displays�the�drive’s�operational�status�and�parameter�settings.

The�P-Series�clearly�marked�terminal�inputs�and�outputs�allow�for�easy�wiring�and�setup.

DimensionsModel Height (w/NEMA kit) Width Depth Weight

CI-007-P2, CI-007-P4 11.19” (11.19”) 5.91” 6.17” 10.8 lbs.

CI-010-P2, CI-010-P4

CI-015-P2, CI-015-P411.19” (11.19”) 7.88” 7.17” 13.2 lbs.

CI-020-P2, CI-020-P4

CI-025-P2, CI-025-P415.17” (17.88”) 9.85” 7.92” 28.7 lbs.

CI-030-P2, CI-030-P4

CI-040-P2, CI-040-P418.12” (23.59”) 11.98” 9.22” 44.1 lbs.

CI-050-P4 20.28” (25.28”) 11.81” 10.46” 59.5 lbs.

CI-060-P4, CI-075-P4 20.28” (25.28”) 11.81” 11.52” 64.0 lbs.

CI-100-P4, CI-125-P4 23.09” (30.22”) 14.57” 13.29” 94.8 lbs.

CI-150-P4, CI-200-P4 30.26” 20.80” 16.64” 223 lbs.

CI-250-P4 33.23” 20.80” 16.64” 252 lbs.

CI-350-P4, CI-400-P4 41.85” 27.17” 17.70” 441 lbs.

Multi-Function InputsProgrammable inputs for flexible system integration

Sleep ModeDrive shuts down at low loads; CPU idles until demand increases

Flying StartDrive matches motor speed at start-up

Dynamic BrakingSpeed reductive capability

Auto Energy SavingsSelf optimizing regulation to slash kWhTrack energy consumption with no added cost!

Multi-Motor ControlControl up to 4 additional motors

Specifications

Output ratingsVoltage (V) Three phase, 200~230V, Three phase, 380~480V

Frequency (Hz) 0~120Hz

Input ratingsVoltage (V) Three phase, 200~230V (-15%, +10%), Three phase, 380~480V (-15%, +10%)

Frequency (Hz) 50~60Hz (±5%)Input Power Factor <.95 from no load to full load

Operation

Drive Efficiency >96%Control method V/F control, Sensorless vector control

Frequency setting resolution Digital reference: 0.01Hz (below 99Hz) & 0.1Hz (100Hz and over); Analog reference: 0.06Hz at 60HzFrequency setting accuracy Digital: 0.01% of maximum output frequency; Analog: 0.1% of maximum output frequency

V/F ratio Linear, Square, User V/FOverload capacity 1 minute at 120%, 10 seconds at 150% (with inverse characteristic proportional to time)

Torque boost Auto, Manual (0~15%)Multi-function input terminals Total 8 inputs (programmable)

Analog output 0~10V linear

Input signal

Operator control 32-character LCD keypad, Terminals, ModBus-RTU communication Optional ModBus-RTU, RS485, ProfiBus-DP, DeviceNet, F-Net

Frequency setting Analog: 0~10V, 4~20mA, additional port for Sub-Board (0~10V); Digital: Keypad, CommunicationStart signal Forward, Reverse

Multi-step operation Setting up to 8 speeds (using multi-function terminal)

Multi-step accel/decel time 0.1~6000 seconds. Maximum 8 pre-defined steps using multi-function terminals

Operational functions

DC braking, Frequency limit, Frequency jump, Second motor function, Slip compensation, Reverse rotation prevention, Auto start, Inverter bypass, Auto-tuning, Dual PID control

Emergency stop Interrupting output from inverterAuto operation Operates from internal sequence by setting multi-function terminal (5 way x 8 step)

Jog Jog operationFault reset Resets fault signal when protective function is active

Output signalOperational status Frequency detection, Overload alarm, Stall, Overvoltage, Undervoltage, Inverter overheat, Run, Stop, Constant speed,

Speed search, Fault output (relay and open collector output), Inverter bypass, Auto-operation sequence

Indicator Output frequency, Output current, Output voltage, DC voltage, Output torque (output voltage: 0~10V)

Protective functionsTrip Overvoltage, Undervoltage, Overcurrent, Inverter overheat, Motor overheat, I/O phase loss, I/O miss wiring, Fuse open,

Ground fault, External fault 1, 2, Option fault, Overload, Speed command loss, Hardware fault, Communication error

Alarm Stall, Overload *Temperature sensor fault

Operatingenvironment

Ambient temperature -10°~40° CStorage temperature -20°~65° C

Humidity Less than 90% Relative Humidity maximum (non-condensing)Altitude-vibration Below 1,000m or 3,300ft. below 59 (=0.6g)

Application site No corrosive gas, combustible gas, oil mist or dust

VARIABLE FREQUENCY DRIVES

Page 34: West Coast Power Cerus Catalog

66

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 67

P-Series VFD (3-Phase, 200~230V)

Standard Duty (VT) Heavy Duty (CT)

HP kW FLA HP kW FLA Part Number 3% Line Reactor*

7.5 5.5 24 5 3.7 17 CI-007-P2 KDRULB23LE01

10 7.5 32 7.5 5.5 23 CI-010-P2 KDRULD25LE01

15 11 46 10 7.5 33 CI-015-P2 KDRULD24LE01

20 15 60 15 11 44 CI-020-P2 KDRULD26LE01

25 18.5 74 20 15 54 CI-025-P2 KDRULC22LE01

30 22 88 25 18.5 68 CI-030-P2 KDRULF24LE01

40 30 115 30 22 84 CI-040-P2 KDRULF25LE01

P-Series VFD (3-Phase, 380~480V)

Standard Duty (VT) Heavy Duty (CT)

HP kW FLA HP kW FLA Part Number 3% Line Reactor*

7.5 5.5 12 5 3.7 8 CI-007-P4 KDRULA4LE01

10 7.5 16 7.5 5.5 11 CI-010-P4 KDRULA5LE01

15 11 24 10 7.5 17 CI-015-P4 KDRULB2LE01

20 15 30 15 11 22 CI-020-P4 KDRULB1LE01

25 18.5 39 20 15 28 CI-025-P4 KDRULD1LE01

30 22 45 25 18.5 34 CI-030-P4 KDRULD2LE01

40 30 61 30 22 44 CI-040-P4 KDRULC1LE01

50 37 75 40 30 55 CI-050-P4 KDRULF2LE01

60 45 91 50 37 66 CI-060-P4 KDRULF4LE01

75 55 110 60 45 80 CI-075-P4 KDRULF3LE01

100 75 152 75 55 111 CI-100-P4 KDRULH3LE01

125 90 183 100 75 134 CI-125-P4 KDRULH2LE01

150 110 223 125 90 183 CI-150-P4 KDRULH1LE01

200 132 264 150 110 223 CI-200-P4 KDRULG3LE01

250 160 325 200 132 264 CI-250-P4 KDRULG1LE01

350 220 432 250 160 325 CI-350-P4 KDRULJ2LE01

400 280 547 300 220 432 CI-400-P4 KDRULJ1LE01

OptionsDescription Part Number

Remote Keypad Mounting Kit (2 Meter Cable) CI-RKPK-EXT2M-P/S

Remote Keypad Mounting Kit (3 Meter Cable) CI-RKPK-EXT3M-P/S

Remote Keypad Mounting Kit (5 Meter Cable) CI-RKPK-EXT5M-P/S

RS485 communication card CI-R4-COM

DeviceNet communication card CI-DN-COM

N2 communication card CI-N2-COM

ProfiBus DP communication card CI-PB-COM

UL Type 3R

Dynamic Braking Units & Resistors (200~230VAC)

Max HP Part Number DB Resistor Part Number Min Ohms kW

20 CI-DBU-20-2 DB8D50-3K20-10600AA0 8.5Ω 3.2

30 CI-DBU-30-2 DB5D8-5K0-10900AA0 5.8Ω 5.0

50 CI-DBU-40-2 DB4D5-6K5-10900AA0 4.5Ω 6.5

75 CI-DBU-50-2 DB3D0-10K0-10900AA0 3.0Ω 10.0

Dynamic Braking Units & Resistors (380~480VAC)

Max HP Part Number DB Resistor Part Number Min Ohms kW

20 CI-DBU-20-4 DB34D0-3K20-10600AA0 34.0Ω 3.2

30 CI-DBU-30-4 DB23D0-5K00-10900AA0 23.0Ω 5.0

50 CI-DBU-40-4 DB17D0-6K50-10900AA0 17.0Ω 6.5

75 CI-DBU-50-4 DB11D5-10K0-10900AA0 11.5Ω 10.0

100 CI-DBU-60-4 DB8D50-13K0-11800AA0 8.5Ω 13.0

Dynamic Braking Units & Resistors100% Braking Torque & 10% Duty CycleCompatible with P Series VFDEnclosed IP20 Chassis

DBU & Resistor Sizing GuideApplication Multiplier (x HP)

Fans, Blowers & Pumps 1.0

Pump Jacks, Washing Machines, Presses & E-Stop Systems 1.5

Cranes, Hoists, High-Inertia Turntables & Elevators 2.0

Responsive Braking For Maximum Process Control � Resistors Sized to Dynamic Braking Unit’s Maximum Capacity � Flexible sizing options using single or multiple units to meet

braking requirements � Built-in thermostat protects from overheating by tripping VFD

if wired to digital input � Combine resistors in series or in parallel connections to

achieve requirements for custom applications

M

P-Series VFDDynamic

Braking Unit

Thermostat Contact

Resistor

Twisted Wires 30” max

Twisted Wires

30” maxPOWER

RUN

OHT

OCT

FOT

VARIABLE FREQUENCY DRIVES

Page 35: West Coast Power Cerus Catalog

ENGINEERED SOLUTIONSBecause not every motor control application is the same, we offer engineered solutions for our starter and VFD products. Modifications include a full range of enclosure options capable of withstanding almost any environment, complex multi-motor control, or simply ensuring the controls follow a specific sequence of operations. We respond, often times with same day quotes depending on application complexity and job requirements.

BYPASSES &ENCLOSED DRIVES Contact�Cerus�for�More�Information

� Cerus P-Drive with Space Vector Control for high efficiency and enhanced motor life

� Fully-enclosed drive options � Bypass cabinets with hinged enclosures and

easy access terminal inputs � Door mounted control options including

HOA and VFD/Off/Bypass switches, speed potentiometer and pilot lights

� Two and Three contactor bypass configurations with disconnect options

� Panel space heaters available for ambient temperatures below 32° F

Page 36: West Coast Power Cerus Catalog

70

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 71

Features � Reduces input line distortion � Eliminates transient and overvoltage

nuisance tripping � Provides maximum harmonic

mitigation without adding capacitance

� Improve true power factor � Helps to prevent VFD

component damage

Optimized Line Reactors (200~230V) 3%

HP Open Chassis

UL Type 1 Enclosed

1/2 KDRA54L KDRULA54LE01 3/4 KDRA53L KDRULA53LE01

1 KDRA25L KDRULA25LE01 1.5 KDRA26L KDRULA26LE01 2 KDRA27L KDRULA27LE01 3 KDRA28L KDRULA28LE01 5 KDRB22L KDRULB22LE01

7.5 KDRB23L KDRULB23LE01 10 KDRD25L KDRULD25LE01 15 KDRD24L KDRULD24LE01 20 KDRD26L KDRULD26LE01 25 KDRC22L KDRULC22LE01 30 KDRF24L KDRULF24LE01 40 KDRF25L KDRULF25LE01

5%

OpenChassis

UL Type 1 Enclosed

KDRA54H KDRULA54HE01 KDRA53H KDRULA53HE01 KDRA25H KDRULA25HE01 KDRA27H KDRULA27HE01 KDRA26H KDRULA26HE01 KDRA28H KDRULA28HE01 KDRB25H KDRULB25HE01 KDRB26H KDRULB26HE01 KDRD21H KDRULD21HE01 KDRD22H KDRULD22HE01 KDRC22H KDRULC22HE01 KDRF28H KDRULF28HE01 KDRF25H KDRULF25HE01 KDRF26H KDRULF26HE01

Optimized Line Reactors (380~480V) 3%

HP Open Chassis

UL Type 1 Enclosed

1/2 KDRA6L KDRULA6LE013/4 KDRA7L KDRULA7LE01

1 KDRA8L KDRULA8LE011.5 KDRA9L KDRULA9LE012 KDRA1L KDRULA1LE013 KDRA2L KDRULA2LE015 KDRA3L KDRULA3LE01

7.5 KDRA4L KDRULA4LE0110 KDRA5L KDRULA5LE0115 KDRB2L KDRULB2LE0120 KDRB1L KDRULB1LE0125 KDRD1L KDRULD1LE0130 KDRD2L KDRULD2LE0140 KDRC1L KDRULC1LE0150 KDRF2L KDRULF2LE0160 KDRF4L KDRULF4LE0175 KDRF3L KDRULF3LE01

100 KDRH3L KDRULH3LE01125 KDRH2L KDRULH2LE01150 KDRH1L KDRULH1LE01200 KDRG3L KDRULG3LE01250 KDRG1L KDRULG1LE01300 KDRG2L KDRULG2LE01350 KDRJ2L KDRULJ2LE01400 KDRJ1L KDRULJ1LE01

5%Open

ChassisUL Type 1 Enclosed

KDRA6H KDRULA6HE01KDRA7H KDRULA7HE01KDRA8H KDRULA8HE01KDRA9H KDRULA9HE01KDRA1H KDRULA1HE01KDRA2H KDRULA2HE01KDRA3H KDRULA3HE01KDRA4H KDRULA4HE01KDRA5H KDRULA5HE01KDRB2H KDRULB2HE01KDRC3H KDRULC3HE01KDRC1H KDRULC1HE01KDRE2H KDRULE2HE01KDRF4H KDRULF4HE01KDRF1H KDRULF1HE01KDRF2H KDRULF2HE01KDRH2H KDRULH2HE01KDRH1H KDRULH1HE01KDRG3H KDRULG3HE01KDRG1H KDRULG1HE01KDRJ1H KDRULJ1HE01KDRL1H KDRULL1HE01KDRL2H KDRULL2HE01KDRL3H KDRULL3HE01KDRL4H KDRULL4HE01

Specifications � Maximum current: 100kA � Maximum energy: 3000J � Unlimited number of surges � Response times to clamp:

- 1 mA test: 5 ns - 10kA: 10 ns - 50kA: 25 ns

Industrial Surge ArrestorsDescription Part Number

3-Phase 200~240V LA-302

3-Phase 440~600V LA-603

Optimized Line Reactors3 Phase, 600V Class UL & CE Marked Open Chassis & UL Type 1

LINE REACTORS

Optimized dV/dT Output FilterHorsepower

Open Chassis UL Type 1Enclosed 240V 480V

- 3/4 V1K2A00 V1K2A011/2 1-1.5 V1K3A00 V1K3A013/4 2 V1K4A00 V1K4A01

1-1.5 3 V1K6A00 V1K6A012 5 V1K8A00 V1K8A013 7.5 V1K12A00 V1K12A015 10 V1K16A00 V1K16A01- 10 V1K18A00 V1K18A01- 15 V1K21A00 V1K21A01

7.5 15 V1K25A00 V1K25A01- 20 V1K27A00 V1K27A01

10 25 V1K35A00 V1K35A0115 30 V1K45A00 V1K45A0120 40 V1K55A00 V1K55A01

25-30 50 - 60 V1K80A00 V1K80A0140 75 V1K110A00 V1K110A01- 100 V1K130A00 V1K130A01- 125 V1K160A00 V1K160A01- 150 V1K200A00 V1K200A01- 200 V1K250A00 V1K250A01- 250 V1K305A00 V1K305A01- 300 V1K362A00 V1K362A01- 350 V1K420A00 V1K420A01- 400 V1K480A00 V1K480A01

Optimized Output ReactorsHorsepower

Open Chassis UL Type 1Enclosed240V 480V

3/4 2 KDRA1P KDRULA1PE011 3 KDRA2P KDRULA2PE012 5 KDRA3P KDRULA3PE013 7.5 KDRA4P KDRULA4PE01- 10 KDRB1P KDRULB1PE015 15 KDRD1P KDRULD1PE01

7.5 20 KDRD2P KDRULD2PE0110 25 KDRD3P KDRULD3PE01- 30 KDRD4P KDRULD4PE01

15 40 KDRC1P KDRULC1PE0120 50 KDRF1P KDRULF1PE0125 60 KDRF2P KDRULF2PE0130 75 KDRF3P KDRULF3PE0140 100 KDRH1P KDRULH1PE01- 125 KDRI1P KDRULI1PE01- 150 KDRI2P KDRULI2PE01- 200 KDRG1P KDRULG1PE01- 250 KDRJ1P KDRULJ1PE01- 300 KDRJ2P KDRULJ2PE01- 350 KDRL1P KDRULL1PE01- 400 KDRL2P KDRULL2PE01

Output Reactors � Protection for motor leads between 50 - 100 ft � Protects VFD output by dampening peak

voltage overshoot � Extends motor life by reducing heat and

audible noise � Helps prevent VFD instantaneous

overcurrent trips

Drive Output Reactors & Filters3 Phase, 600V Class UL & CE Marked UL Type 1 & 3R Available

dV/dT Output Filters � Protection for motor leads exceeding 125 ft � Ensures smooth VFD sinusoidal output to motor � Extends motor life by reducing heat, audible

noise and insulation breakdown � Reduces “reflective wave” effect by limiting peak

voltage and rise time � Helps prevent VFD

instantaneous overcurrent trips

Page 37: West Coast Power Cerus Catalog

72

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 73

Engineered for Superior Accuracy & Performance � ±0.5% overall full scale at room temperature � ±1% overall full scale over -40°C to 105°C for 75 PSI to 200 PSI � Includes repeatability, hysteresis and linearity � Custom ASIC provides signal conditioning for calibration and

temperature compensation � Optional electrical connectors available (Packard, Deutsch, Mini DIN,

M12, Integral Harness)

Solid Construction � Laser-welded stainless steel design for optimal media isolation � Withstands up to three times full scale burst pressure � Reverse voltage protected

Accurate, Reliable & VersatileCerus�pressure�sensors�are�ideal�for�industrial�and�commercial�applications�where�measurement�and�performance�are�critical.�Additionally,�these�micro-machined�sensors�are�compact�in�size,�constructed�of�rugged�materials�designed�to�meet�the�highest�standards�of�chemical�compatibility.

Gage Pressure Sensors0-5VDC Output 4-20mA Output

Pressure Range Part Number Part Number

0-15 PSIG PG-15SB PG-15SC

0-25 PSIG PG-25SB PG-25SC

0-50 PSIG PG-50SB PG-50SC

0-75 PSIG PG-75SB PG-75SC

0-100 PSIG PG-100SB PG-100SC

0-250 PSIG PG-250SB PG-250SC

0-300 PSIG PG-300SB PG-300SC

0-500 PSIG PG-500SB PG-500SC

Gage Pressure Sensors0~500 PSIG ModelsStainless Steel Construction 36” Wire Leads, 1/4”-18 NPT

� Intrinsic flow measurement results in optimal performance � No gravity effect allows mounting in any position � LCD display for easy setup and commissioning � Switch-selectable pressure ranges � Applications include static pressure measurement, variable

air volume system control and monitoring filter status

Specifications

Power Supply 12-30VDC/24VAC, 30mA maximum (13VDC min for 10V full scale output)

Output Type Dual, 4-20mA & 0-5/10VDC (3-wire)

Output Scaling0-1” (Selectable 0.1, 0.5, 1.0) uni or bi-directional0-2” (Selectable 0.5, 1”, 2”) uni or bi-directional

Calibrated Temperature Range 32° to 122°F (0-50°C)

Media compatibility Dry, oil-free air, N2

Sensor Type Digital CMOS intrinsic flow differential pressurePerformance

Position EffectsNone - position insensitiveZero drift

Zero point Accuracy 0.5 PaSpan Accuracy 3% of reading

Zero point repeatability 0.1 PaSpan repeatability 0.5% of reading

Temp offset None (less than resolution)Temp span shift < 0.5% of reading per 10°C

Selectable Ranges, Outputs and Stable Dry Media Operation � Zero drift technology ensures precision measurement � LCD display for easy setup and commissioning � Auto zero pushbutton input and auto zero control

contact for system accuracy � Applications include duct pressure monitoring and

air-flow stations

Specifications

Power Supply 12-30VDC/24VAC, 30mA maximum (13VDC min for 10V full scale output)

Output Type Dual, 4-20mA & 0-5/10VDC (3-wire)

Output Scaling0-10” (Selectable 2.5, 5, 10"WC)0-25” (Selectable 10, 15, 25"WC)

Calibrated Temperature Range 50° to 140°F (10-60°C)

Media Dry, oil-free air, N2Sensor Type Integrated, micro machined silicon piezoresistivePerformance

Accuracy (Linearity, hysteresis,

temperature)2.5% full scale

Auto-zero input Pushbutton and contact closure input provided

Intrinsic Flow Measurement Technology for High Accuracy

Differential Pressure Transducers - 0”~2” WCPressure Range Enclosure Type Part Number

0~1"

Open Frame PDP30-001

NEMA 4 PDP31-001

NEMA 4 w/ Probe PDP32-001

0~2”

Open Frame PDP30-002

NEMA 4 PDP31-002

NEMA 4 w/ Probe PDP32-002

Differential Pressure Transducers - 0”~25” WC

Pressure Range Enclosure Type Part Number

0~10"NEMA 4 PDP31-010

NEMA 4 w/ Probe PDP32-010

0~25"NEMA 4 PDP31-025

NEMA 4 w/ Probe PDP32-025

Differential Pressure Transducers0~2” & 0~25” WC Models Dual Output Signals (4-20mA & 0-5/10VDC) Open Frame & NEMA 4 Enclosure Options

NEMA�4�enclosed�Cerus�Pressure�Transducer�shown�with�probe.

PRESSURE SENSORS/ TRANSDUCERS

Page 38: West Coast Power Cerus Catalog

74

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 75

Standard Features � Compact, space saving soft start with integrated electronic overload � Standard, built-in bypass � Aluminum chassis design ensures cool and efficient operation � Integrated LED display and control terminals � Rated for line or inside delta motor connections

Comprehensive Motor Protection � Current limiting and integrated phase loss � Starter over-temperature shut down with Reset pushbutton � Metal Oxide Varistors (MOV) protect SCRs from damaging surges

Easy Setup & Operation � LED display modes include: On, Ramp Up/Down, Run, Overload,

Phase Loss, Over-temp � Simple dial adjustments for: Motor FLA, Initial Voltage, Current Limit,

Ramp Up/Down Times � Adjustable ramp setting ranges (Up/Down 0-30 seconds) � End of Acceleration Relay (1 N.O. contact) � Fault Output Relay (1 N.O. contact) � Auxiliary relays

Economy Soft Starters Horsepower* Max

Amps Part Number DimensionsH x W x D (in) Weight (lbs)

230V 460V 575V

2 5 7.5 8 RVS-AX-8 9.5 x 4.75 x 4.25 6

5 10 15 17 RVS-AX-17 9.5 x 4.75 x 4.25 6

10 20 30 31 RVS-AX-31 9.5 x 4.75 x 4.25 6

20 40 50 58 RVS-AX-58 11 x 5 x 7.5 12

25 50 60 72 RVS-AX-72 11 x 5 x 7.5 12

30 60 75 85 RVS-AX-85 15 x 5 x 7.5 14

Economy Soft Starters2–75HP, 200~600VACIntegrated Bypass Electronic Motor Protection

Extend Equipment Life & Increase Savings

*�Horsepower�ratings�are�for�estimation�only.�Verify�actual�full�load�amp�requirements.

Reduced Voltage Analog Soft Starters Horsepower* Max

Amps Chassis UL Type 1 UL Type 12230V 460V 575V

5 10 15 15 SS6-15-CH SS6-15-N1 SS6-15-N12

10 25 30 30 SS6-30-CH SS6-30-N1 SS6-30-N12

20 40 50 50 SS6-50-CH SS6-50-N1 SS6-50-N12

30 60 75 75 SS6-80-CH SS6-80-N1 SS6-80-N12

50 100 125 125 SS6-125-CH SS6-125-N1 SS6-125-N12

75 150 200 200 SS6-200-CH SS6-200-N1 SS6-200-N12

150 300 350 350 SS6-360-CH SS6-360-N1 SS6-360-N12

200 400 500 500 SS6-500-CH SS6-500-N1 SS6-500-N12

250 500 600 600 SS6-600-CH SS6-600-N1 SS6-600-N12

300 600 800 800 SS6-800-CH SS6-800-N1 SS6-800-N12

Reduced Voltage Analog Soft Starters3~600HP, 200~600VACBuilt-In Motor Protection Open Chassis & Enclosed Options

Standard Features � Compact, space saving design � Integrated Class 20 electronic overload protection � Reduce peak power consumption during motor starts � Slower application torque reduces equipment shock � Solid-state reversing option eliminates installation of additional components � Dual operation modes to match application needs:

- Constant Current mode for light duty or limited power supplies - Current Ramp mode for high inertia or heavy loads

� Soft stop option controls motor deceleration (eliminates water hammer in pumping applications)

Full-featured Soft Starter with Dual Operation Modes

SOFT STARTS

*�Horsepower�ratings�are�for�estimation�only.�Verify�actual�full�load�amp�requirements.

Page 39: West Coast Power Cerus Catalog

76

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 77

Specifications

Power 3 Phase, 200-600VAC, 50/60Hz

Control* 115VAC 50Hz or 120VAC 60Hz

Digital Inputs 120VAC, 2mA

Bypass Outputs Relay contacts rated at 0.2A, 120VAC

Analog Input 0-10VDC

Analog Output 0-5VDC, 5mA max.

Protection Short circuit by fuses or circuit breaker

EnvironmentAmbient Temp 0° - 40° C

Humidity 90% RH max. (non-condensing)

Altitude & Vibration 1000m max, 5.9m/sec2(0.6g) max.

Reduced Voltage Digital Soft Starters3–1000HP, 200~600VACChassis, NEMA 1 & NEMA 12 Enclosure Options Available Bypass Configuration Option

Display & Control � Keypad and LCD display for easy starter setup, status and diagnostics � Soft stop, up-to-speed contact, shorted SCR detection and line/load

lugs standard with each unit � Enclosed models include control power transformer � 120VAC control inputs for: Start/Stop/Jog/Reverse/Reset/Enable � Two or three wire control allow for remote operation options � Dry contact relay outputs for: Fault/Bypass/Running/Reverse � 18-month warranty

Operation & Features � Provides smooth current ramp output to motor eliminating surges

and equipment shock � Adjustable ramp setting ranges (Up/Down 0-60 seconds) � Dual operation modes to match application needs:

- Constant Current mode for light duty or limited power supplies - Current Ramp mode for high inertia or heavy loads

� Jog speeds: Forward at 14% of full speed, Reverse at 20% of full speed � DC injection braking option for enhanced performance

Protective Functions � Class 10~30 adjustable electronic overload � 500% overload for 30 seconds guarantees heavy duty operation � Single phase protection � Instantaneous over-current trip � Shorted SCR fault output

Integrated Bypass Rated For Emergency Starts � Reduces enclosure size and eliminates need for additional cooling � Ensures reliable operation with automatic transition to bypass

contactor at full speed � Eliminates downtime in critical applications

Extreme Duty Rated Soft Starter For Industrial Demands

*�Control�voltage�not�supplied�by�soft�start.�CPT�option�available�in�bypass�units.

OptionsDescription Part Number

Door Mounted Keypad (RS232/485) SFS-DMK

Fault Pilot Light SFS-FPL

Run Pilot Light SFS-RPL

Reset Pushbutton SFS-RST

Two Position Selector Switch SFS-SSW2

Three Position Selector Switch SFS-SSW3

Stop Pushbutton (Red) SFS-STP

Start Pushbutton (Green) SFS-STR

EtherNetIP Communication Card SFS-EIP-COM

DC Injection Braking UnitsHorsepower

Chassis UL Type 1 UL Type 12230V 460V 575V

7.5 15 20 DCI-20-CH DCI-20-N1 DCI-20-N12

15 30 40 DCI-40-CH DCI-40-N1 DCI-40-N12

30 60 75 DCI-80-CH DCI-80-N1 DCI-80-N12

50 100 125 DCI-125-CH DCI-125-N1 DCI-125-N12

75 150 200 DCI-200-CH DCI-200-N1 DCI-200-N12

125 250 300 DCI-300-CH DCI-300-N1 DCI-300-N12

200 400 500 DCI-500-CH DCI-500-N1 DCI-500-N12

Reduced Voltage Digital Soft Starters - Standard UnitsHorsepower*

Chassis UL Type 12 UL Type 4 UL Type 4X230V 460V 575V

10 20 30 MS6-30-CH MS6-30-N12 MS6-30-N4 MS6-30-N4X

20 40 50 MS6-50-CH MS6-50-N12 MS6-50-N4 MS6-50-N4X

30 60 75 MS6-80-CH MS6-80-N12 MS6-80-N4 MS6-80-N4X

50 100 125 MS6-125-CH MS6B-125-N12 MS6B-125-N4 MS6B-125-N4X

75 150 200 MS6-200-CH MS6B-200-N12 MS6B-200-N4 MS6B-200-N4X

100 200 250 MS6-250-CH MS6B-250-N12 MS6B-250-N4 MS6B-250-N4X

150 350 400 MS6-420-CH MS6B-420-N12 MS6B-420-N4 MS6B-420-N4X

200 400 500 MS6-500-CH MS6B-500-N12 MS6B-500-N4 MS6B-500-N4X

250 500 600 MS6-600-CH MS6B-600-N12 MS6B-600-N4 MS6B-600-N4X

350 700 800 MS6-800-CH MS6B-800-N12 MS6B-800-N4 MS6B-800-N4X

Reduced Voltage Digital Soft Starters - Integrated Bypass Units

Horsepower*Non-Fused Disconnect Fused Disconnect Circuit Breaker UL Type 4 UL Type 4X

230V 460V 575V

10 20 30 MS6B-30-N12-NFD MS6B-30-N12-FD MS6B-30-N12-CB SFS-30-N4 SFS-30-N4X

20 40 50 MS6B-50-N12-NFD MS6B-50-N12-FD MS6B-50-N12-CB SFS-50-N4 SFS-50-N4X

30 60 75 MS6B-80-N12-NFD MS6B-80-N12-FD MS6B-80-N12-CB SFS-80-N4 SFS-80-N4X

50 100 125 MS6B-125-N12-NFD MS6B-125-N12-FD MS6B-125-N12-CB SFS-125-N4 SFS-125-N4X

75 150 200 MS6B-200-N12-NFD MS6B-200-N12-FD MS6B-200-N12-CB SFS-200-N4 SFS-200-N4X

100 200 250 MS6B-250-N12-NFD MS6B-250-N12-FD MS6B-250-N12-CB SFS-250-N4 SFS-250-N4X

150 350 400 MS6B-420-N12-NFD MS6B-420-N12-FD MS6B-420-N12-CB SFS-420-N4 SFS-420-N4X

200 400 500 MS6B-500-N12-NFD MS6B-500-N12-FD MS6B-500-N12-CB SFS-500-N4 SFS-500-N4X

250 500 600 MS6B-600-N12-NFD MS6B-600-N12-FD MS6B-600-N12-CB SFS-600-N4 SFS-600-N4X

350 700 800 MS6B-800-N12-NFD MS6B-800-N12-FD MS6B-800-N12-CB SFS-800-N4 SFS-800-N4X

*�For�900HP�and�above,�please�consult�factory�for�pricing.��

Ordering and Sizing Information

SOFT STARTS

Page 40: West Coast Power Cerus Catalog

78

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 79

Selector SwitchesType Part Number

2-PositionStay Put CB2-BD2

Spring Return CB2-BDR2

3-Position

Stay Put CB2-BD3

Spring Return CB2-BDR3

Spring Return (R to C) CB2-BD8

Spring Return (L to C) CB2-BD7

Non-Illuminated PushbuttonsColor Part Number

FlushMomentary

White CB2-BA1

Black CB2-BA2

Green CB2-BA3

Red CB2-BA4

ProjectingMomentary

White CB2-BL1

Black CB2-BL2

Green CB2-BL3

Red CB2-BL4

Reset*Black (Mechanical) CM2-BA2-RST

Black (Electrical) CB2-BA2-RST

Style Part Number

Emergency Stop(Red, 40mm)

Turn Release CB2-BS44

Key Release CB2-BS14

Push/Pull CB2-BT4

Key SwitchesType Part Number

2-Position Stay Put (All) CB2-BG4

3-Position Stay Put (All) CB2-BG0

Assemblies for Selector Switches & PushbuttonsContact Part Number

Contact Block & Collar

1 NO CB2-BZ101

1 NC CB2-BZ102

2 NO CB2-BZ103

2 NC CB2-BZ104

1 NO & 1 NC CB2-BZ105

Additional Contact Blocks (Max 6)

1 NO CB2-BE101

1 NC CB2-BE102

Pilot Devices & AccessoriesFits 22mm Mounting PatternsUL Type 1, 12, 3R, 4 & 4X

Legend PlatesDescription Part Number

Start CB2-PY2303Forward CB2-PY2305

Up CB2-PY2307On CB2-PY2311

Open CB2-PY2313Auto CB2-PY2315Reset CB2-PY2323Slow CB2-PY2327

Auto-Hand CB2-PY2364Stop CB2-PY2304

Reverse CB2-PY2306Down CB2-PY2308

Off CB2-PY2312Close CB2-PY2314Hand CB2-PY2316Inch CB2-PY2321Fast CB2-PY2328

Hand-Off-Auto CB2-PY2387Low CB2-PY2333High CB2-PY2334

High Low CB2-PY2335Off On CB2-PY2336

Up Down CB2-PY2338

Emergency Stop (60mm) CB2-PY9330

Emergency Stop (90mm) CB2-PY8330

START

*Mechanical�style�Reset�utilizes�CB2-RPX�extension�shaft�and�� electrical�style�utilizes�CB2-BZ�contact�block�assembly.

Complete Stations - Start/Stop Spring ReturnDescription Part Number

Plastic Control Station CC2P-215

Metal Control Station CC2M-215 � Meets UL Type 1, 12, 3R, 4 & 4X Ratings � Rugged Design � Convenient standard knockouts for easy installation

Compact Pilot LightsColor Part Number

Green CB2-B7-IV-73*

Red CB2-B7-IV-74*

Amber CB2-B7-IV-78*

*�Select�Desired�Voltage�From�Table�Upon�Ordering

Voltage Selection ChartAC Voltage 24VAC 110VAC 240VAC

DC Voltage 12VDC 24VDC

Miscellaneous AccessoriesDescription Part Number

Fixing Collar CB2-B

Spare/Replacement Keys CB2-K455

Padlocking Attachment CB2-BZ6

Projecting Pushbutton Boot (Clear) CC-L

Flush Pushbutton Boot (Clear) CC-S

5.125” plastic shaft (can be trimmed to any length) CB2-RPX

Modular LED Pilot Lights (Lens + Assembly)Color Part Number Part Number

Lens

Green CB2-BVL03

Assembly

CB2-BVL73*

Red CB2-BVL04 CB2-BVL74*

Yellow CB2-BVL05 CB2-BVL75*

*�Select�Desired�Voltage�From�Table�Upon�Ordering

ACCESSORIES

Page 41: West Coast Power Cerus Catalog

80

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 81

DK Series - Screw Clamp Connection

Part Number RatedCurrent

Rated Surge Voltage (kV)

Solid Wire(AWG)

Stranded Wire (AWG)

Wire Strip Length (in)

Torque (lb-in) Screw Dimensions

H x W x T (in)

DK2.5 25A 2.2 22~12 22~12 .39~.47 7 M3 .20 x 1.87 x 2.32

DK4 35A 2.2 22~10 22~10 .39~.47 7 M3 .24 x 1.87 x 2.32

DK6 45A 2.2 20~8 20~8 .31 15.6 M4 .31 x 1.87 x 2.32

DK10 60A 2.2 20~6 20~6 .47~.55 15.6 M4 .39 x 1.87 x 2.32

DK16 70A 2.2 14~6 14~6 .59~.67 30.4 M5 .47 x 2.50 x 2.32

DK35 115A 2.2 12~2 12~2 .63~.71 50 M6 .63 x 2.50 x 2.32

DK50 150A 2.2 6~2(105A) 6~1/0 .98~1.18 50 M6 .79 x 3.02 x 2.78

DK95 230A 2.2 2~4(100A) 2~4/0 1.18~1.34 90 M8 .98 x 3.48 x 3.15

Choose�between�cage�inserting�(left)�or�central�type�(right)�jumpers.

Specifications � Increases conductivity and prevents corrosion through electrolytic

copper conductors � Screws and fasteners are made of high carbon steel to withstand

higher torque � Steel yoke for tight wire connections and anti-vibration � Large contact points for reliable connections � Optional pre-printed terminal block markers (standard numeric or

custom marking available)

DIN Rail Mountable Terminal Blocks25~230A at 600VACAccepts Wire Size 22~4/0 AWGCompatible with TS-32 & TS-35 DIN

Standard�numeric�terminal�block�marking�(above).�Custom�marking�available�by�special�order.

Accessories

Model End Cover Partition EndBracket

Cross JumperTerminal Markers*Central Type Cage Inserting

2-Pole 3-Pole 2-Pole 3-Pole

DK2.5/GK2.5 DK2.5C DKSPS-002 SS4 DS2.5-02P DS2.5-03P CSC-2.5-02P CSC-2.5-03P TM08W

DK4/GK4 DK2.5C DKSPS-002 SS4 DS4-02P DS4-03P CSC-4-02P CSC-4-03P TM10W

DK6 DK2.5C DKSPS-002 SS7 DS6-02P DS6-03P CSC-6-02P CSC-6-03P TM11W

DK10/GK10 DK2.5C DKSPS-002 SS7 DS10-02P DS10-03P CSC-10-02P CSC-10-03P TM12W

DK16/GK16 DK16C DKSPS-003 SS6 DS16-02P DS16-03P TM13W

DK35 DK16C DKSPS-003 SS6 DS35-02P TM14W

DK50 SS6 TM14W

DK95 SS6 TM14W

*�Specify�numeric�label�range�or�custom�values�when�ordering

GK Series - Grounding Terminal Blocks

Part Number RatedCurrent

Rated Surge Voltage (kV)

Solid Wire(AWG)

Stranded Wire (AWG)

Wire Strip Length (in)

Torque (LB-in) Screw Dimensions

H x W x T (in)

GK2.5 25A 2.2 26~12 26~12 .39~.55 6.9 M3 .22 x 1.83 x 2.20

GK4 35A 2.2 26~10 26~10 .47~.63 6.9 M3 .26 x 1.83 x 2.20

GK10 50A 2.2 16~8 16~8 .47~.63 15.6 M4 .41 x 1.83 x 2.20

GK16 65A - 14~6 14~6 .55~.71 30.4 M5 .47 x 2.46 x 2.20

High Value, Supplemental Circuit Breaking � D curve magnetic trip point (10x rated current) provides

quick response short circuit protection � UL 1077 listed, supplemental overcurrent protection for

situations where UL 489 branch protection is already provided or unnecessary

� Ideal for highly inductive loads or transformers � IP20 finger safe design and 35mm DIN-rain mountable

Mini Circuit Breakers - D Curve Magnetic Trip (6kA @ 400VAC)

Amps Part Number Part Number Part Number

1 CI-MCB-D/1P-1A CI-MCB-D/2P-1A CI-MCB-D/3P-1A Aux Switch (1 NC) MCB-AUX-1NC

2 CI-MCB-D/1P-2A CI-MCB-D/2P-2A CI-MCB-D/3P-2A Aux Switch (1 NO) MCB-AUX-1NO

3 CI-MCB-D/1P-3A CI-MCB-D/2P-3A CI-MCB-D/3P-3A

4 CI-MCB-D/1P-4A CI-MCB-D/2P-4A CI-MCB-D/3P-4A

6 CI-MCB-D/1P-6A CI-MCB-D/2P-6A CI-MCB-D/3P-6A

10 1-Pole CI-MCB-D/1P-10A 2-Pole CI-MCB-D/2P-10A 3-Pole CI-MCB-D/3P-10A

SK Series - Spring Clamp Connection

Part Number EndCover

Terminal Markers*

RatedCurrent

Rated Surge Voltage (kV)

Solid Wire(AWG)

Stranded Wire (AWG)

Wire Strip Length (in)

DimensionsH x W x T (in)

SK4 SK4C TM10W 20A 2.2 28~12 28~12 .39~.55 1.30 x 2.32 x .24

S4K4 S4K4C TM10W 20A 2.2 28~12 28~12 .39~.55 1.30 x 3.39 x .24

Miniature Circuit Breakers1~10A at 460VACThermal-magnetic Release1, 2 & 3-Pole Models

ACCESSORIES

Page 42: West Coast Power Cerus Catalog

82

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 83

� Standoffs provided for mounting sub-panels

� Continuous hinged door

� Black quarter turn latches operated with screwdriver

� Ground stud on door

� ANSI-61 gray urethane polyester powder coating

*Mounting�holes�are�located�0.75”�in�from�each�side�and�0.455”�from�the�top�and�bottom

UL Type 1 Hinged Door Enclosures

EnclosurePart Number

Dimensions (in) Weight (lbs.)

Sub-Panel Part Number

Dimensions (in) Weight (lbs.)H W D H W

SCE-6N604LP 6 6 4 2 SCE-6N6MP 4 4 1SCE-8N604LP 8 6 4 2 SCE-8N6MP 6 4 1SCE-8N804LP 8 8 4 2 SCE-8N8MP 6 6 1SCE-8N806LP 8 8 6 2 SCE-8N8MP 6 6 1SCE-10N804LP 10 8 4 4 SCE-10N8MP 8 6 2SCE-10N806LP 10 8 6 5 SCE-10N8MP 8 6 2SCE-10N1004LP 10 10 4 4 SCE-10N10MP 8 8 3SCE-10N1006LP 10 10 6 6 SCE-10N10MP 8 8 3SCE-12N1004LP 12 10 4 5 SCE-12N10MP 10 8 3SCE-12N1006LP 12 10 6 8 SCE-12N10MP 10 8 3SCE-12N1204LP 12 12 4 7 SCE-12N12MP 10 10 4SCE-12N1206LP 12 12 6 9 SCE-12N12MP 10 10 4SCE-12N1208LP 12 12 8 12 SCE-12N12MP 10 10 4SCE-14N1204LP 14 12 4 7 SCE-14N12MP 12 10 4SCE-14N1206LP 14 12 6 10 SCE-14N12MP 12 10 4SCE-14N1208LP 14 12 8 13 SCE-14N12MP 12 10 4SCE-16N1206LP 16 12 6 11 SCE-16N12MP 14 10 4SCE-16N1208LP 16 12 8 15 SCE-16N12MP 14 10 4SCE-16N1606LP 16 16 6 16 SCE-16N16MP 14 14 4SCE-16N1608LP 16 16 8 20 SCE-16N16MP 14 14 4SCE-16N2006LP 16 20 6 19 SCE-20N16MP 18 14 7SCE-20N1606LP 20 16 6 19 SCE-20N16MP 18 14 7SCE-20N1608LP 20 16 8 25 SCE-20N16MP 18 14 7SCE-20N2006LP 20 20 6 24 SCE-20N20MP 18 18 9SCE-20N2008LP 20 20 8 31 SCE-20N20MP 18 18 9SCE-20N2010LP 20 20 10 39 SCE-20N20MP 18 18 9SCE-24N1606LP 24 16 6 27 SCE-24N16MP 22 14 7SCE-24N2006LP 24 20 6 28 SCE-24N24MP 22 18 11SCE-24N2008LP 24 20 8 31 SCE-24N20MP 22 18 11SCE-24N2010LP 24 20 10 32 SCE-24N20MP 22 18 11SCE-24N2406LP 24 24 6 40 SCE-24N24MP 22 22 11SCE-24N2408LP 24 24 8 42 SCE-24N24MP 22 22 11SCE-24N2412LP 24 24 12 49 SCE-24N24MP 22 22 11SCE-30N2406LP 30 24 6 51 SCE-30N24MP 28 22 13SCE-30N2408LP 30 24 8 57 SCE-30N24MP 28 22 13SCE-30N2412LP 30 24 12 61 SCE-30N24MP 28 22 13SCE-30N3008LP 30 30 8 60 SCE-30N30MP 28 28 20SCE-36N2406LP 36 24 6 56 SCE-36N24MP 34 22 21SCE-36N2408LP 36 24 8 62 SCE-36N24MP 34 22 21SCE-36N2412LP 36 24 12 73 SCE-36N24MP 34 22 21SCE-36N3006LP 36 30 6 68 SCE-36N30MP 34 28 23SCE-36N3008LP 36 30 8 69 SCE-36N30MP 34 28 23SCE-36N3012LP 36 30 12 83 SCE-36N30MP 34 28 23

UL Listed EnclosuresPowder Coated or Stainless Steel FinishQuarter Turn Latches on Hinged DoorsUL Type 1, 3R, 4, 4X & 12 Available

UL Type 3R Hinged Door Enclosure

EnclosurePart Number

Dimensions (in) Weight (lbs.)

Sub-PanelPart Number

Dimensions Weight (lbs.)H W D H W

SCE-12R1206LP 12 12 6 12 SCE-12DLP12 9 9 3SCE-12R1208LP 12 12 8 14 SCE-12DLP12 9 9 3SCE-16R1206LP 16 12 6 16 SCE-16P12 13 9 4SCE-16R1208LP 16 12 8 19 SCE-16P12 13 9 4SCE-20R1606LP 20 16 6 20 SCE-20P16 17 13 7SCE-20R1608LP 20 16 8 25 SCE-20P16 17 13 7SCE-24R2006LP 24 20 6 28 SCE-24P20 21 17 11SCE-24R2008LP 24 20 8 32 SCE-24P20 21 17 11SCE-24R2012LP 24 20 12 35 SCE-24P20 21 17 11SCE-30R2408LP 30 24 8 60 SCE-30P24 27 21 16SCE-30R2412LP 30 24 12 64 SCE-30P24 27 21 16SCE-36R2408LP 36 24 8 62 SCE-36P24 33 21 22SCE-36R2412LP 36 24 12 73 SCE-36P24 33 21 22SCE-36R3008LP 36 30 8 70 SCE-36P30 33 27 27SCE-36R3012LP 36 30 12 85 SCE-36P30 33 27 27SCE-42R3012LP 42 30 12 114 SCE-42P30 39 27 33

� Integrated rain hood � ANSI-61 gray urethane polyester powder coating over galvanized steel � Hinged door includes gasket

� Spot welded construction

� Black quarter-turn latch with padlocking provision

� Ground studs on door and body

� Standoffs provided for mounting optional sub-panels

UL Type 4/12 & 4X Junction Enclosure

Carbon Steel Part Number

Stainless Steel Part Number

Dimensions (in) Weight (lbs.)

Sub-PanelPart Number

Dimensions Weight (lbs.)H W D H W

SCE-604ELJ SCE-604ELJSS 6 4 4 3 SCE-6P4J 5.25 3.25 1SCE-606ELJ SCE-606ELJSS 6 6 4 4 SCE-6P4J 5.25 5.25 1SCE-806ELJ SCE-806ELJSS 8 6 4 4 SCE-8P6J 7.25 5.25 1SCE-8066ELJ SCE-8066ELJSS 8 6 6 5 SCE-8P6J 7.25 5.25 1SCE-1008ELJ SCE-1008ELJSS 10 8 4 6 SCE-10P8J 9.25 7.25 2SCE-10086ELJ SCE-10086ELJSS 10 8 6 8 SCE-10P8J 9.25 7.25 2SCE-1210ELJ SCE-1210ELJSS 12 10 4 10 SCE-12P10J 11.25 9.25 2SCE-12108ELJ SCE-12108ELJSS 12 10 8 12 SCE-12P10J 11.25 9.25 2SCE-1212ELJ SCE-1212ELJSS 12 12 6 11 SCE-12P12J 11.25 11.25 3SCE-1412ELJ SCE-1412ELJSS 14 12 6 13 SCE-14P12J 13.25 11.25 3SCE-14128ELJ SCE-14128ELJSS 14 12 8 15 SCE-14P12J 13.25 11.25 3SCE-1614ELJ SCE-1614ELJSS 16 14 6 16 SCE-16P14J 15.25 13.25 4SCE-16148ELJ SCE-16148ELJSS 16 14 8 18 SCE-16P14J 15.25 13.25 4SCE-20166ELJ — 20 16 6 21 SCE-20P16J 19.25 15.25 5SCE-20168ELJ — 20 16 8 23 SCE-20P16J 19.25 15.25 5SCE-20206ELJ — 20 20 6 25 SCE-20P20J 19.25 19.25 7SCE-20208ELJ — 20 20 8 28 SCE-20P20J 19.25 19.25 7SCE-202010ELJ — 20 20 10 31 SCE-20P20J 19.25 19.25 7

� Seams continuously welded and ground smooth

� Standoffs provided for mounting optional panels

� Removable stainless steel hinge pins

� Black quarter turn latches - opens with a screwdriver

� Ground stud on door and body

� Standard mounting hole pattern (1.28” from sides, 0.35” from top/bottom) � UL Type 4 enclosures finished with ANSI-61 gray urethane polyester powder

coating over .063” carbon steel � UL Type 4X enclosures finished with #4 brushed .075” Type 304 stainless steel

ENCLOSURES

Page 43: West Coast Power Cerus Catalog

84

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 85

UL Type 4/12 & 4X Enclosures

Carbon Steel Part Number

Weight (lbs.)

Stainless Steel Part Number

Weight (lbs.)

Dimensions Sub-Panel Part Number

Dimensions Weight (lbs.)H W D H W

SCE-12EL1206LP 14 SCE-12EL1206SSLP 15 12 12 6 SCE-12DLP12 9 9 3SCE-12EL2406LP 28 SCE-12EL2406SSLP 24 12 24 6 SCE-12P24 9 21 5SCE-16EL1206LP 17 SCE-16EL1206SSLP 17 16 12 6 SCE-16P12 13 9 4SCE-16EL1208LP 21 SCE-16EL1208SSLP 26 16 12 8 SCE-16P12 13 9 4SCE-16EL1408LP 20 — — 16 14 8 SCE-16DLP14 13 11 4SCE-16EL1606LP 21 SCE-16EL1606SSLP 21 16 16 6 SCE-16P16 13 13 5SCE-16EL1608LP 26 SCE-16EL1608SSLP 26 16 16 8 SCE-16P16 13 13 5SCE-16EL2006LP 27 — — 16 20 6 SCE-20P16 17 13 7SCE-16EL2008LP 27 SCE-16EL2008SSLP 29 16 20 8 SCE-20P16 17 13 7SCE-20EL1206LP 22 — — 20 12 6 SCE-20P12 17 9 5SCE-20EL1606LP 24 SCE-20EL1606SSLP 29 20 16 6 SCE-20P16 17 13 7SCE-20EL1608LP 27 SCE-20EL1608SSLP 27 20 16 8 SCE-20P16 17 13 7

— — SCE-20EL1610SSLP 30 20 16 10 SCE-20P16 17 13 7SCE-20EL1612LP 41 — — 20 16 12 SCE-20P16 17 13 7SCE-20EL2006LP 29 SCE-20EL2006SSLP 32 20 20 6 SCE-20P20 17 17 10SCE-20EL2008LP 31 SCE-20EL2008SSLP 33 20 20 8 SCE-20P20 17 17 10

— — SCE-20EL2010SSLP 42 20 20 10 SCE-24P20 21 17 11SCE-20EL2012LP 37 — — 20 20 12 SCE-20P20 17 17 10SCE-20EL2408LP 35 SCE-20EL2408SSLP 42 20 24 8 SCE-24P20 21 17 11

SCE-24EL1206LP 24 — — 24 12 6 SCE-12P24 9 21 5 SCE-24EL1606LP 31 — — 24 16 6 SCE-24P16 21 13 9SCE-24EL1608LP 30 SCE-24EL1608SSLP 32 24 16 8 SCE-24P16 21 13 9SCE-24EL2006LP 42 SCE-24EL2006SSLP 42 24 20 6 SCE-24P20 21 17 11SCE-24EL2008LP 35 SCE-24EL2008SSLP 37 24 20 8 SCE-24P20 21 17 11SCE-24EL2010LP 37 SCE-24EL2010SSLP 48 24 20 10 SCE-24P20 21 17 11SCE-24EL2012LP 52 SCE-24EL2012SSLP 52 24 20 12 SCE-24P20 21 17 11SCE-24EL2016LP 61 — — 24 20 16 SCE-24P20 21 17 11SCE-24EL2406LP 46 — — 24 24 6 SCE-24P24 21 21 14SCE-24EL2408LP 43 SCE-24EL2408SSLP 47 24 24 8 SCE-24P24 21 21 14SCE-24EL2410LP 54 SCE-24EL2410SSLP 54 24 24 10 SCE-24P24 21 21 14SCE-24EL2412LP 51 SCE-24EL2412SSLP 57 24 24 12 SCE-24P24 21 21 14

Construction & Specifications � Flange collar around all sides of door opening � Removable print pocket � Standoffs provided for mounting sub-panels � Removable and interchangeable doors � Black quarter turn latches operated with screwdriver � Ground stud on door and body

� Standard mounting holes located 0.75” from edges � UL Type 4 enclosures finished with ANSI-61 gray urethane

polyester powder coating over .075” carbon steel � UL Type 4X enclosures finished with #4 brushed .075” Type 304

stainless steel � Optional locking door latches available � Additional accessories available

UL Type 4/12 & 4X Single Door EnclosuresPowder Coated or Stainless Steel FinishDust & Oil Resistant GasketQuarter Turn Latches on Hinged Door

*Mounting�holes�are�located�.75”�in�from�each�side,�top�and�bottom.

Carbon Steel Part Number

Weight (lbs.)

Stainless Steel Part Number

Weight (lbs.)

Dimensions Sub-Panel Part Number

Dimensions Weight (lbs.)H W D H W

SCE-24EL2416LP 71 SCE-24EL2416SSLP 72 24 24 16 SCE-24P24 21 21 14SCE-24EL3008LP 53 SCE-24EL3008SSLP 58 24 30 8 SCE-30P24 27 21 16SCE-24EL3010LP 63 SCE-24EL3010SSLP 64 24 30 10 SCE-30P24 27 21 16SCE-30EL1606LP 42 SCE-30EL1606SSLP 42 30 16 6 SCE-30P16 27 13 12SCE-30EL2008LP 47 SCE-30EL2008SSLP 52 30 20 8 SCE-30P20 27 17 16SCE-30EL2010LP 50 SCE-30EL2010SSLP 57 30 20 10 SCE-30P20 27 17 16SCE-30EL2408LP 55 SCE-30EL2408SSLP 53 30 24 8 SCE-30P24 27 21 16SCE-30EL2410LP 68 SCE-30EL2410SSLP 68 3 24 10 SCE-30P24 27 21 16SCE-30EL2412LP 63 SCE-30EL2412SSLP 69 30 24 12 SCE-30P24 27 21 16SCE-30EL2416LP 80 SCE-30EL2416SSLP 80 30 24 16 SCE-30P24 27 21 16SCE-30EL2420LP 91 — — 30 24 20 SCE-30P24 27 21 16SCE-30EL2424LP 99 — — 30 24 24 SCE-30P24 27 21 16SCE-30EL3008LP 63 SCE-30EL3008SSLP 67 30 30 8 SCE-30P30 27 27 24SCE-30EL3010LP 82 SCE-30EL3010SSLP 81 30 30 10 SCE-30P30 27 27 24SCE-30EL3012LP 82 SCE-30EL3012SSLP 89 30 30 12 SCE-30P30 27 27 24SCE-30EL3608LP 84 SCE-30EL3608SSLP 84 30 36 8 SCE-36P30 33 27 27SCE-36EL2408LP 64 SCE-36EL2408SSLP 66 36 24 8 SCE-36P24 33 21 22SCE-36EL2410LP 74 SCE-36EL2410SSLP 74 36 24 10 SCE-36P24 33 21 22SCE-36EL2412LP 77 — — 36 24 12 SCE-36P24 33 21 22SCE-36EL2416LP 82 — — 36 24 16 SCE-36P24 33 21 22SCE-36EL3008LP 73 SCE-36EL3008SSLP 75 36 30 8 SCE-36P30 33 27 27SCE-36EL3010LP 89 SCE-36EL3010SSLP 89 36 30 10 SCE-36P30 33 27 27SCE-36EL3012LP 87 SCE-36EL3012SSLP 94 36 30 12 SCE-36P30 33 27 27SCE-36EL3016LP 114 — — 36 30 16 SCE-36P30 33 27 27SCE-36EL3020LP 123 — — 36 30 20 SCE-36P30 33 27 27SCE-36EL3608LP 102 SCE-36EL3608SSLP 102 36 36 8 SCE-36P36 33 33 35SCE-36EL3612LP 111 SCE-36EL3612SSLP 111 36 36 12 SCE-36P36 33 33 35SCE-36EL3616LP 122 — — 36 36 16 SCE-36P36 33 33 35SCE-40EL2412LP 89 — — 40 24 12 SCE-40P24 37 21 40SCE-42EL2410LP 79 SCE-42EL2410SSLP 84 42 24 10 SCE-42P24 39 21 33SCE-42EL3008LP 101 — — 42 30 8 SCE-42P30 39 27 33SCE-42EL3010LP 105 SCE-42EL3010SSLP 105 42 30 10 SCE-42P30 39 27 33SCE-42EL3012LP 111 — — 42 30 12 SCE-42P30 39 27 33SCE-42EL3016LP 117 — — 42 30 16 SCE-42P30 39 27 33SCE-42EL3608LP 117 — — 42 36 8 SCE-42P36 39 33 39SCE-42EL3610LP 127 — — 42 36 10 SCE-42P36 39 33 39SCE-42EL3612LP 123 SCE-42EL3612SSLP 124 42 36 12 SCE-42P36 39 33 39SCE-42EL3616LP 149 SCE-42EL3616SSLP 149 42 36 16 SCE-42P36 39 33 39SCE-48EL2408LP 83 — — 48 24 8 SCE-48P24 45 21 31SCE-48EL2412LP 99 — — 48 24 12 SCE-48P24 45 21 31SCE-48EL3010LP 117 — — 48 30 10 SCE-48P30 45 27 39SCE-48EL3016LP 151 — — 48 30 16 SCE-48P30 45 27 39SCE-48EL3608LP 129 — — 48 36 8 SCE-48P36 45 33 46SCE-48EL3610LP 137 — — 48 36 12 SCE-48P36 45 33 46SCE-48EL3612LP 133 SCE-48EL3612SSLP 131 48 36 10 SCE-48P36 45 33 46SCE-48EL3616LP 149 SCE-48EL3616SSLP 153 48 36 16 SCE-48P36 45 33 46SCE-48EL3620LP 173 — — 48 36 20 SCE-48P36 45 33 46SCE-60EL2412LP 141 — — 60 24 12 SCE-60P24 57 21 50SCE-60EL3610LP 164 — — 60 36 10 SCE-60P36 57 33 58SCE-60EL3612LP 162 SCE-60EL3612SSLP 162 60 36 12 SCE-60P36 57 33 58SCE-60EL3616LP 195 SCE-60EL3616SSLP 195 60 36 16 SCE-60P36 57 33 58SCE-60EL3620LP 209 — — 60 36 20 SCE-60P36 57 33 58SCE-72EL3012LP 217 — — 72 30 12 SCE-72P30 69 27 71SCE-72EL3016LP 236 SCE-72EL3016SSLP 236 72 30 16 SCE-72P30 69 27 71SCE-72EL3024LP 242 — — 72 30 24 SCE-72P30 69 27 71SCE-72EL3612LP 222 SCE-72EL3612SSLP 222 72 36 12 SCE-72P36 69 33 74SCE-72EL3616LP 234 SCE-72EL3616SSLP 234 72 36 16 SCE-72P36 69 33 74

ENCLOSURES

Page 44: West Coast Power Cerus Catalog

86

INDUSTRIAL CATALOG

www.westcoastpower.com 1-866-955-0888 87

Solid Construction for Rugged Applications � Designed for high temperature or corrosive environments � Protects components from dirt, dust, oil and water � Compression molded fiberglass reinforced polyester is UV

stabilized for outdoor use � Stainless steel hardware � Hinged door seals with neoprene gasket � Standard mounting flanges keep installation hardware outside

of sealed enclosure

Standards � UL 508 and UL 50 listed (Type 1, 2, 3, 3R, 4, 4X, 12, 13) � CSA Certified � Light gray color (RAL 7035) � Flammability rating meets UL 508 � Joint Industrial Council (JIC) enclosure sizing

EnclosurePart Number

Dimensions (in) Sub-PanelPart Number

Panel Dimensions (in)

H W D H WAMU664HF 6.05 6.27 4.13 P66 4.81 4.81AMU864HF 8.05 6.27 4.13 P86 6.75 4.88AMU1084HF 10.05 8.27 4.13 P108 8.75 6.88AMU1206HF 12.05 10.27 6.13 P1210 10.75 8.88AMU1426HF 14.05 12.27 6.13 P1412 12.75 10.88AMU1648HF 16.05 14.27 8.13 P1614 14.75 12.88AMU1860HF 18.05 16.27 10.13 P1816 16.88 14.88AMU2060HF 20.05 16.27 10.13 P2016 18.44 14.44

UL Type 4X Fiberglass EnclosuresReinforced Polyester ConstructionGasketed & Sealed for Outdoor UseHinged Screw Cover

Additional�options�and�configurations�available�through�special�order.�Enclosure�shown�above�with�clear�poly-carbonate�window.

REFERENCE

EnclosureRating NEMA Specification UL Specification

Type 1

Enclosures are intended for indoor use primarily to provide a degree of protection against contact with the enclosed equipment or locations where unusual service conditions do not exist.

Indoor use primarily to provide protection against contact with the enclosed equipment and against a limited amount of falling dirt.

Type 3R

Enclosures are intended for outdoor use primarily to provide a degree of protection against falling rain and sleet; undamaged by the formation of ice on the enclosure.

Outdoor use to provide a degree of protection against falling rain; undamaged by the formation of ice on the enclosure.

Type 4

Enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against windblown dust and rain, splashing water; and hose directed water; undamaged by the formation of ice on the enclosure.

Either indoor or outdoor use to provide a degree of protection against falling rain, splashing water, and hose-directed water; undamaged by the formation of ice on the enclosure.

Type 4X

Enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose-directed water; undamaged by the formation of ice on the enclosure.

Either indoor or outdoor use to provide a degree of protection against falling rain, splashing water, and hose-directed water; undamaged by the formation of ice on the enclosure; resists corrosion.

Type 12

Enclosures are intended for indoor use primarily to provide a degree of protection against dust, falling dirt, and dripping noncorrosive liquids.

Indoor use to provide a degree of protection against dust, dirt, fiber flyings, dripping water, and external condensation of noncorrosive liquids.

Enclosure StandardsNEMA�and�UL�are�standard�writing�organizations�that�are�commonly�recognized�in�North�America.�Their�ratings�are�based�on�similar�application�descriptions�and�expected�performance.�UL�requires�enclosure�testing�by�a�qualified�evaluator.�Site�inspectors�check�manufacturing�practices�to�ensure�adherence�to�methods�and�materials�utilized.�NEMA�standards�do�not�require�independent�testing�and�allows�manufacturers�to�enforce�their�own�compliance�measures.

This�material�is�reproduced�with�permission�from�NEMA.�The�preceding�descriptions,�however�are�not�intended�to�be�complete�representations�of�the�National�Electrical�Manufacturers�Association�standards�for�enclosures.

This�material�is�reproduced�with�permission�from�Underwriters�Laboratories,�Inc.�Enclosures�for�Electrical�Equipment,�UL�50,�Copyright�1995�and�Industrial�Control�Equipment,�UL�508,�Copyright�1996�by�Underwriters�Laboratories�Inc.

Underwriters�Laboratories�Inc.�(UL)�shall�not�be�responsible�for�the�use�of�or�reliance�upon�a�UL�Standard�by�anyone.�UL�shall�not�incur�any�obligation�or�liability�for�damages,�including�consequential�damages,�arising�out�of�or�connection�with�the�use,�interpretation�of,�or�reliance�upon�a�UL�Standard.

Page 45: West Coast Power Cerus Catalog

88 www.westcoastpower.com 1-866-955-0888 89

UL Sizing Chart (1 Phase)HP Volts Motor

AmpsWire Size

(AWG)

Bend Radius*(Inches)

ContactorCerus Motor Overload

Manual Motor Starter

Motor Circuit ProtectorThermal Electronic

1/10120 3.0 12 - MRC-9 MTK-32/3-4 CRP22-3P 5A CMS-32HI-4 CMS-32HI-4230 1.5 12 - MRC-9 MTK-32/3-1.6 CRP22-3P 5A CMS-32HI-1.6 CMS-32HI-1.6

1/8120 3.8 12 - MRC-9 MTK-32/3-4 CRP22-3P 5A CMS-32HI-4 CMS-32HI-4230 1.9 12 - MRC-9 MTK-32/3-2.5 CRP22-3P 5A CMS-32HI-2.5 CMS-32HI-2.5

1/6120 4.4 12 - MRC-9 MTK-32/3-6 CRP22-3P 5A CMS-32HI-6 CMS-32HI-6230 2.2 12 - MRC-9 MTK-32/3-2.5 CRP22-3P 5A CMS-32HI-2.5 CMS-32HI-2.5

1/4120 5.8 12 - MRC-9 MTK-32/3-8 CRP22-3S 22A CMS-32HI-8 CMS-32HI-6230 2.9 12 - MRC-9 MTK-32/3-4 CRP22-3P 5A CMS-32HI-4 CMS-32HI-4

1/3120 7.2 12 - MRC-9 MTK-32/3-8 CRP22-3S 22A CMS-32HI-8 CMS-32HI-8230 3.6 12 - MRC-9 MTK-32/3-4 CRP22-3P 5A CMS-32HI-4 CMS-32HI-4

1/2120 9.8 12 - MRC-12 MTK-32/3-13 CRP22-3S 22A CMS-32HI-13 CMS-32HI-10230 4.9 12 - MRC-9 MTK-32/3-6 CRP22-3S 22A CMS-32HI-6 CMS-32HI-6

3/4120 13.8 12 - MRC-18 MTK-32/3-18 CRP22-3S 22A CMS-32HI-17 CMS-32HI-17230 6.9 12 - MRC-9 MTK-32/3-8 CRP22-3S 22A CMS-32HI-8 CMS-32HI-8

1120 16.0 12 - MRC-18 MTK-32/3-18 CRP22-3S 22A CMS-32HI-17 CMS-32HI-17230 8.0 12 - MRC-9 MTK-32/3-9 CRP22-3S 22A CMS-32HI-10 CMS-32HI-8

1 1/2120 20.0 12 - MRC-25 MTK-32/3-25 CRP22-3S 22A CMS-32HI-22 CMS-32HI-22230 10.0 12 - MRC-12 MTK-32/3-13 CRP22-3S 22A CMS-32HI-13 CMS-32HI-10

2120 24.0 10 - MRC-25 MTK-32/3-25 CRP40-3S 40A CMS-32HI-26 CMS-32HI-26230 12.0 12 - MRC-18 MTK-32/3-13 CRP22-3S 22A CMS-32HI-13 CMS-32HI-13

3120 34.0 8 1.5 MRC-40 MTK-63/3-40 CRP40-3S 40A CMS-63HI-40 CMS-63HI-40230 17.0 12 - MRC-18 MTK-32/3-22 CRP22-3S 22A CMS-32HI-22 CMS-32HI-17

5120 56.0 6 2 MRC-63 MTK-63/3-65 CRP80-3S 80A CMS-63HI-63 CMS-63HI-63230 28.0 10 - MRC-32 MTK-32/3-32 CRP40-3S 40A CMS-32HI-32 CMS-32HI-32

7 1/2120 80.0 4 3 MRC-85 MTK-95/3-85 - CMS-100HI-90 CMS-100HI-90230 40.0 8 1.5 MRC-40 MTK-63/3-50 CRP80-3S 80A CMS-63HI-50 CMS-63HI-40

10120 100.0 3 3 CRC-100 CTK-100/3-125A - - CMS-100HI-100230 50.0 8 1.5 MRC-63 MTK-63/3-65 CRP80-3S 80A CMS-63HI-63 CMS-63HI-50

15120 135.0 1/0 5 CRC-150 CTK-150/3-150 - - -230 68.0 4 2 CRC-75 CTK-85/3-75 CRP80-3S-80A CMS-100H-75 CMS-100HI-75

Motor Engineering Formulas

P EI R

I x RI2 x R

E x I

PI

ER

E2

R

PE

EI

E2

PPI2

P x R

PR

Ohm’s Law

Motor Application FormulasHorsepower = Torque (lb-ft) x RPM

Torque (lb-ft) = Horsepower x 5252

5252

RPM

AC Efficiency & Power Factor Formulas

To Find Single Phase Three Phase

Efficiency 746 x HPE x I x PF

746 x HPE x I x PF x 1.732

Power Factor Input WattsV x A

Input WattsE x I x PF x 1.732

AC/DC Formulas

To Find Single Phase Three Phase

Amps when HP is known

HP x 746E x Eff

HP x 746E x Eff x PF

HP x 7461.73 x E x Eff x PF

Amps when kW is known

kW x 1000E

kW x 1000E x PF

kW x 10001.73 x E x PF

Amps when kVA is known - kVA x 1000

EkVA x 1000

1.73 x E

Kilowatts I x E1000

I x E x PF1000

I x E x 1.73 x PF1000

Kilovolt (Amps) - I x E

1000I x E x 1.73

1000

Horsepower (Output)

I x E x Eff746

I x E x Eff x PF746

I x E x Eff x 1.73 x PF746

LegendE = Volts I = Amps W = Watts PF = Power Factor Eff = Efficiency HP = Horsepower 1HP = 746 Watts

INDUSTRIAL CATALOG

91

HP Volts Motor Amps

Wire Size (AWG)

Bend Radius

(Inches) Contactor

Cerus Motor OverloadManual Motor

StarterMotor Circuit

Protector*Thermal Electronic

1/2208 2.4 12 - MRC-9 MTK-32/3-2.5 CRP22-3P 5A CMS-32HI-2.5 CMS-32HI-2.5230 2.2 12 - MRC-9 MTK-32/3-2.5 CRP22-3P 5A CMS-32HI-2.5 CMS-32HI-2.5480 1.1 12 - MRC-9 MTK-32/3-1.6 CRP22-3S 1.5A CMS-32HI-1.6 CMS-32HI-1.6

3/4208 3.5 12 - MRC-9 MTK-32/3-4 CRP22-3P 5A CMS-32HI-4 CMS-32HI-4230 3.2 12 - MRC-9 MTK-32/3-4 CRP22-3P 5A CMS-32HI-4 CMS-32HI-4480 1.6 12 - MRC-9 MTK-32/3-1.6 CRP22-3P 5A CMS-32HI-1.6 CMS-32HI-1.6

1208 4.6 12 - MRC-9 MTK-32/3-6 CRP22-3P 5A CMS-32HI-6 CMS-32HI-6230 4.2 12 - MRC-9 MTK-32/3-6 CRP22-3P 5A CMS-32HI-6 CMS-32HI-6480 2.1 12 - MRC-9 MTK-32/3-2.5 CRP22-3P 5A CMS-32HI-2.5 CMS-32HI-2.5

1 1/2208 6.6 12 - MRC-9 MTK-32/3-8 CRP22-3S 22A CMS-32HI-8 CMS-32HI-8230 6.0 12 - MRC-9 MTK-32/3-8 CRP22-3S 22A CMS-32HI-8 CMS-32HI-8480 3.0 12 - MRC-9 MTK-32/3-4 CRP22-3P 5A CMS-32HI-4 CMS-32HI-4

2208 7.5 12 - MRC-9 MTK-32/3-9 CRP22-3S 22A CMS-32HI-8 CMS-32HI-8230 6.8 12 - MRC-9 MTK-32/3-9 CRP22-3S 22A CMS-32HI-8 CMS-32HI-8480 3.4 12 - MRC-9 MTK-32/3-4 CRP22-3P 5A CMS-32HI-4 CMS-32HI-4

3208 10.5 12 - MRC-12 MTK-32/3-13 CRP22-3S 22A CMS-32HI-13 CMS-32HI-13230 9.6 12 - MRC-12 MTK-32/3-13 CRP22-3S 22A CMS-32HI-13 CMS-32HI-10480 4.8 12 - MRC-9 MTK-32/3-6 CRP22-3P 5A CMS-32HI-6 CMS-32HI-6

5208 16.7 12 - MRC-18 MTK-32/3-18 CRP22-3S 22A CMS-32HI-22 CMS-32HI-22230 15.2 12 - MRC-18 MTK-32/3-18 CRP22-3S 22A CMS-32HI-17 CMS-32HI-17480 7.6 12 - MRC-9 MTK-32/3-9 CRP22-3S 22A CMS-32HI-10 CMS-32HI-8

7 1/2208 24.0 10 - MRC-25 MTK-32/3-25 CRP40-3S 40A CMS-32HI-26 CMS-32HI-26230 22.0 10 - MRC-25 MTK-32/3-25 CRP40-3S 40A CMS-32HI-26 CMS-32HI-26480 11.0 12 - MRC-12 MTK-32/3-13 CRP22-3S 22A CMS-32HI-13 CMS-32HI-13

10208 31.0 8 1.5 MRC-35 MTK-63/3-36 CRP40-3S 40A CMS-63HI-40 CMS-63HI-40230 28.0 10 1.5 MRC-32 MTK-32/3-32 CRP40-3S 40A CMS-32HI-32 CMS-32HI-32480 14.0 12 - MRC-18 MTK-32/3-18 CRP22-3S 22A CMS-63HI-50 CMS-32HI-17

15208 46.0 8 1.5 MRC-50 MTK-63/3-50 CRP80-3S 80A CMS-63HI-50 CMS-63HI-50230 42.0 8 1.5 MRC-50 MTK-63/3-50 CRP80-3S 80A CMS-32HI-26 CMS-63HI-50480 21.0 10 - MRC-25 MTK-32/3-25 CRP40-3S 40A CMS-63HI-63 CMS-32HI-26

20208 59.0 6 2 MRC-63 MTK-63/3-65 CRP80-3S 80A CMS-63HI-63 CMS-63HI-63230 54.0 6 2 MRC-63 MTK-63/3-65 CRP80-3S 80A CMS-32HI-32 CMS-63HI-63480 27.0 10 - MRC-32 MTK-32/3-32 CRP40-3S 40A CMS-100HI-90 CMS-32HI-32

25208 75.0 4 2 MRC-75 MTK-95/3-85 CRP80-3S 80A CMS-100HI-75 CMS-100HI-90230 68.0 4 2 MRC-75 MTK-95/3-75 CRP80-3S 80A CMS-63HI-40 CMS-100HI-75480 34.0 8 1.5 MRC-35 MTK-63/3-40 CRP40-3S 40A CMS-100HI-100 CMS-63HI-40

30208 88.0 3 2.5 MRC-95 MTK-95/3-95 - CMS-100HI-90 CMS-100HI-100230 80.0 4 2 MRC-85 MTK-95/3-85 - CMS-63HI-50 CMS-100HI-90480 40.0 8 1.5 MRC-50 MTK-63/3-50 CRP80-3S 80A CMS-63S/H-50 CMS-63HI-50

40208 114.4 2 5 CRC-125 CTK-100/3-125A - - TS250NU ATU 250 250A230 104.0 2 3 CRC-125 CTK-100/3-125A - - TS250NU ATU 250 250A480 52.0 6 1.5 MRC-63 MTK-63/3-65 CRP80-3S 80A CMS-63HI-63 CMS-63HI-63

50208 143.0 1/0 7 CRC-180 CTK-220/3-180A - - TS400NU ATU 400 400A230 130.0 1 6 CRC-150 CTK-150/3-150A - - TS400NU ATU 400 300A480 65.0 6 2 MRC-75 MTK-95/3-75 CRP80-3S 80A CMS-100HI-75 CMS-100HI-75

60208 169.4 2/0 7 CRC-180 CTK-220/3-180A - - TS400NU ATU 400 400A230 154.0 2/0 7 CRC-180 CTK-220/3-180A - - TS400NU ATU 400 400A480 77.0 4 2 MRC-85 MTK-95/3-85 CRP80-3S 80A CMS-100HI-90 CMS-100HI-90

75208 211.2 4/0 10 CRC-300 CTK-400/3-240A - - TS800NU ATU 800 500A230 192.0 3/0 8 CRC-220 CTK-220/3-240A - - TS800NU ATU 800 500A480 96.0 3 3 CRC-125 CTK-100/3-125A - CMS-100HI-100 CMS-100HI-100

100208 272.8 2 x 1/0 12 CRC-300 CTK-400/3-300A - - TS800NU ATU 800 600A230 248.0 2 x 1/0 12 CRC-300 CTK-400/3-300A - - -480 124.0 1 6 CRC-150 CTK-150/3-150A - - TS400NU ATU 400 300A

125208 343.2 2 x 2/0 14 CRC-400 CTK-400/3-400A - - TS800NU ATU 800 800A230 312.0 2 x 2/0 14 CRC-400 CTK-400/3-400A - - TS800NU ATU 800 800A480 156.0 2/0 7 CRC-180 CTK-220/3-180A - - TS400NU ATU 400 400A

150208 396.0 2 x 3/0 8* CRC-600 CTK-600/3-400A - - -230 360.0 2 x 3/0 7* CRC-400 CTK-400/3-400A - - -480 180.0 3/0 7 CRC-220 CTK-220/3-240A - - TS400NU ATU 400 400A

UL Sizing Chart (3 Phase)REFERENCE

*�Field�wiring�requires�two�conductors

Page 46: West Coast Power Cerus Catalog

Check�out�our�NEW�Pump�Products�on�Page�46!�

1550 Montague ExpresswaySan Jose, CA 95131

CER

US IN

DU

STRIA

L 2009 w

ww

.westcoastpow

er.com