SECTION 26 27 26 WIRING DEVICES Display hidden notes to specifier. (Don't know how? Click Here ) Copyright 2010 - 2014 ARCAT, Inc. - All rights reserved 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Wiring devices, including the following: 1.1.1.1 Straight blade receptacles. 1.1.1.2 GFCI receptacles. 1.1.1.3 Surge protected receptacles (SPD). 1.1.1.4 Locking receptacles. 1.1.1.5 Locking plugs and connectors. 1.1.1.6 Cord and plug sets. 1.1.1.7 Toggle switches. 1.1.1.8 Illuminated switches. 1.1.1.9 Key-operated switches. 1.1.1.10 Momentary contact switches. 1.1.1.11 Wall-box dimmers. 1.1.1.12 Fan speed controls. 1.1.1.13 Occupancy/vacancy sensors. 1.1.1.14 Communications outlets. 1.1.1.15 Wall plates. 1.1.1.16 Floor service fittings. 1.1.1.17 Finishes. 1.2 RELATED SECTIONS 1.2.1 Section 27 10 00 - Structured Cabling. 1.3 SUBMITTALS 1.3.1 Submit under provisions of Section 01 30 00 - Administrative Requirements. 1.3.2 Product Data: Manufacturer's data sheets on each product to be used, including: 1.3.2.1 Preparation instructions and recommendations. 1.3.2.2 Storage and handling requirements and recommendations. 1.3.2.3 Installation methods. 26 27 26-1

Upload: others

Post on 07-May-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

SECTION 26 27 26WIRING DEVICES

Display hidden notes to specifier. (Don't know how? Click Here)

Copyright 2010 - 2014 ARCAT, Inc. - All rights reserved

1 GENERAL

1.1 SECTION INCLUDES

1.1.1 Wiring devices, including the following:1.1.1.1 Straight blade receptacles.1.1.1.2 GFCI receptacles.1.1.1.3 Surge protected receptacles (SPD).1.1.1.4 Locking receptacles.1.1.1.5 Locking plugs and connectors.1.1.1.6 Cord and plug sets.1.1.1.7 Toggle switches.1.1.1.8 Illuminated switches.1.1.1.9 Key-operated switches.1.1.1.10 Momentary contact switches.1.1.1.11 Wall-box dimmers.1.1.1.12 Fan speed controls.1.1.1.13 Occupancy/vacancy sensors.1.1.1.14 Communications outlets.1.1.1.15 Wall plates.1.1.1.16 Floor service fittings.1.1.1.17 Finishes.

1.2 RELATED SECTIONS

1.2.1 Section 27 10 00 - Structured Cabling.

1.3 SUBMITTALS

1.3.1 Submit under provisions of Section 01 30 00 - Administrative Requirements.

1.3.2 Product Data: Manufacturer's data sheets on each product to be used, including:1.3.2.1 Preparation instructions and recommendations.1.3.2.2 Storage and handling requirements and recommendations.1.3.2.3 Installation methods.

1.3.3 Selection Samples: For each device and wall plate specified, two complete sets of color chips representing manufacturer's full range of available colors.

1.3.4 Verification Samples: For each finish product specified, two samples of each device and wall plate, representing actual product, color, and patterns.

1.4 QUALITY ASSURANCE

1.4.1 Product Requirements:

26 27 26-1

Page 2:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

1.4.1.1 Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction (AHJ), and marked for permissible application.

1.4.1.2 Comply with NFPA 70.1.4.1.3 Compliance with Federal Specifications - identified by the federal specification

mark (capital letters "F" and "S" each in a wing on either side of the UL Listing mark):

1.4.1.3.1 Receptacles, GFCI's, plugs and cord connectors: Federal Specification number W-C-596.

1.4.1.3.2 Snap switches: Federal Specification number W-S-896.

1.4.2 Mock-Up: Provide a mock-up for evaluation of preparation techniques and installation workmanship.1.4.2.1 Finish areas designated by Architect.1.4.2.2 Do not proceed with remaining work until workmanship is approved by Architect.1.4.2.3 Rework mock-up as required to produce acceptable work.

1.5 DELIVERY, STORAGE, AND HANDLING

1.5.1 Store products in manufacturer's unopened packaging until ready for installation.

1.5.2 Store and dispose of solvent-based materials, and materials used with solvent-based materials, in accordance with requirements of local authorities having jurisdiction.

1.6 PROJECT CONDITIONS

1.6.1 Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

2 PRODUCTS

2.1 MANUFACTURERS

2.1.1 Acceptable Manufacturer: Pass & Seymour, which is located at: P. O. Box 4822 ; Syracuse, NY 13221; Toll Free Tel: 877-295-3472; Email:[email protected],[email protected]; Web:www.legrand.us/PassAndSeymour.

2.1.2 Substitutions: Not permitted.

2.1.3 Requests for substitutions will be considered in accordance with provisions of Section 01 60 00 - Product Requirements.

2.2 STRAIGHT BLADE RECEPTACLES

2.2.1 Convenience Receptacles 125 V, 15 and 20 A:2.2.1.1 Comply with NEMA WD 1, NEMA WD 6 configurations 5-15R and 5-20R, UL

498 and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

2.2.1.2 Products: Pass & Seymour, 5251 (15A single).2.2.1.3 Products: Pass & Seymour, 5262 (15A duplex).2.2.1.4 Products: Pass & Seymour, 5351 (20A single).2.2.1.5 Products: Pass & Seymour, 5362 (20A duplex).2.2.1.6 Products: Pass & Seymour, PT5262 (15A duplex - use with PTRA6STR prewired

pigtail connector).2.2.1.7 Products: Pass & Seymour, PT5362 (20A duplex - use with PTRA6STR prewired

pigtail connector).

26 27 26-2

Page 3:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.2.1.8 Products: Pass & Seymour, 26252 (15A duplex - Heavy Duty).2.2.1.9 Products: Pass & Seymour, PT26252 (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.1.10 Products: Pass & Seymour, 26352 (20A duplex - Heavy Duty).2.2.1.11 Products: Pass & Seymour, PT26352 (20A duplex - use with PTRA6STR

prewired pigtail connector).2.2.1.12 Products: Pass & Seymour, TR26261 (15A single).2.2.1.13 Products: Pass & Seymour, TR26361 (20A single).2.2.1.14 Products: Pass & Seymour, PS8HWL (20A duplex).

2.2.2 Hospital-Grade Duplex Convenience Receptacles, 125 V, 15 and 20 A:2.2.2.1 Comply with NEMA WD 1, NEMA WD 6 configurations 5-15R and 5-20R, UL

498 Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

2.2.2.2 Products: Pass & Seymour, 8201 (15A single).2.2.2.3 Products: Pass & Seymour, 8200H (15A duplex).2.2.2.4 Products: Pass & Seymour, 8301 (20A single).2.2.2.5 Products: Pass & Seymour, 8300H (20A duplex).2.2.2.6 Products: Pass & Seymour, PT8200 (15A duplex - use with PTRA6STR prewired

pigtail connector).2.2.2.7 Products: Pass & Seymour, PT8300 (20A duplex - use with PTRA6STR prewired

pigtail connector).

2.2.3 Isolated-Ground Duplex Convenience Receptacles, 125 V, 15 and 20 A:2.2.3.1 Comply with NEMA WD 1, NEMA WD configurations 5-15R and 5-20R, UL 498

and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

2.2.3.2 Products: Pass & Seymour, IG5261 (15A single).2.2.3.3 Products: Pass & Seymour, IG5262 (15A duplex).2.2.3.4 Products: Pass & Seymour, IG5361 (20A single).2.2.3.5 Products: Pass & Seymour, IG5362 (20A duplex)2.2.3.6 Products: Pass & Seymour, PTIG5262 (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.3.7 Products: Pass & Seymour, PTIG5362 (20A duplex - use with PTRA6STR

prewired pigtail connector).2.2.3.8 Products: Pass & Seymour, IG26262 (15A duplex).2.2.3.9 Products: Pass & Seymour, IG26362 (20A duplex).2.2.3.10 Products: Pass & Seymour, PTIG26262 (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.3.11 Products: Pass & Seymour, PTIG26362 (20A duplex - use with PTRA6STR

prewired pigtail connector).2.2.3.12 Description: Straight blade; equipment grounding contacts shall be connected

only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap. Isolation shall be integral to receptacle construction and not dependent on removable parts. In the case of isolated ground device to be used with prewired pigtail connector: no terminal screws are necessary; plastic barrier shall be present to isolate the grounding terminal from the mounting strap and metal boxes.

2.2.4 Isolated Ground Hospital-Grade Duplex Convenience Receptacles, 125 V, 15 and 20 A:2.2.4.1 Comply with NEMA WD 1, NEMA WD 6 configuration 5-20R, UL 498

Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

26 27 26-3

Page 4:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.2.4.2 Products: Pass & Seymour, IG8200 (15A duplex).2.2.4.3 Products: Pass & Seymour, IG8300 (20A duplex).2.2.4.4 Products: Pass & Seymour, PTIG8200 (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.4.5 Products: Pass & Seymour, PTIG8300 (20A duplex - use with PTRA6STR

prewired pigtail connector).

2.2.5 Tamper-Resistant Hospital-Grade Duplex Convenience Receptacles, 125 V, 15 and 20 A:2.2.5.1 Comply with NEMA WD 1, NEMA WD 6 configurations 5-15R and 5-20R, UL

498 Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

2.2.5.2 Products: Pass & Seymour, TR62H (15A duplex).2.2.5.3 Products: Pass & Seymour, TR63H (20A duplex).2.2.5.4 Products: Pass & Seymour, PTTR62H (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.5.5 Products: Pass & Seymour, PTTR63H (20A duplex - use with PTRA6STR

prewired pigtail connector).2.2.5.6 Products: Pass & Seymour, PTTR8200 (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.5.7 Products: Pass & Seymour, PTTR8300 (20A duplex - use with PTRA6STR

prewired pigtail connector).2.2.5.8 Description: Labeled to comply with NFPA 70, "Health Care Facilities" Article,

"Pediatric Locations" Section.

2.2.6 Tamper-Resistant Convenience Receptacles, 125V, 15 and 20 A:2.2.6.1 Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL498

and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

2.2.6.2 Products: Pass & Seymour, TR62 (15A duplex).2.2.6.3 Products: Pass & Seymour, TR63 (20A duplex).2.2.6.4 Products: Pass & Seymour, PTTR62 (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.6.5 Products: Pass & Seymour, PTTR63 (20A duplex - use with PTRA6STR

prewired pigtail connector).2.2.6.6 Products: Pass & Seymour, TR5251 (15A single).2.2.6.7 Products: Pass & Seymour, TR5262 (15A duplex).2.2.6.8 Products: Pass & Seymour, TR5351 (single).2.2.6.9 Products: Pass & Seymour, TR5362 (20A duplex).2.2.6.10 Products: Pass & Seymour, PTTR5262 (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.6.11 Products: Pass & Seymour, PTTR5362 (20A duplex - use with PTRA6STR

prewired pigtail connector).2.2.6.12 Products: Pass & Seymour, TR26262 (15A duplex).2.2.6.13 Products: Pass & Seymour, TR26362 (20A duplex).2.2.6.14 Products: Pass & Seymour, PTTR26262 (15A duplex). - use with PTRA6STR

prewired pigtail connector).2.2.6.15 Products: Pass & Seymour, PTTR26362 (20A duplex). - use with PTRA6STR

prewired pigtail connector).

2.2.7 Tamper-Resistant Isolated-Ground, Duplex Convenience Receptacles, 125 V, 15 and 20 A:2.2.7.1 Comply with NEMA WD 1, NEMA WD configurations 5-15R and 5-20R, UL 498

and Federal Specification W-C-596.2.2.7.2 Products: Pass & Seymour, TRIG5262 (15A duplex).2.2.7.3 Products: Pass & Seymour, TRIG5362 (20A duplex).

26 27 26-4

Page 5:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.2.7.4 Products: Pass & Seymour, TRIG26262 (15A duplex).2.2.7.5 Products: Pass & Seymour, TRIG26362 (20A duplex).2.2.7.6 Description: Straight blade; equipment grounding contacts shall be connected

only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap. Isolation shall be integral to receptacle construction and not dependent on removable parts.

2.2.8 Tamper-Resistant Isolated-Ground Hospital-Grade Duplex Convenience Receptacles, 125 V, 15 and 20 A:2.2.8.1 Comply with NEMA WD 1, NEMA WD configurations 5-15R and 5-20R, UL 498

Supplement SD and Federal Specification W-C-596.2.2.8.2 Products: Pass & Seymour, TRIG8200 (15A duplex).2.2.8.3 Products: Pass & Seymour, TRIG8300 (20A duplex).2.2.8.4 Products: Pass & Seymour, TRIG26262HG (15A duplex).2.2.8.5 Products: Pass & Seymour, TRIG26362HG (20A duplex).2.2.8.6 Compliance: Labeled to comply with NFPA 70, "Health Care Facilities" Article,

"Pediatric Locations" Section.2.2.8.7 Description: Straight blade; equipment grounding contacts shall be connected

only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap. Isolation shall be integral to receptacle construction and not dependent on removable parts.

2.2.9 Weather-Resistant Convenience Receptacles, 125V, 15 and 20 A:2.2.9.1 Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL498

and Federal Specification W-C-596.2.2.9.2 Products: Pass & Seymour, WR5262 (15A duplex).2.2.9.3 Products: Pass & Seymour, WR5362 (20A duplex).2.2.9.4 Products: Pass & Seymour, 885TRWR (15A duplex).

2.2.10 Illuminated Hospital-Grade Duplex Convenience Receptacles, 125V, 15 and 20 A:2.2.10.1 Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL498

Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec receptacles are approved. Required to be a crimped and welded terminal with right angle application connector.

2.2.10.2 Products: Pass & Seymour, 8200IL (15A duplex).2.2.10.3 Products: Pass & Seymour, 8300IL (20A duplex).2.2.10.4 Products: Pass & Seymour, PT8200IL (15A duplex - use with PTRA6STR

prewired pigtail connector).2.2.10.5 Products: Pass & Seymour, PT8300IL (20A duplex - use with PTRA6STR

prewired pigtail connector).

2.3 GFCI RECEPTACLES

2.3.1 Non-feed-through-type GFCI receptacles for locations in which no protection of downstream receptacles is required.

2.3.2 General Description: Straight blade, non-feed-through-type. Comply with NEMA WD 1, NEMA WD 6, UL 498, Federal Specification W-C-596, and UL943, Class A. Include indicator light that is lighted when device is tripped. Shall have SafeLock protection: If critical components are damaged and ground fault protection is lost, power to receptacle shall be discontinued. Selected items are NAFTA-Compliant.

2.3.3 Duplex GFCI Convenience Receptacles, 125 V, 15 and 20 A:2.3.3.1 Prewired pigtail connectors that accommodate Fed Spec GFCI receptacles are

approved. Shall be crimped and welded terminal right angle application connector.

2.3.3.2 Products: Pass & Seymour, 1595 (15A duplex).

26 27 26-5

Page 6:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.3.3.3 Products: Pass & Seymour, 1595NA (NAFTA, 15A duplex).2.3.3.4 Products: Pass & Seymour, PT1595 (15A duplex - use with PTRA6STR prewired

pigtail connector).2.3.3.5 Products: Pass & Seymour, PT1595NA (NAFTA, 15A duplex - use with

PTRA6STRNA prewired pigtail connector).2.3.3.6 Products: Pass & Seymour, 2095 (20A duplex).2.3.3.7 Products: Pass & Seymour, 2095NA (NAFTA, 20A duplex).2.3.3.8 Products: Pass & Seymour, PT2095 (20A duplex - use with PTRA6STR prewired

pigtail connector).2.3.3.9 Products: Pass & Seymour, PT2095NA (NAFTA, 20A duplex - use with

PTRA6STRNA prewired pigtail connector).2.3.3.10 Products: Pass & Seymour, 2095S (20A duplex with Auto-Ground).2.3.3.11 Products: Pass & Seymour, 2095L (20A duplex - Illuminated).2.3.3.12 Products: Pass & Seymour, 2085 (20A duplex - Dead Front with 1.5 HP motor

control rating).2.3.3.13 Products: Pass & Seymour, 1595SWTTRCC4 (Combination 15A single

receptacle GFCI with single pole switch).2.3.3.14 Products: Pass & Seymour, 1595DSWRBKCC4 (15A duplex GFCI weather

resistant Durashield).2.3.3.15 Products: Pass & Seymour, 2095DSWRBK (20A duplex GFCI weather resistant

Durashield).

2.3.4 Hospital-Grade, Duplex GFCI Convenience Receptacles, 125 V, 15 and 20 A:2.3.4.1 Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL 498

Supplement SD and Federal Specification W-C-596. Prewired pigtail connectors that accommodate Fed Spec GFCI receptacles are approved. Shall be crimped and welded terminal right angle application connector.

2.3.4.2 Products: Pass & Seymour, 1595HG (15A duplex).2.3.4.3 Products: Pass & Seymour, 1595HGNA (NAFTA, 15A duplex).2.3.4.4 Products: Pass & Seymour, 2095HG 20A duplex).2.3.4.5 Products: Pass & Seymour, 2095HGNA (NAFTA, 20A duplex).2.3.4.6 Products: Pass & Seymour, PT1595HG (15A duplex - use with PTRA6STR

prewired pigtail connector).2.3.4.7 Products: Pass & Seymour, PT1595HFNA (NAFTA, 15A duplex - use with

PTR6STRNA prewired pigtail connector).2.3.4.8 Products: Pass & Seymour, PT2095HG (20A duplex - use with PTRA6STR

prewired pigtail connector).2.3.4.9 Products: Pass & Seymour, PT2095HGNA (NAFTA, 20A duplex - use with

PTRA6STRNA prewired pigtail connector).

2.3.5 Tamper-Resistant GFCI Convenience Receptacles, 125 V, 15 and 20 A:2.3.5.1 Comply with NEMA WD1, NEMA WD6 configurations 5-15R and 5-20R, UL 498

Supplement SD, Federal Specification W-C-596 and UL943, Class A, and include indicator light that is lighted when device is tripped. Prewired pigtail connectors that accommodate Fed Spec GFCI receptacles are approved. Shall be crimped and welded terminal right angle application connector

2.3.5.2 Products: Pass & Seymour, 1595TR (15A duplex).2.3.5.3 Products: Pass & Seymour, 1595TRNA (NAFTA, 15A duplex).2.3.5.4 Products: Pass & Seymour, PT1595TR (15A duplex - use with PTRA6STR

prewired pigtail connector).2.3.5.5 Products: Pass & Seymour, PT1595TRNA (NAFTA, 15A duplex - use with

PTRA6STRNA prewired pigtail connector).2.3.5.6 Products: Pass & Seymour, 2095TR (20A duplex).2.3.5.7 Products: Pass & Seymour, 2095TRI (20A duplex - Illuminated).2.3.5.8 Products: Pass & Seymour, PT2095TR (20A duplex - use with PTRA6STR

prewired pigtail connector).

26 27 26-6

Page 7:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.3.5.9 Products: Pass & Seymour, PT2095TRNA (NAFTA, 20A duplex - use with PTRA6STRNA prewired pigtail connector).

2.3.5.10 Products: Pass & Seymour, 1595NTLTR (15A tamper resistant GFCI with nightlight).

2.3.5.11 Products: Pass & Seymour, PT1595NTLTR (15A tamper resistant GFCI with nightlight - use with PTRA6STR prewired pigtail connector).

2.3.5.12 Products: Pass & Seymour, PT1595NTLTRNA (NAFTA, 15A tamper resistant GFCI with nightlight - use with PTRA6STRNA prewired pigtail connector).

2.3.5.13 Products: Pass & Seymour, 2095NTLTR (20A tamper resistant GFCI with nightlight).

2.3.5.14 Products: Pass & Seymour, PT2095NTLTR (20A tamper resistant GFCI with nightlight - use with PTRA6STR prewired pigtail connector).

2.3.5.15 Products: Pass & Seymour, PT2095NTLTRNA (NAFTA, 20A tamper resistant GFCI with nightlight - use with PTRA6STRNA prewired pigtail connector).

2.3.5.16 Products: Pass & Seymour, 1595TRWR (15A duplex GFCI weather resistant).2.3.5.17 Products: Pass & Seymour, 2095TRWR (20A duplex GFCI weather resistant).

2.3.6 Tamper-Resistant, Hospital-Grade, Duplex GFCI Convenience Receptacles, 125 V, 15 and 20 A:2.3.6.1 Comply with UL 498 Supplement SD and Federal Specification W-C-596.

Prewired pigtail connectors that accommodate Fed Spec GFCI receptacles are approved. Shall be crimped and welded terminal right angle application connector.

2.3.6.2 Products: Pass & Seymour, 1595HGTR, (15A duplex).2.3.6.3 Products: Pass & Seymour, 1595HGTRNA (NAFTA, 15A duplex).2.3.6.4 Products: Pass & Seymour, 2095HGTR (20A duplex).2.3.6.5 Products: Pass & Seymour, 2095HGTRNA (NAFTA, 20A duplex).2.3.6.6 Products: Pass & Seymour, PT1595HGTR (15A duplex - use with PTRA6STR

prewired pigtail connector).2.3.6.7 Products: Pass & Seymour, PT1595HGTRNA (NAFTA, 15A duplex - use with

PTRA6STRNA prewired pigtail connector).2.3.6.8 Products: Pass & Seymour, PT2095HGTR (20A duplex - use with PTRA6STR

prewired pigtail connector).2.3.6.9 Products: Pass & Seymour PT2095HGTRNA (NAFTA, 20A duplex - use with

PTRA6STRNA prewired pigtail connector).2.3.6.10 Products: Pass & Seymour, 1595HGNTLTR (15A duplex).2.3.6.11 Products: Pass & Seymour, 1595HGNTLTRNA (NAFTA, 15A duplex).2.3.6.12 Products: Pass & Seymour, 2095HGNTLTR, (20A duplex).2.3.6.13 Products: Pass & Seymour, 2095HGNTLTRNA (NAFTA, 20A duplex).2.3.6.14 Products: Pass & Seymour, PT1595HGNTLTR, (15A duplex - use with

PTRA6STR prewired pigtail connector).2.3.6.15 Products: Pass & Seymour, PT1595HGNTLRNA (NAFTA, 15A duplex - use with

PTRA6STRNA prewired pigtail connector).2.3.6.16 Products: Pass & Seymour, PT2095HGNTLTR, (20A duplex) - use with

PTRA6STR prewired pigtail connector).2.3.6.17 Products: Pass & Seymour, PT2095HGNTLTRNA (NAFTA, 20A duplex - use

with PTRA6STRNA prewired pigtail connector).2.3.6.18 Description: Labeled to comply with NFPA 70, "Health Care Facilities" Article,

"Pediatric Locations" Section.

2.4 SURGE PROTECTED RECEPTACLES (SPD)

2.4.1 General Description: Comply with NEMA WD 1, NEMA WD 6, UL 498, UL 1449 and Federal Specification W-C-596 with integral Surge Protected in line to ground, line to neutral, and neutral to ground.2.4.1.1 Surge Protected Components: Multiple metal-oxide varistors; with a nominal

26 27 26-7

Page 8:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340 joules in each of three modes, according to IEEE C62.41.2 and IEEE C62.45.

2.4.1.2 Active SPD Indication: Visual and audible, with light visible in face of device to indicate device is "active" or "no longer in service."

2.4.2 Duplex Surge Protected Convenience Receptacles:2.4.2.1 Products: Pass & Seymour 5262BLSP (15A duplex).2.4.2.2 Products: Pass & Seymour 5362BLSP (20A duplex).2.4.2.3 Products: Pass & Seymour PT5262BLSP (15A duplex - use with PTRA6STR

prewired pigtail connector).2.4.2.4 Products: Pass & Seymour PT5362BLSP (20A duplex - use with PTRA6STR

prewired pigtail connector).2.4.2.5 Description: Straight blade, 125 V, 15 and 20 A; NEMA WD 6 configuration 5-

20R.

2.4.3 Isolated-Ground, Duplex Convenience Receptacles:2.4.3.1 Products: Pass & Seymour IG5262SP (15A duplex).2.4.3.2 Products: Pass & Seymour IG5362SP (20A duplex).2.4.3.3 Products: Pass & Seymour PTIG5262SP (15A duplex - use with PTRA6STR

prewired pigtail connector).2.4.3.4 Products: Pass & Seymour PTIG5362SP (20A duplex - use with PTRA6STR

prewired pigtail connector).2.4.3.5 Description: Straight blade, 125 V, 15 and 20 A; NEMA WD 6 configuration 5-

20R. Equipment grounding contacts shall be connected only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap. Isolation shall be integral to receptacle construction and not dependent on removable parts.

2.4.4 Hospital-Grade, Duplex Convenience Receptacles:2.4.4.1 Comply with UL 498 Supplement SD.2.4.4.2 Products: Pass & Seymour 8200BLSP (15A duplex).2.4.4.3 Products: Pass & Seymour 8300BLSP (20A duplex).2.4.4.4 Products: Pass & Seymour PT8200BLSP (15A duplex - use with PTRA6STR

prewired pigtail connector).2.4.4.5 Products: Pass & Seymour PT8300BLSP (20A duplex - use with PTRA6STR

prewired pigtail connector).2.4.4.6 Description: Straight blade, 125 V, 15 and 20 A; NEMA WD 6 configuration 5-

20R.

2.4.5 Isolated-Ground, Hospital-Grade, Duplex Convenience Receptacles:2.4.5.1 Products: Pass & Seymour IG8200BLSP (15A duplex).2.4.5.2 Products: Pass & Seymour IG8300BLSP (20A duplex).2.4.5.3 Products: Pass & Seymour PTIG8200BLSP (15A duplex - use with PTRA6STR

prewired pigtail connector).2.4.5.4 Products: Pass & Seymour PTIG8300BLSP (20A duplex - use with PTRA6STR

prewired pigtail connector).2.4.5.5 Description: Straight blade, 125 V, 15 and 20 A; NEMA WD 6 configuration 5-

20R. Comply with UL 498 Supplement SD. Equipment grounding contacts shall be connected only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap. Isolation shall be integral to receptacle construction and not dependent on removable parts.

2.4.6 Surge Protected Panels:2.4.6.1 UL 1449 compliant.2.4.6.2 Construction: NEMA 12 enclosure, audible alarm, lockable rotary disconnect

switch, LED visual indicators and three position test switch.

26 27 26-8

Page 9:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.4.6.3 System Application: 1ph, 3W plus ground (120/240 V).2.4.6.3.1 Light Duty: Model 1224-SL.2.4.6.3.2 Light Duty: Model 1224-SLI.2.4.6.3.3 Medium Duty: Model 1224-SM.2.4.6.3.4 Heavy Duty: Model 1224-SH.2.4.6.3.5 Heavy Duty: Model 1224-SHB.

2.4.6.4 System Application: 3ph, WYE, 4W plus ground (120/240 V).2.4.6.4.1 Light Duty: Model 1220-TWLI.2.4.6.4.2 Medium Duty: Model 1220-TWM.2.4.6.4.3 Heavy Duty: Model 1220-TWH.2.4.6.4.4 Heavy Duty: Model 1220-TWHB.2.4.6.4.5 Heavy Duty: Model 1220-TWH4B.

2.4.6.5 System Application: 3ph, WYE, 4W plus ground (277/480 V).2.4.6.5.1 Light Duty: Model 2748-TWLI.2.4.6.5.2 Medium Duty: Model 2748-TWM.2.4.6.5.3 Heavy Duty: Model 2748-TWH.2.4.6.5.4 Heavy Duty: Model 2748-TWHB.2.4.6.5.5 Heavy Duty: Model 2748-TWH4B.

2.4.6.6 System Application: 3ph, DELTA, 3W plus ground (480 V).2.4.6.6.1 Heavy Duty: Model 480-TDH.

2.4.6.7 System Application: 3ph, DELTA (high leg), 4W plus ground (120/240 V).2.4.6.7.1 Medium Duty: Model 240-TDM.

2.5 LOCKING RECEPTACLES

2.5.1 Single Convenience Receptacles, 125 V:2.5.1.1 Comply with NEMA WD 1, NEMA WD 6 configuration L5-15R, L5-20R and L5-

30R, UL 498 and Federal Specification W-C-596.2.5.1.2 Products: Pass & Seymour, 4710 (15A).2.5.1.3 Products: Pass & Seymour, L520R (20A).2.5.1.4 Products: Pass & Seymour, L530R(30A).

2.5.2 Isolated-Ground, Single Convenience Receptacles, 125 V:2.5.2.1 Comply with NEMA WD 1, NEMA WD 6 configuration L5-15R, L5-20R and L5-

30R, UL 498 and Federal Specification W-C-596.2.5.2.2 Products: Pass & Seymour, IG4710 (15A).2.5.2.3 Products: Pass & Seymour, IGL520R (20A).2.5.2.4 Products: Pass & Seymour, IGL530R (30A).

2.5.3 Isolated-Ground, Duplex Convenience Receptacles, 125 V, 15 A:2.5.3.1 Products: Pass & Seymour, IG4700.2.5.3.2 Description: Comply with NEMA WD 1, NEMA WD 6 configuration L5-20R, and

UL 498. Equipment grounding contacts shall be connected only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap. Isolation shall be integral to receptacle construction and not dependent on removable parts.

2.6 LOCKING PLUGS AND CONNECTORS

2.6.1 Locking Plugs and Connectors:2.6.1.1 Description: Matching, locking-type plug and receptacle body connector; NEMA

WD 6 configurations L5-15P, L5-20P and L5-30P; and L5-15R, L5-20R and L5-30R, heavy-duty grade and Federal Specification W-C-596.

2.6.1.2 Body: Nylon with screw-open cable-gripping jaws and provision for attaching external cable grip.

2.6.1.2.1 Plug: Pass & Seymour, PSL515P (15A).2.6.1.2.2 Connector: Pass & Seymour PSL515C (15A).

26 27 26-9

Page 10:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.6.1.2.3 Plug: Pass & Seymour, L520P (20A).2.6.1.2.4 Connector: Pass & Seymour L520C (20A).2.6.1.2.5 Plug: Pass & Seymour, L530P (30A).2.6.1.2.6 Connector: Pass & Seymour L530C(30A).

2.6.2 External Cable Grips:2.6.2.1 Description: Woven wire-mesh type made of high-strength galvanized-steel wire

strand, matched to cable diameter, and with attachment provision designed for corresponding connector.

2.6.2.2 Products: Pass & Seymour FC__GL Series.

2.7 CORD AND PLUG SETS

2.7.1 Cord and Plug Sets:2.7.1.1 Description: Match voltage and current ratings and number of conductors to

requirements of equipment being connected. Refer to Equipment Schedule.2.7.1.2 Cord: Rubber-insulated, stranded-copper conductors, with Type SOW-A jacket;

with green-insulated grounding conductor and equipment-rating ampacity plus a minimum of 30 percent.

2.7.1.3 Plug: Nylon body and integral cable-clamping jaws. Match cord and receptacle type for connection.

2.8 TOGGLE SWITCHES

2.8.1 Comply with NEMA WD 1, UL 20 and Federal Specification W-S-896.

2.8.2 Switches, 120/277 V:2.8.2.1 Prewired pigtail connectors that accommodate Fed Spec switches are approved.

Shall be crimped and welded terminal right angle application connector.2.8.2.2 Products: Pass & Seymour, PS15AC1 (15A - single pole).2.8.2.3 Products: Pass & Seymour, PT15AC1 (15A - single pole - use with PTS6STR3

prewired pigtail connector).2.8.2.4 Products: Pass & Seymour, PS15AC2 (15A - double pole).2.8.2.5 Products: Pass & Seymour, PS15AC3 (15A - three-way).2.8.2.6 Products: Pass & Seymour, PT15AC3 (15A - three-way - use with PTS6STR4

prewired pigtail connector).2.8.2.7 Products: Pass & Seymour, PS15AC4 (15A - four-way).2.8.2.8 Products: Pass & Seymour, PS20AC1 (20A - single pole).2.8.2.9 Products: Pass & Seymour, PT20AC1 (20A - single pole - use with PTS6STR3

prewired pigtail connector).2.8.2.10 Products: Pass & Seymour, PS20AC2 (20A - double pole).2.8.2.11 Products: Pass & Seymour, PS20AC3 (20A - three-way).2.8.2.12 Products: Pass & Seymour, PT20AC3 (20A - three-way - use with PTS6STR4

prewired pigtail connector).2.8.2.13 Products: Pass & Seymour, PS20AC4 (20A - four-way).2.8.2.14 Products: Pass & Seymour, PS30AC1 (30A - single pole).2.8.2.15 Products: Pass & Seymour, PS30AC2 (30A - double pole).2.8.2.16 Products: Pass & Seymour, PS30AC3 (30A - three-way).2.8.2.17 Products: Pass & Seymour, PS81120 (20A/277V).

2.8.2.17.1 Snap-In Light Module: Pass & Seymour, PS8LM.2.8.2.18 Products: Pass & Seymour, PS811120 (20A/277V).

2.8.2.18.1 Snap-In Light Module: Pass & Seymour, PS8LM.2.8.2.19 Products: Pass & Seymour, 2601 (15A - single pole).2.8.2.20 Products: Pass & Seymour, PT2601 (15A - single pole - use with PTS6STR3

prewired pigtail connector).2.8.2.21 Products: Pass & Seymour, 2603 (15A - three-way).2.8.2.22 Products: Pass & Seymour, PT2603 (15A - three-way - use with PTS6STR4

26 27 26-10

Page 11:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

prewired pigtail connector).2.8.2.23 Products: Pass & Seymour, 2604 (15A - four-way).2.8.2.24 Products: Pass & Seymour, 2621 (20A - single pole).2.8.2.25 Products: Pass & Seymour, PT2621 (20A - single pole - use with PTS6STR3

prewired pigtail connector).2.8.2.26 Products: Pass & Seymour, 2622 (20A - double pole).2.8.2.27 Products: Pass & Seymour, 2623 (20A - three-way).2.8.2.28 Products: Pass & Seymour, PT2623 (20A -three-way - use with PTS6STR4

prewired pigtail connector).2.8.2.29 Products: Pass & Seymour, 2624 (20A - four-way).

2.8.3 Pilot Light Switches, 15, 20 and 30 A for 120V:2.8.3.1 Description: Neon-lighted handle, illuminated when switch is "ON."2.8.3.2 Products: Pass & Seymour, PS15AC1PL (15A - single pole).2.8.3.3 Products: Pass & Seymour, PS15AC3PL (15A - three-way).2.8.3.4 Products: Pass & Seymour, PS20AC1PL (20A - single pole).2.8.3.5 Products: Pass & Seymour, PS20AC2PL (20A - double pole, 120/277 V).2.8.3.6 Products: Pass & Seymour, PS20AC3PL (20A - three-way).2.8.3.7 Products: Pass & Seymour, PS30AC1 (30A - single pole).2.8.3.8 Products: Pass & Seymour, PS30AC2 (30A, 120/277 V - double pole).2.8.3.9 Products: Pass & Seymour, PS30AC3 (30A - three-way).2.8.3.10 Products: Pass & Seymour, 2629 (20A - single pole).

2.8.4 Pilot Light Switches, 20 and 30 A for 277V:2.8.4.1 Description: Neon-lighted handle, illuminated when switch is "ON."2.8.4.2 Products: Pass & Seymour, PS20AC1PL7 (20A - single pole).2.8.4.3 Products: Pass & Seymour, PS20AC2PL7 (20A - double pole).2.8.4.4 Products: Pass & Seymour, PS20AC3PL7 (20A - three-way).2.8.4.5 Products: Pass & Seymour, PS30AC1PL7 (30A - single pole).2.8.4.6 Products: Pass & Seymour, PS30AC2PL7 (30A, 120/277 V - two pole).

2.9 ILLUMINATED SWITCHES

2.9.1 Illuminated Switches, 15 and 20A for 120/277V:2.9.1.1 Description: Neon-lighted handle, illuminated when switch is "OFF."2.9.1.2 Products: Pass & Seymour, PT15AC1SL (15A - single pole - use with

PTS6STR3 prewired pigtail connector).2.9.1.3 Products: Pass & Seymour, PT15AC3SL (15A - three-way - use with PTS6STR4

prewired pigtail connector).2.9.1.4 Products: Pass & Seymour, PS15AC1SL (15A - single pole).2.9.1.5 Products: Pass & Seymour: PS15AC3SL (15A - three-way).2.9.1.6 Products: Pass & Seymour, PT20AC1SL (20A - single pole - use with

PTS6STR3 prewired pigtail connector).2.9.1.7 Products: Pass & Seymour, PS20AC1SL (20A - single pole 120/277 V).2.9.1.8 Products: Pass & Seymour, PS20AC3SL (20A -- three-way).2.9.1.9 Products: Pass & Seymour, PT20AC3SL (20A - three way - use with PTS6STR4

prewired pigtail connector).2.9.1.10 Products: Pass & Seymour, 2625 (20A - single pole).2.9.1.11 Products: Pass & Seymour, PT2625 (20A - single pole - use with PTS6STR3

prewired pigtail connector).2.9.1.12 Products: Pass & Seymour, 2626 (20A - three-way).2.9.1.13 Products: Pass & Seymour, PT2626 (20A - three-way - use with PTS6STR4

prewired pigtail connector).2.9.1.14 Products: Pass & Seymour, 2628 (20A - four-way).

2.10 KEY-OPERATED SWITCHES

26 27 26-11

Page 12:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.10.1 Key-Operated Switches, 120/277 V, 15 and 20 A:2.10.1.1 Description: Single pole, with factory-supplied key in lieu of switch handle.2.10.1.2 Products: Pass & Seymour, PS15AC1-L (15A - single pole).2.10.1.3 Products: Pass & Seymour, PS15AC3-L (15A - three-way).2.10.1.4 Products: Pass & Seymour, PS20AC1-L (20A - single pole).2.10.1.5 Products: Pass & Seymour, PS20AC2-L (20A - double pole).2.10.1.6 Products: Pass & Seymour, PS20AC3-L (20A - three-way pole).2.10.1.7 Products: Pass & Seymour, PS20AC4-L (20A - four-way pole).

2.11 MOMENTARY CONTACT SWITCHES

2.11.1 Single-Pole, Double-Throw, Momentary Contact, Center-Off Switches, 120/277 V, 15, 20 and 30 A: For use with mechanically held lighting contactors.2.11.1.1 Products: Pass & Seymour, 1250 (15A).2.11.1.2 Products: Pass & Seymour, 1251 (20A).2.11.1.3 Products: Pass & Seymour, 1255 (30A).

2.11.2 Single Pole, Momentary Contact, 120/277 V, 15 A:2.11.2.1 Products: Pass & Seymour, TM870STMCC10 (15A).

2.11.3 Double-Pole, Double-Throw, Momentary Contact, 120 V, 15 A:2.11.3.1 Products: Pass & Seymour, TM811DTMO (15A).

2.11.4 Double-Pole, Double-Throw, Momentary Contact, 120 V, 15 A:2.11.4.1 Products: Pass & Seymour, TM811DTMA (15A).

2.11.5 Double-Pole, Double-Throw, Momentary Contact, Center-Off Switches, 120/277 V, 30 A: For use with mechanically held lighting contactors.2.11.5.1 Products: Pass & Seymour, 1256 (30A).

2.11.6 Key-Operated, Single-Pole, Double-Throw, Momentary Contact, Center-Off Switches, 120/277 V, 15, 20 and 30 A: For use with mechanically held lighting contactors, with factory-supplied key in lieu of switch handle.2.11.6.1 Products: Pass & Seymour, 1250L (15A).2.11.6.2 Products: Pass & Seymour, 1251L (20A).2.11.6.3 Products: Pass & Seymour, 1255L (30A).

2.12 WALL-BOX DIMMERS

2.12.1 Dimmer Switches:2.12.1.1 Modular, full-wave, solid-state units with integral, quiet on-off switches, with

audible frequency and EMI/RFI suppression filters.2.12.1.2 Function: Continuously adjustable with single-pole or three-way switching.

Comply with UL 1472.2.12.1.3 Control: Slider.

2.12.2 Incandescent Lamp Dimmers, 120 V:2.12.2.1 Control shall follow square-law dimming curve. On-off switch positions shall

bypass dimmer module. Dimmers shall require no de-rating when ganged with other devices

2.12.2.2 Illuminated when "OFF."2.12.2.3 Products: 700W - Pass & Seymour CD700 Series (slide-to-OFF).2.12.2.4 Products: 700W - Pass & Seymour CD703P Series (Preset).2.12.2.5 Products: 1100W - Pass & Seymour CD1100 Series (slide-to-OFF).2.12.2.6 Products: 1100W - Pass & Seymour CD1103P Series (Preset).2.12.2.7 Products: 1600W - Pass & Seymour CD1600 Series (slide-to-OFF).2.12.2.8 Products: 1600W - Pass & Seymour CD1603P Series (Preset).

26 27 26-12

Page 13:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.12.2.9 Products: 2000W - Pass & Seymour CD2000 Series (slide-to OFF).2.12.2.10 Products: 2000W - Pass & Seymour CD2003P Series (Preset).

2.12.3 Fluorescent Lamp Dimmer Switches:2.12.3.1 Modular; compatible with dimmer ballasts; trim potentiometer to adjust low-end

dimming; dimmer-ballast combination capable of consistent dimming with low end not greater than 20 percent of full brightness

2.12.3.2 Products: 8A, 120V 2 wire, electronic, single pole - Pass & Seymour CDFB8 (slide to off).

2.12.3.3 Products: 8A, 120V 2 wire, electronic, single pole - Pass & Seymour CDFB83 (3-way, preset).

2.12.3.4 Products: 10A, 120V 2 wire, electronic, single pole - Pass & Seymour CDFB10 (slide to off).

2.12.3.5 Products: 10A, 120V 2 wire, electronic, single pole - Pass & Seymour CDFB103 (3-way, preset).

2.12.3.6 Products: 7A, 277V 2 wire, electronic, single pole - Pass & Seymour CDFB7277 (slide to off).

2.12.3.7 Products: 7A, 277V 2 wire, electronic, single pole - Pass & Seymour CDFB73P277 (3-way, preset).

2.13 FAN SPEED CONTROLS

2.13.1 Modular Fan Speed Controls, 120-V:2.13.1.1 Full-wave, solid-state units with integral, quiet on-off switches and audible

frequency and EMI/RFI filters. Comply with UL 1917.2.13.1.2 Products: Continuously adjustable slider - Pass & Seymour, CDSC6 Series.2.13.1.3 Products: Four-speed adjustable slider - Pass & Seymour, CDDH16 Series.

2.14 OCCUPANCY/VACANCY SENSORS

2.14.1 Residential Vacancy Sensors (PIR):2.14.1.1 Manual ON - Auto-OFF:

2.14.1.1.1 Products: Pass & Seymour, RW500BCC4.2.14.1.1.2 Products: Pass & Seymour, RW600BCC4 (neutral required).

2.14.1.2 Auto-ON - Auto-OFF:2.14.1.2.1 Products: Pass & Seymour, RW500UCC4.2.14.1.2.2 Products: Pass & Seymour, RW600UCC4 (neutral required).

2.14.1.3 Manual ON - Auto-ON (selectable): Pass & Seymour, RW3U600.2.14.1.4 Manual ON - (selectable): Pass & Seymour, RW3U603.

2.14.2 Wall-Switch Sensors:2.14.2.1 Products: Pass & Seymour, WSP250.2.14.2.2 Products: Pass & Seymour, PTWSP250 (use with PTS6STR3 prewired pigtail

connector).2.14.2.3 Description: Passive-infrared type, 120/277 V, adjustable time delay up to 30

minutes, 180-degree field of view, with a minimum coverage area of 900 sq. ft. (84 sq. m).

2.14.3 Wall-Switch Sensors:2.14.3.1 Products: Pass & Seymour, OS300S.2.14.3.2 Description: Adaptive-technology type, 120/277 V, adjustable time delay up to 30

minutes, 180-degree field of view, with a minimum coverage area of 900 sq. ft. (84 sq. m).

2.14.4 Wall-Switch Sensors:2.14.4.1 Products: Pass & Seymour, OSR300S.2.14.4.2 Description: Adaptive-technology type, dual-relay (operates both circuits of a bi-

26 27 26-13

Page 14:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

level lighting system), 120/277 V, adjustable time delay up to 30 minutes, 180-degree field of view, with a minimum coverage area of 900 sq. ft. (84 sq. m).

2.14.5 Wall-Switch Sensors:2.14.5.1 Products: Pass & Seymour, WDT100.2.14.5.2 Description: Dual technology (PIR and Ultrasonic) type, 120/277 V, adjustable

time delay up to 30 minutes, 180-degree field of view, with a minimum coverage area of 1050 sq. ft. (98 sq. m).

2.14.6 Wall-Switch Sensors:2.14.6.1 Products: Pass & Seymour, WDT200.2.14.6.2 Description: Dual technology (PIR and Ultrasonic) type, dual-relay (operates

both circuits of a bi-level lighting system), 120/277 V, adjustable time delay up to 30 minutes, 180-degree field of view, with a minimum coverage area of 1050 sq. ft. (98 sq. m).

2.14.7 Long-Range Wall-Switch Sensors:2.14.7.1 Products: Pass & Seymour, WA1001.2.14.7.2 Description: Passive-infrared type, 120/277 V, adjustable time delay up to 30

minutes, 110-degree field of view, with a minimum coverage area of 1200 sq. ft. (111 sq. m).

2.14.8 Wide-Range Wall-Switch Sensors:2.14.8.1 Products: Pass & Seymour, HS1001.2.14.8.2 Description: Passive-infrared type, 120/277 V, adjustable time delay up to 30

minutes, 150-degree field of view, with a minimum coverage area of 1200 sq. ft. (111 sq. m).

2.15 COMMUNICATIONS OUTLETS

2.15.1 Telephone Outlet:2.15.1.1 Description: Single RJ-45 jack for terminating 100-ohm, balanced, four-pair UTP;

TIA/EIA-568-B.1; complying with Category 5e. Comply with UL 1863.

2.15.2 Combination TV and Telephone Outlet:2.15.2.1 Description: Single RJ-45 jack for 100-ohm, balanced, four-pair UTP; TIA/EIA-

568-B.1; complying with Category 5e; and one Type F coaxial cable connector.

2.16 WALL PLATES

2.16.1 Wall Plates:2.16.1.1 General: Single and combination types to match corresponding wiring devices.2.16.1.2 Plate-Securing Screws: Metal with head color to match plate finish.2.16.1.3 Material for Finished Spaces: Steel with primer baked enamel, suitable for field

painting.2.16.1.4 Material for Finished Spaces: Smooth, high-impact thermoplastic.2.16.1.5 Material for Finished Spaces: 0.035 inch (1 mm) thick, satin-finished stainless

steel.2.16.1.6 Material for Finished Spaces: 0.04 inch (1 mm) thick, brushed brass with factory

polymer finish.2.16.1.7 Material for Finished Spaces: 0.04 inch (1 mm) thick steel with chrome-plated

finish.2.16.1.8 Material for Finished Spaces: 0.05 inch (1.2 mm) thick anodized aluminum finish.2.16.1.9 Material for Unfinished Spaces: Galvanized steel.2.16.1.10 Material for Unfinished Spaces: Smooth, high-impact thermoplastic.2.16.1.11 Material for Damp Locations: Thermoplastic with spring-loaded lift cover, and

listed and labeled for use in "wet locations."

26 27 26-14

Page 15:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.16.1.12 Material for Damp Locations: Cast aluminum with spring-loaded lift cover, and listed and labeled for use in "wet locations."

2.16.2 Wet-Location, Weatherproof Cover Plates:2.16.2.1 Compliance: NEMA 250, complying with type 3R weather-resistant with lockable

cover.2.16.2.2 Material: Die-cast aluminum.2.16.2.3 Material: Thermoplastic.

2.17 FLOOR SERVICE FITTINGS

2.17.1 Type: Modular, dual-service units suitable for wiring method used.2.17.1.1 Compartments: Barrier separates power from voice and data communication

cabling.2.17.1.2 Service Plate: Rectangular with satin finish.2.17.1.3 Service Plate: Round with satin finish.2.17.1.4 Service Plate: Die-cast aluminum with satin finish.2.17.1.5 Service Plate: Solid brass with satin finish.2.17.1.6 Power Receptacle: NEMA WD 6 configuration 5-20R, gray finish, unless

otherwise indicated.2.17.1.7 Voice and Data Communication Outlet: Blank cover with bushed cable opening.2.17.1.8 Voice and Data Communication Outlet: Two modular, keyed, color-coded, RJ-45

Category 5e jacks for UTP cable.

2.17.2 Type: Modular, flap-type, dual-service units suitable for wiring method used.2.17.2.1 Compartments: Barrier separates power from voice and data communication

cabling.2.17.2.2 Service Plate: Rectangular with satin finish.2.17.2.3 Service Plate: Round with satin finish.2.17.2.4 Service Plate: Die-cast aluminum with satin finish.2.17.2.5 Service Plate: Solid brass with satin finish.2.17.2.6 Power Receptacle: NEMA WD 6 configuration 5-20R, gray finish, unless

otherwise indicated.2.17.2.7 Voice and Data Communication Outlet: Blank cover with bushed cable opening.2.17.2.8 Voice and Data Communication Outlet: Two modular, keyed, color-coded, RJ-45

Category 5e jacks for UTP cable.

2.17.3 Type: Modular, above-floor, dual-service units suitable for wiring method used.2.17.3.1 Compartments: Barrier separates power from voice and data communication

cabling.2.17.3.2 Service Plate: Rectangular with satin finish.2.17.3.3 Service Plate: Round with satin finish.2.17.3.4 Service Plate: Die-cast aluminum with satin finish.2.17.3.5 Service Plate: Solid brass with satin finish.2.17.3.6 Power Receptacle: NEMA WD 6 configuration 5-20R, gray finish, unless

otherwise indicated.2.17.3.7 Voice and Data Communication Outlet: Blank cover with bushed cable opening.2.17.3.8 Voice and Data Communication Outlet: Two modular, keyed, color-coded, RJ-45

Category 5e jacks for UTP cable.

2.18 FINISHES

2.18.1 Wiring Devices Connected to Normal Power System:2.18.1.1 Color: Light Almond, unless otherwise indicated or required by NFPA 70 or

device listing.2.18.1.2 Color: Black, unless otherwise indicated or required by NFPA 70 or device

listing.

26 27 26-15

Page 16:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

2.18.1.3 Color: Brown, unless otherwise indicated or required by NFPA 70 or device listing.

2.18.1.4 Color: Gray, unless otherwise indicated or required by NFPA 70 or device listing.2.18.1.5 Color: Ivory, unless otherwise indicated or required by NFPA 70 or device listing.2.18.1.6 Color: White, unless otherwise indicated or required by NFPA 70 or device

listing.2.18.1.7 Color: Green, unless otherwise indicated or required by NFPA 70 or device

listing.2.18.1.8 Color: As selected by Architect, unless otherwise indicated or required by NFPA

70 or device listing.

2.18.2 Wiring Devices Connected to Emergency Power System: Red.

2.18.3 Surge Protective Devices: Blue.

2.18.4 Isolated-Ground Receptacles: Orange.

2.18.5 Isolated-Ground Receptacles: As specified above, with orange triangle on face.

3 EXECUTION

3.1 EXAMINATION

3.1.1 Do not begin installation until substrates have been properly prepared.

3.1.2 If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

3.2 PREPARATION

3.2.1 Clean surfaces thoroughly prior to installation.

3.2.2 Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.3 INSTALLATION

3.3.1 Comply with NECA 1, including the mounting heights listed in that standard, unless otherwise noted.

3.3.2 Coordination with Other Trades:3.3.2.1 Take steps to insure that devices and their boxes are protected. Do not place

wall finish materials over device boxes and do not cut holes for boxes with routers that are guided by riding against outside of the boxes.

3.3.2.2 Keep outlet boxes free of plaster, drywall joint compound, mortar, cement, concrete, dust, paint, and other material that may contaminate the raceway system, conductors, and cables.

3.3.2.3 Install device boxes in brick or block walls so that the cover plate does not cross a joint unless the joint is troweled flush with the face of the wall.

3.3.2.4 Install wiring devices after all wall preparation, including painting, is complete.

3.3.3 Conductors:3.3.3.1 Do not strip insulation from conductors until just before they are spliced or

terminated on devices.3.3.3.2 Strip insulation evenly around the conductor using tools designed for the

purpose. Avoid scoring or nicking of solid wire or cutting strands from stranded wire.

3.3.3.3 The length of free conductors at outlets for devices shall meet provisions of

26 27 26-16

Page 17:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

NFPA 70, Article 300, without pigtails.3.3.3.4 Existing Conductors:

3.3.3.4.1 Cut back and pigtail, or replace all damaged conductors.3.3.3.4.2 Straighten conductors that remain and remove corrosion and foreign

matter.3.3.3.4.3 Pigtailing existing conductors is permitted provided the outlet box is large

enough.

3.3.4 Device Installation:3.3.4.1 Replace all devices that have been in temporary use during construction or that

show signs that they were installed before building finishing operations were complete.

3.3.4.2 Keep each wiring device in its package or otherwise protected until it is time to connect conductors.

3.3.4.3 Do not remove surface protection, such as plastic film and smudge covers, until the last possible moment.

3.3.4.4 Connect devices to branch circuits using pigtails that are not less than 6 inches (152 mm) in length.

3.3.4.5 When there is a choice, use side wiring with binding-head screw terminals. Wrap solid conductor tightly clockwise, 2/3 to 3/4 of the way around terminal screw.

3.3.4.6 Use a torque screwdriver when a torque is recommended or required by the manufacturer.

3.3.4.7 When conductors larger than No. 12 AWG are installed on 15- or 20-A circuits, splice No. 12 AWG pigtails for device connections.

3.3.4.8 Tighten unused terminal screws on the device.3.3.4.9 When mounting into metal boxes, remove the fiber or plastic washers used to

hold device mounting screws in yokes, allowing metal-to-metal contact.

3.3.5 Receptacle Orientation:3.3.5.1 Install ground pin of vertically mounted receptacles up.3.3.5.2 Install ground pin of vertically mounted receptacles down.3.3.5.3 Install ground pin of horizontally mounted receptacles to the right.3.3.5.4 Install ground pin of horizontally mounted receptacles to the left.3.3.5.5 Install hospital-grade receptacles in patient-care areas with the ground pin or

neutral blade at the top.

3.3.6 Device Plates: Do not use oversized or extra-deep plates. Repair wall finishes and remount outlet boxes when standard device plates do not fit flush or do not cover rough wall opening.

3.3.7 Dimmers:3.3.7.1 Install dimmers within terms of their listing.3.3.7.2 Verify that dimmers used for fan speed control are listed for that application.3.3.7.3 Install unshared neutral conductors on line and load side of dimmers according

to manufacturers' device listing conditions in the written instructions.

3.3.8 Arrangement of Devices: Unless otherwise indicated, mount flush, with long dimension vertical and with grounding terminal of receptacles on top. Group adjacent switches under single, multigang wall plates.

3.3.9 Adjust locations of floor service outlets and service poles to suit arrangement of partitions and furnishings.

3.4 IDENTIFICATION

3.4.1 Receptacles: Identify panelboard and circuit number from which served. Use hot, stamped or engraved machine printing with -filled lettering on face of plate, and durable wire markers or tags inside outlet boxes.

26 27 26-17

Page 18:  · Web viewSurge Protected Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of 500 volts and minimum single transient pulse energy dissipation of 340

3.4.1.1 Fill Color: Black.3.4.1.2 Fill Color: White.3.4.1.3 Fill Color: Red.

3.5 FIELD QUALITY CONTROL

3.5.1 Perform tests and inspections and prepare test reports.3.5.1.1 In healthcare facilities, prepare reports that comply with recommendations in

NFPA 99.3.5.1.2 Test Instruments: Use instruments that comply with UL 1436.3.5.1.3 Test Instrument for Convenience Receptacles: Digital wiring analyzer with digital

readout or illuminated LED indicators of measurement.

3.5.2 Tests for Convenience Receptacles:3.5.2.1 Line Voltage: Acceptable range is 105 to 132 V.3.5.2.2 Percent Voltage Drop under 15-A Load: A value of 6 percent or higher is not

acceptable.3.5.2.3 Ground Impedance: Values of up to 2 ohms are acceptable.3.5.2.4 GFCI Trip: Test for tripping values specified in UL 1436 and UL 943.3.5.2.5 Using the test plug, verify that the device and its outlet box are securely

mounted.3.5.2.6 The tests shall be diagnostic, indicating damaged conductors, high resistance at

the circuit breaker, poor connections, inadequate fault current path, defective devices, or similar problems. Correct circuit conditions, remove malfunctioning units and replace with new ones, and retest as specified above.

3.5.3 Test straight blade outlets for the retention force of the grounding blade according to NFPA 99. Retention force shall be not less than 4 oz. (115 g).3.5.3.1 Convenience outlets in patient-care areas.3.5.3.2 Hospital-grade convenience outlets.

3.6 PROTECTION

3.6.1 Protect installed products until completion of project.

3.6.2 Touch-up, repair or replace damaged products before Substantial Completion.

END OF SECTION