weave radiant textile panels provide radiant cooling and ... · performance data acoustic ratings...
TRANSCRIPT
![Page 1: Weave radiant textile panels provide radiant cooling and ... · PERFORMANCE DATA Acoustic ratings according to ISO 11654. Weighted sound absorption coefficient = 0.85 Sound absorption](https://reader030.vdocuments.site/reader030/viewer/2022041115/5f270dadfc9c0953c767f9a0/html5/thumbnails/1.jpg)
APPLICATIONS
• Ceilings that have 50-75% of ceiling area active with radiant panels.
STRUCTURAL FORM
• Single-layer thermally par ticipative tensioned textile on aluminium frame and perforated aluminium sheet backed by copper coils and insulation.
DIMENSIONS
• Customised as standard from 300 x 600 mm to 1500 x 3000 mm. Mass of approximately 20 kg/m² when filled with water.
HYDRONICS
• Pure copper tube Ø12.7 with an allowable operating pressure of 10.34 bar (150 psi). Serpentine coil spaced evenly across width of panel. Panel to panel connections with 5/8 in. John Guest push fit flex hoses. Optional panel to header flex hoses based on customer requirement.
TEXTILES
• Four standard textile colour options.
FRAME PROFILE
• Aluminium hollow section profile, height 49mm. • Finish: clear anodised
INSULATION
• Constructed with glass minerals bonded by a thermosetting binder designed specifically for thermal and acoustic performance.
Particularly well suited to:Spaces with high sensible loads or high indoor air quality requirements.Spaces with a requirement for sound absorption.
Weave radiant textile panels provide radiant cooling and heating in addition to acoustic sound dampening. The panels function as part of a hydronic system to provide sensible heating and cooling for superior thermal comfort.
v001
![Page 2: Weave radiant textile panels provide radiant cooling and ... · PERFORMANCE DATA Acoustic ratings according to ISO 11654. Weighted sound absorption coefficient = 0.85 Sound absorption](https://reader030.vdocuments.site/reader030/viewer/2022041115/5f270dadfc9c0953c767f9a0/html5/thumbnails/2.jpg)
MOUNTING
Core is specially designed to integrate with Weave to provide a simple and efficient mechanism to install the panels to a ceiling. Core allows adjustability in the distance from the panel to the face of the installation surface.Torsion springs mounted on the Weave panel interface with slots in Core to provide a secure connection and access to individual panels.
Material: steel springs, aluminium Core
HINGING CAPABILITIES
Panels are permitted to hinge downward 90° as a standard with torsion spring installation.
ACCESS CABLES
Access cables increase accessible space for ease of installation of the panels and their flex hose connections.
↑ ↑ ↑
ACCESSORIES
v001
![Page 3: Weave radiant textile panels provide radiant cooling and ... · PERFORMANCE DATA Acoustic ratings according to ISO 11654. Weighted sound absorption coefficient = 0.85 Sound absorption](https://reader030.vdocuments.site/reader030/viewer/2022041115/5f270dadfc9c0953c767f9a0/html5/thumbnails/3.jpg)
ARCHITECTURAL END CAPS
Front Profile
Side Profile
For covering the small gap between ceiling and Weave panel.
Material: aluminium
Can be upholstered with the same textile as the Weave panel.
ACCESSORIES
v001
![Page 4: Weave radiant textile panels provide radiant cooling and ... · PERFORMANCE DATA Acoustic ratings according to ISO 11654. Weighted sound absorption coefficient = 0.85 Sound absorption](https://reader030.vdocuments.site/reader030/viewer/2022041115/5f270dadfc9c0953c767f9a0/html5/thumbnails/4.jpg)
FIRE RESISTANCE
This clause has been carried out in accordance with clause 11 and 15 of EN 13501-1:2007+A1:2009
EU reaction to fire classification: B-sl, d0
CERTIFICATION
CE (Conformité Européenne)
HEATING PERFORMANCECOOLING PERFORMANCE
W/m
2 Coo
ling
Mean Water Temperature - Air Temp (K)8 9 10 11 127640
70
60
50
80
90
100
110
120
Tested to DIN EN 14240 at WSP lab, Stuttgart.Flow rate: 225 kg/hr
Tested to DIN EN 14037 at WSP lab, Stuttgart.Flow rate: 85 kg/hr
DIMENSIONAL DATA
83 mm 86 mm
36 mm
120 mm130 mmMIN.
(44 mm)
PERFORMANCE DATAHeating performanceCooling performance
W/m
2 Coo
ling
Mean Water Temperature - Air Temp (K)8 9 10 11 127640
70
60
50
80
90
100
110
120
W/m
2 Hea
ting
Mean Water Temperature - Air Temp (K)201714 23115 80
20
40
60
100
80
120
140
160
Tested to DIN EN 14240 at WSP lab, Stuttgart.Flow rate: 225 kg/hr
Tested to DIN EN 14037 at WSP lab, Stuttgart.Flow rate: 85 kg/hr
Acoustic Performance
Rating according to ISO 11654:
+ Weighted Sound Absorption
Coefficient αw = 0.85
+ Sound absorption class: B
Fire Performance
+ EU Reaction to fire classification: B-s1,d0
7v001 | For more information visit [email protected]
RADIANT TEXTILE PANELS
PERFORMANCE DATA
Acoustic ratings according to ISO 11654.
Weighted sound absorption coefficient = 0.85
Sound absorption class: B
ACOUSTIC
High Walls
Front Profile
Side Profile
For covering the small gap between ceiling and Weave panel.
Material: aluminium
Can be upholstered with the same textile as the Weave panel.
Performance
Acoustic
Acoustic ratings according to ISO 11654.
Weighted sound absorption coefficient = 0.85
Sound absorption class: B
v001