wavelet and ann based differential protection of power transformer

Upload: tulasi-priya

Post on 05-Apr-2018

225 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    1/30

    SIMULATION OF TRANSFORMERS USING

    SIMPOWERSYSTEMS

    IINNTTRROODDUUCCTTIIOONN

    Sims Power Systems extends Simulink with tools for modeling and simulating basic

    electrical circuits and detailed electrical power systems. These tools let us model the

    generation, transmission, distribution, and consumption of electrical power, as well as its

    conversion into mechanical power. SimPowerSystems is well suited to the development of

    complex, self-contained power systems, such as those in automobiles, aircraft, manufacturing

    plants, and power utility applications.

    Together, SimPowerSystems and Simulink provide an efficient environment for

    multidomain modeling and controller design. By connecting the electrical parts of the

    simulation to other Simulink blocks, we can rapidly draw the circuit topology and

    simultaneously analyze the circuits interactions with mechanical, thermal, and Control

    systems.

    SSIIMMUULLAATTIIOONN OOFF TTRRAAIINNIINNGG CCAASSEESS FFOORR TTRRAANNSSFFOORRMMEERR::

    Three-phase transformers (One power Transformer and Two distribution Transformers) of 150

    MVA, 110/220 kV; 500 KVA, 11/0.433 kV; and 1000kVA, 11/0.433 kV are modelled using

    MATLAB. The parameters used for the simulation of these two distribution transformers

    through MATLAB were obtained from IT-BHU Substation

    A Three Phase 110/220 kV power system included a 150 km transmission line, as

    shown in Fig.1, has been used to produce the required test and training patterns. The

    simulation was done by means of SimPowerSystems (MATLAB) software.

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    2/30

    Fig 1Simulated power system model

    Table 1represents theassociated data with this power system. Thecombination

    of condition system shown in Table 2, have been produced using this system to train

    the WNN (Wavelet and ANN). Faults are located at different points of transmission

    line.Also,

    they involve inrush current and over excitation condition with differentvoltage angles and with different loads. Here secondary current is converted to primary

    side to make a common base. Breakers are connected to different positions for obtaining

    data for above different conditions of power transformer. Differential current is

    obtained by subtracting the secondary current to primary current.

    TABLE 1 SIMULATED POWER SYSTEM PARAMETERS

    Transformer nominal power

    & frequency

    150 MVA, 50 Hz

    Transformer winding parameters R=.002 pu, L=.08 pu

    Transformer core loss resistance 500 pu

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    3/30

    TABLE 2 TRAINING PATTERNS DATA GENERATION

    Condition

    system

    Internal fault : Transformer secondary is shorted and single

    phase-ground faults and double phase-ground faults and three

    phase faults

    Inrush : At different voltage angles by closing the breaker

    connected

    Over-excitation : At different over voltages

    Voltage

    angle

    0, 10, 20..to 180 degree

    Load(MW) 20, 40, 60, 80 and 100

    Line parameters (150 km) R=.2568 ohm/km, L=2e-3 H/km, c=8.6e-9

    F/km

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    4/30

    Since the network has to distinguish among five kinds of signals, 4sets of example

    signals (cases) have been obtained for this purpose. These cases are normal, internal fault

    current, magnetizing inrush and over- excitation condition

    1. Normal case: Power system is simulated for different voltage angles and for differentloads.

    2. Internal fault : Transformer terminal faults like Single phase to ground, double phaseto ground ,three phase to ground and phase to phase faults

    3. Inrush condition: In this condition transformer secondary is open circuited. Circuitbreaker is connected at primary side, which is primarily open and shorted after two

    cycle.

    4. Over-excitation: For obtaining this condition the load side connected circuit breaker isopened at alternate cycles.

    Following figures 2 show the power system models for creating the data at different

    conditions.

    Fig 2(a) Normal condition

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    5/30

    Fig .2(b) internal fault condition

    Fig

    2(c) Magnetizing Inrush condition

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    6/30

    Fig 2(d) Over-excitation condition

    Following figures 3 show the differential currents of transformer at different conditions.

    Fig-3 (a) Normal condition

    Simulated event of Three phase transformer (SimPowerSystems)

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    7/30

    Fig- 3 (b) internal fault condition

    Simulated event of three phase transformer (SimPowerSystems)

    Fig-3 (c) Inrush condition

    Simulated event of three phase transformer (SimPowerSystems)

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    8/30

    Fig-3 (d) Over-excitation condition

    Simulated event of three phase transformer (SimPowerSystems)

    Different cases of Normal, Fault, and Inrush and over Excitation cases are simulated. The

    fundamental frequency of the current is 50Hz .The differential current waveforms generated

    from using MATLAB software has a sampling frequency of 2 KHz. There are 40 samples/ cycle.

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    9/30

    WAVELET ANALYSIS AND NEURAL NETWORK

    TRAINING AND RESULTS

    Design and Development of WNN (Combined Wavelet and ANN) ForDifferential Relaying:

    WAVELET ANALYSIS:

    There are two aspect had to consider for Wavelet analysis

    1.The differential current waveforms generated from using MATLAB software

    have a sampling frequency of 2 KHz. There are 40 samples/ cycle.

    2. Another aspect had to be consider is no. Of current samples which will beapplied to the feature extractor (DWT) .Here half of the data cycle used as a

    moving window that means 20 samples. This data would be updated by

    incorporating the latest sample and discarding the oldest sample

    EXTRACTING DWT COMPONENTS FOR DIFFERENT

    CONDITION:

    The DWT plots of differential current below demonstrate the importance of

    having DWT as the feature extractor of the Neural Network classifier. Through using

    the features of the DWT extracted from differential current data, the DWT can help with

    the discriminating of different data clusters and groups , thus, benefit the predictive and

    detective system.

    Normal Condition:

    The following fig shows the plots of the coefficients of the Discrete Wavelet

    Transform (DWT) of differential current with 100% load

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    10/30

    Fig: 1 (a) DWT of A-Phase differential current measured for Normal

    condition

    Aamax = 1.251 Damax = 0.3341

    Aaavg = -0.111 Daavg = 0.0028

    Naa = 4.225 Nda = 0.3969

    Fig: 1 (b) DWT of B-Phase differential current measured for Normal condition

    Abmax = 1.2592 Dbmax = 0.1174

    Abavg

    = -0.1076 Dbavg

    = -0.0024

    Nab = 4.230 Ndb = 0.3109

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    11/30

    Fig:1 (c) DWT of C-Phase differential current measured for Normal condition

    Acmax = 1.2517 Dcmax = 0.0395

    Acavg = 0.2187 Dcavg = -3.9e^-4

    Nac = 4.6876 Ndc = 0.0945

    Internal Fault condition:

    Single Phase to ground fault:

    The following fig shows the plots of the coefficients of the Discrete

    Wavelet Transform (DWT) of differential current with single phase( A-Phase) to

    ground fault with zero resistance

    Fig:2(a) DWT of A-Phase differential current measured for Single phase (A-

    Phase) to ground fault

    Aamax = 928.92 Damax = 21.38

    Aaavg = 169.74 Daavg = -4.697

    Naa = 1900 Nda = 80.85

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    12/30

    Fig:2(b) DWT of B-Phase differential current measured for Single phase (A-Phase)

    to ground fault

    Abmax = 1.4100 Dbmax = 0.0542

    Abavg = 0.0414 Dbavg = 5.42e^-4

    Nab = 4.7942 Ndb = 0.1207

    Fig:2(c) DWT of C-Phase differential current measured for Single phase (A-

    Phase) to ground fault

    Acmax = 1.4162 Dcmax = 0.0402Acavg = 0.0349 Dcavg = -1.92e^-4

    Nac = 14.11 Ndc = 0.1445

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    13/30

    Two phase fault:

    The following fig shows the plots of the coefficients of the Discrete Wavelet Transform

    (DWT) of differential current with two phase (R-Y) fault with 10 resistance

    Fig:3(a) DWT of A-Phase differential current measured for Two phase (A-Phase

    to B-Phase) fault with 10 resistance

    Aamax = 813.15 Damax = 13.626

    Aaavg = 222.2 Daavg = -0.4434

    Naa = 1980 Nda = 33.829

    Fig:3(b) DWT of B-Phase differential current measured for Two phase (A-Phase to

    B-Phase) fault with 10 resistance

    Abmax = 7.657 Dbmax = 27.06

    Abavg = -221.98 Dbavg = 0.4416

    Nab = 1980 Ndb = 33.843

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    14/30

    Fig:3(c) DWT of C-Phase differential current measured for Two phase (A-Phase to

    B-Phase) fault with 20 resistance

    Acmax = 1.486 Dcmax = 0.0402

    Acavg = 0.0351 Dcavg = -1.61e^-4

    Nac = 15.093 Ndc = 0.0972

    Three Phase Fault:

    The following fig shows the plots of the coefficients of the Discrete Wavelet Transform

    (DWT) of differential current with three phase (R-Y-B) fault with 20 resistance

    Fig:4(a) DWT of A-Phase differential current measured for Three phase (R-Y-B)

    fault with 20 resistance

    Aamax = 840.01 Damax = 54.95

    Aaavg = 162.54 Daavg = -4.339

    Naa = 1780 Nda = 158.18

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    15/30

    Fig:4(b) DWT of B-Phase differential current measured for Three phase (R-Y-B)

    fault with 20 resistance

    Abmax = 37.52 Dbmax = 33.33

    Abavg = -262.09 Dbavg = -3.430

    Nab = 2200 Ndb = 115.7

    Fig:4(c) DWT of C-Phase differential current measured for Three phase (R-Y-B)

    fault with 20 resistance

    Acmax = 598.2 Dcmax = 111.6

    Acavg = 0.2569 Dcavg = -1.08

    Nac = 5360 Ndc = 285.0

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    16/30

    Inrush condition:

    The following fig shows the plots of the coefficients of the Discrete Wavelet

    Transform (DWT) of differential current of 3 phases with 60 degrees

    Fig:5(a) DWT of A-Phase differential current measured for Inrush condition at 60

    degrees

    Aamax = 855.2 Damax = 43.24

    Aaavg = 162.45 Daavg = 0.6338

    Naa = 1600 Nda = 57.89

    Fig:5(b) DWT of B-Phase differential current measured for Inrush condition at 60

    degrees

    Abmax = 15.55 Dbmax = 19.88

    Abavg = -100.127 Dbavg = -0.621

    Nab = 1200 Ndb = 35.66

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    17/30

    Fig:5(c) DWT of C-Phase differential current measured for Inrush condition at 60

    degrees

    Acmax = 9.5401 Dcmax = 13.08

    Acavg = -86.11 Dcavg = 1.254

    Nac = 1080 Ndc = 23.89

    Over Excitation condition:

    The following fig shows the plots of the coefficients of the Discrete Wavelet Transform

    (DWT) of differential current of 3 phases with 140% of voltage

    Fig:6(a) DWT of A-Phase differential current measured for 140% of voltage

    Aamax = 216.90 Damax = 9.121

    Aaavg = -19.116 Daavg = -0.762

    Naa = 561.05 Nda = 22.0412

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    18/30

    Fig:6(b) DWT of B-Phase differential current measured for 140% of voltage

    Abmax = 223.55 Dbmax = 12.25

    Abavg = 2.19 Dbavg = 0.2803

    Nab = 431.11 Ndb = 27.84

    Fig:6(c) DWT of C-Phase differential current measured for 140% of voltage

    Acmax = 196.62 Dcmax = 22.87

    Acavg = 15.17 Dcavg = 0.164

    Nac = 505 Ndc = 43

    In all DWT processes performed above, the Db-6 type mother wavelet (Daubechies6)

    has been used. Also, the decomposition level of the DWT of these signals has been kept

    at 2 In Mat lab, the some commands were used to calculate the DWT coefficients.The

    maximum, normalisation and average values of detail and approximation coefficients

    are used to train the neural network

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    19/30

    d1 max = maximum value of d1[n] = max[d1[n]]

    d1norm=normalisationvalue of d1[n] =norm[d1[n]]

    d1avg =average value of d1[n] = avg[d1[n]]

    a1max = maximum value of a1[n] = max[a1[n]]

    a1norm=normalisation value of a1[n] =norm[a1[n]

    a1avg =average value of a1[n] = avg[a1[n]]

    For each phase 6 input values so for three phase 18 input values are used to train the

    neural network

    TTEESSTT RREESSUULLTTSS OOFF PPRROOPPOOSSEEDD AANNNN

    A software nntool (graphical user interface) in MATLAB SIMULINK has been

    used for training process. Since the network has to distinguish among four kinds of

    signals, 4 sets of example signals (cases) have been obtained for this purpose. These

    cases are normal, internal fault, magnetizing inrush and over- excitation. The training

    functions and parameters are given in Table-1.

    Table-1 Training function and parameters

    Adaption learning function LEARNGM Training function TRAINGDA

    Hidden layer transfer

    function

    TANSIG Output layer transfer

    function

    TANSIG

    Epochs 2000 mc 0.95

    Goal 0.00000011 Mu-max 100000000

    Max-fail 40 Show 20

    Mem_redu 1 Time Inf

    Min_grad 1e-10 Learning Rate 0.7

    Mu 0.001 Performance function MSE

    LEARNGD-Gradient descent weight and bias learning function

    TRAINGDA-Gradient descent back propagation with adaptive learning rate

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    20/30

    For each Power transformer and distribution transformer 740 training sets of

    samples (580 sets for training and 160 sets for testing purpose) generated by

    SimPowerSystems in MATLAB. Signals are sampled at the sampling rate of 40

    samples per cycle (over a data window of half cycle).

    The Wavelet transform has been used to analyze the transients in the power

    transformers. The data obtained from the simulations are given to the

    MATLAB(Wavelet Analysis) software to calculate DWT coefficients of the signals..

    This 580 training sets of coefficients contain 4 different conditions of power

    transformer (normal, magnetizing inrush, over-excitation, internal fault ) 100 sets of

    coefficients have been taken for normal, 240 sets of coefficients taken for internal fault,

    140 sets of coefficients taken for inrush, 100 sets of coefficients taken for over

    excitation condition.

    After enough experimentation a network with 40 neurons in the hidden layer

    apart from 18 inputs and 4 outputs has been found suitable for monitoring the different

    conditions of power transformer. The outputs of the network have a unique set (e.g.,

    1000 = normal, 0100=internal fault, 0010= inrush, 0001 =over-excitation,). This

    network i.e. with 4 outputs monitors all the conditions occurring in the power

    transformer and it issues the trip signal only in case of internal fault condition i.e. when

    output is 0100.

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    21/30

    Fig:8 Flowchart of ANN Training

    Concerning the ANN architecture, parameters such as the number of inputs to

    the network and the number of neurons in the hidden layer were decided empirically.

    Performance Results for Power Transformer (110/220KV, 150MVA):

    This training process involves experimentation with various network

    configurations. It has been discovered that ANN with less number of input and hidden

    layer perform satisfactorily using the BP training algorithm. The learning process was

    terminated after 2000 cycles. The training error after 2000 epochs was 0.000097 for the

    proposed network and was within acceptable limit. The network responds in a very

    adequate way, performing the discrimination among normal, inrush, over-excitation,

    Preparation of suitable Training

    Selection of a suitable ANN

    Training of the ANN

    Trained

    Evaluation of the trained ANN

    Performance

    Process Terminated

    Poor

    Good

    Creation of Training data

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    22/30

    and internal fault currents correctly for all cases. The competitive model and their

    performance are being discussed here. Table 2 show the different ANN topologies and

    their corresponding errors. On the basis of performance, networks have been classified

    as very good, good, or not good. By very good performance the authors mean that the

    network can be trained to achieve the error goals and can respond adequately to the test

    by good the same can be achieved by increasing the

    Table2

    Performance of network architectures with 18 inputs, 4 outputs, and Variable neurons in

    the hidden layer (Training epochs: 2000)

    ANN topology Training error Training time

    (seconds)

    Performance

    18_10_4 0.000567 71 G

    18_20_4 0.000798 61 NG

    18_30_4 0.000581 50 NG

    18_40_4 0.000097 37 VG

    18_50_5 0.000598 70 NG

    NG = not good; VG = very good; G = good.

    number of iterations. It has been found that a net with 18 inputs, 40 nodes in hidden

    layer, and 4 outputs is capable of reducing the error up to 0.000097, which is quite

    accurate for this problem. Figure 20 shows the learning error over 2000 cycles of the

    architecture (18-40-4), which is continuously decreasing, whereas the same of the other

    topology shows zigzag behaviour. Therefore, for these cases the performance is not

    good. The response can be improved further by undertaking further extensive training,

    but it is realized that the same is not desired. By Using the detail and approximate

    coefficients to train the NN the training time is taken less and for testing it takes only

    few milliseconds. The outputs for test and trained patterns are shown in Tables 3 and 4,

    respectively. The learning errors for other topologies have been shown in in fig.

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    23/30

    Fig:9 Learning error for 18_40_4 topology

    The plot shows the mean squared error of the network starting at a large value and

    decreasing to a smaller value. In other words, it shows that the network is learning.

    The plot has three lines, because the 580 input and targets vectors are randomly divided

    into three sets. 60% of the vectors are used to train the network. 20% of the vectors are

    used to validate how well the network generalized. Training on the training vectors

    continues as long the training reduces the network's error on the validation vectors.

    After the network memorizes the training set (at the expense of generalizing more

    poorly), training is stopped. This technique automatically avoids the problem of over

    fitting, which plagues many optimization and learning algorithms. Finally, the last 20%

    of the vectors provide an independent test of network generalization to data that the

    network has never seen

    Table 3

    Trained output for the architecture

    Types of

    Cases

    ANN

    Architecture

    Outputs

    1

    A P

    2

    A P

    3

    A P

    4

    A P

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    24/30

    Normal 18_40_4 0.9776 1 0.0040 0 0.0041 0 0.00267 0

    Internal Fault 18_40_4 0.00034 0 0.996 1 0.0107 0 0.000839 0

    Inrush 18_40_4 0.0000016 0 0.0153 0 0.989 1 0.00051 0

    Over

    Excitation

    18_40_4 0.000165 0 0.00094 0 0.00478 0 0.9987 1

    Table 4

    Tested output for the architecture

    Types of

    Cases

    ANN

    Architecture

    Outputs

    1

    A P

    2

    A P

    3

    A P

    4

    A P

    Normal 18_40_4 0.9776 1 0.0039 0 0.0040 0 0.0266 1

    Internal Fault 18_40_4 0.0037 0 0.991 1 0.0059 0 0.00117 0

    Inrush 18_40_4 0.00076 0 0.0000034 0 0.9980 1 0.000125 0

    Over-

    excitation

    18_40_4 0.0005517 0 0.0035 0 0.00029 0 0.99900 1

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    25/30

    Fig:10(a).Learning error for 18_10_4 topology

    Fig:10(b) Learning error for 18_20_4 topology

    Fig:10(c) Learning error for 18_30_4 topology

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    26/30

    Fig:10(d) Learning error for 18_50_4 topology

    Response of Relay to Internal fault:

    0 0.025 0.05 0.075 0.10 0.125 0.150 0.175

    0.2

    Fig:11 Response of relay

    From these results, it can be seen that 10 ms after the occurrence of a fault, the

    protection technique developed correctly identifies internal fault.The outputs show the

    satisfactory result for the architectures. The ANN recognizes the fault in all cases and

    gives the trip signal output within half of cycle after the internal fault occurrence.

    trip

    Faultt=0.04

    1

    0

    1

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    27/30

    Performance Results for Distribution Transformer (11/0.433KV, 500KVA):

    Table 5: Performance of network architectures with 18 inputs, 4 outputs, and Variable

    neurons in the hidden layer

    ANN topology Training error Training time

    (seconds)

    Performance

    18_10_4 0.0089 71 G

    18_20_4 0.011 79 NG

    18_30_4 0.0092 84 NG

    18_40_4 0.010 89 NG

    18_50_4 0.0080 90 G

    In above topologies 18_50_4 error is less than other topologies. The trained and tested

    output of the 18_50_4 topology shown in Table and the learning error of the 18_50_4

    topology .

    Table 6 Trained output for the architecture

    Types of

    Cases

    ANN

    Architectur

    e

    Outputs

    1

    A P

    2

    A P

    3

    A P

    4

    A P

    Normal 18_40_4 0.9427 1 8.83e-5 0 0.002 0 0.130

    9

    0

    Internal Fault 18_40_4 0.179 0 0.942 1 0.0063 0 2.65e-

    5

    0

    Inrush 18_40_4 0.0344 0 0.0034 0 0.997 1 0.005

    6

    0

    Over

    Excitation

    18_40_4 0.048 0 1.09e-5 0 8.208e-5 0 0.960 1

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    28/30

    Table 7:Tested output for the architecture

    Types of

    Cases

    ANN

    Architecture

    Outputs

    1

    A P

    2

    A P

    3

    A P

    4

    A P

    Normal 18_40_4 0.89 1 0.067 0 0.003 0 9.8e-5 0

    Internal Fault 18_40_4 0.172 0 0.947 1 0.0048 0 2.67e-7 0

    Inrush 18_40_4 0.0035 0 0.0004 0 0.91 1 0.023 0

    Over

    Excitation

    18_40_4 0.168 0 2.654 0 0.074 0 0.94 1

    Fig.12 Learning error for 18_10_4 topology

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    29/30

    Performance Results for Distribution Transformer (11/0.433KV, 1 MVA):

    Table 8: Performance of network architectures with 18 inputs, 4 outputs, and Variable

    neurons in the hidden layer

    ANN topology Training error Training time

    (seconds)

    Performance

    18_10_4 0.0017 69 VG

    18_20_4 0.0047 76 G

    18_30_4 0.0039 86 G

    18_40_4 0.0033 84 G

    18_50_5 0.0068 91 G

    In above topologies 18_10_4 error is less than other topologies. The trained and tested

    output of the 18_10_4 topology shown in Table and the learning error of 18_10_4

    topology is shown in fig 23

    Table 9: Trained output for the architecture

    Types of

    Cases

    ANN

    Architecture

    Outputs

    1

    A P

    2

    A P

    3

    A P

    4

    A P

    Normal 18_10_4 0.98 1 0.006 0 0.0096 0 0.1 0

    Internal Fault 18_10_4 2.2e-05 0 0.98 0 0.01 0 0.016 0

    Inrush 18_10_4 0.001 0 0.02 0 0.976 1 0.003 0

    Over

    Excitation

    18_0_4 0.00061 0 0.01 0 0.014 0 0.99 1

  • 8/2/2019 Wavelet and Ann Based Differential Protection of Power Transformer

    30/30

    Table 10: Tested output for the architecture

    Types of

    Cases

    ANN

    Architecture

    Outputs

    1

    A P

    2

    A P

    3

    A P

    4

    A P

    Normal 18_10_4 0.842 1 0.157 0 0.011 0 0.017 0

    Internal Fault 18_10_4 7.178e-07 0 0.99 1 0.019 0 0.038 0

    Inrush 18_10_4 0.00067 0 0.0079 0 0.91 1 0.023 0

    Over

    Excitation

    18_10_4 0.0061 0 0.0038 0 0.0036 0 0.9982 1

    Fig.13.Learning error for 18_10_4 topology