vsd specification
DESCRIPTION
york VSD specification chillerTRANSCRIPT
VSD
Variable-Speed Drive
reduceenergy costs
longerequipment life
lowernoise level
lesserinrush current
2
YORK Variable-Speed Drive Retrofit
Cooling a building is not a constant process. The Sun rises and sets. Tenants arrive in the morning and leave in the evening. Summer is
off-set by winter. But do your energy bills fully reflect these variations? They will if you fit a YORK VSD chiller drive.
YORK’s variable-speed drive can cut chiller energy consumption by 30% or more because no constant-speed chiller, not even a high
efficiency model can match the performance of a VSD drive under the real-world plant room operating conditions.
The YORK VSD variable-speed drive was specifically developed for commercial airconditioning applications, delivering optimum efficiency
for virtually any operating condition.
Bringing Value to You:
Superior energy efficiency cuts energy cost, fast payback
Adaptive Capacity Control Logic stable surge-free operation, maximizes energy savings
Automatically corrects power factor
Soft start lesser inrush current, better electrical protection, reduces driveline wear
Low speed operation runs quieter
Direct linkage to control panel convenient monitoring and control
Single-source responsibility designed, built, installed and serviced by YORK
The Adaptive Capacity Control learns and remembers optimum motor speed and PRV position for a given set of conditions, which fine-tunes chiller performance
Chiller Water Temperature
Temperature Setpoint
Evaporator/Condenser Pressure
PRV Positio
Actual Motor Speed
Optimum Motor Speed
Optimum PRV Position
8085 75 70 65 60 55Entering Condenser Water Temp. (oF)
0.60
0.55
0.50
0.45
0.40
0.35
0.30
0.25
0.20
0.15
kW/t
on
TypicalCentrifugalChiller
60%100%
CentrifugalChillerWith VSD
100%60%
3
A typical chiller plant works at less than
its designed maximum performance levels
nearly 99% of the time. By optimizing
chiller operation a YORK VSD drive
accrues energy savings continuously
during off-peak times – by as much as
75% at light loads*. When condenser
water drops, so does the condenser
saturated temperature. As the compressor
head (delta P) reduces, the compressor
torque also reduces. Thus the motor
works lesser and energy consumption is
reduced. As a result, payback is fast
particularly where wet bulb temperature is
low – typically between one to three years
– but the monthly savings continue to
mount up.
With its Adaptive Capacity Control logic,
a YORK VSD drive learns how a chiller
operates and maps surge points. This
enables the fine-tuning of motor speed
and pre-rotation vane (PRV) position for
various load and water temperature
combinations – a performance no simple
variable speed drive can match.
The chil ler plant is often the biggest
energy user in a building and many
electricity companies penalize building
owners for having a low power factor. In
some installations that use constant-
speed chillers, building owners are forced
to install additional power factor correction
capacitors to overcome this problem. This
is an expensive exercise.
Chillers fitted with a YORK VSD drive
and optional filter can correct the power
factor which could do without additional
capacitor. The optional filter also meets
the guidelines of IEEE519-92 for total
harmonic distortion.
Saving Energy and Increasing Reliability
Payback Under 3 Years
* Based on ARI 550/59 – 1998 IPLV part load conditions
Impact of VSD at Off-Design Conditions
Lowers condensing water temperature
Lowers head pressure
Reduces compressor work
Reduces energy consumption
Enthalpy
Pressure
Compressor
Evaporator
Condenser
Hea
d P
ress
ure
Enthalpy
Pressure
Compressor
Evaporator
Condenser
Hea
d P
ress
ure
HighHead
HighHead
LowHead
Fast PaybackUnder 3 YearsFast PaybackUnder 3 Years
0 5 10 20 30 40
500
400
300
200
100
Time (Sec)
Inrush Current
Mo
tor
FLA
(%)
Star-Delta Starter VSD Drive
Compared to electro-mechanical starters. VSD drives reduce current inrush and motor wear.
4
A VSD’s power requirements are frugal
with start-up amps 60% lower than
conventional chiller drives. Conventional
starters can have inrush currents which
generate heat, and flexing critical points in
the motor windings. With a VSD fitted, the
chiller’s motor starts more slowly, (soft
start) never drawing more than 100% of
full-load amps, which increases motor life
and reliability. As proof, chillers controlled
by a VSD drive can be restarted in as little
as few minutes, making quick-turn,
emergency restarts possible.
And because 99% of the time it is not
running at ful l-speed, moving parts
experience less wear, increasing reliability
even further. Slower speeds also mean less
noise. With a YORK VSD in place, chiller
plant noise drops by as much as 10
decibels.
YORK’s distinctive technology is in-built in
the system with display of critical operating
conditions on the Optiview Control Centre.
This simplifies the monitoring and diagnostic
inspection. Hence problems can be
identified and resolved before it’s too late.
VSD Provides Soft Start
Head Pressure
VSD
5
Optimizes PRV position
Motor speed slows down
Optimizes compressor or efficiency
PRV closes as load decreases
Motor remains constant
Adaptive Capacity Control Logic
ConsumesLess EnergyConsumes
Less Energy
To understand how a chiller equipped with
a VSD drive can offer 30% lower energy
costs, consider the two factors that affect
energy consumption: load and entering
condenser-water temperature. A reduction
in either can save energy, however, the
method by which the chiller is controlled
can have a major impact on the magnitude
of these savings.
A constant-speed chiller reacts to lower
load or lower entering-condenser-water
temperature by closing its pre-rotation
vanes (PRV), which throttle the refrigerant
flow and save some energy. However, as
Adaptive Capacity Control Logic
VSD
The Intelligent Approach to Energy Conservationthe vanes continue to close, they create
frictional losses, reducing efficiency and
limiting energy-saving capability.
YORK’s VSD drive monitors several
operating conditions: chilled water, chilled
water set-point, evaporator and condenser
pressures, inlet vane position, and motor
speed. Differences in impeller geometry
make each chiller’s operating characteristics
unique. Adaptive Capacity Control (ACC)
logic determines the optimal motor speed
and inlet vane position – identifying your
chi l ler’s surge points – in order to
maximize efficiency and minimize energy
consumption.
YORK is your choice
YORK, a Johnson Controls Company, is a leading global provider of heating, ventilation, air conditioning, and refrigeration (HVAC&R) products and services.
Our wide breadth of product lines range from small residential room air conditioners to the largest chillers used to cool the tallest buildings, provide life support systems in the deepest diving ocean submarines, and enable critical process cooling in the petrochemical, pharmaceutical and microelectronics industries of the world.
YORK has been chosen by world-renowned organizations including the US Capitol, the Kremlin, the Sydney Opera House, the Trans-Channel Eurotunnel, the National Theatre of China, the Grand Palace of Thailand, the Hong Kong Convention & Exhibition Centre, the Kuala Lumpur City Centre and Taipei 101, the world's tallest building.
YORK reserves the right to change product features without prior notice.
Form
No.:
E-E1
7.SL.H
K(03
06)
Supe
rsede
s: E-
E17.S
L.HK(
1105
)
Asia Pacific Headquarters1 Genting Lane, #03-00 Kenwood Building, Singapore 349544Tel: +65 6748 0202 Fax: +65 6743 4420 Greater China Headquarters 15/F, Telecom Tower, Whart T & T Square, 123 Hoi Bun Rd, Kwun Tong, Kowloon, Hong KongTel: +852 2331 9286 Fax: +852 2331 9840
YORK’s Commitment - Superior Quality • Excellent Service • Distinctive Technology
www.york.com
Australia Tel: +61 (7) 3391 4772 Fax: +61 (7) 3391 4704
China (Shanghai) Tel: +86 (21) 6276 6509 Fax: +86 (21) 6277 3543
Hong Kong Tel: +852 2331 9286 Fax: +852 2331 9840
India Tel: +91 (22) 3088 1455 Fax: +91 (22) 3088 1534
Indonesia Tel: +62 (21) 626 3535 Fax: +62 (21) 659 8875
Japan Tel: +81 (0) 78 991 6885 Fax: +81 (0) 78 991 6889
Korea Tel: +82 (2) 548 2114 Fax: +82 (2) 548 3222
New Zealand Tel: +64 (9) 444 6434 Fax: +64 (9) 444 2092
Philippines Tel: +63 (2) 830 0291 Fax: +63 (2) 812 0928
Singapore Tel: +65 6284 5722 Fax: +65 6283 3015
Taiwan Tel: +886 (2) 2599 2255 Fax: +886 (2) 2599 3377
Thailand Tel: +66 (2) 721 0500 Fax: +66 (2) 721 1590
Vietnam Tel: +84 (8) 930 2820 Fax: +84 (8) 930 2822
15-25%
YORK Energy Saving Excellence
YORK’s VSD reduces chiller energy consumption by 15-25% annually
Reference Projects in Asia
Academy for Performing Arts, Hong KongCastle Peak Hospital, Hong KongCauseway Bay CRC, Hong KongChangi Water Reclamation Plant, SingaporeChina Square, SingaporeEast Point Centre, Hong KongHarbour Centre, Hong Kong HASEL, Hong KongHitachi, ThailandInfineon Technology, SingaporeJohnson & Johnson, ThailandKowloon Shangri-La Hotel, Hong KongKwai Chung Plaza, Hong KongLangham Place, Hong KongMacau Fisherman’s Wharf, Macau
Macau Government Hospital, MacauMacau Mandarin Oriental Hotel, MacauMaxim’s Food Factory, Hong KongNational University of Singapore, SingaporeOcean Centre, Hong KongOcean Terminal, Hong KongQueensway Government Office, Hong KongPlaza Singapura, SingaporeScience Park Building 9, Hong KongShenzhen Sheraton Hotel, PRCShui On Centre, Hong KongSkyplaza Building, Hong KongSun Hung Kai Centre, Hong KongTsuen Wan Plaza, Hong KongUS Embassy, Thailand