EERs & COPsCompany EER COP
Daikin VRV IV 4.40 4.51
Koolman DC Inverter 4.28 4.39
LG Multi V IV 5.20 5.74
Hitachi Set Free 3.92 4.17
GreenAir GAV M5 4.29 4.39
Chigo CMV Series 4.35 4.66
Gree GMV IV 4.06 4.29
Mitsubishi City Multi Series 3.64 4.18
Samsung DVM S 2.8 2.86
Midea V4 Plus 4.29 4.39
![Page 5: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/5.jpg)
Electricity Consumption (Cooling) Brand kW / Ton (lowest values)
Daikin VRV IV 0.756
Koolman DC Inverter 0.820
LG Multi V IV 0.673
Hitachi Set Free 0.897
GreenAir GAV M5 0.820
Chigo CMV Series 0.808
Gree GMV IV 0.863
Mitsubishi City Multi Series 0.916
Samsung DVM S 7.54
Midea V4 Plus 0.820
![Page 6: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/6.jpg)
Operating Range Company Cooling Range (°CDB) Heating Range (°CWB)
Daikin VRV IV -5 to 49 -20 to 15.5
Koolman DC Inverter -5 to 48 -20 to 27
LG Multi V IV -10 to 43 -25 to 18
Hitachi Set Free -5 to 43 -20 to 15
GreenAir GAV M5 -5 to 52 -20 to 27
Chigo CMV Series -5 to 50 -20 to 28
Gree GMV IV -5 to 48 -20 to 27
Mitsubishi City Multi Series -15 to 43 -20 to 15.5
Samsung DVM S -5 to 49 -20 to 24
Midea V4 Plus -5 to 48 -20 to 27
![Page 7: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/7.jpg)
Sound Pressure LevelCompany Noise Level dB(A)
Daikin VRV IV 55
Koolman DC Inverter 57
LG Multi V IV 58.5
Hitachi Set Free 58
GreenAir GAV M5 57
Chigo CMV Series 58
Gree GMV IV 58
Mitsubishi City Multi Y Series 56
Samsung DVM S 60
Midea V4 Plus 57
![Page 8: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/8.jpg)
External Static Pressure (ESP)Company ESP (Pa)
Daikin VRV IV 78.4
Koolman DC Inverter -
LG Multi V IV 80
Hitachi Set Free 60
GreenAir GAV M5 60
Chigo CMV Series 85
Gree GMV IV 75
Mitsubishi City Multi Y Series 60
Samsung DVM S 78.4
Midea V4 Plus 60
![Page 9: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/9.jpg)
Max Indoor AttachmentCompany No. of Indoor Attached
Daikin VRV IV 64
Koolman DC Inverter 24
LG Multi V IV 64
Hitachi Set Free 64
GreenAir GAV M5 64
Chigo CMV Series 64
Gree GMV IV 64
Mitsubishi City Multi Y Series 32
Samsung DVM S -
Midea V4 Plus 64
![Page 10: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/10.jpg)
Total Piping lengthCompany Total Piping Length (m)
Daikin VRV IV 1000
Koolman DC Inverter 500
LG Multi V IV 1000
Hitachi Set Free 70
GreenAir GAV M5 1000
Chigo CMV Series 1000
Gree GMV IV 500
Mitsubishi City Multi Y Series 300
Samsung DVM S 220
Midea V4 Plus 1000
![Page 11: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/11.jpg)
SALIENT FEATURES
![Page 12: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/12.jpg)
Daikin VRV IV Space mounted technology (SMT) packaging technology• Protects your computer board from the adverse effect of sandy and humid weather VRT Technology• Energy efficient- 4 modes available: Powerful mode, Quick mode, Mild mode & Eco
mode Refrigerant PCB cooling• More efficient cooling without affected by the ambient temperature• Ensure stability of PCB temperature Neodymium magnet based compressors• 50% more neodymium magnet in scroll compressors Ceiling mounted round flow cassette with sensors• Presence of people and floor temperature can be detected to provide comfort and
energy savings Individual airflow direction control• Air flow direction can be individually adjusted for each air discharge outlet (Position 0 to
4, Swing, No individual setting are selectable)
![Page 13: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/13.jpg)
Daikin VRV IV Auto airflow rate• Airflow rate automatically adjusted depending upon the difference b/w
room temperature & set temperature. Set point range• Saves energy by limiting the min. and max. set temperature Set point auto reset• If the set temperature is changed, it returns to preset temperature
after preset time. Period selection ranges from 30 min to 120 min Setback• Maintain the room temperature in a specific range during unoccupied
time by temporarily starting the AC that was turned OFF- Cooling: 33-37°C with recovery differential -2 to -8°C, Heating: 10-15°C with recovery differential 2 to 8°C
![Page 14: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/14.jpg)
Daikin VRV IV Sensing sensor low mode• When there are no people in a room, set temperature is shifted
automatically (Shift temperature and time can be selected from 0.5 to 4°C in 0.5°C increments and 15, 30, 45, 60, 90 or 120 minutes respectively with remote controller)
Sensing sensor stop mode• When there are no people in a room, the system stops
automatically (Absent stop time can be selected from 1 to 24 hrs in 1 hr increments with remote controller)
Airflow block function• Enhances comfort- Airflow block function prevents uncomfortable
drafts by reducing air velocity by approx. 0.3 m/s
![Page 15: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/15.jpg)
LG Multi V IV • HiPOR™ (High pressure oil return)• Variable heat exchanger circuit• Vapor injection• Active refrigerant control• Continuous heating operation in defrost• Cannon fan: high air volume, low noise level and high efficiency• New refrigerant quantity decision feature• FDD (Fault detection & diagnosis)• Smartphone monitoring & control • Auto refrigerant collection• Auto compressor oil management
![Page 16: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/16.jpg)
Hitachi Set Free• DC motor with reduced noise & higher efficiency• Motion sensor• Anti-bacterial condensate drain• Independent louver control• Ferrite magnet based DC motor• Econofresh kit optional enthalpic and CO2 sensor• Centralized controller• Capacity adjustment using DIP switch• Adaptability to high ceiling
![Page 17: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/17.jpg)
Chigo CMV• Brushless DC motor• 180° sine wave control• Cross flow fins• Super cooling flow path design• 2 in 1 refrigerant path design• Anti vibration fan blade• Streamline duct design• Anti snow function• Circuit silencer• Emergency stop operation• Adjustable outdoor fan ESP• Oil control technology
![Page 18: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/18.jpg)
Gree GMV IV
• DC fan motor• Lower noise and better performance based
condensing fan• Precise temperature control• Intelligent defrost technology• Wide voltage operation range: 342V to 456V• PCB protection design• New generation of oil return• High efficiency oil balanced technology
![Page 19: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/19.jpg)
Mitsubishi City Multi Y Series
• Draft free airflow• Humidification control• Complete zoning control• Green technology-Energy saving• Centralized controller• Intelligent energy usage• Superior air distribution• Independent vane motor control• i-See sensor
![Page 20: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/20.jpg)
Samsung DVM S• 3rd generation vapor injection system-20% more refrigerant flow rate• Refrigerant PCB cooling• Auto oil balancing• Large oil storage capacity• Plate heat exchanger-30% more efficient than shell & tube type, 50% more efficient than
double tube type intercooler• Auto commissioning & management• Automatic data backup-last 30 minutes of operation• Wifi monitoring system• Auto snow blowing function• Powerful airflow• Individual blade control• Motion detection sensor• Surround airflow• Smart pressure control• Optimized refrigerant distribution control
![Page 21: VRF Systems comaprison](https://reader031.vdocuments.site/reader031/viewer/2022012312/55ce7f3fbb61ebad088b4589/html5/thumbnails/21.jpg)
Midea V4 Plus• DC fan motor-50% Energy Saving• Dynamic gas balance technology • High efficiency oil balance technology • Intelligent soft start technology• Quick warm-up & cool-down design• Built in Formaldehyde nemesis filter • Active-carbon and biological anti-virus filter are optional• Connectable to various sized Gateway• High air flow• ID & OD centralized control