vive maestro wireless dimmers and switches spec...
TRANSCRIPT
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 1 08.27.18
Vive Maestro Wireless Dimmers and SwitchesThe Maestro Wireless solution incorporates Maestro Wireless load controls, wireless sensors, and wireless remote controls, which provide a system that delivers energy savings, convenience, and ease of installation.Maestro Wireless dimmers and switches use Lutron patented Clear Connect RF Technology, which enables wireless communication with Radio Powr Savr sensors and Pico remote controls for light control and general switched loads.
These products are also compatible with the Vive hub which enables a simple setup process using a standard web browser on any Wi-Fi enabled phone, tablet or computer. It also enables control and monitoring of all Vive devices. The Vive hub can be added at any time. System reprogramming will be required. For a complete list of features supported with the Vive hub, see specification submittal 369902.
Note for Replacement: MRF2S - the “S” model can replace the non-”S” model.
Features• TheMaestroWirelesssolutionprovidesdimming/
switchingofmultipleloadtypes,occupancy/vacancysensing, and daylight harvesting.
• LutronpatentedClearConnectRFTechnologyworksthrough walls and floors.
• IncorporatesadvancedfeaturessuchasfadeON/fadeOFF,high-endtrim,andrapidfull-ON (a Vive hub is required to set high-end trim).
• ControlsincludeFrontAccessibleServiceSwitch(FASS)forsafelampreplacement.
• Two-wiredimmersandswitchesavailableforretrofitapplications.
• Powerfailurememory:Ifpowerisinterrupted,thecontrol will return to its previously set level prior to interruption.
Receiving DevicesMaestro Wireless Controls
Neutral and Non-Neutral Dimmers
Neutral and Non-Neutral Switches
Transmitting DevicesRadio Powr Savr Sensors
Pico Remote Controls
Ceiling-Mounted Occupancy and Vacancy Sensors
Wall-Mounted Occupancy and Vacancy Sensors
Daylight Sensors
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 2 08.27.18
Maestro Wireless Dimmers
Models AvailableDimmersCFL / LED/Halogen / IncandescentMRF2S-6CL-XX 1 150WCFL/LEDDimmer; 600W/600VAIncandescent,120V~
MRF2S-6ND-120-XX 1,2 600W/600VASpec-GradeNeutralWireDimmer,120V~ 150WCFL/LEDDimmer
Electronic Low-Voltage DimmerMRF2S-6ELV120-XX1 600WELVDimmer120V~ (neutral required) 150WCFL/LEDDimmer
Companion DimmersClaro Gloss FinishesMA-R-XX1,2 Companion Dimmer 120 V~
Satin Colors Satin FinishesMSC-AD-XX1 Companion Dimmer 120 V~
1 “XX”inthemodelnumberrepresentscolor/finishcode.SeeColors and Finishes at end of document.2 BAA-compliantmodelnumbersavailable.Adda“U”prefixtothemodelnumber.
Dimmer
Companion Dimmer
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 3 08.27.18
Ganging and DeratingWhencombiningcontrolsinthesamewallbox,deratingisrequired.Dimmer Load Type and Capacity
No Neutral Required
A B B B C B
Control Voltage Load Type Minimum LoadMaximum Load
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-6CL 1,2,3 120 V~CFL/LED See lamp list See Mixing Lamp TypesIncandescent/Halogen 50 W 600 W 500 W 400 W
Note:DonotmixELVandMLVloadtypesonasinglecontrol.1 DimmerLoadType:
• MRF2S-6CLisdesignedforusewithpermanently-installedincandescent,CFL,LED,ortungstenhalogenonly.• MRF2S-6ND-120isdesignedforusewithpermanently-installedincandescent,CFL,LED,magneticlow-voltage,ortungstenhalogenonly.CancontrolPowerModules(PHPM-
PA-DV,PHPM-3F-DV-WH,PHPM-WBX-DV-WH,andGRX-TVI)andlegacyinterfacesHi-Power2•4•6Boosters(HP-2,HP-4,HP-6).• MRF2S-6ELV120isdesignedforusewithpermanently-installedelectroniclow-voltage,incandescent,CFL,LEDortungsten/halogenonly.Donotinstalldimmerstocontrol
receptacles or motor-operated appliances.2 Low-VoltageApplications:
• UseMRF2S-6ND-120withmagnetic(coreandcoil)low-voltagetransformersonly.Notforusewithelectronic(solid-state)low-voltagetransformers.• UseMRF2S-6ELV120withelectronic(solid-state)low-voltagetransformersonly.Operationofalow-voltagecircuitwithlampsinoperativeorremovedmayresultintransformer
overheatingandprematurefailure.Lutronstronglyrecommendsthefollowing:– Do not operate low-voltage circuits without operative lamps in place.– Replaceburned-outlampsasquicklyaspossible.– Usetransformersthatincorporatethermalprotectionorfusedtransformerprimarywindingstopreventtransformerfailureduetoovercurrent.
• SeeApplicationNote#559fordimminglowvoltageLEDs.3 BAA-compliantmodelnumbersavailable.Adda“U”prefixtothemodelnumber.
Mixing Lamp TypesMixinglamptypes(usingacombinationofCFL/LED,andIncandescent/Halogenbulbs)andganging with other dimmers or electronic switches may reduce maximumwattage,asshown.
Example:Iffinsfromonesideofdimmerareremovedand you have two 24 W bulbs installed (total CFL Wattage = 48 W), you may add up to 300 W of incandescent or halogen lighting.
Do not remove outside fins on ends of ganged controls (shaded areas below)
A B B B C B
Total CFL/LED WattageTotal Incandescent/Halogen Wattage
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-6CL0 W + 50 W – 600 W Or 50 W – 500 W Or 50 W – 400 W1 W – 25 W + 0 W – 500 W Or 0 W – 400 W Or 0 W – 300 W26 W – 50 W + 0 W – 400 W Or 0 W – 300 W Or 0 W – 200 W51 W – 75 W + 0 W – 300 W Or 0 W – 200 W Or 0 W – 100 W76 W – 100 W + 0 W – 200 W Or 0 W – 100 W Or 0 W – 50 W101 W – 125 W + 0 W – 100 W Or 0 W – 50 W Or 0 W126 W – 150 W + 0 W Or 0 W Or 0 W
Neutral Required
Control Voltage Load Type Minimum LoadMaximum Load
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-6ELV1201,2 120 V~ELV 5 W 600 W 500 W 400 W
CFL/LED See lamp list See Mixing Lamp Types
MRF2S-6ND-120 1,2,3 120 V~
Incandescent/Halogen 25 W 600 W 500 W 400 W
MLV 2 25W/VA 450W/600VA 400W/500VA 300W/400VA
CFL/LED See lamp list See Mixing Lamp Types
Example:Ifadimmerisinstalledinlocation“B”aboveand there are two 24 W CFL bulbs installed (Total CFL Wattage = 48 W), you may add up to 300 W of incandescent or halogen lighting.
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 4 08.27.18
Maestro Wireless Switches
Models AvailableSwitchesLighting and motor loadsMRF2S-6ANS-XX1,2,4 6ALighting/3AFan(1/10HPmotor), ElectronicSwitch120 V~
MRF2S-8ANS120-XX1,2,4 8ALighting,5.8AFan(1/4HPmotor),Spec-Grade ElectronicSwitch120V~
MRF2S-8S-DV-XX 2,3,4 8ALighting,3AFan(1/10HPmotor,120V~ only), Spec-GradeElectronicSwitch120–277V~, no neutral wire required
Companion SwitchesClaro Gloss FinishesMA-AS-XX2,4 Companion Switch 120 V~
MA-AS-277-XX2,4 Companion Switch 277 V~
Satin Colors Satin FinishesMSC-AS-XX4 Companion Switch 120 V~
MSC-AS-277-XX4 Companion Switch 277 V~
1 Neutral wire required.
2 BAA-compliantmodelnumbersavailable.Adda“U”prefixtothemodelnumber.
3 MayrequireLUT-MLC(includedwithMRF2S-8S-DVmodels)toensureproperfunctionwithlow-wattageloadtypes. See page 11 for details.
4 “XX”inthemodelnumberrepresentscolor/finishcode.SeeColors and Finishes at end of document.
Switch
Companion Switch
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 5 08.27.18
Ganging and DeratingWhencombiningcontrolsinthesamewallbox,deratingisrequired.Switch Load Type and Capacity
No Neutral Required
A B B B C B
Control Voltage Load Type Minimum LoadMaximum Load
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-8S-DV 1,5
120 – 277 V~ Incandescent/Halogen 25 W 8A 8A/7A4 7A120 – 277 V~ Fluorescent/LED/CFL 40W(LUT-MLC)3 8A 8A/7A4 7A120 V~ Fan Motor 0.4A 1/10HP(3A) 1/10HP(3A) 1/10HP(3A)
1 SwitchLoadType:• MRF2S-8ANS120isdesignedforusewithpermanently-installedlightingloadsandwithfanmotorloadsupto1/4HP(5.8A).
• MRF2S-8S-DVisdesignedforusewithpermanently-installedlightingloadsandwithfanmotorloadsupto1/10HP(3A,120V~ only).
• MRF2-6ANSisdesignedforusewithpermanently-installedlightingloadsandwithfanmotorloadsupto1/10HP(3A).
2 Forloadslargerthan8A(120V~),theMRF2S-8ANS120switchcanbeusedwiththePHPM-SW-DV-WHpowerbooster.
3 TheLUT-MLCensuresproperfunctionwithlow-wattagefluorescent,CFL,andLEDloadtypes.See page 11 for details.
4 Maximumloadfordouble-gangapplicationis8A.Triple-gangapplicationderatesmaximumloadto7A.
5 BAA-compliantmodelnumbersavailable.Adda“U”prefixtothemodelnumber.
Neutral Required
A B B B C B
Control Voltage Load Type Minimum LoadMaximum Load
A: Not Ganged B: End of Gang C: Middle of Gang
MRF2S-8ANS1201,2,5 120 V~Lighting 25 W 8A 6.5A 5AFan Motor 0.2A 1/4HP(5.8A) 1/4HP(5.8A) 1/6HP(4.4A)
MRF2-6ANS1 120 V~Lighting 25 W 6A 5A 3.5AFan Motor 0.2A 1/10HP(3A) 1/10HP(3A) 1/10HP(3A)
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 6 08.27.18
SpecificationsRegulatory Approvals
• UL® Listed.• cUL® Listed (MRF2S-6CL only).• CSACertified(exceptforMRF2S-6CL).• FCCApproved.ComplieswiththelimitsforaClassB
digital device, pursuant to Part 15 of the FCC Rules.• IndustryCanadaCertified.• Thefollowingmodelnumbershavebeentestedand
foundcompliantwithUL2043foruseinairhandlingspaces:MRF2S-6CL-GR,MRF2S-6ELV-GR, MRF2S-6ND-GR
PowerOperatingvoltage:
• 120V~50/60Hz(allmodels)• 277V~50/60Hz(MRF2S-8S-DV)
Environment• Ambientoperatingtemperature:32°Fto104°F
(0 °Cto40°C)• 0%to90%humidity,non-condensing.• Indooruseonly.• AlldriversandballastsusedwithVivewireless
controlsmustcomplywiththelimitsforaClassAdevice pursuant to Part 15 of the FCC Rules.
Key Design FeaturesDimmers
• Onasingle-tap,lightsfadeUPorDOWN.• Onadouble-tap,lightsgotofullON.• Lightlevelscanbefine-tunedbypressingand
holdingthedimmingrockeruntilthedesiredlightlevel is reached.
• Two-wiredimmersavailable.
Switches• Onasingle-tap,lightsturnONorOFF.• Two-wireswitchesavailable.
All RF Local Controls• Testedtowithstandelectrostaticdischargewithout
damageormemoryloss,inaccordancewithIEC61000-4-2.
• Testedtowithstandsurgevoltageswithout damage or loss of operation, in accordance with IEEEC62.41-1991RecommendedPracticeonSurgeVoltagesinLow-VoltageACPowerCircuits.
• Controlsalwaysoperatelocallyanddonotrequiresystem control.
• Powerfailurememory:shouldpowerbeinterrupted,the control will return to its previously-set level prior to the interruption when power is restored.
• Usesconventional3-wayand4-waywiring.• MultiplelocationcontrolfromDimmer/Switchandup
tonineCompanionDimmers/Switches.• UseLutronDesigner(ClaroandSatinColors)
wallplates or designer-style wallplates from other manufacturers. Wallplates are sold separately.
• LutronClaroandSatinColorswallplatessnaponwith no visible means of attachment.
• Requiresaone-gangU.S.wallbox;31⁄2 in (89 mm) deep recommended, 21⁄4 in (57 mm) deep minimum.
• Greenindicatorlights.
System Communications and Capacity• MaestroWirelesscontrolscommunicatewiththe
Pico remote controls and Radio Power Savr sensors through radio frequency (RF).
• Receiveswirelessinputsfromupto10Picoremotecontrols, 10 Radio Powr Savr occupancy/vacancysensors, and 1 Radio Powr Savr daylight sensor
• MaestroWirelesslocalcontrolsmustbelocatedwithin 60 ft (18 m) line-of-sight or 30 ft (9 m) through walls, of Radio Power Savr sensors. The 60 ft (18 m) range is not reduced by a ceiling tile obstruction.
• MaestroWirelesslocalcontrolsmustbelocatedwithin 60 ft (18 m) line-of-sight or 30 ft (9 m) through walls, of a Pico remote control. The 60 ft (18 m) range is not reduced by a ceiling tile obstruction.
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 7 08.27.18
WallplateAdapter/Wallplatepurchasedseparately
WallplateAdapter Wallplate
Wallbox
Control
AdapterMountingScrews
Control Mounting Screws
Mounting
DimensionsAlldimensionsareshownas:in(mm)
Side View
5/16(8)
1 1⁄8(30)
Front View
4 11⁄16(119)
2 15⁄16(75)
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 8 08.27.18
Operation
Status LEDsIndicatelightlevel;glowsoftlyasnight light when light is OFF
Dimming RockerPress to brightenPress to dim
TapswitchTapON/OFF;Double-tap:lightsgotofullON
FASSFrontAccessibleServiceSwitch
FASSFrontAccessibleServiceSwitch
FASS Front Accessible Service SwitchImportant Notice: To service load, removepowerbypullingtheFASSoutcompletelyoneithertheDimmer/SwitchorCompanionDimmer/Switch.Afterservicingload,pushtheFASSbackinfullyto restore power to the control.
Dimmer
TapswitchTapON/OFF
SwitchStatus LEDIndicatesloadstatus;glowssoftlyasnight light when light is OFF
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 9 08.27.18
1 When using controls in single location installations, tighten the blue terminal without any wires attached. Do not connect the blue terminal to any other wiring or to ground.
2 UptonineMaestroCompanionDimmersmaybeconnectedtotheMaestroWirelessDimmer.Totalblueterminalwirelengthmaybeupto250ft(76m).
Wiring DiagramsSingle-Location Dimmer Installation without NeutralMRF2S-6CL
Dimmer
Load
Brass
Black
Line/Hot
Green
Blue 1
Ground
Neutral
120 V~60Hz
Multi-Location Dimmer Installation without Neutral 2MRF2S-6CLwithMA-R/MSC-AD
Companion Dimmer Companion Dimmer Dimmer
BrassBrassBrass
BlackBlackBlack
Line/Hot
GreenGreenGreen
BlueBlueBlue
GroundGroundGround
Neutral
120 V~60Hz Load
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 10 08.27.18
1 When using controls in single location installations, tighten the blue terminal without any wires attached. Do not connect the blue terminal to any other wiring or to ground.
2 UptonineMaestroCompanionDimmers/SwitchesmaybeconnectedtotheMaestroWirelessDimmer/Switch.Totalblueterminalwirelengthmaybeupto250 ft (76 m).
3 Neutral-wireDimmers/SwitchesmustbeconnectedontheLoadsideofamulti-locationinstallation.
Wiring Diagrams (continued)
Multi-Location Dimmer / Switch Installation with Neutral 2,3
MRF2S-6ND-120and-6ELV120withMA-R/MSC-ADorMRF2S-8ANS120and-6ANSwithMA-AS/MSC-AS
Companion Dimmer/Switch
Companion Dimmer/Switch Dimmer/Switch
Brass
Silver
BrassBrass
BlackBlackBlack
Line/Hot
GreenGreenGreen
BlueBlueBlue
GroundGroundGround
Neutral
120 V~60Hz Load
Single-Location Dimmer / Switch Installation with NeutralMRF2S-6ND-120,-6ELV120,-8ANS120,and-6ANS
Dimmer/Switch
Load
Brass
Black
Silver
Line/Hot
Green
Blue 1
Ground
Neutral
120 V~60Hz
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 11 08.27.18
1 ALUT-MLCensuresproperfunctionwhenfluorescent,CFL,orLEDloadsareused.InstalltheLUT-MLCinsidealoadfixtureorinaseparateJ-boxwithinthecircuit.
2 When using controls in single-location installations, tighten the blue terminal without any wires attached. Do not connect the blue terminal to any other wiring or to ground.
3 UptonineMaestroCompanionSwitchesmaybeconnectedtotheMaestroWirelessSwitch.Totalblueterminalwirelengthmaybeupto250ft(76m).4 RequiresMA-AS/MSC-ASfor120V~applications,andMA-AS-277/MSC-AS-277for277V~ applications.
Single-Location Switch Installation with LUT-MLC 1MRF2S-8S-DV
Switch
Load LUT-MLC1
Brass
Black
Line/Hot
Green
Optional *
Blue 2
Ground
Neutral
120 V~60Hz or 277 V~60Hz
Multi-Location Switch Installation with LUT-MLC 1,2,3
MRF2S-8S-DVwithMA-AS/MA-AS-277orMSC-AS/MSC-AS-2774
Companion Switch Companion Switch Switch
BrassBrassBrass
BlackBlackBlack
Line/Hot
GreenGreenGreen
BlueBlueBlue
GroundGroundGround
Neutral
120 V~60Hz or 277 V~60Hz
Load LUT-MLC1
Optional *
Wiring Diagrams (continued)
* Optional Procedure: UsingLUT-MLCwithMRF2S-8S-DV-XX
•InstallMRF2S-8S-DV-XXfirstwithoutLUT-MLCtoseeifrequired.Checkforproblemswithload.
•Problemscanoccurwhenlow-wattageloadsareused (< 40 W).
•WatchforflickeringloadswhendimmerisinelectronicOFF state.
•Ifrequired,LUT-MLCcanbeinstalledbetweenswitchedhotandneutralinwallboxifneutralispresent,orinanyfixtureontheswitchedcircuit.
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 12 08.27.18
1 When using controls in single-location installations, tighten the blue terminal. Do not connect the blue terminal to any other wiring or to ground.2 UptonineMaestroCompanionSwitchesmaybeconnectedtotheMaestroWirelessSwitch.Totalblueterminalwirelengthmaybeupto250ft(76m).3 Neutral-wire Switches must be connected on the Load side of a multi-location installation.
Wiring Diagrams (continued)
Single-Location Switch Installation with Power Booster Single FeedMRF2S-8ANS120and-6ANSwithPHPM-SW-DV-WH
Switch
Brass Blue 1
Zone In
Black
Silver
Line/Hot
SwitchedLine/Hot
Line/Hot
NeutralNeutral
Neutral
Ground
Ground
Green
120 V~60Hz
Load
Multi-Location Switch Installation with Power Booster Single Feed 2,3
MRF2S-8ANS120and-6ANSwithMA-AS/MSC-ASandPHPM-SW-DV-WH
Companion Switch Switch
Brass BlueBlue
Zone In
Black
Silver
Line/Hot
SwitchedLine/Hot
Line/Hot
Brass
Black
NeutralNeutral
Neutral
Ground
Ground
Green
Ground
Green
120 V~60Hz
Load
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 13 08.27.18
Multi-Location Switch Installation with Power Booster Dual Feed 1,2
MRF2S-8ANS120and-6ANSwithMA-AS/MSC-ASandPHPM-SW-DV-WH
Companion Switch Switch
Brass BlueBlue
Zone In
Black
Silver
Line/Hot
Switched Line/Hot
Line/Hot
Brass
Black
NeutralNeutral
Neutral
Neutral
Ground
Ground
Green
Ground
Green
120 V~60Hz or 277 V~60Hz
120 V~60Hz
Load
Wiring Diagrams (continued)
Single-Location Switch Installation with Power Booster Dual FeedMRF2S-8ANS120and-6ANSwithPHPM-SW-DV-WH
Switch
Brass Blue 1
Zone In
Black
Silver
Line/Hot
Switched Line/Hot
Line/Hot
NeutralNeutral
Neutral
Neutral
Ground
Ground
Green
120 V~60Hz or 277 V~60Hz
120 V~60Hz
Load
1 When using controls in single-location installations, tighten the blue terminal. Do not connect the blue terminal to any other wiring or to ground.2 UptonineMaestroCompanionSwitchesmaybeconnectedtotheMaestroWirelessSwitch.Totalblueterminalwirelengthmaybeupto250ft(76m).3 Neutral-wire Switches must be connected on the Load side of a multi-location installation.
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 14 08.27.18
1 When using controls in single-location installations, tighten the blue terminal. Do not connect the blue terminal to any other wiring or to ground.2 UptonineMaestroCompanionDimmersmaybeconnectedtotheMaestroWirelessDimmer.Totalblueterminalwirelengthmaybeupto250ft(76m).3 Neutral-wire Dimmers must be connected on the Load side of a multi-location installation.
Wiring Diagrams (continued)
Single-Location Switch Installation with Power Booster Single FeedMRF2S-6ND-120withPHPM-PA-DV-WH
Dimmer
DH
Brass Blue 1
Zone In
Black
Silver
Line/Hot
SwitchedLine/Hot
Line/Hot
NeutralNeutral
Neutral
Ground
Ground
Green
120 V~60Hz
Load
Multi-Location Switch Installation with Power Booster Single Feed 2,3
MRF2S-6ND-120withMA-R/MSC-ADandPHPM-PA-DV-WH
Companion Dimmer Dimmer
DH
Brass BlueBlue
Zone In
Black
Silver
Line/Hot
SwitchedLine/Hot
Line/Hot
Brass
Black
NeutralNeutral
Neutral
Ground
Ground
Green
Ground
Green
120 V~60Hz
Load
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 15 08.27.18
1 When using controls in single-location installations, tighten the blue terminal. Do not connect the blue terminal to any other wiring or to ground.2 UptonineMaestroCompanionDimmersmaybeconnectedtotheMaestroWirelessDimmer.Totalblueterminalwirelengthmaybeupto250ft(76m).3 Neutral-wire Dimmers must be connected on the Load side of a multi-location installation.
Wiring Diagrams (continued)
Single-Location Switch Installation with Power Booster Single FeedMRF2S-6ND-120withPHPM-PA-DV-WH
Multi-Location Switch Installation with Power Booster Single Feed 2,3
MRF2S-6ND-120withMA-R/MSC-ADandPHPM-PA-DV-WH
Companion Dimmer Dimmer
Brass BlueBlue
Zone In
Black
Silver
Line/Hot
Switched Line/Hot
Line/Hot
Brass
Black
NeutralNeutral
Neutral
Neutral
Ground
Ground
Green
Ground
Green
120 V~60Hz or 277 V~60Hz
120 V~60Hz
Load
Dimmer
Brass Blue 1
Zone In
Black
Silver
Line/Hot
Switched Line/Hot
Line/Hot
NeutralNeutral
Neutral
Neutral
Ground
Ground
Green
120 V~60Hz or 277 V~60Hz
120 V~60Hz
Load
RF Local Controls
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive Designer-style: Maestro
369904h 16 08.27.18
Colors and Finishes
Gloss Finishes Satin Finishes
Metal Finish (wallplate only)
Stainless Steel SS
Taupe TP
Turquoise TQ
Plum PL
Merlot MR
Terracotta TC
Sienna SI
Midnight MN
Hot HT
Desert Stone DS
Eggshell ES
Biscuit BI
Snow SW
Palladium PD
Greenbriar GB
Bluestone BG
Mocha Stone MS
Goldstone GS
Stone ST
Limestone LS
White WH
Ivory IV
Almond AL
LightAlmond LA
Gray GR
Brown BR
Black BL
• Duetoprintinglimitations,colorsand finishes shown cannot be guaranteed to perfectly match actual product colors.
• Colorchipkeychainsareavailableformoreprecisecolormatching: GlossFinishes:DG-CK-1 SatinFinishes:SC-CK-1
When using Stainless Steel wallplates, it is recommended that you order the dimmer/switchinMidnight(MN).
)Lutron, Lutron, Maestro, Maestro Wireless, Clear Connect, Pico, Claro, Vive, and Satin Colors aretrademarksofLutronElectronicsCo.,Inc.,registeredintheU.S.andothercountries.
FASS,Hi-Power2•4•6,andRadioPowrSavraretrademarksofLutronElectronicsCo.,Inc.