LIGHTNING PROTECTION SYSTEM STUDY USING EARTH ELECTRODES AND
ENHANCEMENT MATERIALS
ByBuba, Sani Dahiru
GS25573Master of Science
Supervisors: Dr. Wan Fatinhamamah Wan Ahmad, Chair
Dr. Jasronita Jasni, Member Prof. Madya Dr. W. N. Wan Daud,
Member
![Page 2: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/2.jpg)
Presentation outline
Introduction Problem statement Objectives Methodology
Literature review
Installation of earthing systems/earth resistance measurements
Results and Findings
![Page 3: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/3.jpg)
Introduction
What is Earthing ?
‘The provision of permanent and continuous conductive
path to the ground having sufficient capacity to carry any
fault current liable to be imposed upon it, with sufficiently
low impedance to limit voltage rise above ground
potential, and be able to facilitate the operation of
protective devices’ Hinde (2009).
![Page 4: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/4.jpg)
Introduction contd.
Commonly used earthing structures includes single
horizontal wire, vertical rods, ring conductors,
multiple conductors forming triangular or
rectangular shapes and earthing grids, Liu (2004).
![Page 5: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/5.jpg)
Introduction continued
What is the purpose of earthing systems?
at power/low frequency is basically to provide a safe path/return for dissipation of stray/faults currents.
for transient/lightning protection is to dissipate transient charges, static charges, electromagnetic interference (EMI), and radio frequency interference (RFI).
for signal/high frequency systems, is to provide zero signal reference.
![Page 6: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/6.jpg)
Introduction contd.
Other purposes for which earthing is provided include;
to ensure safety of general public and personnel
against contact with energized circuits or systems.
protection of equipments against damage by
overvoltages
to provide safe and correct operation of power system both under normal, earth fault and transient conditions.
![Page 7: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/7.jpg)
Introduction contd.
Types of earthing
functional earthing system, specific to sensitive
electronic equipment and data networks, safety is
not a major concern
system earthing, neutral point of a transformer
![Page 8: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/8.jpg)
Introduction contd.
equipment earthing, connection of metallic
parts to earth
protective earthing refers to bonding of all
exposed metallic and extraneous conductive
parts
![Page 9: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/9.jpg)
Problem statement
The earth resistance of an electrode system consists of,
Resistance of the earth electrode
Contact resistance between the electrode and soil
Resistance of the soil surrounding the earth electrode
The first two resistances are negligible for most practical
purposes, IEEE Std 142-2007.
![Page 10: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/10.jpg)
Problem statement contd.
Resistance of the soil is therefore dependent on the soil resistivity.
Soil resistivity ρ varies with depth from the surface, type of soil,
concentration and type of soluble salts (chemicals) in the soil, moisture
content and soil temperature. In other words, the resistivity is that of
the electrolyte in the soil’, IEEE Std 142-2007.
![Page 11: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/11.jpg)
Objectives
Determine soil properties relevant to earthing systems
Install earthing systems using chemical
enhancement materials (CEM) and natural
enhancement materials (NEM).
Determine the best performed enhancement
material and earthing installation.
![Page 12: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/12.jpg)
Methodology
Selection of experiment sites Soil tests
Physical analysis Chemical analysis
Installation of soil parameter data loggers
Installation of earthing system using CEM and NEM
Earth resistance measurements
![Page 13: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/13.jpg)
Selection of experiment site
Site 1 Near Canteen Site 2 near guard house
![Page 14: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/14.jpg)
Results of soil tests
Results for Site 1 Results for Site 2
![Page 15: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/15.jpg)
Selection of site contd.
• BS7430-1998, recommends that where there is an option, the following types of soil should be chosen ,
wet marshy ground Clay, loamy soil etc.
![Page 16: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/16.jpg)
Literature Review
Chemical enhancement materials (CEM)
Soil resistivity may be reduced anywhere from
15% to 90% by chemical treatment of the soil,
(IEEE Std 142-2007).
Uman (2008), suggested that the resistivity of
soil can be reduced by adding chemicals to the
soil surrounding a grounding electrode.
![Page 17: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/17.jpg)
Literature review contd.
Brieals (1991), recommended the use of
common salting materials such as sodium
chloride (NaCl), magnesium chloride (MgCl2),
calcium chloride (CaCl2 ) and copper sulphate
(CuSO4 ) for soil enhancement purposes.
Wan Ahmad (2010), used NaCl, NH4Cl, CuSO4,
Na2S2O3, and MgCl2 around a circular trench.
![Page 18: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/18.jpg)
Literature review contd.
Natural enhancement materials (NEM)/backfill
BS7430-1998, Recommends replacement of soil
immediately around an electrode with a lower
resistivity material to improve earth electrode
contact resistance may be used in special or
difficult locations.
![Page 19: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/19.jpg)
Literature review contd.
Gomes et al. (2010), industrial wastes, bentonite and NaCl
Kumarasinghe (2008), paddy dust, coir peat, bentonite
Eduful et al. (2009), palm kernel fibre
![Page 20: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/20.jpg)
Reference diagram for CEM installation, (Megger manual)
CEM
![Page 21: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/21.jpg)
Cross section of circular trench and dimensions
![Page 22: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/22.jpg)
Installation of earthing systems contd.
CEM
Measure intervals and mark electrode positions
Drive earth electrode into the soil
Dig circular trench
Pour/place CEM inside circular trench
Backfill the trench with soil
![Page 23: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/23.jpg)
Grass clearing for installation of earthing system
![Page 24: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/24.jpg)
Earth electrode being driven into the soil
![Page 25: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/25.jpg)
circular trench marked out
![Page 26: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/26.jpg)
Completed circular trench
![Page 27: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/27.jpg)
Installation of earthing system contd.
‘Fourty to ninety pounds of chemical will initially be
required to maintain effectiveness of earthing system for
two to three years’, MIL STD HBK-419A, Vol. 1(1987).
1 pound = 0.453kg
40 pounds = 18.12kg assumed to be effective for 2 years
Experiment was designed for one year, the quantity of
CEM used was 18.12/2 = 9.06 kg rounded to 10kg.
![Page 28: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/28.jpg)
Typical CEM placed in circular trench
CEM
![Page 29: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/29.jpg)
A typical circular trench backfilled with soil
Earth electrode
![Page 30: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/30.jpg)
Typical PVC earth chamber placed on earthing installation
![Page 31: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/31.jpg)
Installation of earthing system using NEM
NEM
Bore/drill hole
Fill the hole with NEM and compress
Drive earth electrode at the middle
Cover the top with soil
![Page 32: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/32.jpg)
Cross section of earthing installation using NEM as infill, Chen (2009).
![Page 33: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/33.jpg)
Drilling hole for installation of earthing system using NEM
Hole drilling equipment
Water pump
![Page 34: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/34.jpg)
Earth resistance measurements
Earth resistance measurement was conducted using 3-point fall of potential method (Wenner method).
Earth Tester Megger DET3TC
Potential and current probe positions were fixed using rule of 62%
Measurements were conducted for different angles between current and voltage probes initially.
![Page 35: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/35.jpg)
Earth resistance measurements contd.
Zero degrees between potential and current
probes was chosen for simplicity and popularity.
Additional data recorded during measurements
includes, ambient temperature, ambient
weather, soil condition and humidity.
![Page 36: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/36.jpg)
Table 1 Results and Findings for CEM installations
![Page 37: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/37.jpg)
Results for CEM contd.
Link to tables of percentage reduction of earth resistance for CEM
![Page 38: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/38.jpg)
Table 2 Results and Findings for NEM installations
![Page 39: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/39.jpg)
Results for NEM contd.
Link to tables of percentage reduction of earth resistance for NEM
![Page 40: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/40.jpg)
Table 3 comparison between CEM and NEM
![Page 41: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/41.jpg)
Table 4 soil condition before and after experiment
![Page 42: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/42.jpg)
Comparison contd.
Environmental condition after 365 days
![Page 43: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/43.jpg)
Contributions of the study
The results from this study has revealed that, soil
treatment with suitable CEMs can significantly
reduce earth resistance.
Performance of CEM for reduction of earth
resistance was reported in terms of actual earth
resistance and percentage values.
![Page 44: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/44.jpg)
Contributions contd.
10kg of CEM is effective for one year in clay
loam type of soil.
Soil treatment with CEMs raises the pH from
acidic to alkaline which is good for plant growth.
Soil treatment with CEMs slightly changes the
soil texture from clay loam to sandy clay loam.
![Page 45: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/45.jpg)
Contributions contd.
Electrode encasement/enhancement using
biodegradable materials are effective for short
periods only.
Suitable maintenance period was recommended.
Performance of CEMs in clay loam type of soil
was reported.
![Page 46: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/46.jpg)
Conclusion
It is concluded from the study that;
In terms of earth resistance readings,
comparison between different earthing
installations in the CEM category indicated that
CaCl2 is the best performed CEM.
In terms of percentage reduction of earth
resistance, NaCl is the best performed CEM.
![Page 47: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/47.jpg)
Conclusion contd.
In NEMs category, comparison between different
earthing installations in terms of earth resistance
readings, and percentage reduction of earth
resistance indicated that bentonite installation is
the best performed.
![Page 48: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/48.jpg)
Conclusion contd.
When the performances of CEM and NEM
installations are compared, it was found that CEM
installations performed better than NEM
installations both in terms of earth resistance
readings and percentage reduction of earth
resistance.
![Page 49: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/49.jpg)
Conclusion contd.
Therefore CEMs such as CaCl2, NaCl, MgCl2, and
Na2S2O3 are considered effective in reduction of
earth resistance in clay loam type of soil.
Similarly, NEMs such as bentonite and palm
kernel fibre are also considered an effective
backfill materials for reduction of earth
resistance.
![Page 50: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/50.jpg)
Table 5 List of Publications
![Page 51: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/51.jpg)
THANK YOU
![Page 52: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/52.jpg)
Graphs
Soil parameter graphs
Different angles of measurement
![Page 53: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/53.jpg)
References
[1] Hinde, S., Overhead Line Guidelines, British Columbia Safety Authority Information Bulletin No: B- E30903121, 12th March, 2009.
[2] Liu, Y., Transient Response of Grounding Systems Caused by Lightning: Modelling and Experiments, PhD Dissertation from the Faculty of Science and Technology, University Uppsala, Sweden, November, 2004.
[3] IEEE STD 142TM: 2007, Recommended Practice for
Grounding of Industrial and Commercial Power Systems, Pp169.
![Page 54: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/54.jpg)
References contd.
[4] British Standard BS7430-1998, Code of Practice for Earthing.
[5] Uman, M. A., the Art and Science of Lightning Protection, Cambridge University Press, New York, 2008, Pp. 85.
[6] Briels, G., Chapter 4 of Electrical Hazards and Accidents, Van Nostrand Reinhold, New York, 1991, Pp. 72-73.
![Page 55: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/55.jpg)
References contd.
[7] Wan Ahmad, W. F., Abdul Rahman M. S., Jasni, J., Ab Kadir, M. Z., A., and Hizam, H., Chemical Enhancement Materials for Grounding Purposes, Presented at the 30thInternational Conference on Lightning Protection, ICLP 2010, Cagliari, Sardinia, Italy, 13-17 Sept.2010.
[8] Gomes, C., Lalitha, C., and Priyadarshanee, C., “Improvement of Earthing Systems with Backfill
Materials,” presented at the 30th International Conference on Lightning Protection, ICLP 2010, Cagliari, Sardinia, Italy, 2010.
![Page 56: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/56.jpg)
References contd.
[9] Kumarasinghe, N., “A Low Cost Lightning Protection System and its Effectiveness,” presented at the 20th International Lightning Detection Conference and 2nd International Lightning Meteorology Conference,
Tucson, Arizona, U. S. A, 2008.
[10] Eduful, G., and Cole, J. E., “Palm Kernel Oil Cake as an Alternative to Earth Resistance Reducing Agent,” presented at the Power Systems Conference and Exposition, Seattle, WA, 2009, p.2
![Page 57: VIVA VOCE SLIDES.ppt](https://reader038.vdocuments.site/reader038/viewer/2022102423/55cf9b43550346d033a55dba/html5/thumbnails/57.jpg)
References contd.
[11] A Practical Guide to Earth Resistance Testing, www.megger.com/det
[12] Grounding, Bonding, and Shielding for Electronic Equipment and Facilities, Military Handbook,
MIL- HDBK-419A, Vol. 1, December 1987, Ch2. Pp 63.
[13] Chen, L. H., Chen, J. F., and Wang, W. I., “Research on Used Quantity of Ground Resistance Reduction Agent for Ground Systems,” European Transactions on Electrical Power, Online, Wiley Inter Science, 2009.