  • We do more with electricity

    Earth fault relays withseparate toroids

    Vigirex Merlin GerinCatalogue

  • 3earth fault relayswith separate toroids

    Vigirexpage

    1/ presentation 22/ functions and 5characteristics

    3/ installation 13and connection

    4/ complementary 17technical information

    5/ catalogue numbers 23

  • 4 Merlin Gerin

    operation and useOperationVigirex relays are designed for use on lowvoltage AC installations. When the residualcurrent detected by the toroid exceeds acertain threshold, referred to as the residualoperating current In, the Vigirex relay tripsthe associated circuit breaker via a voltagerelease on the breaker.The control signal issued by the relay maybe instantaneous or delayed.Depending on the model, the operatingthresholds and time delays may or may notbe adjustable.UseVigirex relays are used on low voltage ACinstallations with TT, IT or TNS systemearthing arrangements for voltages up to1000 V AC and frequencies up to 400 Hz.They are particularly well suited for use withCompact and Masterpact circuit breakersequipped with voltage releases.

    The choice of the right Vigirex relay model fora given application depends on the type ofprotection required:c additional protection against direct contact;c protection against indirect contact;c protection against fire hazards;c source ground fault protection;c motor protection.These five types of protection are covered bystandards and correspond to different currentthresholds and time delays on the products.

    Vigirex: presentationearth fault relays with separate toroids

    E263

    50 321NPE

    Vigirex

    Vigirex:earth fault protectionThe purpose of earth fault protection is tomeasure the earth leakage current of anelectrical installation, or part of aninstallation, and interrupt the supply of powerif this current becomes dangerous to life orproperty.Vigirex is a range of earth fault relays withseparate toroids, a solution offering bothflexibility and performance.

    functionsDiscrimination and settingsc discriminationDiscrimination consists in:v dividing the installation into a number ofgroups of circuits and protecting each groupwith an appropriate residual current device,v coordinating the upstream and downstreamdevices such that only the faulty section isshut down.c settingsDiscrimination is said to be total if theprotection devices meet two conditions:v the non-operating current of the upstreamdevice is higher than the operating current ofthe downstream device,v the non-operating time of the upstreamdevice is longer than the operating time of thedownstream device.Vigirex relays can be set to obtain up to eightlevels of discrimination, extending from thefinal outgoers up to the circuit breaker at thehead of installation.In/2 alarm thresholdVigirex type AP relays have an alarmthreshold that warns of a non-criticaldegradation of the insulation, leaving time tocarry out preventive maintenance.The alarm threshold is set automatically atIn/2, where I/n is the residual operatingcurrent.The alarm is indicated by a LED and operatesan auxiliary contact.

    Auxiliary power alarmLoss of the auxiliary power supplying Vigirexrelays is indicated by a LED on the front ofthe device and by the operation of a fail-safealarm contact.Indication and protectionVigirex relays are available in two versions:c without earth fault memory: indication only.Non-latching relay;c with earth fault memory: indication andcircuit breaker tripping. Latching relay.

    standardsc IEC 364 ch 4 and 5;c IEC 755;c IEC 947.2 appendix B;c UTE C 60-130;c VDE 664;c NF C 61-141 ad. 1;c NF C 15-100.

    toroidsVigirex relays are used with closed (type A,diameter 30 to 300 mm) or split (type OA,diameter 46 to 110 mm) toroids. All toroidsare easy to mount due to a wide range ofinstallation possibilities.

    E264

    08

    HV/LV

    ID n = 300 mAt = 250 msRH ...

    ID n = 100 mAt = 90 msRH ...

    ID n = 30 mAt = 0 sRH ...

    RH ... ID n = 1At = 500 ms

    0425

    87

  • Merlin Gerin 5

    MERLIN GERIN

    RH328A

    test

    reset

    on

    1 2 3 4 5 6

    7 8 9 10 11 12 13 14

    vigirex

    screw terminals

    In/2 alarm

    auxiliary power

    fault

    test

    reset

    In setting

    sealable cover

    time delays

    screw terminals

    RH328APEarth fault relay32 residual operating current settings In8 time delaysauxiliary power alarmIn/2 alarm

    main characteristics of atype AP relayc d immunity to nuisance tripping;c k class A direct component withstand;c continuous monitoring of the detectioncircuit;c operation under all unbalanced phaseconditions;c status indications:v red LED: fault,v orange LED: alarm threshold exceeded(warning),v green LED: auxiliary power on;c discrimination over several levels so thatonly the faulty circuit is shut down;c fault alarm with or without fail-safe feature;c In/2 alarm;c modular case, eight 9 mm modules wide;c horizontal or vertical flush or surfacemounting on a symmetrical rail;c automatic or remote reset.

    application examples

    model codes

    E281

    76

    protection against fire hazardse.g.: In = 300 mA 90 ms time delay

    E281

    77

    protection of property (motors, etc.)e.g.: In = 3 A 250 ms time delay

    E281

    75

    protection of persons*e.g.: In = 30 mA instantaneous

    RH328AP

    *depending on the opening time of the circuit breaker orassociated contactor.

    E304

    66

  • Merlin Gerin6

  • 7earth fault relayswith separate toroids

    Vigirex

    2/ functions andcharacteristics

    page

    relay selection 6RH type E relays 8RH type A/AP relays 10toroids 12

  • 8 Merlin Gerin

    Vigirex: functions and characteristicsrelay selection

    type E relays

    E187

    10

    MERLIN GERINvigirexRH240E

    test reset

    1 2 3 4 5 6 7

    8 9 10 11 12 13 14

    MERLIN GERINvigirexRH240E

    test reset

    1 2 3 4 5 6 7

    8 9 10 11 12 13 14

    MERLIN GERINvigirexRH248E

    test reset

    1 2 3 4 5 6 7

    8 9 10 11 12 13 14

    E187

    12

    E187

    20

    E187

    11

    MERLIN GERINvigirexRH328A

    test

    reset

    on

    1 2 3 4 5 6

    7 8 9 10 11 12 13 14

    MERLIN GERINvigirexRH320A

    test

    reset

    on

    1 2 3 4 5 6

    7 8 9 10 11 12 13 14

    E187

    16

    E187

    21E1

    8721

    E187

    17

    E187

    21

    E187

    18

    MERLIN GERINvigirexRH10A

    test

    reset

    on

    1 2 3 4 5 6

    7 8 9 10 11 12 13 14

    E187

    20E1

    8720

    protection installation residual time delay relay associatedoperating toroidscurrent

    protection against LV 0.03 or 0 s RH10E type Edirect and indirect 0.3 Acontact+ fire

    protection against LV 0.03 to 0 s RH240E type Edirect and indirect 25 Acontact+ fire

    protection against LV 0.03 to 0 to 1 s RH248E type Edirect and indirect 25 Acontact+ fire+ motor

    type A relaysprotection installation residual time delay relay associated

    operating toroidscurrent

    protection against LV 0.03 or 0 s RH10A type A, OAdirect and indirect 0.3 Acontact+ fire

    protection against LV 0.03 to 0 s RH320A type A, OAdirect and indirect 250 Acontact+ fire+ earthconductor

    protection against LV 0.03 to 0 to 1 s RH328A type A, OAdirect and indirect 250 Acontact+ fire+ motor+ earthconductor

  • 9Merlin Gerin

    type AP relays

    MERLIN GERINvigirexRH320AP

    test

    reset

    on

    1 2 3 4 5 6

    7 8 9 10 11 12 13 14

    E187

    14

    MERLIN GERINvigirexRH320AP

    test

    reset

    on

    1 2 3 4 5 6

    7 8 9 10 11 12 13 14

    E187

    14

    E187

    21E1

    8721

    E187

    21

    MERLIN GERINvigirexRH10AP

    test

    reset

    on

    1 2 3 4 5 6

    7 8 9 10 11 12 13 14

    E187

    13

    protection installation residual time delay relay associatedoperating toroidscurrent

    protection against LV 0.3 or 0 s RH10AP type A, OAindirect contact 1 A+ fire +

    In/2 alarm

    protection against LV 0.03 to 0 s RH320AP type A, OAdirect and indirect 250 Acontact ++ fire In/2 alarm+ earthconductor

    protection against LV 0.03 to 0 to 1 s RH320AP type A, OAdirect and indirect 250 Acontact ++ fire In/2 alarm+ motor+ earthconductor

  • Merlin Gerin10

    Vigirex: functions and characteristicsRH type E relays

    operationUsed in conjunction with a standardMerlin Gerin toroid (type E), this type ofrelay trips the associated switching devicewhen it detects a residual current above theset residual operating current (In).Depending on the model, tripping is eitherinstantaneous or delayed (RH248E).Characteristicsc red LED indicates the trip threshold hasbeen exceeded;c failure of the detection circuit (connectingcable and toroid) trips the circuit breaker.Advantages of the RH248Ec protection can be adapted to anyinstallation;c vertical discrimination possible over anumber of levels.

    installationc live part in a disconnectable, insulatingmoulded case, eight 9 mm modules wide,with sealable transparent cover;c horizontal or vertical mounting on asymmetrical rail;c connection by tunnel terminals for 2.5mm2 wire sizes.

    (1) Type T2 tropicalisation:c damp heat: 55 C, 95 % relative humidity,28 cycles (as per IEC 68-2-30) ;c salt spray: 5 % NaCl, 48 hours3 months' storage (as per IEC 68-2-11).(2) Maximum lengths: see table, page 16.

    Vigirex relaystype of installation to be monitoredelectrical characteristicsIn residual operating number of settingscurrent

    selector

    time delay (ms)device tests local

    automaticresetlocal indicationoutput contact number

    contact typerating 220/240 V AC p.f. = 0.7

    220 V DC L/R = 0 s120 V DC L/R = 0 s48 V DC L/R = 0 s24 V DC L/R = 0 s

    max. consumption 48-240 V AC and 48-300 V DC380-480 V AC

    auxiliary power supply ACoperating range DCmechanical characteristicsweight (kg)thermoplastic case disconnectable mountingdegree of protection front panel

    case

    other characteristicstemperature range operating(as per IEC 755) storageenvironmental conditions tropicalisationtoroidstoroids to be usedtoroid-relay connection

  • 11Merlin Gerin

    multipliercoefficient

    RH10E RH240E RH248E LV AC - 50/60/400 Hz - type TT IT TNS

    1: 30 mA (with toroids TE30 and PE50 only) 24: 30 mA to 25 A, set by 2 selectorsor 300 mA (30 mA to 250 mA: with toroids TE30 and PE50 only, 300 mA to 25 A: all toroids diameters)0 selector 1 : 30, 50, 75, 100, 125, 150, 200, 250

    selector 2 : x 1: 30 to 250 mA (with toroids TE30 and PE50) x 10: 300 mA to 2.5 A x 100: 3 A to 25 A

    0 0 0, 50, 90, 140, 250, 350, 500, 1000electronic + indicator light + contactdetection circuitlocal, and remote by disconnection of the auxiliary supplyinsulation fault or detection circuit failure by latched indicator light1 1 1changeover, latched5 A 5 A 5 A0.45 A 0.45 A 0.45 A0.65 A 0.65 A 0.65 A2.5 A 2.5 A 2.5 A10 A 10 A 10 A4 VA 4 VA 4 VA5 VA/3 W 5 VA/3 W 5 VA/3 W 15 % / + 10 % 15 % / + 10 % 15 % / + 10 % 20 % 20 % 20 %

    0.3 kg 0.3 kg 0.3 kghorizontal and vertical horizontal and vertical horizontal and verticalIP 30 IP 30 IP 30IP 20 IP 20 IP 20

    5 C to + 55 C 5 C to + 55 C 5 C to + 55 C 40 C to + 70 C 40 C to + 70 C 40 C to + 70 Ctype T2 (1) type T2 (1) type T2 (1)

    type E type E type Eby shielded wire(2) by shielded wire(2) by shielded wire(2)

    0420

    52

    0420

    53

    0420

    54

  • Merlin Gerin12

    Vigirex: functions and characteristicsRH type A/AP relays

    operationUsed in conjunction with a standardMerlin Gerin toroid (type A or OA), this typeof relay trips the associated switchingdevice, after the selected time delay, when itdetects a residual current above the setresidual operating current (In). The APversion also issues an alarm when theresidual current exceeds half the residualoperating current (i.e. In/2).Characteristicsc green LED indicates presence of auxiliarypower;c red LED indicates the trip threshold hasbeen exceeded;c orange LED indicates the alarm thresholdhas been exceeded (AP);c failure of the detection circuit (connectingcable and toroid) trips the circuit breaker.Advantagesc protection can be adapted to anyinstallation;c vertical discrimination possible over anumber of levels;c an alarm threshold provides a warning ofa non-critical degradation of the insulation,leaving time to carry out preventivemaintenance;c auxiliary power alarm via fail-safe contact.

    installationc live part in a disconnectable, insulatingmoulded case, eight 9 mm modules wide,with sealable transparent cover;c horizontal or vertical flush or surfacemounting on a symmetrical rail;c connection by tunnel terminals for wiresizes:v 1.5 mm2 for terminals 1 to 6;v 2.5 mm2 for terminals 7 to 14.

    (1) Type T2 tropicalisation:c damp heat: 55 C, 95 % relative humidity,28 cycles (as per IEC 68-2-30) ;c salt spray: 5 % NaCl, 48 hours3 months' storage (as per IEC 68-2-11).(2) Maximum lengths: see table, page 16.

    Vigirex relaystype of installation to be monitoredelectrical characteristicsIn residual operating number of settingscurrent selector

    time delay (ms)alarm (warning) threshold

    time delaydevice tests local

    automaticresetlocal indication insulation fault or detection circuit failure indicator light

    alarm

    output contacts fault numbercontacts

    contact type changeover

    alarm numbercontact contact type changeoverrating 380/415 V AC p.f. = 0.7

    220/240 V AC p.f. = 0.7220 V DC L/R = 0 s120 V DC L/R = 0 s48 V DC L/R = 0 s24 V DC L/R = 0 s

    max. consumption 48 to 240 V CA and 48 to 300 V DC380 to 480 V CA

    auxiliary power supply ACoperating range DCmechanical characteristicsweight (kg)thermoplastic case disconnectable mountingdegree of protection front panel

    case

    other characteristicstemperature range operating(as per IEC 755) storageenvironmental conditions tropicalisationtoroidstoroids to be usedtoroid-relay connection

  • 13Merlin Gerin

    0443

    22

    0425

    83

    multipliercoefficient

    RH10A RH10AP RH320A RH320AP RH328A RH328APfrequency - 50/60/400 Hz - type TT, IT, TNS

    1 : 30 mA or 300 mA 300 mA or 1 A 32 : 30 mA to 250 A, set by 2 selectors- - selector 1 : 30, 50, 75, 100, 125, 150, 200, 250 mA

    selector 2 : x 1 : 30 to 250 mA x 10 : 300 mA to 2.5 A

    x 100 : 3 A to 25 A x 1000 : 30 A to 250 A

    0 0 0, 50, 90, 140, 250, 350, 500, 1000.- auto. set to half the - auto. set to half the - auto. set to half the

    residual op. current residual op. current residual op. current- 200 ms - 200 ms - 200 mselectronic + indicator light + contactdetection circuitlocal, and remote by disconnecting the auxiliary power supplyby indicator light by indicator light by indicator light by indicator lightwith latching with latching with latching with latching- by indicator light - by indicator light - by indicator light

    without latching without latching without latching2 : 1 standard + 1 standard 2 : 1 standard + 1 standard 2 : 1 standard + 1 standard1 fail-safe 1 fail-safe 1 fail-safelatched latched latched or

    non-latched0 1 fail-safe 0 1 fail-safe 0 1 fail-safe- non-latched - non-latched - non-latched3 A 3 A 3 A5 A 5 A 5 A0.45 A 0.45 A 0.45 A0.65 A 0.65 A 0.65 A2.5 A 2.5 A 2.5 A10 A 10 A 10 A4 VA - 4 VA - 4 VA -5 VA/3 W 5 VA/3 W 5 VA/3 W 15 %/+ 10 % 15 %/+ 10 % 15 %/+ 10 % 20 % - 20 % - 20 % -

    0.4 kg 0.4 kg 0.4 kghorizontal and vertical horizontal and vertical horizontal and verticalIP 30 IP 30 IP 30IP 20 IP 20 IP 20

    5 C to + 55 C 5 C to + 55 C 5 C to + 55 C 40 C to + 70 C 40 C to + 70 C 40 C to + 70 Ctype T2(1) type T2(1) type T2(1)

    type A, OA type A, OA type A, OAby shielded wire(2) or toroid plugged into relay for TA30 and PA50

    0443

    20

    0425

    85

    0443

    21

    0425

    87

  • Merlin Gerin14

    electrical characteristicstransformation 1/1000 1/1000 1/1000ratiomaximum permissible c c ccurrent:1 kA continuous -2.5 kA/1 s - 30 kA/0.05 smechanical characteristicsweights (kg) 30 0.120 0.120

    50 0.200 0.200 80 0.420 0.510 120 0.590 0.690 200 1.320 1.570 300 2.230 46 1.300 110 3.200

    other characteristicstemperature range storage 40 C to + 70C 40 C to + 70C 40 C to + 70C operating 5 C to + 55 C 5 C to + 55 C 5 C to + 55 Cdegree of protection IP 20 IP 20 IP 20

    Vigirex: functions and characteristicstoroids

    closed toroids, split toroids, closed toroids,type A type OA type Efor: for: for:Vigirex RH10A, RH10AP, H320A, Vigirex RH10A, RH10AP, H320A, Vigirex RH10E, RH240E, RH248ERH320AP, RH328A, RH328AP RH320AP, RH328A, RH328AP

    utilisationc closed toroids for new installations c split toroids for renovations c closed toroids for new installationsand extensions. and extensions. and extensions.

    functionsc detect the leakage current and c detect the leakage current and c detect the leakage current andtransmit a proportional signal to transmit a proportional signal to transmit a proportional signal tothe associated relay. the associated relay. the associated relay.

    installationc enclosed in an insulated c enclosed in an insulated c enclosed in an insulatedcasing; casing; casing;c mounting, 3 possibilities: c mounted on plate or cable. c mounted on plate or cable.v 30-50 for clipping ontoVigirex relay,v 30-50-80 on a symmetrical rail;v any diameter on plate and cables;c connection:v 30-50 plugged directly intoVigirex relay,v 30 to 200 by connectors for0.22 mm2 wires min.;v 300 by 6.35 mm tab connectors.

    dimensionstype A (mm) type OA (mm) type E (mm)TA 30 POA 46 TE30 30 (all settings)PA 50 GOA 110 PE50 50 (all settings)IA 80 IE80 80 (settings u 300 mA)MA 120 ME120 120 (settings u 300 mA)SA 200 SE200 200 (settings u 300 mA)GA 300

    0425

    89

    0425

    96

    0513

    52

  • 15

    earth fault relayswith separate toroids

    Vigirex

    3/ installationand connection

    page

    relays 14toroids 15auxiliaries 16

  • Merlin Gerin16

    Vigirex: installation and connectionrelays

    RH10E-RH240E-RH248E

    MERLIN GERINvigirexRH240E

    test reset

    1 2 3 4 5 6 7

    8 9 10 11 12 13 14

    8 9

    1 2 3 6 7

    ut

    aa

    1 2

    t

    NL1L2L3

    Key:aa: auxiliary power supplyt : type A, AO, or E toroid depending onrelayut:RH10E, RH240E, RH248Eut: used for control of a switching deviceRH10A, RH320A, RH328Aut1, ut2: remote indication or controlof a switching deviceut1: standard changeover contactut2: fail-safe contactRH10AP, RH320AP, RH328APut1: standard changeover contact forcontrol of a switching deviceut2: fail-safe alarm contact

    MERLIN GERINvigirexRH328A

    test

    reset

    on

    1 2 3 4 5 6

    7 8 9 10 11 12 13 14

    RH10A/AP-RH320A/AP-RH328A/AP

    7 8

    5

    ut1aa

    1

    t

    NL1L2L3

    62

    9 10 11 12 13 14

    ut2

    RH10E-RH240E-RH248E RH10A/AP-RH320A/AP-RH328A/APMounted on symmetrical rail IP 20 Flush mounting IP 30 Surface mounting IP 20

    72

    8145

    446065,5

    73

    46

    6573,5

    E187

    10

    E187

    10E1

    8718

    E262

    92

    E262

    90

    E262

    91

    E184

    59E1

    8460

    73,537,5

    45

    7257

    66

    2 4,2 4

    81

    10,5

  • 17Merlin Gerin

    toroidstype A types A and E type Ediam. 30 and 50 diam. 80 to 200 diam. 30 and 50

    B

    LDC

    KF G

    E

    12

    3

    H

    J

    5

    F

    B

    8

    C

    D

    E

    5

    16

    4

    2921

    2 4,5

    type B C D E FTA30 30 31 60 53 82 50PA50 52 45 87 66 108 60

    H G

    E

    B

    D

    12F

    J

    K

    L

    C

    5

    type A type OAdiam. 300 diam. 46 and 110

    HL

    L

    HB

    5

    type H L B CPOA 46 68 148 57 38GOA 110 68 224 76 44

    type H LGA300 299 29 344

    type B C D E F G H J K LTE30 27 60 22 18 75 45 25 18 4 34 28PE50 50 86 22 18 101 61 41 33 5 50 28

    Vigirex

    immunity to lineovercurrentsLine overcurrents due to motor starting ortransformer switching may causeunnecessary tripping of residual currenttype relays.This can be avoided by a few very simpleprecautions with cumulative effects:c place the toroid on a straight section ofcable;c centre the cable in the toroid;c use a toroid with a much larger diameterthan the cable going through it2 x dia (fig.1).For very severe operating conditions, theuse of a mild steel sleeve placed around thecable inside the toroid considerablyincreases immunity.Recommended characteristics:c mild steel foil 0.1 mm thick to be wrappedseveral times around the cable inside thetoroid (minimum thickness 1 mm);c inner diameter of the toroid > 1.4 x outerdiameter of the cable bundle (fig. 2).

    A, OA, E toroidsassociated with the Vigirex

    type B C D E F G H J K LIA80, IE80 80 122 26.5 35 150 80 55 40 126 65 44MA120, ME120 120 164 26.5 35 190 80 55 40 166 65 44SA200, SE200 196 256 29 37 274 120 90 60 255 104 46

    Toroid locationc on all the cables (phases and neutral) of afeeder downstream of the switching deviceassociated with the Vigirex;c for a TT system, if a toroid cannot beinstalled on a transformer output (busbars orcables in parallel): place a toroid on thetransformer neutral-earth path.

    toroid A, OA E E mm 30 to 300 30 and 50 80 to 200relaysRH10E c vRH240E c vRH248E c vRH10A cRH320A cRH328A cRH10AP cRH320AP cRH328AP c

    E242

    91

    E186

    64

    E187

    22

    E121

    10

    E242

    93

    E242

    94

    Vigirex: installation and connectiontoroids

    figure 2figure 1

    Keyv these toroids can only be used with relayshaving In residual operating currentsgreater than 300 mA;c no residual operating current restrictions.

    N 12 3 PE

    E138

    56 A

    E138

    56B

    N 12 3 PE

  • 18 Merlin Gerin

    Vigirex: installation and connectionauxiliaries

    resistance must not exceed 3 ohms;c shielded wires: available with 1 or 2conductors in reels of 20 or 100 m;c cable size 0.22 mm2.

    examples of type A mountingOn Vigirex, diam. 30 or 50 On rail, diam. 30 to 80 On plate, type A or E, diam. 30 to 200

    0425

    90

    0425

    92

    0443

    24

    On cable, diam. 120 to 300

    0443

    23

    0425

    93

    0425

    91

    toroid-relay connection circuitwire size (mm2) max. length (m)0,22 180,75 601 801,5 1252,5 200c the maximum toroid-relays connection

  • 19

    earth fault relayswith separate toroids

    Vigirex

    4/ complementarytechnical information

    page

    implementation of residualcurrent devices 18electrical systems 20useful definitions 21

  • improvement of operating conditions - implementation ofdiscrimination between residual current devices

    20 Merlin Gerin

    Vigirex: complementary technical informationimplementationof residual current devices (RCDs)

    The use of residual current devices isdescribed below according to the type ofelectrical system (TT, TN or IT).Protection of sensitive locations against firehazards must also be considered.For such locations, a residual current devicewith a residual operating current i 300 mAshould be provided at the head of the feederconcerned.

    introduction

    TT systems exposed conductive parts interconnected and connectedto the same earthing electrode1. Condition satisfiedA single device at the head of the installationis sufficient to ensure protection againstelectric shock.Its residual operating current is selectedaccording to the resistance of the earthingsystem.

    2. Condition not satisfiedThis is the case in particular in installationswhere the loads are far apart.It is essential to have:c one RCD per group of interconnectedexposed conductive parts;c one RCD at the head of the installation,unless the head circuit breaker and the maincircuit breakers are in the sameswitchboard or in switchboards located nextto one another (or linked by a class IIconnection).

    Horizontal discriminationThis technique consists of transferring theresidual current protection from the head ofthe installation to the downstream feeders:in this case, power is cut only on the faultyfeeder. It is not possible unless the headcircuit breaker and the main circuit breakersare in the same switchboard or inswitchboards located next to one another (orlinked by a class II connection).

    Vertical discriminationDownstream of the head circuit breaker, themain circuit breakers are provided withRCDs. In this case, power is cut only on thefaulty feeder, subject to compliance with thefollowing rules:InA > 2 x InB,T no A > T brk B,InA and InB are the residual operatingcurrents of RCDs A and B,T no A = non operating time of A,T brk B = total break time of B (including thetime due to the switching device).

    E269

    64E2

    6963

    E269

    62E2

    6961 HV/LV

    RB RA

    RCD

    HV/LV

    RCD

    RB RA2

    RCD

    RA1

    RCD

    HV/LV

    RB RA

    RCDRCD

    RCD

    ARCD

    B

  • earthingpath

    HV/LV

    RB RA

    CIM

    RCD

    Merlin Gerin 21Merlin Gerin 21

    exposed conductive parts interconnected and connectedto the same earthing electrode, itself connected to thesubstation earthing system

    IT systems

    1. Condition not satisfiedc substation earthing system not connectedto exposed conductive parts: place an RCDat the head of the installation;c exposed conductive parts notinterconnected:place an RCD on each group of exposedconductive parts. To be supplemented by anRCD at the head of the installation unlessthe head circuit breaker and the main circuitbreakers are in the same switchboard or inswitchboards located next to one another (orlinked by a class II connection).

    Note: CIM is insulation monitoring device.

    2. Condition satisfiedProtection against electric shock in the eventof a double fault is provided by theovercurrent protection.Residual current devices must be used inthe following cases:c feeder with excessive cable length;c circuit supplying portable equipment (suchas socket outlet circuits);c circuit where there is a risk of theprotective conductor breaking.

    Safety against electric shock is ensured bythe overcurrent protection. Residual currentdevices must be used in the following cases:c feeder with excessive cable length;c circuit supplying portable equipment (suchas socket outlet circuits);c circuit where there is a risk of theprotective conductor breaking.

    TN systems

    E269

    65E2

    6966

    E269

    67

    L1L2L3N

    HV/LV

    PE

    RCD

    TNC system TNS system

    RB

    PE

    HV/LV

    RCD

    RB RA 2

    RCD

    RA 1

    CIM

    RCD

  • 22 Merlin Gerin

    Vigirex: complementary technical informationelectrical systems

    consequences of aninsulation fault

    ReminderAn insulation fault occurs when a liveconductor - phase or neutral - comes incontact with an exposed conductive part(e.g. motor casing).

    ConsequencesThe consequences depend upon the type ofelectrical system (TT, IT or TN) used in theinstallation or part of installation concerned.Such faults create hazards to life and property.

    TT systems An insulation fault between phase and earthcauses a current flow which is limited inpractice only by the earthing resistances Rnand RA. Hazardous voltages exist on theexposed conductive parts. The fault currentis a few amperes.Tripping is essential.In the example opposite, with the followingvalues for RA and Rn.RA = 20 ; Rn = 10 .The fault current is 7.3 (220 V/30 ohms) andthe voltage Ud on the exposed conductiveparts is 147 V.

    The fault current depends on the insulationimpedance (Zct) of the installation in normaloperation.As this impedance is high by its nature, thefault current is relatively low. The same istrue for the voltage on the exposedconductive parts.Tripping is unnecessary.The fault must be reported, located andeliminated.In this example, with Zct = 3500 ohms(case of a 1 km installation).The fault current is 62 mA (220 V/3500 ohms).The touch voltage Uc between the twosimultaneously accessible exposedconductive parts depends on the resistanceRAB of link AB.In an extreme case where RAB = 2 ohms,Uc = 2 x 0.062 = 0.124 V.

    IT systems

    TN systems

    E269

    71E2

    6969

    E269

    68

    If a second fault occurs before the first faulthas been cleared, it rapidly becomes a shortcircuit between phases (or between phaseand neutral), with the followingconsequences:c the exposed conductive parts carry a highvoltage;c the fault current is equal to the short-circuitcurrent.Tripping is essential.The initial voltage on the busbar supplyingthe two feeders must be estimated at80 percent of the nominal voltage betweenphases.As the loop impedance is 99 milliohms(neglecting the reactances), the fault currentis equal to 3070 A (380 x 0.8/0.099).The touch voltage Uc is equal to half theinitial voltage, i.e.: 0.8 x 380/2 = 152 V.

    An insulation fault results in a short-circuitbetween phase and neutral.The resulting current flow is high. Theexposed conductive parts are at ahazardous voltage.Tripping is essential.The initial voltage on the faulty feeder mustbe estimated at 80 percent of the nominalvoltage between phase and neutral. Thetouch voltage Uc is equal to half 0.8 x 220 V,i.e. 88 V.

    E269

    70

    L1L2L3N

    HV/380V

    UdRn : 10W RA : 20W

    L1L2L3PE

    HV/380V

    Rn

    A

    Zct

    Uc

    B

    Id

    L1L2L3PE

    HV/380V

    Rn

    Zct

    Uc

    50 m50 mm2

    Ra

    30 m25 mm2

    Id

    L1L2L3PEN

    HV/380V

    RnA Uc

  • Merlin Gerin 23

    Vigirex: complementary technical informationuseful definitions

    The definitions below are intended forpractical purposes only and do not claim tobe exhaustive or theoretical.

    Protective conductor PEConductor used for protection againstindirect contact and for interconnectingexposed conductive parts:c to one another;c to extraneous conductive parts;c to earthing electrodes or earthed parts.The presence of switchgear on suchconductors is prohibited.Residual currentRoot-mean-square vector sum of thecurrents flowing through all the liveconductors. It is equal to zero in theabsence of an insulation fault. In case of aninsulation fault, the residual current is theleakage current returned to thesource through the earth and the protectiveconductor.For the value of In, see residual operatingcurrent.Residual current device (RCD)A device that opens the associatedswitchgear when it detects a residual currentabove its residual operating current In (seeresidual current).Residual operating current (In)Value of the residual current which causes aresidual current device to operate.Service voltagePreferred term: rated operating voltage.The rated operating voltage Ue of a systemis the voltage which, together with the ratedcurrent of the system, determines the load.For three-phase systems, it is the voltagebetween phases.Shock protection deviceThis device must automatically separatefrom the source any part of theinstallation on which there is a faulthazardous to life.Depending on the system earthing arrange-ment of the installation, this device is eithera residual current device (characterised byIn, its residual operating current, and itstotal break time) or an overcurrent device(fuse or circuit breaker).break timeTotal time from fault detection to completearc extinction.Time delayIntentional delay before operation of adevice.The time delay on operation of an upstreamcircuit breaker allows time discriminationwith the downstream circuit breaker.The time delay, which is voluntary, shouldnot be confused with the break time of adevice which is intrinsic to the device.

    Touch voltageVoltage in case of an insulation faultacross simultaneously accessible parts.Uc = f(t) safety curveUc = f(t) is the maximum voltage that thehuman body can withstand for a givenperiod of time, depending on externalconditions (nature of the premises, presenceof water, etc. - see NF C 15-100,Sec. 481.1.1, table 48A).

    Direct contactContact of persons with the normally liveparts of electrical equipment.DiscriminationCoordination of the automatic switchingdevices such that only the faulty part of theinstallation is cut off by opening of the devicelocated immediately upstream of the fault.Double insulationinsulation including both:c basic insulation required for protectionagainst direct contact, andc supplementary insulation required forprotection against indirect contact in caseof a fault of the basic insulation.Exposed conductive partAny accessible metal part of an electricalequipment item other than the live parts andwhich can accidentally become live.Fault (electrical)Accidental connection between two points atdifferent potentials, such as aninsulation fault. A fault may be solid or mayexhibit a certain impedance. A solid faultbetween live conductors is a short circuit.A distinction is made between phase-exposed conductive parts, phase-earth,phase-phase, phase-neutral, neutral-exposed conductive parts and neutral-earthfaults.Fault voltageVoltage, in case of an insulation fault,across an exposed conductive part and anearthing reference, i.e. a point on which thevoltage is not modified when the exposedconductive part becomes live.Indirect contactContact of persons with exposed conductiveparts accidentally live due to an insulationfault.Insulation voltagePreferred term: rated insulation voltage. Therated insulation voltage of an assembly isthe voltage characterising it and used asreference for the dielectric tests, the isolatingdistances and the creepage distance.Live conductorConductor used for transmission of electricalpower during normal operation (including theneutral conductor).PEN conductorIn a TNC system, acts both as neutralconductor and as protective conductor(size u 10 mm2).The presence of switchgear on suchconductors is prohibited.

  • Merlin Gerin24

  • 25

    earth fault relayswith separate toroids

    Vigirex

    5/ catalogue numberspage

    earth fault relaysaccessories and toroids

  • Merlin Gerin24

    protection against direct and indirect contact + firenetwork BT 50/60 Hzsensitivity 0.03 or 0.3 Atime delay 0 ssingle phase auxiliary power supply (V) in = 30 mA in = 300 mA48 V AC 50/60 Hz48 to 120 V DC110 to 130 V AC 50/60 Hz220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz

    protection against direct and indirect contact + firenetwork BT 50/60 Hzsensitivity 0.03 to 25 Atime delay 0 ssingle phase auxiliary power supply (V)48 V AC 50/60 Hz48 to 120 V DC110 to 130 V AC 50/60 Hz220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz

    protection against direct and indirect contact + fire + motornetwork BT 50/60 Hzsensitivity 0.03 to 25 Atime delay 0 to 1 ssingle phase auxiliary power supply (V)48 V AC 50/60 Hz48 to 120 V DC110 to 130 V AC 50/60 Hz220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz

    protection against direct and indirect contact + firenetwork BT 50/60/400 Hzsensitivity 0.03 to 0.3 Atime delay 0 ssingle phase auxiliary power supply (V) in = 30 mA in = 300 mA48 V AC 50/60 Hz48 to 120 V DC110 to 130 V AC 50/60 Hz220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz440 to 480 V AC 50/60 Hz

    protection against direct and indirect contact + fire + earth conductornetwork BT 50/60/400 Hzsensitivity 0.03 to 250 Atime delay 0 ssingle phase auxiliary power supply (V)48 V AC 50/60 Hz48 to 120 V DC110 to 130 V AC 50/60 Hz220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz440 to 480 V AC 50/60 Hz

    Vigirex: price listearth leakage relays with separate toroids

    earth leakage relay RH10E

    MERLIN GERINvigirexRH10E

    50622

    1414131312121111101099

    test

    11 22 33 44 55 66 77

    88

    reset

    300mA

    inst.

    MERLIN GERINvigirexRH240E

    50632

    1414131312121111101099

    test

    11 22 33 44 55 66 77

    88

    reset

    30

    50

    75

    100 125

    150

    200

    250x1

    x10 x100

    mA

    MERLIN GERINvigirexRH248E

    50632

    1414131312121111101099

    test

    11 22 33 44 55 66 77

    88

    reset

    inst.

    50

    90

    140 250

    350

    500

    1000

    mS30

    50

    75

    100 125

    150

    200

    250x1

    x10 x100

    mA

    test

    reset

    7 8 9 10 11 12 13 147 8 9 10 11 12 13 14

    11 2 3 4 5 62 3 4 5 6

    on

    MERLIN GERINvigirexRH10A

    50637

    test

    reset

    7 8 9 10 11 12 13 147 8 9 10 11 12 13 14

    11 2 3 4 5 62 3 4 5 6

    on

    MERLIN GERINvigirexRH320A

    50646

    A0,1

    0,030,2

    0,125

    0,250,05

    0,075 0,15

    x1

    x0,1

    x10

    x100

    earth leakage relay RH248E

    earth leakage relay RH10A

    earth leakage relay RH320A

    earth leakage relay RH240E

    50453

    504525045450623

    50456

    504555045750628

    50459

    504585046050633

    50736

    50735507375064150642

    50739

    50738507405064750648

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    50450

    504495045150621

    50733

    50732507345063850639

    .

    .

    .

    .

    .

    .

    .

    .

    .

  • Merlin Gerin 25

    protection against direct and indirect contact + fire + earth conductor + motornetwork BT 50/60/400 Hzsensitivity 0.03 to 250 Atime delay 0 to 1 ssingle phase auxiliary power supply (V) standard standard

    latched relay unlatched relay+ fail safe + fail safelatched relay unlatched relay

    12 V DC24 V DC48 V AC 50/60 Hz48 to 120 V DC110 to 130 V AC 50/60 Hz220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz440 to 480 V AC 50/60 Hz500 to 525 V AC 50/60 Hz

    protection against indirect contact + firenetwork BT 50/60/400 Hzsensitivity 0.3 or 1 A + warningtime delay 0 ssingle phase auxiliary power supply (V) in = 300 mA in = 1 A220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz440 to 480 V AC 50/60 Hz

    protection against direct and indirect contact + fire + earth conductornetwork BT 50/60/400 Hzsensitivity 0.03 to 250 A + warningtime delay 0 ssingle phase auxiliary power supply (V)220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz440 to 480 V AC 50/60 Hz500 to 525 V AC 50/60 Hz

    protection against direct and indirect contact + fire + earth conductor + motornetwork BT 50/60/400 Hzsensitivity 0.03 to 250 A + warningtime delay 0 to 1 ssingle phase auxiliary power supply (V) latched unlatched

    relay relay220 to 240 V AC 50/60 Hz380 to 415 V AC 50/60 Hz440 to 480 V AC 50/60 Hz500 to 525 V AC 50/60 Hz

    protection against direct contact (30 mA)specific for command motor by Telemecanique ATV66 variable speed controllersingle phase auxiliary power supply (V)220 to 240 V AC 50/60 Hz

    unit price (excl. VAT) in French francs

    earth leakage relay RH328A

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    test

    reset

    7 8 9 10 11 12 13 147 8 9 10 11 12 13 14

    11 2 3 4 5 62 3 4 5 6

    on

    140

    inst.500

    250

    1s50

    90 350

    mS

    MERLIN GERINvigirexRH328A

    50652

    A0,1

    0,030,2

    0,125

    0,250,05

    0,075 0,15

    x1

    x0,1

    x10

    x100

    test

    reset

    7 8 9 10 11 12 13 147 8 9 10 11 12 13 14

    11 2 3 4 5 62 3 4 5 6

    on

    MERLIN GERINvigirexRH10AP

    50652

    earth leakage relay RH10AP

    test

    reset

    7 8 9 10 11 12 13 147 8 9 10 11 12 13 14

    11 2 3 4 5 62 3 4 5 6

    on

    MERLIN GERINvigirexRH320AP

    50652

    A0,1

    0,030,2

    0,125

    0,250,05

    0,075 0,15

    x1

    x0,1

    x10

    x100

    earth leakage relay RH320AP

    test

    reset

    7 8 9 10 11 12 13 147 8 9 10 11 12 13 14

    11 2 3 4 5 62 3 4 5 6

    on

    140

    inst.500

    250

    1s50

    90 350

    mS

    MERLIN GERINvigirexRH328AP

    50652

    A0,1

    0,030,2

    0,125

    0,250,05

    0,075 0,15

    x1

    x0,1

    x10

    x100

    earth leakage relay RH328AP

    50746

    5074550747506575065850659

    506665066750668

    50672506735067450675

    50683506845068550686

    50055

    earth leakage relay RH328AF

    test

    reset

    7 8 9 10 11 12 13 147 8 9 10 11 12 13 14

    11 2 3 4 5 62 3 4 5 6

    on

    140

    inst.500

    250

    1s50

    90 350

    mS

    MERLIN GERINvigirexRH328A

    50652

    A0,1

    0,030,2

    0,125

    0,250,05

    0,075 0,15

    x1

    x0,1

    x10

    x100

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    506615066250743

    5074250744506535065450655

    506635066450665

    50679506805068150682

  • Merlin Gerin26

    Vigirex: price listearth leakage relays with separate toroids

    accessories and toroidsunit price (excl. VAT) in french francs

    toroid-relay link

    toroids for RH10A/AP -RH320A/AP - RH328A/AP

    toroids for RH10E -RH240E - RH248E

    5013750136

    504375043850439504405044150442

    5048550486

    5043050431504325043350434

    screened cable (cable size 0.22 mm2)1 conductor 2 conductors

    roll of 20 mroll of 100 m

    closed toroid, type Atype (mm)TA 30PA 50IA 80MA 120SA 200GA 300

    opening toroid, type OAtype (mm)POA 46GOA 110

    closed toroid, type Etype (mm)TE30 30PE50 50IE80 80ME120 120SE200 200

    5015750158

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

    .

  • As standards, specifications and designs change from time to time, please ask for confirmationof the information given iin this publication

    ce document a t imprim sur du papier cologique.

    BTP207E 09-99

    This document has been printed on ecological paper