vigilohm insulation monitoring devices
DESCRIPTION
VIGILOHM insulation monitoring devices. by Patrick HENRY Business Development Manager Energy Management Solutions. Contents. Introduction – What is Vigilohm? Earthing arrangements Applications How does Vigilohm work? The Vigilohm offer Strong points Conclusion. - PowerPoint PPT PresentationTRANSCRIPT
VIGILOHMinsulation monitoring devices
by Patrick HENRYBusiness Development Manager
Energy Management Solutions
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 2
Contents
1. Introduction – What is Vigilohm?
2. Earthing arrangements
3. Applications
4. How does Vigilohm work?
5. The Vigilohm offer
6. Strong points
7. Conclusion
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 3
WHAT IS VIGILOHM?Section 1 - Introduction
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 4
What is Vigilohm?
●Vigilohm is the range of Insulation Monitoring Devices for Schneider Electric.
●Used in IT earthing arrangements, the solution●Guarantees process continuity in case of earth fault,●Improves staff and process safety, and●Optimizes maintenance.
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 5
Vigilohm products and solutions
Manual faultlocation
Automatic faultlocation
Measurement perfeeder
Level 1 Level 3Level 2
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 6
Insulation monitoring device (IMD) functions
●Level 1 : fault detection and signaling, manual fault location (all IMDs)
IM9: for AC networks onlyIM9OL: for off-line motor monitoring (TN, TT or IT networks) IM10, IM20: for AC and DC networksXGR, XRM: fault location is done manually (current probe + mobile
detector)
●Level 2 : automatic fault location
XM200 + XD devices + use of current probe + mobile detector
●Level 3 : feeder measurement + communication
XML / XM300C + XL devices, XD devicesXLI, XTU interfaces
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 7
EARTHING ARRANGEMENTSSection 2
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 8
The letters in earthing arrangements
●1st letter represents the transformer neutral connection to earth T (terre – earth) or I (isolated)
●2nd letter represents the load frame connection:frame connected to earth (T) or neutral (N)
Neutre isoléDe la TerreNeutre isoléDe la Terre
Grounded neutral Ungrounded neutral
Grounded load frame Load frame connected to neutral
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 9
TT earthing arrangements
●The exposed conductive parts of the installation are connected to an earth electrode (Ra) which is electrically separated from the LV substation earth electrode (Rb).
●Protection by RCDsR
B
R
A
PE
L1L2NL3
MV LV
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 10
TN earthing arrangements
●Protection by overcurrent tripping
RP
AB
L1L2
PENL3
TN-C
RPA
B
L1L2NL3PE
TN-S
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 11
IT earthing arrangements
●No protection is needed
R
PAB
L1L2
PE
L3
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 12
Earthing arrangement & applications
●Earthing arrangement choice will depend on the type of application:
●TT: small tertiary and residential networks●TN: industrial networks, large tertiary networks●IT: marine, some specific hospital areas, for industry applications
with a high service continuity need
●All systems are equivalent with regard to people safety
●In large installations, the best system is a combination of earthing arrangements.
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 13
Earth fault consequence
●TN-C / TN-S : CB magnetic tripping
●TT : CB tripping with RCD
●IT : First fault - No effect !!!Second fault - CB magnetic tripping (like TN-C/TN-S)
R1< 10
Ph
NCB
230V
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 14
Case of a second fault in IT system
●A short circuit means breaker trips!
R PAB
L1L2
PE
L3
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 15
Earthing arrangement comparison
TT
IT First Fault
TN-C
TN-S
Observation
Safety of person
+
++
+
+
IT: UC # 0 on the 1st fault
Fire
+
++
--
-
IT: I is very low on the 1st fault
Explosion
+
++
--
-
IT: I is very low on the 1st fault
Availability
+
++
+
+
Further to the first fault
Maintenability
+
++
-
-
Preventive maintenance
Reliability of the installation
++
++
-
+
Small I fault (damage-electrodynamic forces)
Easy implementation
+
-
++
+
Need a permanent insulation module/system Difficult to implement on big networks Some technical difficulties
Cost
+
-
++
+
Need a permanent insulation module/system And a transformer per sub-network
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 16
Indirect contact and insulation fault (TT)
Hypothesis: R1 = R2 = 10 U body: UB = 230 * R2/(R1+R2) = 115 V
I body: Ib = 115V / 1K = 115 mA (high risk over 30mA)
Fault current: 230V / 20 = 11.5A
This current is not high enough to trip the circuit breaker.
This is why RCDs are mandatory in TT; the RCD makes the protection.
R1< 10
Ph
NCB
1 K
230V
R2< 10
R C D30mA / 10mA
R2
Ground
Ph
Defect
N
R1
U0
UB
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 17
Indirect contact & insulation fault (IT)
Hypothesis: R1 = 1 M U body: : Ub = 230 V * R2/(R1+R2)=230*R2/R1 = 2.3 mV I body: Ib= Ub /1 k = 2.3 mV / 1k = 2,3 µAI body increases with R1 decreaseFault current IR1 = 230V / 1M = 0.2 mA
No risk after the first fault: no trip is needed.What happens after a second fault on another phase?
Short circuit so the circuit breaker will open.It is necessary to detect the first fault.
Ph
NCB
1 K
230V
R2< 10
R1< 1 M
R2
Ground
Ph
Defect
N
R1
U0
Ub
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 18
Limits for an IT earthing network1 wire: 10 M / km0.3 µF / km (10.6 K / Km @ 50 Hz)
3 wires * ==> 0.9 µF / Km (* 3 rather than 4 as one capacitance is
in // with the defect)
Uc max = 50V (safety limit)Uc = U0 * RT/Zc
C max to have Uc < or = to 50VCmax = Uc / U0 * RT * 2*pi * fCmax = 1 / U0 * 62.8 (for 50Hz)
Max length according to the voltage Ph - Ph = 760V ==> Ph - N = 760 / 1.732 = 439V => 36 µF0.9 µF / Km ==> limit = 40 Km240V = 66 µF ==> limit = 73 Km (3 phases)
RT
Ground
Ph
Defect
N
Zc
U0
Uc
4 x 10 µF
40 µF
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 19
IT earthing arrangement: Pros & Cons
●Energy availability - Up-time >>●Fire and explosion risks●ED life time●Preventive and corrective maintenance
But●Implementation costs●Network size●Fault localisation
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 20
IT EARTHING APPLICATIONSSection 3
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 21
Typical applications in IT arrangement
Some hospital areas
Ships
Industrial applicationswith continuous or sensitive processes( furnaces, industrial robots…)
AvailabilityFire
Explosion
Airports(runway lighting, traffic supervision)
Nuclear plants
Safety lighting
= mandatory
= prescription / promotion
Oil & Gaz
Off-shore
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 22
Hospital applications
Hospital Anaesthetic room
Hospital Operating theatre
Hospital Operating preparation room
Hospital Operating plaster room
Hospital Operating recovery room
Hospital Heart catheterization room
Hospital Intensive care room
Hospital Angiographic examination room
•Key application driver : patient safety•Product features for this environment
•AC internal impedance > 100 kOhms•Test voltage (=injection voltage) <= 25 Vdc•Injected current <= 1mA, even under fault conditions•50 kOhms threshold
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 23
Marine applications
●All vessel types (both commercial and military) and the whole LV electrical distribution
●5 to 10 devices par vessel●Cruise liners, transport ships – car
ferries, containers, navy vessels
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 24
Industry and infrastructure applications
Oil & Gaz - Extraction & refineries All the process in LV
Cement LV motors
Steel Cold or hot mills
Glass Furnaces. If the furnaces stops, it is dead
Paper Mill
Aluminium Electrolysis vat
Chemical Furnaces. If the furnace stops, it is dead
Mechanics, car makers Yes
Power generation - Nuclear or thermal Auxiliary equipement
Power generation - Solar Solar farm
Food & Beverage Conveyor
Pharmaceutical industry Conveyor
Semi-conductor Various process machines
Key application drivers : energy availability and safety
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 25
HOW DOES VIGILOHM WORK?Section 4
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 26
How does Vigilohm work?
●IT earthing arrangement is used to guarantee supply continuity (energy availability) in an electrical installation
●Requirements of the IT system:
●Continuously monitor the installation insulation by DC injection or AC injection
●Signal the first fault
●Locate faults (manually or automatically)
●The Vigilohm range of IMDs provide a permanent insulation monitoring solution
●Thus helping end users to increase process availability and improving staff and process safety
Protection threshold
Fault threshold
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 27
Operating diagram
●Vigilohm IMDs are connected to neutral or to a network phase
IMD connected to neutral
E95484
L1
L2
L3
IMD V3
V
L1
L2
L3
IMD connected to a phase
E95485
V
V
IMD
When the first fault occurs,the IMD detects the network phase-to-phase voltage Vacross its terminals
When the first fault occurs,the IMD detects the network phase-to-neutral voltage across its terminals
Multiple sources > A single Insulation Monitoring Device
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 28
Current injection
●In IT arrangement, because the fault current is very small, and therefore difficult to measure, the insulation monitoring device (IMD) injects a low frequency or a DC current. This current can go though the IMD because the IMD impedance is high at 50Hz (IT) but low for the injected current (equivalent to a TT).
●The aim is to measure the return current to calculate the system’s impedance.
●This current depends on the leakage impedance of the network to be monitored.
LF generator
Locating insulation faults is done by tracing the path of a low frequency current injected at the origin of the installation.
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 29
What does Vigilohm measure & monitor?
●Insulation resistance●If the resistance value is under the set-point, an alarm is triggered●This resistance value is displayed on some modules●For more advanced modules:
●Insulation resistance and 2 set-points (warning and alarm)●Leakage capacitance
●Resistance and capacitance are good ways to know the status of the system
●Allows preventive maintenance
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 30
Why do we measure the network capacitance?●Monitoring the C value is essential on large networks since the
C-related impedance can cause these networks to drift towards a TT arrangement. This configuration would generate a dangerous voltage contact and a high fault current in case of earth fault.
●Only Schneider Electric monitors these value.
●Thus, during ED design, it will be highly recommended to limit network size (long cables).
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 31
Operating principle: DC Injection
●The capacitance of the network is irrelevant when a DC voltage injection IMD is used to measure the insulation.
●DC voltage injection IMDs can only be used on AC networks
E95476
R network =i Rs
Vi - Rs and i =Vs
R network = RsVs
(Vi - Vs)
Vi
IMD Network
i
Vs
Rs
R network C network
i
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 32
Operating principle: AC Injection
●The resistance and capacitance of the network are displayed by measuring the insulation with an AC voltage injection IMD.
●Synchronous demodulation is used to indicate the real and imaginary parts of Z and therefore to calculate the resistance R and capacitance C of the network.
E95480
Vi
IMD Network
i
R network C network
Z = R network // ,1C network x
network complex impedance
RS
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 33
Different injection methods, different IMDs
●There are two types of permanent insulation monitors that use different injection methods:
●DC current injection IMD
●AC current injection IMD (can be communicating)
IM10 / IM20IM10 / IM20H
XM200 XM300C
IM9 / IM9OL
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 34
Two Types of monitoring
●On-line insulation monitoring●IT system for a part or the
whole installation●IT system for AC or DC
installations
●Off-line insulation monitoring●Load insulation monitoring
MV/LV
CPI
P1
CPI
CPI
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 35
Multiple configuration options
●Network type : AC / DC●Injection type : AC / DC●Injection type : permanent or non permanent
AC DC
AC Yes Yes
DC Yes
Network type
Injection type
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 36
THE VIGILOHM OFFERSection 5
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 37
Vigilohm offer
●Level 1 solution – Manual fault location●Hospital – IM10H, IM20H, HRP ●Marine, Industry & Infrastructures: IM9, IM10, IM20●Industry / off-line monitoring: IM9OL
●Level 2 solution – Automatic fault location●XM200, XD3xx
●Level 3 solution – Feeder measurement & communication●XML3xx, XM300C●XL3xx, XD308C, XLI / XTU communication interface
●Accessories●Toroids●Cardew surge limiter●ZX impedance●HV-IM20-1.7 subassembly●PHT1000 subassembly●Mobile fault location kit
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 38
LEVEL 1 SOLUTIONMANUAL FAULT LOCATION
The Vigilohm Offer
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 39
Vigilohm offer : HospitalsProduct featuresVigilohm IM10-H, IM20-H and HRP help ensure patient safety
IM10-H●Fault detection and signaling●Insulation resistance value display
IM20-H:●Fault detection and signaling●Insulation resistance value display●Transformer monitoring (current and temperature)●Modbus communication●Alarm log
HRP●Insulation fault remote indicator (audible & visual)●Electrical fault (transformer overload or circuit breaker tripping ) remote indicator
(audible & visual)●Insulation daily test
IM10-H / IM20-H
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 40
Vigilohm offer : HospitalsKey technical specifications
IM10-H / IM20-H●Standards: IEC 60364-7-10, IEC 61557-8●Network voltage: up to 230 V ac, 50 or 60 Hz●Insulation resistance value reading: from 1 kOhm to 1
MOhm●Minimal fault threshold: 50 kOhms●Accuracy : 5%●Auxiliary supply: AC or DC (generally the monitored
network)
HRP key technical features:●Tested with Anios products (anti-bacterial cleaning product)●Insulation Monitoring test button●24 Vdc auxiliary supply
HRP:Hospital remote panel
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 41
Vigilohm offer : Marine, Industry, Infra.Product features (Online insulation monitoring)IM9, IM10 and IM20 help ensure process continuity, staff and process safety in IT earthing
network arrangements
IM9●Fault detection and signaling without display (only for monitoring small AC networks)●Pre-alarm threshold
IM10:●Fault detection and signaling with large, intuitive multi-language display●Insulation resistance value display
IM20:●Same as IM10 plus●Leakage capacitance measurement display●Transformer monitoring (current and temperature)●Modbus communication●Alarm log●Current injection inhibition feature●Compatible with higher network nominal voltages with the HV subassembly
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 42
Vigilohm offer : Marine, Industry, Infra.Specific standards for IM9, IM10 and IM20
●IEC 60364-4-41 : Electrical standards in buildings
●IEC 61557-8 : Insulation Monitoring Devices in IT earthing arrangement
●IEC 61557-9 : Equipment for insulation fault location in IT earthing arrangements
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 43
Vigilohm offer : Marine, Industry, Infra. IM9 key technical specifications
●Network voltage
●Up to 480 Vac L-L, 50, 60 or 400 Hz
●Two alarm thresholds
●Pre-alarm: from 2,5 to 500 kOhms
●Alarm: from 1 to 250 kOhms
●1 changeover contact in case of earth fault
●Auxiliary supply:
●110 to 415 Vac (+/- 15%)
●125 to 250 Vdc (+/-15%) IM9
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 44
Vigilohm offer : Marine, Industry, Infra. IM10 / IM20 key technical specifications
●Network voltage: ●Up to 480 Vac L-L, 50, 60 or 400 Hz ●Up to 345 Vdc ●Up to 1700 Vac L-L with subassembly (IM20)
●Range for leakage capacitance readings:●0,1 – 40 µF (IM20) – Impedance display
●2 thresholds●Pre-alarm: from 1 kOhm to 1 Mohms●Alarm: from 0,5 kOhm to 500 kOhms
●1 changeover contact in case of earth fault●Auxiliary supply:
●110 to 415 Vac (+/-15%) / 125 to 250 Vdc (+/-15%)
●Multi-language support for English, French, Spanish, Italian, Portuguese, Chinese, and Russian
●DNV approval for the Marine market
IM10 / IM20
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 45
Vigilohm offer : IndustryIM9-OL Product features (Offline insulation monitoring)
IM9-OL for insulation monitoring of offline motors (i.e., motors that are not normally powered, such smoke extractors)
●Functions
●Insulation monitoring with an adjustable threshold
●Motor start inhibition with a second threshold
●Ability to authorize start, even in case of low insulation
●Fault detection and signaling in all motor earthing arrangements (TN, TT, IT)
●Standards
●Product: IEC 61557-8, Safety : 61010-1
●Features
●Motor nominal voltage : up to 690 V
●Pre-alarm threshold: from 0,5 to 10 Mohms
●Motor inhibition threshold: from 0,25 to 2 Mohms
●Suitable for 1 ph or 3 ph motors, including star/delta start
IM9-OL
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 46
LEVEL 2 SOLUTIONAUTOMATIC FAULT LOCATION
The Vigilohm Offer
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 47
Vigilohm offer - automatic fault location
●Ideal for medium or large networks with a significant number of feeders
●Typical architecture●XM200 IMD that displays global R and C●XD312 / XD301 automatic fault locators
●The customer typically uses a manual fault locating kit for the downstream distribution
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 48
Automatic fault location – strong points
●Global network monitoring (R and C)●Unlimited number of locators●No link between the XM200 (injector)
and XD devices (locators)●Transient fault management on
both XM200 and XD devices●Both XD312 and XD301
locate the fault
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 49
XM200 key technical features
●Network voltage:●up to 760 Vac (injection connected to
neutral)●up to 440 Vac (injection connected to
phase)●up to 500 Vdc●For higher voltages, please use XM300C.
●Range for insulation resistance readings: ●from 0,1 to 999 kOhms
●Range for leakage capacitance readings: ●from 0,1 to 199 µF
●2 thresholds (pre-alarm and alarm) and 2 output contacts
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 50
XD301 / XD312 key technical features
●Immediate identification of the faultyfeeder
●Network type:●low voltage, AC (45 to 400 Hz) or DC
●Operating threshold:●2,5 mA @ 2,5 Hz
●Polling time:●20 s per channel
●1 output contact
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 51
LEVEL 3 SOLUTIONFEEDER MEASUREMENT & COMMUNICATION
The Vigilohm Offer
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 52
Vigilohm offer - measurement per feeder and communication
●Ideal for medium or large network monitoring, especially for control networks with multiple incomers and feeders
●R and C measurement per feeder is prescribed
●The customer wants to monitor insulation from the supervisory system
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 53
Level 3 solution - architecture overview
XM300C XML308 XL308 XD308C
XML316 XL316
XLI300/XTU300
ION Entreprise
Supervision
Modbus /Serial communication
Vigilohm bus
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 54
Level 3 solution – typical architectures
● Typical architecture● XML308 / XML316 IMDs for global network monitoring with feeder
measurement up to 8/16 feeders● XL308 / XL316 automatic fault locators incl. feeder measurement● XLI / XTU communication interfaces
● This architecture suits large network management, up to 192 feeders.
● Additionally there could be a few XD301 or XD312 fault locators in the downstream distribution
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 55
Level 3 solution – strong points
●IT distribution networks●AC, DC, mixed●Non linear loads: rectifiers, static
converters, variable speed drives
●Measurement and monitoring of network insulation
●R and C measurement, globally and on the most critical feeders
●Display and supervision of measurements and setting parameters
XM300C
XML308/316
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 56
Level 3 solution – main technical features
●Injection of low frequency AC voltage between the network and earth
●Measurement of R and C
●2 settings: ●adjustable pre-alarm and alarm thresholds●1 adjustable feeder threshold
●2 output relays●Measurement:
● from 0.1 to 999 k / from 0,1 to 1000 µF
●Network voltage : ●from 440 Vac to 1700 Vac depending on the
selected injection cable and a possible interface from 500 Vdc to 1200 Vdc
U
IcI
Ir
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 57
ACCESSORIESThe Vigilohm Offer
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 58
Toroids for automatic fault detection
●A single range of toroids for XD and XL devices
●Open or split core
● GA 300● SA 200● MA 120● IA 80● PA 50● TA 30
●POA● GOA
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 59
Cardew surge limiter
●Protects the electrical distribution – including the insulation monitor - against overvoltages
●Mandatory with NF C 63-150 (French standard) / not mandatory to comply with IEC 60364 standard.
●To be connected the closest to MV / LV transformer – between neutral and earth or phase and earth.
●Not necessary for LV / LV transformer
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 60
MV/LV
IMD
ZX impedance
●Reduces voltage differences between network and earth
●Impedance value:●1,5 kΩ at 50 Hz●1 MΩ at 2,5 Hz / DC●U < 500 V AC
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 61
HV-IM20-1.7 subassembly
●Makes Vigilohm IM20 IMD compatible with higher network nominal voltages:
●415 Vac < U < 1000 Vac for phase connection
●415 Vac < U < 1700 Vac for neutral connection
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 62
PHT1000 subassembly
●Reduce the input voltage for IMDs like XM300c and XML with the following network voltages
●440 < U < 1000 Vac for phase connection●760 < U < 1700 Vac for neutral connection●500 < U < 1200 Vdc for DC networks
MV/LV
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 63
Mobile fault locating kit
●This equipment can be used on DC or AC networks.
●It includes:●A 2.5 Hz generator: XGR●a 2.5 Hz receiver: XRM ●Three probes: P15 - P50 - P100
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 64
Mobile fault locating kit
●Fault locating principle to be used when the IMD detected a fault:
●Calibrate the receiver●Locate the faulty feeder
IMD or
XGR
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 65
STRONG POINTSSection 6
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 66
Strong points of the Vigilohm offer
Technical features●The new offer re-uses Vigilohm injection principle and improves it●Customer benefits: better accuracy and behavior with non linear loads●Wide range of insulation resistance measurement and display●Possibility of leakage capacitance measurement (IM20)
Implementation●Very easy to install – Din rail or flush mount
Operation●Very intuitive human man interface●Multi-language LCD display
●Supports English, French, Spanish, Italian, German, Portuguese, Russian and Chinese
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 67
CONCLUSIONSection 7
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 68
Conclusion
●Vigilohm range is Schneider Electric’s insulation monitoring solution for ungrounded neutral networks
●For process continuity in case of earth fault●For staff and process safety●For maintenance optimisation
●From single motor insulation monitoring to the most advanced network insulation monitoring