Applications Cookbook Occupancy Sensors

FOR REFERENCE ONLY

Version 3.0

Page 2: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

OCCUPANCY SENSOR COOKBOOK NOTES

1. Refer to manufacturer’s data sheets and installation instructions prior to installation

2. Line feed 120/230/277VAC, 60Hz

3. Ground not shown. Ground devices per applicable national and local codes and best practices

4. For emergency power situations, illustrations assume transfer switch by others upstream of shown devices

5. Line voltage load not to exceed contact rating per device specifications

6. Power packs receiving separate feeds for switched loads and self power must have both feeds on the same phase

7. All low-voltage devices consume current. See product literature for specific current draw

8. Maximum run length for analog wiring is 1000’ feet @ #18 AWG

9. Sensors wired in parallel will cause line voltage relay closure when occupancy is detected by any unit

10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents

11. Trough mounted, pendant mounted, and pendant mounted indirect lighting sources affect the operation of locally mounted sensors. Contractor is responsible for adjusting sensor locations to allow for proper operation

12. Contractor is responsible for proper sensitivity and time delay settings for non-adaptive products, following the manufacturer’s recommended placement, and filed verification of circuits with respect to power pack placement

13. Contractor is responsible for coordinating the operational options of sensors and power packs with the specific work requirements:

-Work relevant energy code requirements affect circuits to be controlled and their control characteristics

-One power pack is required for each controlled circuit

-Refer to power pack data sheet for power output and installation guide for maximum number of sensors connected to a power pack

-If multiple circuits are to be controlled by a sensor, auxiliary relays may be used in conjunction with a power pack

14. Do not exceed relay rating(s) per product specifications

15. Ceiling sensors mounted over doorways should be place one (1) foot inside the threshold

16. Up to 100 Mark VII style ballasts may be controlled per daylighting zone by mini-Z

17. All relays shown in de-energized state

18. Individually cap off unused leads

19. One-line parenthesis use:

(x) - Function

(#) - Terminal

Devices wired in parallel

DRAWING ABBREVIATIONS

DRAWING SYMBOLS

No connection

Connection

LV Low voltage

HV High voltage switch (maintained)

LVM Low voltage switch (momentary) - equal to Leviton 1081 (toggle) or Leviton 56081 (Decora)

LVT Low voltage switch (maintained) - equal to Leviton 12021-2 (toggle) or Leviton 56021-2 (Decora)

LV2 miniZ low voltage switch

Page 3: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

TABLE OF CONTENTSPAGE DESCRIPTION

4 Power Pack with Separate Load and Feed (Sweep Off Load)

5 Two Circuits, One Zone, One Power Pack CAN Power Attached Devices

6 One Circuit, One Zone, Two Power Packs are Required to Power Attached Devices

7 Auto ON/OFF, Manual ON/OFF

8 Manual ON/OFF, Manual ON/OFF (Vacancy Sensor)

9 2-Zone Manual ON/OFF, Auto OFF (Vacancy Sensor)

10 Occupancy Sensing—2 Separate Restrooms with Shared Exhaust Fan

11 Energy Code Compliant Plug Load Control

12 Photocell Only Room Control, Switched, ODC0P-S0W

13 Photocell Only Room Control, 0-10V Dimming, ODC0P-D0W

14 Daylighting, Switched, Manual-ON/OFF, Auto-OFF, ODC0P-S0W

15 Daylighting, 0-10V Dimming, Manual-ON/OFF, Auto-OFF, ODC0P-D0W

16 Daylighting, Switched, Auto-ON/OFF, Manual-ON/OFF, ODC0P-S0W

17 Daylighting, 0-10V Dimming, Auto-ON/OFF, Manual-ON/OFF, ODC0P-D0W

18 Daylighting, Switched, Manual-ON/OFF, Auto-OFF, ODC0P-S0W

19 Daylighting, 0-10V Dimming, Manual-ON/OFF, Auto-OFF, ODC0P-D0W

20 Daylighting, Dimming, 3-Zones, ODC0P-00W

21 Daylighting, Dimming, 2-Room, Single Zone Per Room, ODC0P-00W

22 Daylighting, Dimming 2 Zones Plus 2 Switched Zones, ODC0P-00W

23 Daylighting, 33%, 67%, 100%

24 Low Voltage Wallbox Sensor, Switch with Power Pack

25 Line Voltage and Low Voltage Sensor Control Circuit

26 Multiple Title 24 Plug Load Control Overhead Lighting

27 Plug Load Control/Title 24 and Overhead Lighting of Different Voltage

28 Multiple Title 24 Plug Loads Control Different Voltage Overhead Lighting

29 Daylighting, Fixture Mt Sensor HB011, Individual Auto-ON/OFF, Manual Sweep ON/OFF

30 EZ-MAX Daylighting, Fixture Mt Sensor HBE11, Individual Auto-ON/OFF, Manual/Time Clock Sweep ON/OFF

Page 4: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

POWER PACK WITH SEPARATE LOAD AND FEED (SWEEP OFF LOAD)

Page 5: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

TWO CIRCUITS, ONE ZONE, ONE POWER PACK CAN POWER ATTACHED DEVICES

Page 6: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

ONE CIRCUIT, ONE ZONE, TWO POWER PACKS ARE REQUIRED TO POWER ATTACHED DEVICES

Page 7: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

AUTO ON/OFF, MANUAL ON/OFF

Page 8: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

MANUAL ON/OFF, AUTO OFF (VACANCY SENSOR)

Page 9: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

2-ZONE MANUAL ON/OFF, AUTO OFF (VACANCY SENSOR)

Page 10: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

OCCUPANCY SENSING—2 SEPARATE RESTROOMS WITH SHARED EXHAUST FAN

Page 11: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

ENERGY CODE COMPLIANT PLUG LOAD CONTROL

Page 12: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

PHOTOCELL ONLY ROOM CONTROL, SWITCHED, ODC0P-S0W

Page 13: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

PHOTOCELL ONLY ROOM CONTROL, 0-10V DIMMING, ODC0P-D0W

Page 14: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, SWITCHED, MANUAL-ON/OFF, AUTO-OFF, ODC0P-S0W

Page 15: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, 0-10V DIMMING, MANUAL-ON/OFF, AUTO-OFF, ODC0P-D0W

0

Page 16: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, SWITCHED, AUTO-ON/OFF, MANUAL-ON/OFF, ODC0P-S0W

Page 17: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, 0-10V DIMMING, AUTO-ON/OFF, MANUAL-ON/OFF, ODC0P-D0W

Page 18: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, SWITCHED, MANUAL-ON/OFF, AUTO-OFF, ODC0P-S0W

Page 19: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, 0-10V DIMMING, MANUAL-ON/OFF, AUTO-OFF, ODC0P-D0W

Page 20: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, DIMMING, 3-ZONES, ODC0P-00W

Page 21: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, DIMMING, 2-ROOM, SINGLE ZONE PER ROOM, ODC0P-00W

Page 22: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, DIMMING 2 ZONES PLUS 2 SWITCHED ZONES, ODC0P-00W

Page 23: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, 33%, 67%, 100%

Page 24: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

LOW VOLTAGE WALLBOX SENSOR, SWITCH WITH POWER PACK

Page 25: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

LINE VOLTAGE AND LOW VOLTAGE SENSOR CONTROL CIRCUIT

Page 26: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

MULTIPLE TITLE 24 PLUG LOADS CONTROL OVERHEAD LIGHTING

Page 27: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

PLUG LOAD CONTROL/TITLE 24 AND OVERHEAD LIGHTING OF DIFFERENT VOLTAGE

Page 28: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

MULTIPLE TITLE 24 PLUG LOADS CONTROL DIFFERENT VOLTAGE OVERHEAD LIGHTING

Page 29: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

DAYLIGHTING, FIXTURE MT SENSOR HB011, INDIVIDUAL AUTO-ON/OFF, MANUAL SWEEP ON/OFF

Page 30: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,

EZ-MAX DAYLIGHTING, FIXTURE MT SENSOR HBE11, INDIVIDUAL AUTO-ON/OFF, MANUAL/TIME CLOCK SWEEP ON/OFF

Page 31: Version 3 - Leviton...occupancy is detected by any unit 10. Ultrasonic ceiling mount sensors should be located a minimum of six (6) feet from HVAC supply/return vents 11. Trough mounted,