versatec installation manual - waterfurnace · interior piping all units are recommended to be...
TRANSCRIPT
-
WF
I
IM2601 11/06
Installation Information
Water Piping Connections
Electrical Connections
Microprocessor Control
Startup Procedures
Preventive Maintenance
Ver
sate
c In
stal
latio
n M
anua
l
Water Source/Geothermal Heat Pumps7 thru 10 Ton Horizontal7 thru 23 Ton Vertical
••
-
2
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Model Nomenclature
Model TypeVL = Versatec (Low Temp)VX = Versatec (Ext. Range)
Unit Capacity080 MBTUH095 MBTUH120 MBTUH180 MBTUH240 MBTUH275 MBTUH
Discharge Air ConfigurationT = Top Discharge VerticalE = End Discharge HorizontalS = Side Discharge Horizontal
Return Air ConfigurationL = LeftR= Right
Voltage3 = 208-230/60/34 = 460/60/35 = 575/60/3
Blower Options0 = Standard Blower1 = Oversized Blower Cabinet Options
0 = Painted1 = Nonpainted
Source Coax OptionsC = CopperN = Cupronickel
Sound KitA = NoneB = Blanket
Non-Standard Options Details
VintageC = All
Control Options4 = FX10 (standard - no communication)5 = FX10 w/ Open N2 Com Card6 = FX10 w/ Lonworks Com Card7 = FX10 w/ BacNet Com Card8 = FX10 std. no communication, w/User Interface9 = FX10 w/Open N2 Com Card, w/User Interface0 = FX10 w/Lonworks Com Card, w/User Interface3 = FX10 w/BacNet Com Card, w/User Interface
Non-Standard Options
VL 240 T L 4 0 0 C A 4 S S C
-
3
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Table of Contents
General Installation Information 4
Water Quality 5
General Piping 6
Installing Horizontal Units 7-8
Installing Vertical Units 9
Electrical Connections 10-11
Wiring Schematic 12
FX10 Microprocessor Control & Operation 13-15
Duct System 16
Blower Drive Sheaves 16
Blower Performance Data 17
System Cleaning and Flushing 18
Unit Startup 19
Unit Operating Parameters 20
Water Pressure Drop 21
Preventive Maintenance 22
Replacement Procedures 23
-
4
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Moving and Storage Move units in the normal “Up” orientation as indicated by the labels on the unit packaging. Units may be stacked a maximum of two high and should be unstacked before attempting to move units. When the equipment is received, all items should be carefully checked against the bill of lading to ensure that all crates and cartons have been received in good condi-tion. Examine units for shipping damage, removing unit packaging if necessary to properly inspect unit. Units in question should also be internally inspected. If any damage is observed, the carrier should make the proper notation on delivery receipt acknowledging the damage.
Water Source Temperatures Low temperature units (VL series) should not be installed in applications where entering water temperatures will be consistently below 50°F.
Unit Location Locate the unit in an indoor area that allows for easy removal of the air fi lter, service access panels and has enough space for service personnel to perform maintenance or repair. Provide suffi cient room to make water, electrical and duct connections. If the unit is located in a confi ned space such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Care should be taken when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
If the unit is connected to existing ductwork, the capacity and condition of the duct should be inspected to ensure that the new system will be capable of delivering adequate airfl ow. If any defects or problems are identifi ed during the inspec-tion, repairs should be made to the ductwork prior to the unit’s installation. The duct system should be sized to handle the design airfl ow quietly. To maximize sound attenuation of the unit blower, the supply and return air plenums should be lined with an insulated duct liner or be constructed of ductboard for the fi rst few feet. If air noise or excessive airfl ow is a problem, the blower speed can be changed. See the Blower Performance Data table for further details and blower motor speed selections.
General Installation Information
Safety Considerations Installing and servicing air conditioning and heating equipment can be hazardous due to system pressure and electrical components. Only trained and qualifi ed service personnel should install, repair or service these systems. Untrained personnel can perform the basic maintenance functions of cleaning coils and replacing air fi lters. Trained service personnel should perform all other operations. When working on air conditioning and heating equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have a fi re extinguisher available for all brazing operations.
Note: Before installing, check voltage of unit(s) to ensure proper voltage.
WARNING: Before performing service or maintenance operations on the system, turn off main power switches to the unit. Turn off accessory heater power switch if applicable. Electrical shock could cause serious personal injury.
CAUTION: Duct connections should be made with 1/2-inch sheet metal screws to prevent damage to pip-ing and other internal components.
CAUTION: Be sure to remove the shipping material from the blower throat before connecting ductwork.
-
5
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
General In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be pres-ent, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualifi ed service mechanic, as special solutions and pumping equipment are required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional fl ushing.
Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning.
Iron, Fe2+ (Ferrous)Bacterial Iron Potential
Material Copper 90/10 Cupro-Nickel
pH Acidity/Alkalinity 7- 9 5 - 9
Scaling Calcium and Magnesium Carbonate (Total Hardness) less than 350 ppm (Total Hardness) less than 350 ppm
Hydrogen SulfideLess than .5 ppm
(rotten egg smell appears at 0.5 PPM) 10 - 50 ppm
Sulfates Less than 125 ppm Less than 125 ppm
Chlorine Less than .5 ppm Less than .5 ppm
Chlorides Less than 20 ppm Less than125 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm
Ammonia Chloride Less than .5 ppm Less than .5 ppm
Ammonia Nitrate Less than .5 ppm Less than .5 ppm
Ammonia Hydroxide Less than .5 ppm Less than .5 ppm
Ammonia Sulfate Less than .5 ppm Less than .5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000-1500 ppm
None None
Iron OxideLess than 1 ppm. Above this level
deposition will occur.Less than 1 ppm. Above this level
deposition will occur.
Suspended SolidsLess than 10 ppm and filtered for max
of 600 micron sizeLess than 10 ppm and filtered for max
of 600 micron size
Threshold Velocity (Fresh Water) 5-8 ft/sec 8-12 ft/sec
Corrosion
Iron Fouling(Biological Growth)
Erosion
Note: Grains = PPM divided by 17 • mg/l is equivalent to PPM
Water Quality
-
6
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
General Piping
Water ConnectionsAll supply and return water connections are female pipe thread of size specifi ed in physical dimensions. Never use fl ex-
ible hoses smaller than separate water connections on the unit and limit hose length to 10 ft. per connection. Check care-
fully for water leaks.
Interior PipingAll units are recommended to be connected to supply and return piping in a two-pipe reverse return confi guration. A
reverse return system is inherently self-balancing and requires only trim balancing when multiple quantities of units with dif-ferent fl ow and pressure drop characteristics are connected to the same loop. A direct return system may also be made to work acceptably, but proper water fl ow balance is more diffi cult to achieve and maintain.
Supply and return runouts are usually connected to the unit by short lengths of high pressure fl exible hose which are sound attenuators for both unit operating noise and hydraulic pumping noise. One end of the hose should have a swivel fi tting to facilitate removal for service. Hard piping can also be connected directly to the unit although it is not recommended since no vibration or noise attenuation can be accomplished. The hard piping must have unions to facilitate unit removal (see fi gure 1 & 6) for typical application).
Some fl exible hose threaded fi ttings are supplied with sealant compound. If not, apply Tefl on tape to assure a tight seal.Supply and return shutoff valves are required at each unit. The return shutoff valve can be used for balancing and
should be adjusted for proper fl ow required, or a manual or automatic fl ow control device should be on the leaving water hose assembly.
No unit should be connected to the supply and return piping until the water system has been cleaned and fl ushed com-pletely. After the cleaning and fl ushing has taken place, the initial connection should have all valves wide open in prepara-tion for water system fi lling.
-
7
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Installing Horizontal Units
Mounting Horizontal UnitsUnits are available with side or end discharge in left-hand or right-hand return air confi gurations. Horizontal units are
normally suspended from a ceiling by four 1/2-inch diameter threaded rods. The rods are usually attached to the unit cor-ners by the bottom panel mounting channel and the mounting grommets furnished with each unit.
CAUTION: Do not use rods smaller than 1/2-inch diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling (the units are approximately 800 lbs.).
Top View
27.24
94.0
Figure 3: Mounting HardwareFigure 2: Mounting Rod Layout
Ball ValvesWater Loop
Flexible DuctCollar
1/2”Threaded Rods
(4)
P/T Plugs
Hose Kits
Insulate supplyplenumanduse atleast a 90° elbowto reduce noise
CondensateDrain
Connection
PowerDisconnect Low
Voltage
IsolationGrommets(Included)
Figure 1: Typical Horizontal Application
Layout the threaded rods per the dimensions in Figure 2. Assemble the hangers to the unit as shown in Figure 3. Securely tighten the brackets to the unit. When attaching the hanger rods to the bracket, a double nut is recommended since vibration could loosen a single nut. The unit should be pitched approximately 1/2-inch towards the drain in both directions, to facilitate condensate removal.
1/2" Threaded Rod(not included)
VibrationIsolator
Washer(not included)
Hex Nuts(not included)
-
8
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
1.5" 1.5"
Vent (if needed)
1/8" per foot
Copper Tube Stub
1/2'' PitchFigure 5: Unit Pitch for DrainFigure 4: Suggested Layout of Condensate Drain Line
Duct SystemA supply air duct fl ange is provided for fi eld installation to facilitate the secure duct connection at the job site. A fl ex-
ible connector is recommended for discharge and return air duct connections on metal duct systems to prevent vibration transmission. It is recommended that all ductwork be insulated with a minimum of 1/2-inch coated insulation. Installation of the units with uninsulated ductwork in an unconditioned space is not recommended, as the system’s performance will be adversely affected.
Condensate DrainThe condensate disposal piping must be trapped a minimum of 1 1/2-inches and the piping must be pitched away from
the unit not less than 1/8-inch per foot (see Figure 4). The condensate drain pan includes a drain tube, which is brazed to the drain pan. Horizontal units must be pitched 1/2-inch in both directions toward the drain tube for proper condensate drainage (see Figure 5).
Installing Horizontal Units (cont.)
-
9
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Control Box
CondensateDrain
Water Supplyand ReturnConnections
Flexible ductCollar
ACCESS
PANEL
ACCESS
PANEL
PANEL
ACCESS
Figure 6: Typical Vertical Application
Installing Vertical Units
Mounting Vertical UnitsUnits are available with top discharge, left-hand or right-hand return air confi gurations. Vertical units are assembled on
rails which facilitate moving and placement of the units. It is not necessarty to anchor the unit to the fl oor.
Duct SystemA supply air duct fl ange is provided for fi eld installation to facilitate the secure duct connection at the job site. A fl ex-
ible connector is recommended for discharge and return air duct connections on metal duct systems to prevent vibration transmission. It is recommended that all ductwork be insulated with a minimum of 1/2-inch coated insulation. Installation of the units with uninsulated ductwork in an unconditioned space is not recommended, as the system’s performance will be adversely affected.
Condensate DrainIn vertical units, the internal condensate drain assembly consists of a fl exible drain tube which is attached to the drain
pan and a 3/4-inch (7-10 tons) or 1-inch (15, 20&23 tons) female pipe thread. An external water trap is not required as the drain tube serves as a trapping loop. The fi eld-installed piping and unit connection must be properly installed and sealed to prevent water leakage.
-
10
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Electrical Connections
GeneralBe sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage
wiring must be done in accordance with local codes or the National Electric Code.
Unit Power ConnectionLine voltage connection is made by connecting the incoming line voltage wires to the terminal bock as shown in Figure
on the unit’s wiring diagram attached to the inside front panel. Consult the Unit Electrical Data below for correct fuse size.
208 Volt OperationNote: All 208-230 volt units are factory wired for 230 volt operation. For 208 volt operation, the red and the blue transform-er wires must be switched between terminal strip PS and contactor RB.
SIZE RATEDVOLTAGEVOLTAGEMIN/MAX
COMPRESSOR* FANMOTORFLA***
FANHP
TOTALUNITFLA
MINCIRCAMP
MAXFUSE
MAXHACR
BREAKERMCC RLA LRA
080
208-230/60/3 197/253 14.0 9.0 70.0 5.6 1.5 23.6 25.9 30 30
460/60/3 414/506 7.1 4.6 33.0 2.8 1.5 12.0 13.2 15 15
575/60/3 518/633 5.3 3.4 27.0 2.0 1.5 8.8 9.6 10 10
080**
208-230/60/3 197/253 14.0 9.0 70.0 6.6 2.0 24.6 26.9 35 35
460/60/3 414/506 7.1 4.6 33.0 3.5 2.0 12.7 13.9 15 15
575/60/3 518/633 5.3 3.4 27.0 2.4 2.0 9.2 10.0 10 10
095
208-230/60/3 197/253 16.7 10.7 85.0 6.6 2.0 28.0 30.7 40 40
460/60/3 414/506 8.2 5.3 42.0 3.5 2.0 14.0 15.4 20 20
575/60/3 518/633 6.7 4.3 34.0 2.4 2.0 11.0 12.1 15 15
095**
208-230/60/3 197/253 16.7 10.7 85.0 9.2 3.0 30.6 33.3 40 40
40/60/3 414/506 8.2 5.3 42.0 4.3 3.0 14.9 16.2 20 20
575/60/3 518/633 6.7 4.3 34.0 3.6 3.0 12.2 13.3 15 15
120
208-230/60/3 197/253 27.0 17.3 123.0 9.2 3.0 43.8 48.1 60 60
460/60/3 414/506 14.0 9.0 62.0 4.3 3.0 22.3 24.6 30 30
575/60/3 518/633 11.0 7.1 50.0 3.6 3.0 17.8 19.6 25 25
Notes: HACR circuit breaker in USA only. All fuses class RK-5.* Ratings per each compressor – unit supplied with two.** With optional motor.*** Ratings per each motor – V180, V240 and V275 supplied with two.
Unit Electrical Data - Horizontal
-
11
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
SIZE RATEDVOLTAGEVOLTAGEMIN/MAX
COMPRESSOR* FANMOTORFLA***
FANHP
TOTALUNITFLA
MINCIRCAMP
MAXFUSE
MAXHACR
BREAKERMCC RLA LRA
080
208-230/60/3 197/253 14.0 9.0 70.0 3.8 1.0 21.8 24.1 30 30
460/60/3 414/506 7.1 4.6 33.0 1.9 1.0 11.1 12.3 15 15
575/60/3 518/633 5.3 3.4 27.0 2.0 1.5 8.8 9.7 10 10
080**208-230/60/3 197/253 14.0 9.0 70.0 5.6 1.5 23.6 25.9 30 30
460/60/3 414/506 7.1 4.6 33.0 2.8 1.5 12.0 13.2 15 15
095
208-230/60/3 197/253 16.7 10.7 85.0 5.6 1.5 27.0 29.7 40 40
460/60/3 414/506 8.2 5.3 42.0 2.8 1.5 13.4 14.7 20 20
575/60/3 518/633 6.7 4.3 34.0 2.0 1.5 10.6 11.7 15 15
095**
208-230/60/3 197/253 16.7 10.7 85.0 6.6 2.0 28.0 30.7 40 40
460/60/3 414/506 8.2 5.3 42.0 3.5 2.0 14.1 15.4 20 20
575/60/3 518/633 6.7 4.3 34.0 2.4 2.0 11.0 12.1 15 15
120
208-230/60/3 197/253 27.0 17.3 123.0 6.6 2.0 41.2 45.5 60 60
460/60/3 414/506 14.0 9.0 62.0 3.5 2.0 21.5 23.8 30 30
575/60/3 518/633 11.0 7.1 50.0 2.4 2.0 16.6 18.4 25 25
120**
208-230/60/3 197/253 27.0 17.3 123.0 9.2 3.0 43.8 48.1 60 60
460/60/3 414/506 14.0 9.0 62.0 4.3 3.0 22.3 24.6 30 30
575/60/3 518/633 11.0 7.1 50.0 3.6 3.0 17.8 19.6 25 25
180
208-230/60/3 197/253 29.5 18.9 146.0 5.6 1.5 49.0 53.7 70 70
460/60/3 414/506 14.9 9.5 72.0 2.8 1.5 24.6 26.9 35 35
575/60/3 518/633 11.8 7.6 58.0 2.0 1.5 19.1 21.0 25 25
180**
208-230/60/3 197/253 29.5 18.9 146.0 6.6 2.0 51.0 55.7 70 70
460/60/3 414/506 14.8 9.5 72.0 3.5 2.0 26.0 28.3 35 35
575/60/3 518/633 11.8 7.6 58.0 2.4 2.0 19.9 21.8 25 25
240
208-230/60/3 197/253 47.0 30.1 225.0 6.6 2.0 73.5 81.0 110 110
460/60/3 414/506 24.2 15.5 114.0 3.5 2.0 38.0 41.9 50 50
575/60/3 518/633 18.9 12.1 80.0 2.4 2.0 29.0 32.1 40 40
240**
208-230/60/3 197/253 47.0 30.1 225.0 9.2 3.0 78.7 86.2 110 110
460/60/3 414/506 24.2 15.5 114.0 4.3 3.0 39.6 43.5 50 50
575/60/3 518/633 18.9 12.1 80.0 3.6 3.0 31.4 34.5 45 45
275 460/60/3 414/506 26.9 17.2 125.0 4.3 3.0 43.2 47.5 60 60
Unit Electrical Data - Vertical
Notes: HACR circuit breaker in USA only. All fuses class RK-5.* Ratings per each compressor – unit supplied with two.** With optional motor.*** Ratings per each motor – V180, V240 and V275 supplied with two.
Electrical Connections (cont.)
-
12
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Wiring SchematicV Series - Commercial 208-230/60/3, 460/60/3, 575/60/37-20 Ton Johnson Control 97P681-03 6/23/04
Transformer
Compressor 2
CC2T1
L1
T2
L2
T3
L3
CR
S
Blue BlackRed
Compressor 1
CC1T1
L1
T2
L2
T3
L3
CR
S
Blue BlackRedUnit Power Supply208-230/60/3, 480/60/3, or 575/60/3
L3L1 L2G
RedRed
YellowWhite
WhiteBrown
BlackBlack
Gray
RBT2 T1T3
L2 L1L3
Green
YellowBrown Gray
Gray
Belt DriveBlowerMotor
Belt DriveBlowerMotor Green
NOTE 2
Blue 230V460V575V
Red 208V
Black
Yellow
Blk/Wht
Note 1
Green
TDABlack
Black/Red
TFP1WhiteWhite
TFP2Gray
Gry/Wht
HP1Black Black
Black Black
Black Blk/WhtRB
HP2
RV1Red Red
RV2Red Red
BrownCO
LP1
Blk/Wht
Blk/Wht
L1
L2
S1
S2
Tan
TanT
CPM2CompressorProtection
Module
L1
L2
S1
S2
Tan
TanT
Black
Black
Note 3
Black
BlackRed
BlackLP2 VioletWhite
NOTE 5
White Blue
Blk/WhtOS
PB1
Red
L1
L2
Black
L1
L2
PB2
Yellow
OrangeGreen
Blue
VioletWhite
Yellow
Violet
White
Yellow
CC2
Black
Black
CC1
Gry/Wht
Blk/WhtYellow
NOTE 6
NOTE 7
ES
Brown 11K
Johnson FX-10
5VDCAI3
23242526272829303132333435363738
+-
AI5-+
AI4-+
AI6
AI2
AI1
5VDC
5VDC
LED
-
-
-
+
+
+
24VAC
24VACCom
GROUND
394041
PWM2PWM2 ComPWM1
42434445464748
24VAC ComDI12DI11DI10DI9DI8DI7
4950515253545556
DI 3/4/5/6/ ComDI6DI5DI4DI3DI2
DI1
9VDC
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
D09
D08
D07
D06
D05
D04
D03
D02
D01
J8
J2
J10
J9
J7
A23A13A11
A21A12
A25A22
A32
A31A35
A14A24
A34
A33
A15
Thermistor - Johnson Control
Relay coil
Switch - High pressure
Switch - Low pressure
Polarized connector
Condensate Overflow
Compressor contactor 1
Condensate overflow
132
P
Factory low voltage wiringFactory line voltage wiringField low voltage wiringField line voltage wiringOptional block
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Notes:
CC1 -
CO - HP1 -
LP1 -
RB -RV1 -
Stage 1 High Pressure
Stage 1 Low Pressure
Blower power relayReversing Valve coil 1
L1
LegendRelay Contacts-
N.O., N.C. Freeze protection sensor 1FP1 -
T
1 - Switch blue and red wires for 208V operation
Discharge Air TemperatureDA -Dirty Filter or Air ProvingDF/AP-
CP/FP- Compressor Proving or Fan Proving
Freeze protection sensor 2FP2 -HP2 - Stage 2 High Pressure
LP2 - Stage 2 Low Pressure
RV2 - Reversing Valve coil 2CC2 - Compressor contactor 2
2 - Second Blower used only on 15 - 20 Ton units
CPM1 - Compressor Protection Module 1CPM2 - Compressor Protection Module 2
3 - Compressor Protection Module is used only on 575/60/3, 15-20 ton units4 - R, C, Y1, Y2, O, and G are for use with a wall mounted thermostat5 - Disconnect for 15 degree freeze protection
OS - Occupied SwitchES - Emergency Shutdown
6 - Acc 1 output is cycled with the compressor7 - Acc 2 output is cycled with the fan
Orange
Red
Blue/Wht
OrangeOrg/Wht
Gry/Wht
Gry/Wht
Black
TB
R
C
Y1
O
G
L
X1
X2
24VAC
24V COM
Alarm
Acc 1
Acc 2
Fan
Rev Valve
Comp 1
SS
AIC
RS
SC
TO
Setpoint Shift
AI Com
Room Sensor
Sensor Com
Temp Occ
Y2Comp 2
Green
Note 4
Gray
Pink
Orange
Orange
Pink
Orange
Orange
CPM1CompressorProtection
Module
-
13
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
The Johnson Controls FX10 board is specifi cally designed for commercial heat pumps and provides control of the entire unit as well as input ports for Open N2, LonTalk, BacNet communication protocols as well as an input port for a user inter-face. The user interface is an accessory item that can be used to aid in diagnostics and unit setup. A 16 pin low voltage terminal board provides terminals for common fi eld connections.
Installation OptionsUnits using the FX10 have three different installation options.
Stand-alone unit controlled by an electronic room thermostat.Stand-alone with a zone temperature sensor. A zone temperature sensor is a non-programmable temperature sensor that allows the user to adjust the zone temperature by +/- 5°F. A user interface (Kit # MUIK1) is required to change any zone temperature set points beyond 5 degrees.Integrated into a building automation system by using a zone temperature sensor and adding a communication mod-ule for Open N2, LonTalk, or BacNet.
Regardless of which installation option is chosen all low voltage wiring will be done through the 16-pin terminal board (see fi gure 7).
1.2.
3.
C
G
LC1
Y2
X1
R
AIC
SC
O
Y1
LC2
L
X2
SS
RS
TO
REV. VALVE
COMPRESSOR1
N/A
LOCKOUT
ACCESSORY
SETPOINT SHIFT
ROOM SENSOR
TEMP OCCUPIED
COMMON
FAN
N/A
COMPRESSOR2
ACCESSORY 1
24VAC
AI COMMON
SENSOR COMMON
Figure 7: 16-Pin Terminal Board Wiring
FX10 Microprocessor Control
CAUTION: The FX10 control incorporates static sensitive CMOS devices. Touching the board or its compo-nenets may result in damage as a result of static discharge. To prevent damage during service, it is recommend-ed that the technician use a static discharge wrist strap, which is grounded to the heat pump chassis. When handling the circuit board, hold by the edges and avoid contact with electrical components. Circuit boards should always be stored in a static protected bag prior to installation.
-
14
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
FX10 Microprocessor Control
Electronic Thermostat Connections If an electronic thermostat is being used, wire as shown in Figure 8.
Zone Sensor Wiring Installation options 2 and 3 will use the wiring diagram for the zone temperature sensor, Figure 9.
R
C
Y1
Y2
O
G
L
24VAC(HOT)
24VAC(COMMON)
COMPRESSOR1
Term
inal
Boa
rdC
onne
ctio
ns ThermostatC
onnections
COMPRESSOR2
REVERSINGVALVE
BLOWERRELAY
SYSTEMMONITOR
Figure 8: Electronic Thermostat Connections
SS
RS
AIC
TO
SC
SETPOINTSHIFT
ROOMSENSOR
AICOMMON
Term
inal
Boa
rdC
onne
ctio
ns
ZoneS
ensorConnections
PUSHBUTTON
DICOMMON
Figure 9: Zone Sensor Connections
-
15
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
StartupThe unit will not operater until all the inputs and safety controls are checked for normal operating conditions.
Fault RetryAll faults are tested twice before fi nally locking the unit out to prevent nuisance service calls.
Component Sequencing DelaysComponents are sequenced and delayed for optimum unit performance. See Table below.
CONTROL TIMING
Lead compressor ON delay 90 seconds
Lag compressor ON delay 120 seconds
Short cycle delay 4 minutes
Minimum compressor ON time 2 minutes (except for fault condition)
High pressure fault recognition Less than 1 second
Low pressure fault recognition delay 30 seconds
Freeze protection fault recognition delay 30 seconds
Condensate overfl ow fault recognition delay 30 seconds
Low pressure fault bypass delay 2 minutes
Freeze protection fault bypass delay 2 minutes
Random start delay 0-120 seconds
Short Cycle ProtectionThe control allow a minimum compressor off time of 4 minutes and a minimum compresor run time of 2 minutes for short
cycle protection.
Random StartA random start delay of 1 to 120 seconds is generated after each power up to prevent simultaneous start-up of all units
within a building after the release from an unoccupied cycle or power loss.
Emergency ShutdownA normally open dry contact must be placed between DI2 and PB2-L2 (see unit schematic). Closing the contact will set
the unit into emergency shutdown mode. All unit operation is suspended while in emergency shutdown mode.
Condensate Overfl ow ProtectionThe board incorporates an impedance liquid sensor at the top of the condensate drain pan. Upon a continuous 30 sec-
ond sensing of the condensate, the operation of the unit is suspended.
Safety ControlsThe FX10 board receives separate signals from a high pressure switch for safety, a low pressure switch to detect loss of
refrigerant charge an a low suction temperature thermistor for freeze protection. Upon a continuous 30 second measure-ment of the fault (immediate for high pressure), compressor operation is stopped.
Freeze Protection
Notes: For applications using a closed loop antifreeze solution, remove the wire between DI5 and PB2-L1 (see unit sche-matic). On applications using an open loop/ground water system, make sure the wire is connected. For additional informa-tion on the FX10 Control, refer to Application Guide AGFX10 or Submittal Data SD 1981.
FX10 Operation
-
16
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Duct System
Duct SystemAn air outlet collar is provided on all units to facilitate a duct connection. A fl exible connector is recommended for dis-
charge and return air duct connections on metal duct systems. Any uninsulated duct should be insulated with a minimum of one-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, a previous check should have been made to assure that the duct has the capacity to handle the air required for the unit’s application. If ducting is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repairs.
The duct system should be sized to handle the design airfl ow quietly. To maximize sound attenuation of the unit blower, the supply and return plenums should include internal duct liner of glass fi ber or be of ductboard construction for the fi rst few feet. If air noise or excessive air fl ow is a problem, the blower speed can be changed (minimum air fl ow must be main-tained). See the Blower Sheave Adjustment section below and Blower Performance Data chart, page 16.
Blower Drive Sheaves
Blower Sheave Adjustment Follow the procedures listed below if airfl ow of heat pump is to be changed from factory setting. (Refer to Figure 10.)
Loosen the blower motor fastening nuts from the motor mount. Turn the adjusting bolts until the tension is off the drive belt. Remove belt from sheave and loosen allen heat set screw “B”. Adjust sheave pitch diameter for desired speed by opening or closing moveable portion in or out in 1/2-turn incre-
ments. Do not open more than 5 full turns.Sheave should be mounted with set screw “A” toward the motor. Be sure driven and drive sheaves are in alignment
and parallel. Retighten set screw “B” and replace drive belt on sheaves. Turn motor mount adjusting bolts until belt has approximately 1/2-inch of defl ection midway between sheaves
(4 lbs. tension if measured with gauge, see Figure 11). Retighten motor mounting nuts. Belt tension of a new belt will drop rapidly during the fi rst few hours of operation. Check and readjust as needed.
1.2.3.4.
5.
6.7.
8.9.
Set Screw “A” Set Screw “B”
KeywayMoveablePortion MODEL DRIVE SHEAVE
FACTORY SETTING
Vertical080 3 Turns Open095 4 Turns Open120 5 Turns Open180 4 Turns Open240 4 Turns Open275 4 Turns Open
Horizontal080 2 Turns Open095 3 Turns Open120 2 Turns Open
Figure 10: Blower Motor Sheave Adjustments and Settings Figure 11: Checking Drive Belt Tension
DeflectionDriven Sheave
Drive Sheave
-
17
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Blower Performance Data
Notes: Drive Sheave factory setting shown in bold. Shaded areas require larger blower motor and sheaves.
SIZE DRIVESHEAVEAirfl ow (CFM) at External Static Pressure (in. wg)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.2 1.4 1.6 1.8 2.0
HO
RIZ
ON
TAL
V080
Closed 3900 3800 3650 3500 3300 3100 2950 2750 2450 3050 26501 Turn Open 3700 3550 3400 3200 3000 2800 2550 3200 3000 2800
2 Turns Open 3400 3200 3050 2850 2650 2400 3200 2900 26503 Turns Open 3050 2900 3650 2400 3300 3150 2900 26504 Turns Open 2800 2550 3350 3850 2900 26505 Turns Open 2450 3250 3000 2750
V095
Closed 4450 4350 4200 4050 3900 3750 3600 3400 3250 3050 3800 3450 30001 Turn Open 4350 4200 4050 3990 3750 3600 3400 3200 3000 3900 3400 29502 Turns Open 4150 4000 3950 3650 3500 3400 3200 2900 3850 3600 32503 Turns Open 3900 3800 3650 3500 3300 3100 2900 3500 3300 30004 Turns Open 3700 3550 3350 3050 2900 3400 3200 3000 28005 Turns Open 3450 3250 3000 3500 3300 3100 2850
V120
Closed 4900 4800 4700 4600 4450 4300 4000 3700 4550 4400 41501 Turn Open 4900 4800 4700 4600 4450 4300 4200 4000 3700 4550 4300 4050
2 Turns Open 4800 4700 4550 4450 4300 4200 4050 3900 3750 3350 4300 40503 Turns Open 4600 4450 4350 4250 4100 3950 3750 3650 3500 3250 4200 39504 Turns Open 4400 4250 4100 4000 3850 3700 3550 3550 32005 Turns Open 4200 4050 3950 3750 3600 3450 3200
VE
RT
ICA
L
V080
Closed 4225 4100 3900 3700 3500 3250 3000 2700 3600 3400 2900 1 Turn Open 4000 3825 3600 3400 3100 2850 3550 3350 3100 28002 Turns Open 3725 3500 3300 3000 2700 3300 3200 2850 25003 Turns Open 3400 3150 2900 2800 2700 25504 Turns Open 3050 2800 3150 2900 26005 Turns Open 3150 2900 2600
V095
Closed 4400 4250 3950 3850 3600 3400 3100 4550 4150 3700 3000 1 Turn Open 4550 4400 4200 4000 3800 3550 3300 3000 4350 4150 3700 30002 Turns Open 4300 4100 3900 3700 3450 3200 2900 4250 4000 3700 31003 Turns Open 4100 3850 3600 3400 3150 2900 4000 3800 3500 3200 28504 Turns Open 3800 3600 3350 3150 2850 3800 3550 3300 29505 Turns Open 3550 3300 3050 2750 3600 3400 3150 2800
V120
Closed 5100 4900 4800 4550 4100 4900 4500 4150 36501 Turn Open 5200 5000 4800 4600 4400 4150 4950 4700 4360 38502 Turns Open 5000 4800 4650 4500 4400 4200 3950 3700 4850 4450 39003 Turns Open 4900 4700 4500 4350 4150 3900 3600 4800 4450 39504 Turns Open 4700 4600 4400 4200 4000 3700 4900 4700 4600 40505 Turns Open 4800 4600 4350 4100 3900 3600 4700 4500 4300 4050 3500
V180
Closed 9600 9200 8800 8500 8100 7600 7200 6600 6000 9200 8200 7000 54001 Turn Open 9600 8700 8400 7900 7400 7000 6400 5900 8500 8100 6900 54002 Turns Open 8600 8200 7800 7300 6800 6300 5800 8100 7700 7100 58003 Turns Open 8000 7600 7200 6700 6200 5800 8100 7600 7000 62004 Turns Open 7500 7000 6600 6000 7900 7700 7200 6500 5800 54005 Turns Open 7000 6500 5900 7800 7400 6800 6100 5200
V240
Closed 10400 10200 10000 9700 9400 9100 8300 9900 9000 8200 72001 Turn Open 10200 9900 9700 9400 9200 8900 8500 8100 9900 9200 8400 74002 Turns Open 9700 9400 9100 8900 8700 8400 8100 7700 7100 9200 8400 73003 Turns Open 10300 10000 9600 9200 8900 8500 8100 7600 7000 9600 8600 75004 Turns Open 9700 9300 9000 8500 8100 7700 7200 9500 9200 8700 76005 Turns Open 9000 8600 8200 7800 7400 6800 9200 8800 8400 7800
V275
Closed 10900 10400 9900 90001 Turn Open 11000 10700 10400 9900 92002 Turns Open 11200 10900 10600 10250 9900 92003 Turns Open 10600 10300 10000 9800 9600 86004 Turns Open 11200 10900 10600 10250 9900 9700 9500 9200 87005 Turns Open 10500 10200 9900 9500 9100 8900 8700
-
18
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
System Cleaning and Flushing
Cleaning and FlushingPrior to startup of any heat pump, the water circulating system must
be cleaned and fl ushed of all dirt and debris.If the system is equipped with water shutoff valves, the supply and
return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Figure 12). The system should be fi lled at the water make-up connection with all air vents open. After fi lling, vents should be closed.
The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should be opened for initial fl ush and blowdown, making sure water fi ll valves are set at the same rate. Check the pres-sure gauge at the pump suction and manually adjust the make-up water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and return connections.
Refi ll the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specifi ed percentage of antifreeze may also be added at this time. Use commercial grade anti-freeze designed for HVAC systems only. WFI recommends Environol™ brand antifreeze.
Once the system has been fi lled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, fl ow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full fl ow has been established through all components including the heat rejector (regard-less of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and startup and for air and water balancing, Use forms when performing commercial check, test and startup. Obtain these forms from your commercial representative or Customer Service.
Ground Source Loop System CheckoutOnce piping is completed between the unit pumping system and ground loop, fi nal purging and charging of the loop is
needed. A high pressure pump is needed to achieve adequate fl ow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of 40-50 psi (summer) or 50-75 psi (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely purged of air will allow for the “break-in” period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the fi rst time. Loop static pressure will also fl uctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fl uctuation is normal and should be considered when charging the system initially.
Insure the pump provides adequate fl ow through the unit by checking pressure drop across the heat exchanger. Usually 2.25-3.0 GPM of fl ow per ton of cooling capacity is recommended in earth loop applications.
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts InitiallyConnected Together
Figure 12: Flushing Internal Piping
-
19
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Unit Startup
Before powering the unit, check the following:High voltage is correct and matches nameplateFuses, breakers and wire size are correctLow voltage wiring is completePiping has been completed and water system cleaned and fl ushedAir is purged from closed loop systemIsolation valves are open and water control valves or loop pumps wiredCondensate line is open and correctly pitchedTransformer has been switched to lower voltage tap if neededBlower rotates freelyBlower speed is correctAir fi lter is clean and in positionService/access panels are in placeReturn air temperature is between 60°F-80°F in heating and 70°F-95°F in coolingAir coil has been cleaned
Startup StepsInitiate a control signal to energize the blower motor. Check blower operation.Initiate a control signal to place the unit in the cooling mode. Cooling set point must be set below room temperature.First stage cooling will energize after a time delay. Check for correct rotation of scroll compressors in 120, 180, 240 units. Incorrect rotation will cause unusual noise and low refrigerant pressures. Switch any two power leads at the compressor or contractor to reverse rotation.Be sure the compressor and water control valve or loop pumps are activated.Initiate a control signal to energize second stage cooling.Second stage cooling will energize after a time delay. Check for correct rotation as indicated in step 3.Verify that the water fl ow rate is correct by measuring pressure drop through the heat exchanger using the P/T plugs and comparing to Water Pressure Drop Table on page 20.Check the temperature of both the supply and discharge water. Refer to Unit Operating Pressures and Temperatures Table page 18.Check for an air temperature drop of 15° to 25°F across the air coil, depending on fan speed and entering water temperature.Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or pumps deactivate.Initiate a control signal to place the unit in the heating mode. Heating setpoint must be set above room temperature.First stage heating will energize after a time delay.Initiate a control signal to energize second stage heating.Second stage heating will energize after a time delay.Check the temperature of both the supply and discharge water. Refer to Unit Operating Pressures and Temperatures Table on page 19.Check for an air temperature rise of 20°F to 25°F across the air coil, depending on the fan speed and entering water temperature.Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps deactivate.During all testing, check for excessive vibration, noise or water leaks.Set system to desired normal operating mode and set temperature to maintain desired comfort level.Instruct the owner/operator in the proper operation of the thermostat and system maintenance.Check belt tension and readjust as necessary after fi rst few hours.
••••••••••••••
1.2.3.
4.5.6.7.
8.
9.
10.
11.12.13.14.15.
16.
17.
18.19.20.21.
-
20
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
EWT
WATERFLOW/TON
(GPM)
COOLING HEATING
SUCTIONPRESSURE
DISCHARGEPRESSURE
SUPERHEAT
SUBCOOLING
WATERRISE° F
AIRDROP° F
SUCTIONPRESSURE
DISCHARGEPRESSURE
SUPERHEAT
SUBCOOLING
WATERDROP° F
AIRRISE° F
30
1.5 61-70 100-117 25-35 15-25 21-24 21-26 34-39 163-183 9-14 5-9 7-8 14-20
2.3 62-71 92-109 25-35 15-25 13-16 21-26 37-42 165-185 9-14 5-9 5-6 16-22
3.0 62-71 88-104 25-35 15-25 6-11 21-26 38-44 167-186 9-14 5-9 3-4 16-22
50
1.5 79-85 145-170 10-18 12-25 20-23 20-25 51-58 175-202 10-14 5-9 10-12 23-29
2.3 75-83 130-155 10-18 12-25 12-15 20-25 53-62 178-206 10-14 5-9 7-8 24-30
3.0 72-82 125-150 10-18 12-25 8-12 20-25 55-65 180-208 10-14 5-9 5-6 25-31
70
1.5 78-88 180-200 9-14 13-18 19-22 19-24 71-82 215-250 12-16 5-8 14-15 28-34
2.3 78-90 169-187 9-14 13-18 11-14 19-24 77-89 203-235 12-16 5-8 9-10 30-37
3.0 78-91 160-180 9-14 13-18 7-12 19-24 81-92 200-235 12-16 5-8 7-8 31-38
90
1.5 79-92 230-272 8-13 13-18 18-21 17-23 – – – – – –
2.3 80-93 215-248 8-13 13-18 10-14 17-23 – – – – – –
3.0 80-93 208-240 8-13 13-18 6-11 17-23 – – – – – –
Unit Operating Parameters
Vertical Units
EWT
WATERFLOW/TON
(GPM)
COOLING HEATING
SUCTIONPRESSURE
DISCHARGEPRESSURE
SUPERHEAT
SUBCOOLING
WATERRISE° F
AIRDROP° F
SUCTIONPRESSURE
DISCHARGEPRESSURE
SUPERHEAT
SUBCOOLING
WATERDROP° F
AIRRISE° F
30
1.5 61-70 100-117 25-35 15-25 21-24 21-26 34-39 163-183 9-14 5-9 7-8 14-20
2.25 62-71 92-109 25-35 15-25 13-16 21-26 37-42 165-185 9-14 5-9 5-6 16-22
3 62-71 88-104 25-35 15-25 6-11 21-26 38-44 167-186 9-14 5-9 3-4 16-22
50
1.5 79-85 145-170 10-18 12-25 20-23 20-25 51-58 175-202 10-14 5-9 10-12 23-29
2.25 75-83 130-155 10-18 12-25 12-15 20-25 53-62 178-206 10-14 5-9 7-8 24-30
3 72-82 125-150 10-18 12-25 8-12 20-25 55-65 180-208 10-14 5-9 5-6 25-31
70
1.5 78-88 180-200 9-14 13-18 19-22 19-24 71-82 215-250 12-16 5-8 14-15 28-34
2.25 78-90 169-187 9-14 13-18 11-14 19-24 77-89 203-235 12-16 5-8 9-10 30-37
3 78-91 160-180 9-14 13-18 7-12 19-24 81-92 200-235 12-16 5-8 7-8 31-38
90
1.5 79-92 230-272 8-13 13-18 18-21 17-23 – – – – – –
2.25 80-93 215-248 8-13 13-18 10-14 17-23 – – – – – –
3 80-93 208-240 8-13 13-18 6-11 17-23 – – – – – –
Horizontal Units
-
21
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
SIZE FLOW RATEGPMPRESSURE DROP (PSI)
30°F 50°F 90°F
08010 2.6 2.5 2.316 5.6 5.4 5.022 7.9 7.5 6.0
09512 2.4 2.2 2.318 5.5 5.0 5.024 9.5 8.8 7.7
12016 3.0 2.7 2.622 5.6 5.1 4.728 8.7 7.9 7.2
Water Pressure Drop
SIZE FLOW RATEGPMPRESSURE DROP (PSI)
30°F 50°F 90°F
08010 2.6 2.5 2.316 5.6 5.4 5.022 7.9 7.5 6.0
09512 2.4 2.2 2.118 5.5 5.0 4.824 9.5 8.6 7.7
12016 3.0 2.7 2.622 5.6 5.1 4.728 8.7 7.9 7.2
18020 1.8 1.7 1.432 4.4 4.2 3.644 8.2 7.8 7.1
24032 2.9 2.6 2.544 5.3 4.8 4.556 8.7 7.9 7.2
27534 3.1 2.8 2.652 8.2 7.4 6.970 11.7 10.9 10.1
Horizontal UnitsVertical Units
-
22
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Preventive Maintenance
Water Coil MaintenanceKeep all air out of the water. An open loop system should be checked to insure that the well head is not allowing air to infi ltrate the water line. Lines should always be airtight.Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure or air vents may draw air into the system.
Notes: If the installation is performed in an area with a known high mineral content ( 125 P.P.M. or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water fl owing through the unit, the less chance for scaling.
Other MaintenanceFilters
Filters must be clean to obtain maximum performance. They should be inspected every two to three months under nor-mal operating conditions and be replaced when necessary. Units should never be operated without a fi lter.
Condensate DrainIn areas where airborne bacteria produce a residual buildup in the drain pan, it may be necessary to chemically treat
the pan to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty fi lters. Inspect twice a year to avoid the possibility of overfl ow.
Air CoilThe air coil must be clean to obtain maximum performance. Check once a year under normal operating conditions and
brush, vacuum or chemically clean the air coil if necessary. Care must be taken not to damage or disturb the aluminum fi ns while cleaning.
Drive BeltsCheck periodically for proper tension. (Refer to page 15.)
1.
2.
CAUTION: Fin edges are sharp.
-
23
VERSATEC 7 THRU 23 TON INSTALLATION MANUAL
Replacement Procedures
Obtaining PartsContact your distributor for service or replacement parts required.
In-warranty Material ReturnMaterial may not be returned except by permission of authorized service personnel. Contact your local distributor for
warranty return authorization and assistance.
-
Manufactured by WFI9000 Conservation WayFort Wayne, IN 46809
WFI has a policy of continuous product research and development and reserves the right to change design and specifi cations without notice. ©2006 WFI.
Product: Versatec Type: Water Source/Geothermal Heat PumpsSize: 7 thru 23 Tons
Document Type: Installation ManualPart Number: IM2601Release Date: 11/06Supercedes: IM2601 (03/06)