Venting Installation Diagrams & Examples for On‐Demand Water Heaters:
NovaVent Line
JUNE 2012 324192‐000
TABLE OF CONTENTS
3” Intake & 4” Exhaust
Standard Sidewall Termination – Noncombustible Wall (Example 1) .................................................................. 1A
Standard Sidewall Termination – Noncombustible Wall (Example 2) .................................................................. 2A
Standard Sidewall Termination – Noncombustible Wall (Example 3) .................................................................. 3A
Standard Sidewall Termination – Combustible Wall (Example 1) ......................................................................... 4A
Standard Sidewall Termination – Combustible Wall (Example 2) ......................................................................... 5A
Standard Sidewall Termination – Combustible Wall (Example 3) ......................................................................... 6A
Direct‐Vent Sidewall Termination – Combustible Wall (Example 1) .................................................................... 7A Direct‐Vent Sidewall Termination – Combustible Wall (Example 2) .................................................................... 8A Direct‐Vent Sidewall Termination – Combustible Wall (Example 3) .................................................................... 9A Concentric Direct‐Vent Sidewall Termination (Example 1) ................................................................................ 10A Concentric Direct‐Vent Sidewall Termination (Example 2) ................................................................................ 11A Standard Roof Termination (Flat Roof) .............................................................................................................. 12A Standard Roof Termination (Angled Roof) ......................................................................................................... 13A Direct‐Vent Roof Termination (Flat Roof) .......................................................................................................... 14A Direct‐Vent Roof Termination (Angled Roof) ......................................................................................................15A
4” Intake & 4” Exhaust
Direct‐Vent Sidewall Termination – Combustible Wall (Example 1) .................................................................... 7B Direct‐Vent Sidewall Termination – Combustible Wall (Example 2) .................................................................... 8B Direct‐Vent Sidewall Termination – Combustible Wall (Example 3) .................................................................... 9B Concentric Direct‐Vent Sidewall Termination (Example 1) ................................................................................ 10B Concentric Direct‐Vent Sidewall Termination (Example 2) ................................................................................ 11B Direct‐Vent Roof Termination (Flat Roof) .......................................................................................................... 14B Direct‐Vent Roof Termination (Angled Roof) ..................................................................................................... 15B
5” Intake & 5” Exhaust
Standard Sidewall Termination – Noncombustible Wall (Example 1) .................................................................. 1C
Standard Sidewall Termination – Noncombustible Wall (Example 2) .................................................................. 2C
Standard Sidewall Termination – Noncombustible Wall (Example 3) .................................................................. 3C
Standard Sidewall Termination – Combustible Wall (Example 1) ......................................................................... 4C
Standard Sidewall Termination – Combustible Wall (Example 2) ......................................................................... 5C
Standard Sidewall Termination – Combustible Wall (Example 3) ......................................................................... 6C
Direct‐Vent Sidewall Termination – Combustible Wall (Example 1) .................................................................... 7C Direct‐Vent Sidewall Termination – Combustible Wall (Example 2) .................................................................... 8C Direct‐Vent Sidewall Termination – Combustible Wall (Example 3) .................................................................... 9C Concentric Direct‐Vent Sidewall Termination (Example 1) ..................................................................................10C
Concentric Direct-Vent Sidewall Termination (Example 2) ................................................................................ 11C Standard Roof Termination (Flat Roof) .............................................................................................................. 12C Standard Roof Termination (Angled Roof) ......................................................................................................... 13C Direct-Vent Roof Termination (Flat Roof) .......................................................................................................... 14C Direct-Vent Roof Termination (Angled Roof) ..................................................................................................... 15C
NOTES: For longer horizontal vent runs, please use support straps every 4 ft., and pitch the run so that any
condensate formed will roll back toward the condensate trap.
Please locate the intake and exhaust sidewall terminations on the same side wall (same pressure zone). The intake and exhaust sidewall terminations should be at least 3 feet apart.
Please follow all local codes when draining condensate.
This illustration is intended as a basic guide only. There is a wide variety Designers must add all necessary safety and auxiliary equipment to conform
to code requirem
These illustrations are intended as basic guides only. There is a wide variety of
situations that will require different parts and/or modifications to these basic
designs. Designers must add all necessary safety and auxiliary equipment to
conform to code requirements and design practices.
Improper venting of this appliance can result in excessive levels of carbon monoxide which can result in severe personal injury or death.
Improper installation can cause nausea or asphyxiation, severe injury or death from carbon monoxide and flue gases poisoning. Improper installation will void product warranty.
When installing the vent system, all applicable national and local codes must be
followed. If you install thimbles, fire stops or other protective devices and they
penetrate any combustible or noncombustible construction, be sure to follow all
applicable national and local codes.
VENTING INSTRUCTIONS
The water heater must be vented in accordance with the section “Venting of Equipment" of the latest edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the United States and/or Section 7 of the CAN/CSA B149.1 Natural Gas and Propane Installation Code in Canada, as well as applicable local building codes.
CAUTION
WARNING
Qualified Installer or Service Agency Installation and service of this water heater requires ability equivalent to that of a Qualified Agency (as defined by ANSI below) in the field involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service. ANSI Z223.1 2006 Sec. 3.3.83: “Qualified Agency” - “Any individual, firm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction.” If you are not qualified (as defined by ANSI above) and licensed or certified as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual.
General rules for venting water heaters are:
Place the water heater as close as possible to the vent terminator.
The vent collar of the water heater must be fastened directly to an unobstructed vent pipe.
Do not weld the vent pipe to the water heater’s vent collar.
Do not cut the vent collar of the unit.
The vent must be easily removable from the top of the water heater for normal service and inspection of the unit.
The water heater vent must not be connected to any other gas appliance or vent stack.
Avoid using an oversized vent pipe or using extremely long runs of the pipe.
For rooftop venting, a rain cap or other form of termination that prevents rain water from entering into the water heater must be installed.
Do not common vent or connect any vent from other appliances to the water heater vent.
General rules for vent terminations:
Avoid locating the water heater vent terminator near any air intake devices. These fans can pick up the exhaust flue products from the water heater and return them to the building. This can create a health hazard.
Locate the vent terminator so that it cannot be blocked by any debris, at any time. Most codes require that the terminator be at least 12 inches above grade or anticipated snow level, but the installer may determine if it should be higher depending on the job site condition and applicable codes.
A proper sidewall terminator is recommended when the water heater is vented through a sidewall.
Regarding the clearances from the exhaust terminator to the air inlet or opening, refer to the unit installation manual and venting manufacturer installation manual.
tice.
Ø5" DESCRIPTION
9007998005 9008189005 Wall Thimble (4”‐7”)
9007997005 9008190005 Wall Thimble (5”‐10”)
Support
9007989005 9008204005 Support Strap (1")
9007987005 9008181005 6” Straight Vent Pipe
9007986005 9008182005 12” Straight Vent Pipe
9007984005 9008183005 24” Straight Vent Pipe
9007983005 9008184005 36” Straight Vent Pipe
9007982005 9008185005 48” Straight Vent Pipe
Adjustable
9007985005 9008186005Adjustable Vent Pipe (7.0”‐
9.9”)
9007981005 9008187005 45 Degree Elbow
NovaVentWall Thim
ble
Straight
Elbow
Ø4"
9007980005 9008188005 90 Degree Elbow
9008146005 9008201005
Universal Adaptor‐3‐in‐1
(F‐F Adaptor, condensate drain,
& back‐flow preventer)
9007979005 9008203005 Female‐Female Adaptor
Backflow
Preventer
9007996005 90082020054” Backflow Preventer & F‐F
Adaptor
Firestop
9007988005 9008194005 Vertical Firestop
Adaptor
Ø 5" DESCRIPTION
9007999005 9008197005 Terminator Hood
9008004005 N/ASidewall Vent Terminator (Hood)
and Wall Thimble (4”‐7”)
9008005005 N/ASidewall Vent Terminator (Hood)
and Wall Thimble (5”‐10”)
9008144005 9008198005 Terminator Tee
9007995005 N/A Rain Cap
9008145005 9008200005 Extreme Weather Rain Cap
9007994005 9008191005 Drain Tee (Horizontal)
9007993005 9008192005 Drain Tee (Vertical) M‐F
Term
ination
Conden
sation Drain
Ø 4"
9007992005 9008195005 Flat Roof Flashing
9007991005 9008196005 Angled Roof Flashing
Storm
Collar
9007990005 9008193005 Storm Collar
Roof Flashing
Direct Vent Conversion Kit For
T-KJr2(110)/T-K4 (310)/
T-D2 (510)
Direct Vent Conversion Kit For
T-M32 (710/710A)
Direct Vent Conversion Kit For
T-M50 (910/910A)
3" Intake, 4" Exhaust 4" Intake & 4" Exhaust 5" Intake & 5" Exhaust
5.0" to 10.0" 9008147005 9008149005 9008208005
12.0" to 18.0" 9008148005 9008150005 9008209005
3" Intake, 4" Exhaust 4" Intake & 4" Exhaust 5" Intake & 5" Exhaust
5.0" to 10.0" 9008001005 9008206005 9008210005
12.0" to 18.0" 9008000005 9008207005 9008205005
Intake Hood (Galvanized)
Ø3" Ø4" Ø5"
9008142005 9008143005 9008180005
Includes : DV Conversion Kit, Concentric Termination, Universal Adaptor 3-in-1, Aluminum Flex and Gear Clamp
Concentric Direct-Vent Terminaton
9007667005
9007668005
9007669005
Concentric Direct-Vent Termination Kit
Water Heaters DV Conversion Kit
1A9007999005Sidewall Hood Terminator
900798000590° Elbow
Standard Sidewall Termination - Noncombustible Wall
(Example 1)
90081460054" Universal Appliance Adaptor Kit
1A
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007999005Sidewall Hood Terminator
900798000590° Elbow
90081460054" Universal Appliance Adaptor Kit
2A2A
Standard Sidewall Termination - Noncombustible Wall
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
900798300536" Straight Pipe
9007999005Sidewall Hood Terminator
90081460054" Universal Appliance Adaptor Kit
900798300536" Straight Pipe
900798000590° Elbow
3A
Standard Sidewall Termination - Noncombustible Wall
(Example 3)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
900798300536" Straight Pipe
4A9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
90081460054" Universal Appliance Adaptor Kit
900798000590° Elbow
Standard Sidewall Termination - Combustible Wall
(Example 1)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
5A
900798000590° Elbow
900798300536" Straight Pipe
90081460054" Universal Appliance Adaptor Kit
9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
Standard Sidewall Termination - Combustible Wall
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
6A
900798000590° Elbow
900798300536" Straight Pipe
900798300536" Straight Pipe
90081460054" Universal Appliance Adaptor Kit
9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
Standard Sidewall Termination - Combustible Wall
(Example 3)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
7A9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
90081460054" Universal Appliance Adaptor Kit
3" Air Intake Pipe(Not offered)
900798000590° Elbow
90081420053" Air Intake Hood
Direct-Vent Sidewall Termination - Combustible Wall
(Example 1)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
9007667005Direct VentCoversion Kit
8A9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
90081460054" Universal Appliance Adaptor Kit
900798200536" Straight Pipe
900798000590° Elbow
90081420053" Air Intake Hood
Direct-Vent Sidewall Termination - Combustible Wall
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
3" Air Intake Pipe(Not offered)
9007667005Direct VentCoversion Kit
9A
9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
900798200536" Straight Pipe
90081460054" Universal Appliance Adaptor Kit
900798000590° Elbow
900798200536" Straight Pipe
90081420053" Air Intake Hood
Direct-Vent Sidewall Termination - Combustible Wall
(Example 3)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
3" Air Intake Pipe(Not offered)
9007667005Direct VentCoversion Kit
10A
90081460054" Universal Appliance Adaptor Kit
90081470054" X 3" Concentric TerminationAdjustable (5"-10")
90081480054" X 3" Concentric TerminationAdjustable (12"-18")3" Flex Pipe
9007667005Direct VentCoversion Kit
Concentric Direct-Vent Sidewall Termination -
(Example 1)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note:9008001005 Concentric DV Termination Kit (5.0" to 10.0")9008000005 Concentric DV Termination Kit (12.0" to 18.0")Includes:- Direct Vent Conversion Kit- 3X4 Concentric Termination- Universal Adaptor 3-in-1- Aluminum Flex- Gear Clamp
90081470054" X 3" Concentric TerminationAdjustable (5"-10")
90081480054" X 3" Concentric TerminationAdjustable (12"-18")3" Flex Pipe
90081460054" Universal Appliance Adaptor Kit
11A
Concentric Direct-Vent Sidewall Termination -
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note:9008001005 Concentric DV Termination Kit (5.0" to 10.0")9008000005 Concentric DV Termination Kit (12.0" to 18.0")Includes:- Direct Vent Conversion Kit- 3X4 Concentric Termination- Universal Adaptor 3-in-1- Aluminum Flex- Gear Clamp
9007667005Direct VentCoversion Kit
900798300536" Straight Pipe
9007990005Storm Collar
9007995005Extreme Weather Rain Cap or9008145005Rain Cap
9007992005Flat Roof Flashing
9007988005Vertical Firestop
900798300536" Straight Pipe
900798000590° Elbow9008146005
4" Universal Appliance Adaptor Kit
900798300536" Straight Pipe
Standard Roof Termination(Flat Roof)
90079890051" Support Strap
12A
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
900798300536" Straight Pipe
900798000590° Elbow
9007991005Angled Roof Flashing
9007990005Storm Collar
9007988005Vertical Firestop
900798300536" Straight Pipe
90079890051" Support Strap
90081460054" Universal Appliance Adaptor Kit
13A
Standard Roof Termination(Angeled Roof)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007995005Extreme Weather Rain Cap or9008145005Rain Cap
900798600512" Straight Pipe
9007990005Storm Collar
9007992005Flat Roof Flash
900798400524" Straight Pipe
900798300536" Straight Pipe
recommended minimum distance of 4 ft. air intake
(not offered)
9007988005Vertical Firestop
900798000590° Elbow
90081460054" Universal Appliance Adaptor Kit
90079890051" Support Strap
3" air intake pipe(not offered)
14A
Direct-Vent Roof Termination(Flat Roof)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007995005Extreme Weather Rain Cap or9008145005Rain Cap
9007667005Direct VentConversion Kit
900798600512" Straight Pipe
9007988005Vertical Firestop
900798300536" Straight Pipe
900798400524" Straight Pipe
9007991005 Angled Roof Flash
9007990005Storm Collar
90081460054" Universal Appliance Adaptor Kit
90079890051" Support Strap
900798000590° Elbow
recommended minimum
distance of 4 ft. 15A
Direct-Vent Roof Termination(Angled Roof)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007995005Extreme Weather Rain Cap or9008145005Rain Cap
9007667005Direct Vent Kit
air intake (not offered)
3" air intake pipe(not offered)
Direct-Vent Sidewall TerminationCombustible Wall
(Example 1)
7B9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
90081460054" Universal Appliance Adaptor Kit
900798000590° Elbow
90081430054" Air Intake Hood
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
9007668005Direct Vent Conversion Kit
4" Air intake(Not offered)
8B9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
90081460054" Universal Appliance Adaptor Kit
900798000590° Elbow
90081430054" Air Intake Hood
Direct-Vent Sidewall TerminationCombustible Wall
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
4" Air intake(Not offered)
9007668005Direct Vent Conversion Kit
900798300536" Straight Pipe
9B9008004005Sidewall Hood Terminator and Wall Thimble (4"-7")
9008005005Sidewall Hood Terminator and Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
900798300536" Straight Pipe
900798300536" Straight Pipe
90081460054" Universal Appliance Adaptor Kit
900798000590° Elbow
90081430054" Air Intake Hood
Direct-Vent Sidewall TerminationCombustible Wall
(Example 3)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
4" Air intake(Not offered)
9007668005Direct Vent Conversion Kit
Concentric Direct-Vent Sidewall Termination
(Example 1)
10B
90081460054" Universal Appliance Adaptor Kit
90081490054" X 4" Concentric TerminationAdjustable (5"-10")
90081500054" X 4" Concentric TerminationAdjustable (12"-18")
4" Flex Pipe
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note:9008206005 Concentric DV Termination Kit (5.0" to 10.0")9008207005 Concentric DV Termination Kit (12.0" to 18.0")Includes:- Direct Vent Conversion Kit- 4X4 Concentric Termination- Universal Adaptor 3-in-1- Aluminum Flex- Gear Clamp
9007668005Direct Vent Conversion Kit
11B90081490054" X 4" Concentric TerminationAdjustable (5"-10")
90081500054" X 4" Concentric TerminationAdjustable (12"-18")
4" Flex Pipe
9007668005Direct Vent Conversion Kit
90081460054" Universal Appliance Adaptor Kit
Concentric Direct-Vent Sidewall Termination
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note:9008206005Concentric DV Termination Kit (5.0" to 10.0")
9008207005Concentric DV Termination Kit(12.0" to 18.0")
Includes:- Direct Vent Conversion Kit- 4X4 Concentric Termination- Universal Adaptor 3-in-1- Aluminum Flex- Gear Clamp
4"intake air pipe(not offered)
900798300536" Straight Pipe
14B
Direct-Vent Roof Termination(Flat Roof)
9007995005Extreme Weather Rain Cap or9008145005Rain Cap
900798600512" Straight Pipe
9007990005Storm Collar
9007992005Flat Roof Flash
9007988005Vertical Fire Stop
900798300536" Straight Pipe
90079890051" Support Strap
900798000590° Elbow
90081460054" Universal Appliance Adaptor Kit
air intake(not offered)
recommended min.
distance of 4ft.
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007668005Direct Vent Conversion Kit
4"intake air pipe(not offered)
15B
4"intake air pipe(not offered)
90081460054" Universal Appliance Adaptor Kit
9007988005Vertical Fire Stop
900798300536" Straight Pipe
9007991005Angled Roof Flash
900798600512" Straight Pipe
90079890051" Support Strap
900798000590° Elbow
900798000590° Elbow
recommended min.
distance of 4ft.
9007990005Storm Collar
Direct-Vent Roof Termination(Angled Roof)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007995005Extreme Weather Rain Cap or9008145005Rain Cap
9007668005Direct Vent Conversion Kit
air intake(not offered)
1C
Standard Sidewall Termination -Noncombustible Wall
(Example 1)
9008197005Sidewall Hood Terminator
900818800590° Elbow
90082010055" Universal Appliance Adaptor Kit
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
2C9008197005Sidewall Hood Terminator
90082010054" Universal Appliance Adaptor Kit
900818800590° Elbow
Standard Sidewall Termination -Noncombustible Wall
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
900818400536" Straight Pipe
3C
9008197005Sidewall Hood Terminator
900818400536" Straight Pipe
90082010054" Universal Appliance Adaptor Kit
900818800590° Elbow
Standard Sidewall Termination -Noncombustible Wall
(Example 3)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
900818400536" Straight Pipe
4C9008189005 Wall Thimble (4"-7")
9008190005 Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)9008188005
90° Elbow
90082010055" Universal Appliance Adaptor Kit 9008197005
5" Termination Hood
Standard Sidewall Termination -Combustible Wall
(Example 1)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
5C
90082010055" Universal Appliance Adaptor Kit
900818800590° Elbow
900818400536" Straight Pipe
9008189005Wall Thimble (4"-7")
9008190005Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
90081970055" Termination Hood
Standard Sidewall Termination -Combustible Wall
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
6C
90082010055" Universal Appliance Adaptor Kit
900818400536" Straight Pipe
900818400536" Straight Pipe
900818800590° Elbow
90081970055" Termination Hood
9008189005Wall Thimble (4"-7")
9008190005Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
Standard Sidewall Termination -Combustible Wall
(Example 3)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
7C
900818800590° Elbow
90081970055" Termination Hood
90081800055" Air Intake Hood
9008189005Wall Thimble (4"-7")
9008190005Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
Direct-Vent Sidewall Termination -Combustible Wall
(Example 1)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
9007669005Direct Vent Conversion Kit
5" air intake pipe(not offered)
8C9008189005Wall Thimble (4"-7")
9008190005Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
90081800055" Air Intake Hood
90081970055" Termination Hood
90082010055" Universal Appliance Adaptor Kit
900818800590° Elbow
Direct-Vent Sidewall Termination -Combustible Wall
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
9007669005Direct Vent Conversion Kit
5" air intake pipe(not offered)
900818400536" Straight Pipe
9C
90081800055" Air Intake Hood
900818800590° Elbow
900818400536" Straight Pipe
90082010055" Universal Appliance Adaptor Kit
90081970055" Termination Hood
9008189005Wall Thimble (4"-7")
9008190005Wall Thimble (5"-10")
(Please check the wall thickness for proper installation)
Direct-Vent Sidewall Termination -Combustible Wall
(Example 3)
Note: For direct-vent sidewall terminations that use two separate penetrations for the intake and exhaust, distance the intake and exhaust terminations at least 3 ft. away from each other, no matter the orientation.
9007669005Direct Vent Conversion Kit
5" air intake pipe(not offered)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
10C
90082010055" Universal Appliance Adaptor Kit
90082080055" X 5" Concentric TerminationAdjustable (5"-10")
90082090055" X 5" Concentric TerminationAdjustable (12"-18")
5" Aluminum Flex
Concentric Direct-Vent Sidewall Termination
(Example 1)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007669005Direct Vent Conversion Kit
Note:9008210005 Concentric DV Termination Kit (5.0" to 10.0")9008205005 Concentric DV Termination Kit (12.0" to 18.0")Includes:- Direct Vent Conversion Kit- 5X5 Concentric Termination- Universal Adaptor 3-in-1- Aluminum Flex- Gear Clamp
90082010055" Universal Appliance Adaptor Kit
90082080055" X 5" Concentric TerminationAdjustable (5"-10")
90082090055" X 5" Concentric TerminationAdjustable (12"-18")
5" Aluminum Flex
9007669005Direct Vent Conversion Kit
5" air intake pipe(not offered)
11C
Concentric Direct-Vent Sidewall Termination
(Example 2)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
900818400536" Straight Pipe
Note:9008210005 Concentric DV Termination Kit (5.0" to 10.0")9008205005 Concentric DV Termination Kit (12.0" to 18.0")Includes:- Direct Vent Conversion Kit- 5X5 Concentric Termination- Universal Adaptor 3-in-1- Aluminum Flex- Gear Clamp
Standard Roof Termination(Flat Roof)
900818800590° Elbow9008201005
5" Universal Appliance Adaptor Kit
900818400536" Straight Pipe
9008193005Storm Collar
9008200005Extreme Weather Rain Cap
9008195005Flat Roof Flashing
9008194005Vertical Firestop
900818400536" Straight Pipe
12C
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9008196005Angled Roof Flashing 9008193005
Storm Collar
900818400536" Straight Pipe
90082010055" Universal Appliance Adaptor Kit
900818800590° Elbow
900818400536" Straight Pipe
9008194005Vertical Firestop
Support Strap
13C
Standard Roof Termination(Angled Roof)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9008200005Extreme Weather Rain Cap
90082010055" Universal Appliance Adaptor Kit
900818800590° Elbow
Support Strap
900818400536" Straight Pipe
9008194005Vertical Firestop
900818300524" Straight Pipe
900818200512" Straight Pipe
9008193005Storm Collar
9008195005Flat Roof Flash
air intake
recommended min. distance of 4 ft. 14C9008200005Extreme Weather Rain Cap
Direct-Vent Roof Termination(Flat Roof)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007669005Direct Vent Conversion Kit
5" air intake pipe(not offered)
900818200512" Straight Pipe
9008193005Storm Collar
9008196005Angled Roof Flash
9008194005Vertical Firestop
900818400536" Straight Pipe
900818300524" Straight Pipe
90082010055" Universal Appliance Adaptor Kit
Support Strap
900818800590° Elbow
air intake
recommended min. distance of 4 ft. 15C9008200005Extreme Weather Rain Cap
Direct-Vent Roof Termination(Angled Roof)
These illustrations are intended as basic guides only. There is a wide variety of situations that will require different parts and/or modifications to these basic designs. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practices.
9007669005Direct Vent Conversion Kit
5" air intake pipe(not offered)