variable refrigerant flow systems: technology...
TRANSCRIPT
1
ASHRAE Winter Conference 2016
Variable Refrigerant Flow Systems:
Technology Introduction
Dermot McMorrow, CEng Peng
Sponsored byASHRAE Technical Committee 8.7
Copyright Materials
• Copyright 2016 by ASHRAE. All rights reserved.
• No part of this presentation may be reproduced without written permission from ASHRAE, nor may any part of this presentation be reproduced, stored in a retrieval system or transmitted in any form or by any means (electronic, photocopying, recording or other) without written permission from ASHRAE.
2
2
AIA/CES Registered Provider
• ASHRAE is a Registered Provider with The American Institute of
Architects Continuing Education Systems. Credit earned on completion
of this program will be reported to CES Records for AIA members.
Certificates of Completion for non-AIA members are available on
request.
• This program is registered with the AIA/CES for continuing professional
education. As such, it does not include content that may be deemed or
construed to be an approval or endorsement by the AIA of any material
of construction or any method or manner of handling, using,
distributing, or dealing in any material or product. Questions related to
specific materials, methods, and services will be addressed at the
conclusion of this presentation.3
Learning Objectives
• Provide overview of variable refrigerant flow (VRF) system technology
• Discuss considerations for design and application of VRF systems in buildings
• Describe applicability of ASHRAE Standard 15, Safety Standard for Refrigeration Safety requirements to VRF systems
• Review application of VRF systems in Green Buildings in cold climates
4
3
DEFINITION – What is Variable Refrigerant Flow?
ASHRAE Journal, April 2007The term “Variable Refrigerant Flow” refers to the capability of an HVAC system to control the amount of refrigerant flowing to each of the indoor units/evaporators, enabling the use of multiple evaporators of differing capacities and configurations, individualized comfort control, simultaneous heating and cooling in different zones with heat recovery from one zone to another.
AHRI Standards & Policy Committee, June 2009 Variable Refrigerant Flow (VRF) System is an engineered direct exchange (DX) multi‐
split system incorporating at least one variable capacity compressor distributing
refrigerant through a piping network to multiple indoor fan coil units each capable
of individual zone temperature control, through a zone temperature control devices
and common communications network. Variable refrigerant flow implies three or
more steps of control on common, interconnecting piping.
5
Exp
ansi
on C
ycle
Enthalpy
Low psi
High psi
Typical Pressure-Enthalpy Diagram
Condensing
EvaporatingTH 22
Refrigerant in liquidand gaseous states S
ub-c
oole
d re
frig
eran
t
Superheat Differential
TH 23
Pressure
Operating Parameters6
4
Indoor Units
WCU
InverterVariable speed control
Compressor
Accumulator
Heat Exchanger
Condenser
4-Way Valve – Changeover Heating to Cooling
Variable Refrigerant Flow – Typical System Elements
Heat Rejected
COOLING MODE
Linear Expansion Valve
T1 T2
T
HEAT SINK
WATER LOOP
GROUND
7
Indoor Units
WCU
InverterVariable speed control
Compressor
Accumulator
4-Way Valve – Changeover Heating to Cooling
Heat Absorbed
HEATING MODE
Linear Expansion Valve
T1 T2
T
Heat Input ThruCompression
Refrigerant Flow
HEAT SINK
WATER
GROUND
Variable Refrigerant Flow – Typical System Elements
ASHRAE Winter Conference 2016
8
5
What is Variable Refrigerant Flow (VRF)?Compressor Speed
Heating or
Cooling Output
Lower Limit of Compressor Speed and Capacity
9
VRF Technology Benefits
• Zoning Applications
• Variable Capacity
• Distributed Control
• Low Operating Sound
• Simultaneous Heating & Cooling
• Effective Energy Usage
• Quick Installation
• Low Ambient Operation
• Low Maintenance Costs10
6
VRF System Types – Heat Pump
• Heats or cools (H/C) a given space• Indoor units operate in same mode of H/C
11
System Types – Heat Recovery
• Provides simultaneous H/C
• Indoor units have individual control and H/C mode capabilities
• Energy is transferred from one indoor space to another through a refrigerant line
• Double heat recovery potential in water-source VRF formats
12
7
Water-Source VRF Heat PumpHeat Recovery in Water Loop Only
Water Circuit
System A in COOLING Mode(refrigerant absorbing heat)
Heat is recovered between the WCU within the water loop
System B in HEATING Mode(refrigerant discharging heat)
PQHY Unit “A”
PQHY Unit “B”
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
Heating
13
Two-Pipe Heat Recovery VRF System
14
8
Three-Pipe Heat Recovery VRF SystemsParallel Configuration Hybrid Series/Parallel Configuration
15
Zone Load Report – Peak Heating/Cooling
16
9
DOE Report – Annual Hours of Heat Recovery
17
VRF Applications
• High- or low-rise offices
• Educational facilities
• Healthcare facilities
• Multiple-tenant residential buildings
• Data center cooling-only applications
• Retail stores
• Hospitality centers
• Restaurants
• Banquet halls
• Hotels
• Motels
• Cultural facilities
18
10
Zoned Comfort Control
• Zone-by-zone temperature control
• Seamless H/C switchover for decentralized systems
• Traditional unitary system standards – ASHRAE Standard62.1
• Integrates with DOAs
• Integrates with ERB
• Factors include:– Design zone air change rate
– Level of ventilation air supplied
– Degree of airflow filtration
Figure: System Design 19
Annual Operating Efficiency Characteristics
Key Performance Factors include:
• Occupancy profile
• Orientation
• Design ventilation air requirements
• Construction
• Local outdoor ambient design parameters
• Air source vs. water-source heat rejection strategies
20
11
ECWT @ 50 F Nom CLG kW Output Factor Actual CLG kW Output Nom CLG Input kW Factor Actual CLG input kW CLG COP
WCU 6 T 21.3 1 21.3 3.85 0.66 2.54 8.38
WCU 8 T 26.2 1 26.2 5.61 0.66 3.70 7.08
WCU 10 T 35.2 1 35.2 7.51 0.66 4.96 7.10
WCU 12 T 42.6 1 42.6 7.94 0.66 5.24 8.13
WCU 14 T 49.6 1 49.6 9.73 0.66 6.42 7.72
WCU 16 T 56.4 1 56.4 11.55 0.66 7.62 7.40
WCU 18 T 63.3 1 63.3 13.5 0.66 8.91 7.10
WCU 20 T 70.3 1 70.3 15.47 0.66 10.21 6.89
ECWT21
Life Cycle Cost Comparison
• Installed Capital Costs
• Life Cycle Operating Costs
▫ Annual operating costs
▫ Routine maintenance costs for inspection
▫ Equipment life expectancy• 15-20 years for air source
• 20-25 years for water source
22
12
Industry Performance StandardsAHRI Standard 1230 (for VRF systems with capacity ≤ 760,000 Btu/h)
Table: VRF Multi-split System Classifications
23
VRF Outdoor Units
• Heat Pump
• Heat Pump with Heat Recovery
• Variable Speed Compressor
• Multiple Modules can be combined to operate as a higher capacity system
• Air-to-Refrigerant
• Water-to-Refrigerant
24
13
Indoor Units• Wall-mounted
• Recessed-ceiling cassette
• Ceiling-suspended
• Floor-standing
• Ducted
25
Local Controller
Central Controller
Control Communication
Controls
14
Local and Remote Monitoring
• Manufacturer-specific controls protocol to communicate between outdoor units, indoor units, and available system-specific accessories
• Designer should consult:▫ Operation manual
▫ Systems and component engineering
27
System Operation Factors
• Load Management
• Cooling Operation
• Heating Operation
• Heat Recovery Operation
– Two-pipe systems
– Three-pipe systems
– Multi-layer heat recovery in water-source VRF systems
• Defrost Operation
• Oil Recovery Operation
• Humidity Control
ASHRAE Winter Conference 2016
28
15
Load Management
• Indoor units control capacity through an EEV or LEV
• Outdoor unit conducts load management through inverter-driven variable-speed compressor
• Alternative combo for varying capacity and variable-speed outdoor unit fans
29
Cooling Operation
Outdoor Units
• Compressor(s) adjust to match total system load by varying refrigerant flow with compressor speed or capacity control
• Main driver of system efficiency
Indoor Units• Variable cooling capacities
• LEVs/EEVs are controlled to maintain a target superheat value or evaporator temp
• Temp difference ↓
(setpoint temp – zone temp)
Then superheat ↑
(vapor pipe thermistor temp –liquid pipe thermistor temp)
And vice versa
30
16
Heating Operation
Outdoor Units• EEV/LEV electronic
expansion valve opens and closes to maintain target superheat value
• Main driver of system efficiency
Indoor Units• EEV/LEV controlled to
maintain subcooling
• Temp difference ↓
(setpoint temp – zone temp)
Then subcooling ↑
And vice versa
31
Heat Recovery Operation
• Two-Pipe Systems
• Three-Pipe Systems
• Multilayer Heat Recovery in Water-Source VRF Systems
32
17
Two-Pipe Heat Recovery Systems
In a balanced system, peak zone heating and cooling loads are equal:
1. Refrigerant gas is delivered from outdoor unit → heat recovery control unit (HRCU)
2. Subcooled refrigerant or refrigerant gas → indoor units in cooling or heating mode
3. Refrigerant vapor leaves indoor unit → HRCU
4. Vapor → outdoor unit where it is compressed
5. Cycle repeats
33
Three-Pipe Heat Recovery Systems
• HRCU controls direction of refrigerant flow through indoor units
• In cooling mode, indoor unit is an evaporator
Low pressure vapor pipe OPENS
High pressure vapor pipe CLOSES
• In heating mode, indoor unit is a zoned condenser
Low pressure vapor pipe CLOSES
High pressure vapor pipe OPENS
• Ports ≤ 634
18
Multi-layer Heat Recovery in Water-Source VRF
2 levels of heat recovery:– Heat energy exchanged between zones
at refrigerant level
– Heat energy exchanged between systems through water loop
35
Defrost Operation
Systems that require heating operation to shut off:
– Reverse refrigerant flow
– Outdoor unit coil becomes a condenser to melt frost
– Indoor units switch off
Systems that do not require heating operation to shut off:
– Split-coil configuration in outdoor unit(s) defrosts only half the coil at a time,
– Defrost each outdoor unit separately, or
– Defrost outdoor units on a single system together
36
19
Oil Recovery Management
• Manufacturers may include oil separator for each compressor in system
• To reclaim small amount of oil that settles in system:▫ Controls open EEV/LEV in all indoor units after a set
period of compressor operation
▫ Compressor switches to a predetermined speed to ensure oil in system flushes back to the compressor sump
▫ Oil recovery cycle lasts from 3-6 min
• Included in AHRI testing if expected to occur every 2 hours or less
37
Humidity Control
• Indoor unit dry mode activates when zone temp > dew-point temp
• A supplemental humidification unit can be used through the ventilation air system to▫ Humidify cool dry supply air through moist exhaust
air
▫ Send moisture from supply air to the dry exhaust air
38
20
Design Considerations• Building orientation and layout
• New construction or retrofit applications
• Construction schedule
• Building occupancy characteristics
• Peak heating and cooling load profiles
• Integration of renewable energy sources
• Zone-specific design considerations
• Building space allocation for mechanical equipment
• Application-specific ventilation air requirements
• Local design weather conditions
• Local/remote control/monitoring requirements
• Life-cycle performance
• Green building certifications expectations
Figure: Indoor Unit Layout 39
Water-Source VRF Systems
• High annual system COP levels
• Consistent performance
• Low-or-high ambient heating or cooling
• No defrost cycles
• Multi-layer heat recovery
• Nominal capacities for entering water temp:
– Heating - 21°C
– Cooling - 29°C
40
21
Air-Source VRF Systems
• External ambient design applications between 115 and -20°F
• High-sensible-heat-ratio cooling applications
• External ambient heating-dominant applications lower than -13°F
• Supplemental Heating Strategies to offset ambient derating at lower temperatures- Zone or Condensing Unit Side
41
Low External Ambient Heating –Dominant Applications
• Four strategies:▫ Integration with supplemental heating
sources
▫ Water-source VRF systems
▫ High-heating-performance air-source VRF units
▫ Locating air-source unit in a temperate or controlled ambient environment
42
22
Integration with SupplementalHeating Sources
• Supplemental heating components can be enabled based on:▫ Preset ambient temperature measured at
outdoor unit
▫ Zone-by-zone basis
43
High-Heating PerformanceAir-Source VRF Units
• 100% nominal heating performance as low as -15°C ambient and 80% heating output at -25°C
• Strategies used to achieve above levels include:▫ Flash injection technology
▫ Staged compression cycle with intermediate economizer
44
23
Flash Injection Technology• Flash injection
cycle only operates in heating mode
• Increased heating output at lower ambient temperatures
• Compressor speed is optimized based on the circuit load
45
Staged Compression Cycle
• Alternative approach to achieving higher-temperature outputs at lower ambient conditions
• Adopts compound compression with intermediate economizers
46
24
Generating Radiant Heating/Cooling and Domestic Hot Water
• System includes a refrigerant-water indoor heat exchange module with integrated controls
• Strategies for achieving each capability include:▫ Radiant floor or cooling/heating panel that receives
water from a refrigerant-to-water heat exchanger replaces indoor unit(s)
▫ VRF system can generate domestic hot water with leaving water temp ≤ 71°C by using a heat exchanger with a booster refrigeration cycle
▫ Refrigerant-to-water heat exchanger can be used for preheating purposes
47
VRF System Design Example
1. Performing a Load-Profile Analysis
2. System Type Selection, Zoning and Potential for Heat Recovery
3. Accurately Sizing Outdoor & Indoor Units
4. Selecting Indoor Units
5. Ventilation Air Strategy
6. Refrigerant Piping
48
25
Performing a Load-Profile Analysis
• Careful planning at the design stage
• Detailed analysis of project needs
• Building’s annual H/C load profiles are required before equipment is selected and sized
49
System Type Selection, Zoningand Potential for Heat Recovery
• System selection driven by determining best balance between operating costs and capital costs per unit area.
• A complete energy analysis of the building:
– To evaluate system type(s)
– To determine most appropriate system for application
50
26
Accurately Sizing Outdoor & Indoor Units
– Derating factor: Verifies chosen system will provide the required capacity at design temps
Factors to consider include: – Outdoor unit size: Based on actual peak
cooling or heating load
– Effect of local ambient conditions on system performance
– Connected nominal capacity of indoor units is within operating parameters of selected system
51
Design Example: Outdoor Unit SizingOutdoor Unit Sizing is based on actual peak cooling or heating load, whichever is higher. Peak cooling load at 3:00pm in August = 27.5 kW
Peak heating load at 8:00pm in January = 21.7 kW
28 kW ODU should be selected:• 28 kW cooling load
• 31.7 kW heating load
Account for derate and corrected heating capacity factors:• Heating:▫Design winter ambient = –9°C, Derate factor = 0.74▫Refrigerant piping length correction factor at 37 m = 0.98▫Corrected heating capacity = 31.7 × 0.74 × 0.98 = 23 kW
• Cooling:▫Design summer ambient = 34.4°C db, Derate factor = 1.00▫Refrigerant piping length correction factor at 37 m = 0.98▫Corrected cooling capacity = 28.2 × 0.98 = 27.6 kW
52
27
Selecting the Indoor Units
Factors to consider:– Peak cooling and heating
capacities
– Ratio of sensible to latent cooling load
– Air change rate (following ASHRAE Standard 62 criteria)
– Sound performance criteria
– Terminal unit air-side distribution and location restrictions
– Ventilation air strategy
– Any integration with supplemental heating components
Design Example: Indoor Unit Sizing• Connected nominal capacity of IDU must fall within operating parameters
of the selected system: VRF HP systems with a connected nominal capacity of up to 130% of OFU nominal capacity. Total indoor unit connected capacity = 35.8 kW Nominal outdoor unit capacity is 28 kW Therefore, 35.8 kW/28 kW = 128%
• The reception area requires other design considerations: Peak cooling load = 6.6 kW Peak heating load = 5.5 kW Air change rate = 4 ach Sound performance criteria = NC 35 Ventilation supply = 0.04 L/s
• Designer could choose a ceiling-recessed IDU with: Nominal cooling output of 7 kW Nominal heating output of 7.9 kW Sound performance rating of NC 30 Nominal airflow rate of 225 - 315 L/s 54
28
System Ventilation Air Strategy
• Three main strategies:– Direct
– Integrated
– Decoupled
• Selection depends on:– Climate
– Application
– Equipment type55
Refrigerant Piping Design
• Refrigerant liquid and gas piping sizes
• System design verification based on:
– Max height and length differences
– Ratio of indoor unit to outdoor unit nominal capacity
• Equipment bill of materials/quantities
• Project numbering and product specifications
• Control and power schematics
56
29
Local System Control
• Individual control by local controllers
• Temperature sensing at the return air or local controller
• Several indoor units can be grouped together under one local controller (shown above).
• Grouped indoor units may operate under individual control but must function in same mode
• Functions include:– Local setpoint control
– Scheduling and setback capability
– Cooling/heating/auto modes
– Fan-coil/fan speed control 57
Central System Control
• Users can monitor and optimize the operation of multiple zones, including any decentralized compatible energy recovery ventilators
• Functionality offers: – Seasonal scheduling
– Remote monitoring and diagnostics
– Ability to integrate building plans and schematics
– System energy management such as sliding temperature control, optimized start-up control, and setback capabilities 58
30
Remote System Monitoring and Control
• Users can access system remotely for:– Operation
– Monitoring
– Optimization
• Access can be secured through:– Web-based access licenses
– Manufacturer-specific software tools
59
Gateway Control to Integrate with Third-Party, Protocols, Devices or Systems
• VRF systems can monitor and control third-party devices through network-based control components.
• VRF systems may be integrated with building management systems (BMS) through a single-interface modulethat communicates with industry standard communication protocols.
60
31
Safety Considerations for Refrigerants• ASHRAE Standard 15 specifies:
– Safe design, construction, installation, operation and inspection of mechanical refrigeration systems
• To successfully apply ASHRAE Standard 15 to a project requires:
– Classification and RCL of the refrigerant used
– Classification of occupancy type in which indoor unit or piping will be located
– Total amount of refrigerant used in system
– Any individual occupied zone(s) geometry and connected zones
– Methodology to calculate maximum amount of refrigerant that can be safely dispersed into a specific zone
• NFPA Standard 70 specifies:– Options available to manage smaller
spaces
• ASHRAE Standard 34 lists the most current information related to:
– Refrigerant designations, safety classifications, and refrigerant concentration limits (RCL)
61
HVAC Industry Standards/Guidance• ARI 1230 Testing Standard
• ASHRAE VRF Design Guide Equipment & Systems 2012
• ASHRAE 34 2010 Safety Classification of Refrigerants
• ASHRAE 15 2010 Safety Standard
• CSA B52 2013 Refrigerant System Safety Standard
• CSA 22.2 No. 236 Product Safety Standard
• ASTM B280 Refrigerant Piping/Tubing Standard
• ASME 31.5 Refrigerant Piping/Tubing Standard
• ASME 16.22 Refrigerant System Component Standard
• NATIONAL & PROVINCIAL Building Codes62
32
No CRN Numbers, Refrigerant Relief Valves
63
64
33
Refrigerant Pipework Design and Installation Guidelines
65
Refrigerant Pipework Design and Installation Guidelines
66
34
67
Determining the Space Volume for Refrigerant Dilution?
68
35
Classification of Refrigerants – ASHRAE 34 & CSA B52
69
Classification of Systems – ASHRAE 15 & CSA B52
36
Establishing the Impact of Building Occupancy Type on Code RCL Requirements
71
72
37
73
ASHRAE 34 Standard – Refrigerant Concentrations
38
CODE – Refrigerant Concentrations
75
Why Do the RCL Values Sometimes Differ from Those in ASHRAE 34?
The value listed in CSA B52 Table 1 references the allowed % volume of refrigerantwhich is equivalent to 69,100 ppm/v (6.9% vol.) of refrigerant. This is the value used in calculating RCL when a building is located at 1500 m (or higher) above sea level taking into account for the adjustments in air density and associated impact on oxygen levels.
The value listed in ASHRAE 34 Table 1 references the allowed % volume of refrigerantwhich is equivalent to 140,100 ppm/v (14% vol.) of refrigerant. This is the value used in calculating RCL when a building is located at sea level. The adjustment factor for RCL considering ODL and ATEL. For a location @ 100 m above sea level RCL = 25.78 lbs/1000 ft3
39
Location Altitude, m ATEL, kg/m3 ODL, kg/m3 R-410 A RCL,lbs/1000 ft3
Halifax 145 m 0.4155 0.4163 25.90
Quebec City 98 m 0.4131 0.4163 25.78
Montreal 233 m 0.4086 0.4163 25.50
Ottawa 70 m 0.4140 0.4163 25.84
Toronto 105 m 0.4128 0.4163 25.77
Winnipeg 238 m 0.4085 0.4163 25.55
Saskatoon 481 m 0.4004 0.4163 25.24
Calgary 1084 m 0.3805 0.3331 20.79
Edmonton 671 m 0.3941 0.4163 24.60
Vancouver 152 m 0.4113 0.4163 25.67
Refrigerant Concentration Levels – Evaluating R‐410 A ‐ ATEL & ODL
The lowest value of ATEL vs. ODL must be applied in each case
77
Confirming if the System Meets the RCL Levels?Commercial Office/Location Toronto/Consulting Table 1/ASHRAE 34 – RCL = 26 lbs
IU
1000 ft3 1000 ft3 1000 ft3
Smallest Occupied Space - Dilution Volume =
1000 ft3
IUIU
IU
CU10 T
IU IU IU IU IU
Total System Charge = 22 lbs
78
40
What if the Refrigerant Concentration Exceeds the Code Levels?1. Reduce the system refrigerant volume – Decentralize Condensing Units/System
IU
CU10T
IU IU IU IU IU
IU IU IU IU IU IU
CU5T
CU5T
79
What if the Refrigerant Concentration Exceeds the Code Levels?1. Reduce the system refrigerant volume – Re-evaluate VRF System Selection
- Heat Recovery vs. Heat Pump VRF System
N
S
Heat Pump System # 1
Heat Pump System # 2
80
41
What if the Refrigerant Concentration Exceeds the Code Levels?2. Increase the refrigerant dilution volume – Re-evaluate System Zoning
IU
1000 ft3 1000 ft3 1000 ft3
Connecting Spaces - Total Dilution Volume = 3000 ft3
Code Table 1 Note (c) ‘When the air duct system serves several enclosed spaces, the permissible quantity of refrigerantin the system shall not exceed the amount determined by using the total volume of those spacesin which the airflow cannot be reduced to less than one-quarter of its maximum when the fan is operating.’
81
What Next if the Refrigerant Concentration Exceeds the RCL Levels?2. Increase the refrigerant dilution volume – Re-evaluate Dilution Transfer Openings
ISO/FDIS 519-36.3.2 Dilution transfer openings for natural convection
Dilution Transfer Area Opening = 0.0032 x M/(QLMV * V)
where,
A = required opening area, m2
M = refrigerant charge, kgV = room volume, m3
QLMV = RCL is the maximum refrigerant concentration for the space, kg/m3
ASHRAE 15-2010 7.3.1 Non-connecting Spaces
‘Where a refrigerating system or part of therefore is located in one or more enclosedoccupied spaces that do not connect through permanent openings or HVAC ducts, the volume of the smallest occupied space shall be used to determine the refrigerant quantity limit in the system.’
The Japanese Refrigeration Standard [JRA-GL13] defines a permanent opening as one that has an area of 0.15% or more of the total floor area of the smaller enclosed occupied space in which refrigerant-containing parts are located.
82
42
System Expansion for Future Reconfiguration
• During design phase, designer and client can discuss any possible future or changing needs within the building envelope
• Easy system expansion or reconfiguration as building needs change, like:▫ Upsizing VRF outdoor units to anticipate supplementary
indoor units
▫ Indoor units can be added to the VRF system
▫ Indoor units can be exchanged for different models or capacities
83
Optimizing VRF Systems Minimize Environmental Impact
• Part-load capabilities, modular design, zoned approach, heat recovery operation, and use of VFD compressors provide comfort while consuming less energy
• Factors that increase efficiency:
– Correct sizing
– System control
– Proper maintenance
– Correct installation
– Maximizing heat recovery potential
– Zone control and energy performance optimization
43
What Constitutes Good HVAC System Design Practice???
Good Design = Sustainable Design?
85
What is Sustainable Design?‘Sustainable design is defined as creating a product (building) that has maximum impact for our client but has minimum impact on the earth or its resources, both now and in the future.’
86
44
What is the Fundamental Requirementof an HVAC System in a Building?
‘Provide the desired environmentto realize occupant comfort’
V
87
What Environmental Conditions Facilitate Human Comfort?
88
45
Comfort Goals 1. Space Temperature2. Space Humidity3. Air Motion4. Air Quality5. Air Changes per Hour6. Air and/or water velocity requirements7. Local Climate8. Space Pressure Requirements9. Capacity requirements from a load calculation analysis10. Redundancy 11. Spatial requirements12. Security Concerns13. First Cost14. Operating Cost including energy and power costs15. Maintenance Cost16. Reliability17. Flexibility18. Controllability19. Life Cycle Analysis 20. Sustainability of design21. Acoustics and Vibration22. Mold & mildew prevention
Additional Goals1. Increasing marketability of rental spaces2. Increasing net rental income3. Increasing property salability4. Public Image of Property.
2012 ASHRAE Handbook‐
HVAC Systems & Equipment
89
Complete Building Integration with the Environment
90
46
Where Do I Start and Where Do I Finish?
Five key strategies for optimizing the performance of building systems: 1. Where feasible, reduce the total output or the duty seen by the system.
2. Make use of available environmental resources (thermal for HVAC systems).
3. Optimize the efficiency of the individual components of the system.
4. Accurate system control and functional coordination of the components.
5. Where possible, offset system energy input with renewable energy sources.
91
What are the hierarchy of building elementsthat must be considered during the design process?
92
47
Building: Two Story, LEED Platinum 36,000 ft2 Office BuildingOwner: Upper Thames Regional Conservation AuthorityLocation: London, Ontario Design Data: Winter/Summer – 160C/ + 300C
Building Name: Water‐shed Conservation Centre
93
94
48
Solar Wall Technology Tempering Ventilation Air
95
Solar Wall and Earth Tube Layout
96
49
Solar Wall Installation
97
Solar Wall Installation
98
50
AUGUST DATA- ENERMODAL ENGINEERING
FEBRUARY DATA- ENERMODAL ENGINEERING
Ventilation Air Preheat/Cool via Earth TubeWINTER: UP TO 20OF TEMPERATURE RISESUMMER: UP TO 6OF TEMPERATURE DROP
99
STORAGE CLASSROOM
MEETINGOFFICEOFFICE
OUTSIDE AIR (OA)-VENTILATION AIR
SUPPLY AIR
RETURN AIR
AHU
10% OA 40% OA
30% OA15% OA15% OA
35% OA
PROBLEM: YOU END UP OVER-VENTILATING MOST SPACES
ASHRAE Std 62.1
AHU IS USED FOR:1. Heating2. Cooling3. Ventilating
T
Ventilation System Design Concept
100
51
STORAGE CLASSROOM
MEETINGOFFICEOFFICE
OUTSIDE AIR (OA)-VENTILATION AIR
SUPPLYAIRAHU
10% OA 40% OA
30% OA15% OA15% OA
ASHRAE 62.1: OUTSIDE AIR IS A FUNCTION OF AREA AND NUMBER OF PEOPLE IN SPACEDEMAND CONTROL VENTILATION
100% OA
AHU IS USED FOR:Ventilating only
Heating and cooling is done through dedicated zonal units
CO2
OO CO2
H/C
VFD ON SUPPLY FAN
T
Ventilation System Design Concept
101
Ventilation System Design
102
52
Ventilation System Design – DOAS Unit
103
Ventilation System Design
104
53
Ventilation System Design
105
Ventilation System Design
106
54
Ventilation System Design
107
108
Variable Refrigerant Flow Condensing Units
55
Variable Refrigerant Flow Piping Schematic
Heat Pump
Compressor Energy1 kW
Low Temperature RenewableHeat Recovered from the Air
High TemperatureHeat Output to Space
5 kW
Heat Pump
Compressor Energy1 kW
Heat rejected to Outside Ambient
Space Cooling Input 5 kW
109
Variable Refrigerant Flow System Piping Layout
110
56
Variable Refrigerant Flow System Layout – BC Controller Installation
111
Variable Refrigerant Flow System Layout – Ducted Indoor Units
112
57
Variable Refrigerant Flow System Layout – Ducted Indoor Units
113
Variable Refrigerant Flow System Layout – Cassette Style Units
114
58
116
59
SUMMERWINTER
Domestic Hot Water Heating
SPRING, AUTUMN SPRING, AUTUMN
Variable Refrigerant Flow System Layout –Heat Recovery Potential
TANK
Bathroom
Shower
Sanitary equipment
117
Pump Water
LEV
Booster Unit
Comp.R134
a
CONDENSING
UNIT
BC controller
Indoor unit
Indoor unit
R410A
Up to 2.15 m3/h or 9.46 gpm
T_water_outlet+5degC(9F)75 (167F)
(160F)
40 (104F)
50 (122F)
65 (149F)
Closed loop circuit
Treat the water with additive
TANK
Bathroom
Shower
Sanitary equipment
Heat recovery
Cooling
Variable Refrigerant Flow System Layout – Heat Recovery Potential
60
119
Variable Refrigerant Flow System Layout – Heat Recovery Potential
Variable Refrigerant Flow System Layout – Heat Recovery Potential
120
61
Variable Refrigerant Flow System Layout – Heat Recovery Potential
121
Building Energy Analysis & Performance
Additional Capital Cost 160,000 $Savings per Year 33,726 $Payback Period 4.74 Years
The latest field measurements indicate annual energy usage 61.6 kwh/m2/yearHVAC System = 26-28 kwh/m2/yr
122
62
Questions/Conclusion
123
Evaluation and Certificate
• ASHRAE values your comments about this course. You will receive your Certificate of Attendance when you complete the online course evaluation at this URL: http://ali.ashrae.biz/2016winterconferenceAccess code: d4c2 Be sure to add your appropriate license numbers.
• If you have any questions about ASHRAE Certificates, please contact Kelly Arnold at [email protected]
• If you have any questions about ASHRAE courses, please contact Martin Kraft, Managing Editor, at [email protected]
124
63
ASHRAE Career EnhancementCurriculum Program
Expand your knowledge of IAQ and Energy Savings Practices through a select series of ASHRAE Learning Institute courses
• Receive up-to-date instruction on new technology from industry experts
• Gain valuable HVAC knowledge
• Accelerate your career growth
• Receive a certificate for successful completion of the course series
Visit www.ashrae.org/careerpath to learn more.
ASHRAE Professional Certification• Do you want to stand out from the crowd? Become ASHRAE
certified. ASHRAE certification serves as a springboard for your continued professional development.
• Assure employers and clients that you have mastered the body of knowledge that subject matter experts have identified as reflecting best practices.
• Please visit the following URL to learn more about our programs: www.ashrae.org/certification▫ Building Energy Assessment Professional
▫ Building Energy Modeling Professional
▫ Commissioning Process Management Professional
▫ Healthcare Facility Design Professional
▫ High-Performance Building Design Professional
▫ Operations & Performance Management Professional126