valve tech laboratory,

17
580-256-7677 FAX 256-7677 Email: [email protected] 506 48TH P.O. BOX 746 WOODWARD, OK 73802 VALVE TECH LABORATORY, DCP VALVES TESTED BY VALVE TECH LABORATORY, INC. Forgan 580-256-7677 WOODWARD, OK 73801 October 06, 2021 JOB # 16725

Upload: others

Post on 22-Mar-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

580-256-7677 FAX 256-7677 Email: [email protected]

506 48TH P.O. BOX 746 WOODWARD, OK 73802

VALVE TECH LABORATORY,

DCP

VALVES TESTED

BY VALVE TECH LABORATORY, INC.

Forgan

580-256-7677

WOODWARD, OK 73801

October 06, 2021

JOB # 16725

Valve Tech Laboratory, Inc.

580-256-7677 Fax: 256-7677 Email: [email protected]

506 48TH P.O. BOX 746 WOODWARD, OK 73802

March 21, 2022

DCP

12260 Road R 15 miles East on HWY 54, 1.5 miles North

Liberal, KS 67901

Re: Valves tested in October

Dear Shannon Burk,

On October 6, 2021 we were asked to test and/or repair valves at the Clem. Eight (8) relief and vent valves were

inspected under Work Order “16725”.

The valves were tested and reset per your instructions. All tests were completed in accordance with the National

Board Inspection Code. Any valve failing to meet specific requirements set forth by the manufacturer, National Board

of Boiler and Pressure Vessel Inspectors or your company was considered in need of adjustment of repair .

Enclosed you will find the register of the valves that were tested and reset. The register will provide specific

information about each valve for quick reference. The column TEST NO., found on the register, is a number given to

each valve in the order in which it was brought to the mobile unit for testing. This number is a “unique identifier”

which is stamped on the last line of the repair nameplate and provides a means of identifying each valve.

Immediately following the register, you will find the actual field test reports. The field test reports contain some of the

same information found on the register. These reports will provide a more detailed account of the test and/or repair

information for each valve.

We appreciate the opportunity to help you in maintaining your relief valves and look forward to being of service to you

in the future. If you have any questions, please give me a call (580) 256-7677 or e-mail me at

[email protected].

Ranson Pierce

Sincerely,

Pressure Relief Valves Tested Job NumberDCPWednesday , Oct 6 , 2021 16725

Clem

Orifice Area Code3

Test No. PSV No. Set PressManufacturerStatus Valve Type Serial No.Equipment Size21

Capacity

1 CLM1 Adjust 1 1/2" G 0.503 Farris 26GA10-140 19689-A8 UV1421 ScfmUnit #1 Interstage 150

2 CLM7 Test 1/2" - 0.089 Farris 1890 4086-3-M UV239 ScfmUnit #1 Fuel Pot 125

3 CLM2 Adjust 1" -8 0.196 AGCO 83MC88-8 M91-07671 UV1333 ScfmUnit #1 Discharge 400

4 CLM6 Test 3/4" E 0.212 Mercer Valve 8114121111R 4899 UV557 ScfmUnit #1 Suction 150

5 CLM4 Test 1" - 0.292 Consolidated 1993C-1-CC-DA-31-SC-SC-GS TL65497 UV794 ScfmStarting Gas 150

6 CLM3 Test 3" K 2.138 Consolidated 1905Kc TB89325 None0 ScfmInlet Scrubber 20

8 CLM4 New 1" F 0.337 Mercer Valve 9123F51V09U1 1665948 UV908 ScfmStarting Gas 150

1. API Orifice Designation Page 1 of 1Monday, March 21, 2022

3. A.S.M.E. Code Status

2. Flow Area In Square Inches

Pressure Vent Valves Tested Job NumberWednesday , Oct 6 , 2021 16725

DCP

PSV No. Equipment Model Number Valve Style Size Inlet Type Vacuum Set PressManufacturerStatusTest No.

Clem

Flanged8"Thief HatchJT-8JaycoT1 THTestCLM5 7 0.40 4.00

Page 1 of 1Monday, March 21, 2022

VALVE TECH LABORATORY, INC.Woodward, Oklahoma (580) 256-7677

SAFETY/RELIEF VALVE INSPECTION/TEST REPORT Work Order No.

VTL Serial Number Traveler PSV Number16184-1-1 CLM1

16725 - 1 - 1

Customer Name

Contact Person

Phone Number

Location

Equipment

Customer P.O. NO.

Date Valve Received

Date Required

Customer Comments Back Pressure

Service Temp.

Service

DOT JurisdictionalDCP 10/06/2021

Shannon Burk 10/06/2021 Gas

(580) 651-7557 AMB

Clem

Unit #1 Interstage

¨

As Received Condition

Manufacturer

Model No.

Serial No.

Shop Number

Orig Set Pres.

CDTP

Original Capacity

Code Type

Size and Orifice

Inlet X Outlet

Prev Repair Co

Prev W.O No.

Prev Model No

Prev Set Pres.

Prev Capacity

Seal Intact

Man Tag Intact

Valve Cond.

Report Only Test and Report Recondition

Pre-Test Test and Adjust

New Valve

Not Worth Repair

Change Set Pres.

Replaces

Replaced With

New Set Pres

New Capacity

Conversion

New Model Numbe

Reason for Conversion

Previous Information Services Performed

Farris

26GA10-170

19689-A8

88.00 P.S.I.G.

1020 Scfm

UV

1 1/2" G 2 1/2"

150 Ser. RF X 150

Ser. RF

Valve Tech Laboratory

16184-1-1

26GA10-140

No

Yes

Fair

¨ þ ¨þ þ

¨¨¨

¨

Original Nameplate Data

0.00 P.S.I.G.

150.00 P.S.I.G.

1421 Scfm0.00 P.S.I.G.

Final Test Record

Pre-Test Gauge No.

Pre-Test Medium

Desired Set Pres.

As Found

Pre-Test 2nd Pop

Final Test Gauge No.

Calibration Due Date

Final Test Medium

As Left

Comments

Desired Set Pres.

As Left Pres.

CDTP

Disassembly, Inspection and Repair

Cap/Lever

Adj Screw

Spindle

Bonnet

Body

Disc Holder

Disc

Guide

Guide Ring

Nozzle

Nozzle Ring

Spring Number

Caliper Number

Ring Pins

Nuts/Bolts

Spring Washers

Gaskets

Seals

Bellows

Retainer

Retainer Screw

Liner

Piston

Tubing/Con.

Spring Range

Caliper Calibration Due Date

As Found As Left As Found As Left

Comments

DTG-8

Nitrogen

150.00

150.00

158.00

150.00

Adjusted

DTG-8

10/15/2021

Nitrogen

150.00

150.00

Actual Blowdown

Pre-Test Record

Customer and Service Information

0.00

Record of "VR" Sign-Offs

Original Nameplate

Customer Info.

Pre-Test

Inspection

Disassembly

Maching

Part Replacement

Lapping

Reassembly

Final Test

New Nameplate

Initials Date

RKP

RKP

RKP

RKP

RKP

RKP

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

List of Replacement Parts

Quantity Part Description P.O. No.Manuf Part No.

Repaired By:Valve Tech Laboratory, Inc.

Woodward, Oklahoma

Type/Model

Set Pres.: Cold Set:

Cap: Temp:

PSV No: Repair Date:

Work Order No:

"VR" Stamp Applied

26GA10-140

AMB

CLM1 10/06/2021

16725 - 1 - 1

¨

10/06/2021

150.00

1421 Scfm

No. 531,

Date:Signature:

¤ ¤

532

P.S.I.P.S.I.

F

¨¨

"TO" Stamp Applied

VALVE TECH LABORATORY, INC.Woodward, Oklahoma (580) 256-7677

SAFETY/RELIEF VALVE INSPECTION/TEST REPORT Work Order No.

VTL Serial Number Traveler PSV Number16184-1-2 CLM7

16725 - 1 - 2

Customer Name

Contact Person

Phone Number

Location

Equipment

Customer P.O. NO.

Date Valve Received

Date Required

Customer Comments Back Pressure

Service Temp.

Service

DOT JurisdictionalDCP 10/06/2021

Shannon Burk 10/06/2021 Gas

(580) 651-7557 AMB

Clem

Unit #1 Fuel Pot

¨

As Received Condition

Manufacturer

Model No.

Serial No.

Shop Number

Orig Set Pres.

CDTP

Original Capacity

Code Type

Size and Orifice

Inlet X Outlet

Prev Repair Co

Prev W.O No.

Prev Model No

Prev Set Pres.

Prev Capacity

Seal Intact

Man Tag Intact

Valve Cond.

Report Only Test and Report Recondition

Pre-Test Test and Adjust

New Valve

Not Worth Repair

Change Set Pres.

Replaces

Replaced With

New Set Pres

New Capacity

Conversion

New Model Numbe

Reason for Conversion

Previous Information Services Performed

Farris

1890

4086-3-M

125.00 P.S.I.G.

239 Scfm

UV

1/2" - 1"

MNPT X FNPT

Valve Tech Laboratory

16184-1-2

1890

Yes

Yes

Fair

¨ þ ¨þ ¨

¨¨¨

¨

Original Nameplate Data

125.00 P.S.I.G.

125.00 P.S.I.G.

239 Scfm0.00 P.S.I.G.

Final Test Record

Pre-Test Gauge No.

Pre-Test Medium

Desired Set Pres.

As Found

Pre-Test 2nd Pop

Final Test Gauge No.

Calibration Due Date

Final Test Medium

As Left

Comments

Desired Set Pres.

As Left Pres.

CDTP

Disassembly, Inspection and Repair

Cap/Lever

Adj Screw

Spindle

Bonnet

Body

Disc Holder

Disc

Guide

Guide Ring

Nozzle

Nozzle Ring

Spring Number

Caliper Number

Ring Pins

Nuts/Bolts

Spring Washers

Gaskets

Seals

Bellows

Retainer

Retainer Screw

Liner

Piston

Tubing/Con.

Spring Range

Caliper Calibration Due Date

As Found As Left As Found As Left

Comments

DTG-8

Nitrogen

125.00

124.00

124.00

124.00

DTG-8

10/15/2021

Nitrogen

125.00

124.00

Actual Blowdown

Pre-Test Record

Customer and Service Information

0.00

Record of "VR" Sign-Offs

Original Nameplate

Customer Info.

Pre-Test

Inspection

Disassembly

Maching

Part Replacement

Lapping

Reassembly

Final Test

New Nameplate

Initials Date

RKP

RKP

RKP

RKP

RKP

RKP

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

List of Replacement Parts

Quantity Part Description P.O. No.Manuf Part No.

Repaired By:Valve Tech Laboratory, Inc.

Woodward, Oklahoma

Type/Model

Set Pres.: Cold Set:

Cap: Temp:

PSV No: Repair Date:

Work Order No:

"VR" Stamp Applied

1890

AMB

CLM7 10/06/2021

16725 - 1 - 2

¨

10/06/2021

125.00

239 Scfm

No. 531,

Date:Signature:

¤ ¤

532

P.S.I.P.S.I.

F

¨¨

"TO" Stamp Applied

VALVE TECH LABORATORY, INC.Woodward, Oklahoma (580) 256-7677

SAFETY/RELIEF VALVE INSPECTION/TEST REPORT Work Order No.

VTL Serial Number Traveler PSV Number16184-1-3 CLM2

16725 - 1 - 3

Customer Name

Contact Person

Phone Number

Location

Equipment

Customer P.O. NO.

Date Valve Received

Date Required

Customer Comments Back Pressure

Service Temp.

Service

DOT JurisdictionalDCP 10/06/2021

Shannon Burk 10/06/2021 Gas

(580) 651-7557 AMB

Clem

Unit #1 Discharge

¨

As Received Condition

Manufacturer

Model No.

Serial No.

Shop Number

Orig Set Pres.

CDTP

Original Capacity

Code Type

Size and Orifice

Inlet X Outlet

Prev Repair Co

Prev W.O No.

Prev Model No

Prev Set Pres.

Prev Capacity

Seal Intact

Man Tag Intact

Valve Cond.

Report Only Test and Report Recondition

Pre-Test Test and Adjust

New Valve

Not Worth Repair

Change Set Pres.

Replaces

Replaced With

New Set Pres

New Capacity

Conversion

New Model Numbe

Reason for Conversion

Previous Information Services Performed

AGCO

83MC88-8

M91-07671

350.00 P.S.I.G.

1172 Scfm

UV

1" -8 1"

MNPT X FNPT

Valve Tech Laboratory

16184-1-3

83MC88-8

Yes

Yes

Fair

¨ þ ¨þ þ

¨¨¨

¨

Original Nameplate Data

0.00 P.S.I.G.

400.00 P.S.I.G.

1333 Scfm0.00 P.S.I.G.

Final Test Record

Pre-Test Gauge No.

Pre-Test Medium

Desired Set Pres.

As Found

Pre-Test 2nd Pop

Final Test Gauge No.

Calibration Due Date

Final Test Medium

As Left

Comments

Desired Set Pres.

As Left Pres.

CDTP

Disassembly, Inspection and Repair

Cap/Lever

Adj Screw

Spindle

Bonnet

Body

Disc Holder

Disc

Guide

Guide Ring

Nozzle

Nozzle Ring

Spring Number

Caliper Number

Ring Pins

Nuts/Bolts

Spring Washers

Gaskets

Seals

Bellows

Retainer

Retainer Screw

Liner

Piston

Tubing/Con.

Spring Range

Caliper Calibration Due Date

As Found As Left As Found As Left

Comments

DTG-8

Nitrogen

400.00

401.00

415.00

401.00

Adjusted

DTG-8

10/15/2021

Nitrogen

400.00

401.00

Actual Blowdown

Pre-Test Record

Customer and Service Information

0.00

Record of "VR" Sign-Offs

Original Nameplate

Customer Info.

Pre-Test

Inspection

Disassembly

Maching

Part Replacement

Lapping

Reassembly

Final Test

New Nameplate

Initials Date

RKP

RKP

RKP

RKP

RKP

RKP

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

List of Replacement Parts

Quantity Part Description P.O. No.Manuf Part No.

Repaired By:Valve Tech Laboratory, Inc.

Woodward, Oklahoma

Type/Model

Set Pres.: Cold Set:

Cap: Temp:

PSV No: Repair Date:

Work Order No:

"VR" Stamp Applied

83MC88-8

AMB

CLM2 10/06/2021

16725 - 1 - 3

¨

10/06/2021

400.00

1333 Scfm

No. 531,

Date:Signature:

¤ ¤

532

P.S.I.P.S.I.

F

¨¨

"TO" Stamp Applied

VALVE TECH LABORATORY, INC.Woodward, Oklahoma (580) 256-7677

SAFETY/RELIEF VALVE INSPECTION/TEST REPORT Work Order No.

VTL Serial Number Traveler PSV Number16184-1-4 CLM6

16725 - 1 - 4

Customer Name

Contact Person

Phone Number

Location

Equipment

Customer P.O. NO.

Date Valve Received

Date Required

Customer Comments Back Pressure

Service Temp.

Service

DOT JurisdictionalDCP 10/06/2021

Shannon Burk 10/06/2021 Gas

(580) 651-7557 AMB

Clem

Unit #1 Suction

¨

As Received Condition

Manufacturer

Model No.

Serial No.

Shop Number

Orig Set Pres.

CDTP

Original Capacity

Code Type

Size and Orifice

Inlet X Outlet

Prev Repair Co

Prev W.O No.

Prev Model No

Prev Set Pres.

Prev Capacity

Seal Intact

Man Tag Intact

Valve Cond.

Report Only Test and Report Recondition

Pre-Test Test and Adjust

New Valve

Not Worth Repair

Change Set Pres.

Replaces

Replaced With

New Set Pres

New Capacity

Conversion

New Model Numbe

Reason for Conversion

Previous Information Services Performed

Mercer Valve

8114121111R

4899

250.00 P.S.I.G.

898 Scfm

UV

3/4" E 1"

MNPT X FNPT

Valve Tech Laboratory

16184-1-4

8114121111R

Yes

Yes

Fair

¨ þ ¨þ ¨

¨¨¨

¨

Original Nameplate Data

0.00 P.S.I.G.

150.00 P.S.I.G.

557 Scfm0.00 P.S.I.G.

Final Test Record

Pre-Test Gauge No.

Pre-Test Medium

Desired Set Pres.

As Found

Pre-Test 2nd Pop

Final Test Gauge No.

Calibration Due Date

Final Test Medium

As Left

Comments

Desired Set Pres.

As Left Pres.

CDTP

Disassembly, Inspection and Repair

Cap/Lever

Adj Screw

Spindle

Bonnet

Body

Disc Holder

Disc

Guide

Guide Ring

Nozzle

Nozzle Ring

Spring Number

Caliper Number

Ring Pins

Nuts/Bolts

Spring Washers

Gaskets

Seals

Bellows

Retainer

Retainer Screw

Liner

Piston

Tubing/Con.

Spring Range

Caliper Calibration Due Date

As Found As Left As Found As Left

Comments

DTG-8

Nitrogen

150.00

148.00

148.00

148.00

Spring needs

verified on the

pressure change.

DTG-8

10/15/2021

Nitrogen

150.00

148.00

Actual Blowdown

05-011 191-350

Pre-Test Record

Customer and Service Information

0.00

Record of "VR" Sign-Offs

Original Nameplate

Customer Info.

Pre-Test

Inspection

Disassembly

Maching

Part Replacement

Lapping

Reassembly

Final Test

New Nameplate

Initials Date

RKP

RKP

RKP

RKP

RKP

RKP

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

List of Replacement Parts

Quantity Part Description P.O. No.Manuf Part No.

Repaired By:Valve Tech Laboratory, Inc.

Woodward, Oklahoma

Type/Model

Set Pres.: Cold Set:

Cap: Temp:

PSV No: Repair Date:

Work Order No:

"VR" Stamp Applied

8114121111R

AMB

CLM6 10/06/2021

16725 - 1 - 4

¨

10/06/2021

150.00

557 Scfm

No. 531,

Date:Signature:

¤ ¤

532

P.S.I.P.S.I.

F

¨¨

"TO" Stamp Applied

VALVE TECH LABORATORY, INC.Woodward, Oklahoma (580) 256-7677

SAFETY/RELIEF VALVE INSPECTION/TEST REPORT Work Order No.

VTL Serial Number Traveler PSV Number16184-1-5 CLM4

16725 - 1 - 5

Customer Name

Contact Person

Phone Number

Location

Equipment

Customer P.O. NO.

Date Valve Received

Date Required

Customer Comments Back Pressure

Service Temp.

Service

DOT JurisdictionalDCP 10/06/2021

Shannon Burk 10/06/2021 Gas

(580) 651-7557 AMB

Clem

Starting Gas

¨

As Received Condition

Manufacturer

Model No.

Serial No.

Shop Number

Orig Set Pres.

CDTP

Original Capacity

Code Type

Size and Orifice

Inlet X Outlet

Prev Repair Co

Prev W.O No.

Prev Model No

Prev Set Pres.

Prev Capacity

Seal Intact

Man Tag Intact

Valve Cond.

Report Only Test and Report Recondition

Pre-Test Test and Adjust

New Valve

Not Worth Repair

Change Set Pres.

Replaces

Replaced With

New Set Pres

New Capacity

Conversion

New Model Numbe

Reason for Conversion

Previous Information Services Performed

Consolidated

1993C-1-CC-DA-31-SC-SC-GS

TL65497

200.00 P.S.I.G.

1037 Scfm

UV

1" - 1 1/2"

MNPT X FNPT

Valve Tech Laboratory

16184-1-5

1993C-1-CC-DA-31-SC-SC-GS

Yes

Yes

Fair

¨ þ ¨þ ¨

¨¨¨

¨

Original Nameplate Data

200.00 P.S.I.G.

150.00 P.S.I.G.

794 Scfm0.00 P.S.I.G.

Final Test Record

Pre-Test Gauge No.

Pre-Test Medium

Desired Set Pres.

As Found

Pre-Test 2nd Pop

Final Test Gauge No.

Calibration Due Date

Final Test Medium

As Left

Comments

Desired Set Pres.

As Left Pres.

CDTP

Disassembly, Inspection and Repair

Cap/Lever

Adj Screw

Spindle

Bonnet

Body

Disc Holder

Disc

Guide

Guide Ring

Nozzle

Nozzle Ring

Spring Number

Caliper Number

Ring Pins

Nuts/Bolts

Spring Washers

Gaskets

Seals

Bellows

Retainer

Retainer Screw

Liner

Piston

Tubing/Con.

Spring Range

Caliper Calibration Due Date

As Found As Left As Found As Left

Comments

DTG-8

Nitrogen

150.00

146.00

146.00

146.00

Adjustment screw

is locked up and

egged. Valve needs

DTG-8

10/15/2021

Nitrogen

150.00

146.00

Actual Blowdown

Pre-Test Record

Customer and Service Information

0.00

Record of "VR" Sign-Offs

Original Nameplate

Customer Info.

Pre-Test

Inspection

Disassembly

Maching

Part Replacement

Lapping

Reassembly

Final Test

New Nameplate

Initials Date

RKP

RKP

RKP

RKP

RKP

RKP

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

List of Replacement Parts

Quantity Part Description P.O. No.Manuf Part No.

1 Car Seal STK14998

Repaired By:Valve Tech Laboratory, Inc.

Woodward, Oklahoma

Type/Model

Set Pres.: Cold Set:

Cap: Temp:

PSV No: Repair Date:

Work Order No:

"VR" Stamp Applied

1993C-1-CC-DA-31-SC-SC-GS

AMB

CLM4 10/06/2021

16725 - 1 - 5

¨

10/06/2021

150.00

794 Scfm

No. 531,

Date:Signature:

¤ ¤

532

P.S.I.P.S.I.

F

¨¨

"TO" Stamp Applied

VALVE TECH LABORATORY, INC.Woodward, Oklahoma (580) 256-7677

SAFETY/RELIEF VALVE INSPECTION/TEST REPORT Work Order No.

VTL Serial Number Traveler PSV Number16184-1-7 CLM3

16725 - 1 - 6

Customer Name

Contact Person

Phone Number

Location

Equipment

Customer P.O. NO.

Date Valve Received

Date Required

Customer Comments Back Pressure

Service Temp.

Service

DOT JurisdictionalDCP 10/06/2021

Shannon Burk 10/06/2021 Gas

(580) 651-7557 AMB

Clem

Inlet Scrubber

¨

As Received Condition

Manufacturer

Model No.

Serial No.

Shop Number

Orig Set Pres.

CDTP

Original Capacity

Code Type

Size and Orifice

Inlet X Outlet

Prev Repair Co

Prev W.O No.

Prev Model No

Prev Set Pres.

Prev Capacity

Seal Intact

Man Tag Intact

Valve Cond.

Report Only Test and Report Recondition

Pre-Test Test and Adjust

New Valve

Not Worth Repair

Change Set Pres.

Replaces

Replaced With

New Set Pres

New Capacity

Conversion

New Model Numbe

Reason for Conversion

Previous Information Services Performed

Consolidated

1905Kc

TB89325

20.00 P.S.I.G.

0 Scfm

None

3" K 4"

150 Ser. RF X 150

Ser. RF

Valve Tech Laboratory

16184-1-7

1905Kc

Yes

Yes

Fair

¨ þ ¨þ ¨

¨¨¨

¨

Original Nameplate Data

0.00 P.S.I.G.

20.00 P.S.I.G.

0 Scfm0.00 P.S.I.G.

Final Test Record

Pre-Test Gauge No.

Pre-Test Medium

Desired Set Pres.

As Found

Pre-Test 2nd Pop

Final Test Gauge No.

Calibration Due Date

Final Test Medium

As Left

Comments

Desired Set Pres.

As Left Pres.

CDTP

Disassembly, Inspection and Repair

Cap/Lever

Adj Screw

Spindle

Bonnet

Body

Disc Holder

Disc

Guide

Guide Ring

Nozzle

Nozzle Ring

Spring Number

Caliper Number

Ring Pins

Nuts/Bolts

Spring Washers

Gaskets

Seals

Bellows

Retainer

Retainer Screw

Liner

Piston

Tubing/Con.

Spring Range

Caliper Calibration Due Date

As Found As Left As Found As Left

Comments

DTG-8

Nitrogen

20.00

22.00

22.00

22.00

DTG-8

10/15/2021

Nitrogen

20.00

22.00

Actual Blowdown

Pre-Test Record

Customer and Service Information

0.00

Record of "VR" Sign-Offs

Original Nameplate

Customer Info.

Pre-Test

Inspection

Disassembly

Maching

Part Replacement

Lapping

Reassembly

Final Test

New Nameplate

Initials Date

RKP

RKP

RKP

RKP

RKP

RKP

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

10/06/2021

List of Replacement Parts

Quantity Part Description P.O. No.Manuf Part No.

1 Car Seal STK14996

Repaired By:Valve Tech Laboratory, Inc.

Woodward, Oklahoma

Type/Model

Set Pres.: Cold Set:

Cap: Temp:

PSV No: Repair Date:

Work Order No:

"VR" Stamp Applied

1905Kc

AMB

CLM3 10/06/2021

16725 - 1 - 6

¨

10/06/2021

20.00

0 Scfm

No. 531,

Date:Signature:

¤ ¤

532

P.S.I.P.S.I.

F

¨¨

"TO" Stamp Applied

VALVE TECH LABORATORY, INC.Woodward, Oklahoma (580) 256-7677

SAFETY/RELIEF VALVE INSPECTION/TEST REPORT Work Order No.

VTL Serial Number Traveler PSV Number16725-2-8 CLM4

16725 - 2 - 8

Customer Name

Contact Person

Phone Number

Location

Equipment

Customer P.O. NO.

Date Valve Received

Date Required

Customer Comments Back Pressure

Service Temp.

Service

DOT JurisdictionalDCP 10/06/2021

Shannon Burk 11/10/2021 Gas

(580) 651-7557

Clem

Starting Gas

¨

As Received Condition

Manufacturer

Model No.

Serial No.

Shop Number

Orig Set Pres.

CDTP

Original Capacity

Code Type

Size and Orifice

Inlet X Outlet

Prev Repair Co

Prev W.O No.

Prev Model No

Prev Set Pres.

Prev Capacity

Seal Intact

Man Tag Intact

Valve Cond.

Report Only Test and Report Recondition

Pre-Test Test and Adjust

New Valve

Not Worth Repair

Change Set Pres.

Replaces

Replaced With

New Set Pres

New Capacity

Conversion

New Model Numbe

Reason for Conversion

Previous Information Services Performed

Mercer Valve

9123F51V09U1

1665948

150.00 P.S.I.G.

908 Scfm

UV

1" F 1 1/2"

MNPT X FNPT

Valve Tech Laboratory

16725-2-8

9123F51V09U1

Yes

Yes

New

16725-1-5

¨ þ ¨¨ ¨

þ¨¨

¨

Original Nameplate Data

0.00 P.S.I.G.

150.00 P.S.I.G.

908 Scfm0.00 P.S.I.G.

Final Test Record

Pre-Test Gauge No.

Pre-Test Medium

Desired Set Pres.

As Found

Pre-Test 2nd Pop

Final Test Gauge No.

Calibration Due Date

Final Test Medium

As Left

Comments

Desired Set Pres.

As Left Pres.

CDTP

Disassembly, Inspection and Repair

Cap/Lever

Adj Screw

Spindle

Bonnet

Body

Disc Holder

Disc

Guide

Guide Ring

Nozzle

Nozzle Ring

Spring Number

Caliper Number

Ring Pins

Nuts/Bolts

Spring Washers

Gaskets

Seals

Bellows

Retainer

Retainer Screw

Liner

Piston

Tubing/Con.

Spring Range

Caliper Calibration Due Date

As Found As Left As Found As Left

Comments

DTG-8

Nitrogen

150.00

DTG-8

01/15/2022

Nitrogen

150.00

Actual Blowdown

05-009 101-180

Pre-Test Record

Customer and Service Information

0.00

Record of "VR" Sign-Offs

Original Nameplate

Customer Info.

Pre-Test

Inspection

Disassembly

Maching

Part Replacement

Lapping

Reassembly

Final Test

New Nameplate

Initials Date

RKP

RKP

RKP

RKP

11/10/2021

11/10/2021

11/10/2021

11/10/2021

List of Replacement Parts

Quantity Part Description P.O. No.Manuf Part No.

1 Car Seal STK14920

1 1F1 1/2 set @150's 1672591-23F51V09U1

Repaired By:Valve Tech Laboratory, Inc.

Woodward, Oklahoma

Type/Model

Set Pres.: Cold Set:

Cap: Temp:

PSV No: Repair Date:

Work Order No:

"VR" Stamp Applied

9123F51V09U1

CLM4 11/10/2021

16725 - 2 - 8

¨

11/10/2021

150.00

908 Scfm

No. 531,

Date:Signature:

¤ ¤

532

P.S.I.P.S.I.

F

¨¨

"TO" Stamp Applied

VALVE TECH LABORATORY, INC.

REPAIR AND TEST REPORT

WOODWARD, OKLAHOMA (580)-256-7677

THIEF HATCH

VENT VALVE

DISASSEMBLY, INSPECTION AND REPAIR

LID

BASE

PRESSURE SEAL

VACUUM SEAL

PRESSURE SPRING

BASE GASKET

VACUUM SPRING

HINGE PIN

HINGE SPRING

LATCH

FLANGE

PISTON

LIFT LEVER

LID SEAL

BODY - PLUG

WEIGHTS

NUTS / BOLTS

ITEMS AS FOUND AS LEFT REPLACED

¨

¨

¨

SIGN-OFF: Ranson Pierce

¨

¨

¨¨

¨

¨

¨

¨

¨

¨

¨

¨

¨

¨

COMMENTS:

SET PRESSURE: SET VACUUM: SIGN-OFF: 0.40 4.00 Ranson Pierce

TEST MEDIUM: DATE: STATUS:Nitrogen 10/06/2021 Test

TEST RECORD

SIGN-OFF: Ranson PierceSET PRESSURE: SET VACUUM: 4.00 0.40

MANUFACTURER: MODEL:Jayco JT-8

SIZE: INLET TYPE: 8.00 Flanged

VALVE STYLE:AS REC'D CONDITION: Fair Thief Hatch

EQUIP. CONDITION AND ORIGINAL DATA

Customer W/O NO: SIGN-OFF: Ranson Pierce

Phone No: (580) 651-7557 EQUIPMENT: T1 TH

Contact: Shannon Burk LOCATION: Clem

Customer: DCP EQUIP. ID NO: CLM5

WORK ORDER NO:Date: 10/06/2021

CUSTOMER INFORMATION

16725 - 1 - 7

SIGNATURE : 10/06/2021DATE:

Action Needed to be TakenTest Number Date Completed Sign-Off

Appendix

Spring needs verified on the pressure change.16725-1-4

Adjustment screw is locked up and egged. Valve needs

to be replaced.

16725-1-5

Please review the appendix for additional informaton concering problem areas or concerns noted during testing.