UTPB – Valet and Driveway Reno Page 1 UTPB - VALET AND DRIVEWAY RENOVATION 6410 Fannin Street/ Houston, Texas 77030 Date: December 16, 2019 Johnston Project No.: 19-00032-00 Prepared by: Paula Gaviria Notice to General Contractor: A. Receipt of this Addendum shall acknowledge revisions to Contract Documents for above referenced project. B. This Addendum forms part of the Contract documents for the above referenced project and shall be incorporated integrally there with. C. Where provisions of the following supplemental data differ from those of the original Contract Documents, this Addendum shall govern. DOCUMENTS ATTACHED: 1. This Addendum addresses architectural, mechanical and electrical revisions as noted below, per comments from EH&S: REVISED DRAWINGS ISSUED GENERAL 1. G0.00: COVER Revised the name of the issue. 2. G0.01: DRAWING SHEET INDEX Added Addendum #01 column and checked the sheets that are being issued. 3. G1.00: LIFE SAFETY PLAN Revised existing and new fire tapes as smoke partitions. ARCHITECTURAL 1. A1.01: OVERALL FLOOR PLAN Revised existing and new fire tapes as smoke partitions. 2. A3.01: ENLARGED FLOOR PLAN & REFLECTED CEILING PLAN – INTERIOR Revised existing and new fire tapes as smoke partitions. Revised wall types to be smoke partitions. Added exit sign to Corridor 103. Added Fire Rated Legend to sheet. Added a smoke detector in Pharmacy Added and relocated fire strobes. 3. A10.04: PARTITION TYPES Added wall type SA to sheet. Removed wall type 1A from sheet. 4. A11.01: OPENING SCHEDULE Revised door 105.1 and 106.1 fire rating. APPENDIX FIVE CONSTRUCTION PROJECT MANUAL AND DRAWINGS

Upload: others

Post on 29-Jun-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

UTPB – Valet and Driveway Reno

Page 1

UTPB - VALET AND DRIVEWAY RENOVATION 6410 Fannin Street/ Houston, Texas 77030

Date: December 16, 2019

Johnston Project No.: 19-00032-00

Prepared by: Paula Gaviria

Notice to General Contractor:

A. Receipt of this Addendum shall acknowledge revisions to Contract Documents for above referenced project.

B. This Addendum forms part of the Contract documents for the above referenced project and shall be incorporated integrally there with.

C. Where provisions of the following supplemental data differ from those of the original Contract Documents, this Addendum shall govern.

DOCUMENTS ATTACHED:

1. This Addendum addresses architectural, mechanical and electrical revisions as noted below, percomments from EH&S:

REVISED DRAWINGS ISSUED

GENERAL 1. G0.00: COVER

Revised the name of the issue.2. G0.01: DRAWING SHEET INDEX

Added Addendum #01 column and checked the sheets that are being issued.3. G1.00: LIFE SAFETY PLAN

Revised existing and new fire tapes as smoke partitions.

ARCHITECTURAL 1. A1.01: OVERALL FLOOR PLAN

• Revised existing and new fire tapes as smoke partitions.2. A3.01: ENLARGED FLOOR PLAN & REFLECTED CEILING PLAN – INTERIOR

• Revised existing and new fire tapes as smoke partitions.

• Revised wall types to be smoke partitions.

• Added exit sign to Corridor 103.

• Added Fire Rated Legend to sheet.

• Added a smoke detector in Pharmacy

• Added and relocated fire strobes.3. A10.04: PARTITION TYPES

• Added wall type SA to sheet.

• Removed wall type 1A from sheet.4. A11.01: OPENING SCHEDULE

• Revised door 105.1 and 106.1 fire rating.

APPENDIX FIVECONSTRUCTION PROJECT MANUAL AND DRAWINGS

cthornton1
Typewritten Text
cthornton1
Typewritten Text
Page 2: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

UTPB – Valet and Driveway Reno

Page 2

MECHANICAL 1. M0.01: MECHANICAL SCHEDULES, CONTROLS, AND DETAILS

Replaced detail for smoke dampers.2. M2.01: MECHANICAL DUCTWORK PLAN – LEVEL 1

Revised keynote number 12 referring to smoke damper installation.

ELECTRICAL 1. E1.01: ELECTRICAL SITE PLAN

• Revised keynote L03 referring to existing lights2. E2.01: ELECTRICAL LIGHTING PLAN – LEVEL 1

• Revised emergency lighting in Waiting Room and Valet Office.

• Added exit sign to Corridor.3. E3.01: ELECTRICAL POWER PLAN – LEVEL 1

• Added outlets to Corridor and Valet Office.4. E5.01: ELECTRICAL FIRE ALARM PLAN – LEVEL 1

• Added fire alarm pull string to Waiting Room.

• Added and relocated fire strobes.

• Added a smoke detector to Pharmacy.

END OF UTPB - VALET AND Driveway RENOVATION -

Page 3: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

PROJECT NO. :

CONSULTANTS:

DATE ISSUED:

WALTER P MOORE1301 MCKINNEY, SUITE 1100HOUSTON, TX 77010

JOHNSTON, LLC2603 AUGUSTA DR., SUITE 1500HOUSTON, TX 77057

2019 12 16

UT HEALTH SYSTEM

19-00032-00

6410 FANNIN ST.HOUSTON, TX 77030

UTPB - VALET &DRIVEWAYRENOVATION

MEP

CIVIL & STRUCTURAL

UTPB - VALET & DRIVEWAYRENOVATION

1

Page 4: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

- ANCHOR BOLT - AIR CONDITIONING- ACCESSIBLE - ACOUSTICAL - AREA DRAIN - AMERICANS WITH DISABILITIES ACT- ADA ARCHITECTURAL GUIDELINES - ADDITIONAL - ADJUSTABLE - ABOVE FINISH FLOOR - AGGREGATE - ALTERNATE - ALUMINUM - ANCHOR - ANODIZED - ACOUSTICAL PANEL CEILING - APPROVED - APPROXIMATE - ARCHITECTURAL, ARCHITECT - ACOUSTICAL CEILING TILE- AUTOMATIC - AUDIO VISUAL

- BOARD - BRICK EXPANSION JOINT - BUILDING - BLOCK - BEAM - BOTTOM - BRICK - BRONZE- BASEMENT - BOLT - BUILT-UP ROOFING

- STRUCTURAL STEEL CHANNEL- CABINET - CATEGORY - CATCH BASIN - CHALK BOARD - CEMENTITIOUS BACKER UNIT - CENTER TO CENTER- CEMENT - CERAMIC - CORNER GUARD - COAT HOOK, CHILLER - CHANNEL - CAST IRON - CAST-IN-PLACE - CONTROL JOINT / CONSTRUCTION JOINT - CENTER LINE - CEILING - CLEAR - CONCRETE MASONRY UNIT - COUNTER - CLEANOUT - COLUMN - COMPARTMENT - CONCRETE - CONDITION - CONNECTION - CONTINUOUS - CONTRACTOR - COORDINATE - CORRIDOR - CARPET- CERAMIC TILE / COOLING TOWER - CENTER - COLD WATER (PIPING)

- DEPTH, ELECTRICAL DEDICATED CIRCUIT - DISABLED - DECIBEL- DOUBLE - DEGREE - DEMOLITION - DEPARTMENT - DETAIL - DRINKING FOUNTAIN - DIAMETER - DIFFUSER - DIMENSION - DISABLED - DISPENSER - DAMP PROOFING - DEMOUNTABLE - DOWN - DOOR OPENING - DIMENSION POINT - DEMOUNTABLE PARTITION - DOOR - DRAIN - DOWNSPOUT - DISHWASHER - DRAWING - DRAWER

- EXISTING - EAST, ELECTRICAL EMERGENCY CIRCUIT - EACH - EXPANSION BOLT (EXPANSION ANCHOR) - EXTERIOR INSULATION AND FINISH SYSTEM - EXTERIOR FINISH SYSTEM - EXPANSION JOINT - ELEVATION - ELECTRICAL - ELEVATOR - EMERGENCY - ENCLOSURE - ELECTRICAL PANEL BOARD - ELECTRONIC PROJECTION SCREEN - EQUAL - EQUIPMENT - ESCALATOR - ICC EVALUATION SERVICE REPORT- ELECTRICAL WATER COOLER - EXHAUST - EXPANSION - EXISTING - EXTERIOR

- FIRE ALARM - FABRIC- FACE BRICK - FILE CABINET- FLOOR DRAIN - FIRE DEPARTMENT CONNECTION - FOUNDATION - FIRE EXTINGUISHER - FIRE EXTINGUISHER CABINET - FURNITURE, FINISHES & EQUIPMENT - FINISH FLOOR ELEVATION - FLAT HEAD - FIRE HOSE CABINET - FINISH - FIXTURE - FLOOR - FLASHING - FLUORESCENT - FACE OF - FACE OF FINISH- FIRE PROTECTION - FIREPROOFING - FRAME - FEET - FIRE RETARDANT TREATED WOOD - FOOTING - FURNITURE - FIELD VERIFY- FABRIC WALL COVERING - FABRIC WRAPPED PANEL

- GROUND - GAUGE / GAGE - GALVANIZED - GRAB BAR - GENERAL CONTRACT(OR) - GROUND FAULT INTERUPTED- GLASS FIBER REINFORCED CONCRETE - GLASS FIBER REINFORCED GYPSUM - GLASS - GRADE- GROUND - GYPSUM WALLBOARD

AB AC ACC ACOUS AD ADAADAAGADD ADJ AFF AGGR ALT ALUM ANCH ANOD APC APPD APPROX ARCH ACT AUTO AV

BD BEJ BLDG BLK BM BOT BRK BRZBSMT BT BUR

CCAB CAT CB CBD CBU C/CCEM CER CG CH CHAN CI CIP CJ CL CLG CLR CMU CNTR CO COL COMPART CONC COND CONN CONT CONTR COORD CORR CPTCT CTR CW

D DA DBDBL DEG DEMO DEPT DET DF DIA DIFF DIM DIS DISP DMPF DMT DN DO DP DPTN DR DRN DS DW DWG DWR

(E) E EA EB EIFS EFS EJ EL ELEC ELEV EMERG ENCL EP EPSEQ EQUIP ESC ESREWC EXH EXP EXIST EXT

FA FABFB FC FD FDC FDN FE FEC FF&E FFEL FH FHC FIN FIXT FL FLASH FLUOR FO FOFFP FPG FR FT FRTW FTG FURNFV FWC FWP

G GA GALV GB GC GFIGRC GRG GL GR GRD GYP BD

- HOSE BIBB - HOLLOW CORE - HANDICAPPED - HARDWARE - HARDWOOD- HEAT STRENGTHENED (GLASS) - HOLLOW METAL (STEEL FRAME) - HANDRAIL - HOLD-OPEN - HORIZONTAL - HIGH POINT - HOSE REEL CABINET - HOUR - HOLLOW STRUCTURAL SECTION - HEIGHT - HEATING, VENTILATING, AIR CONDITIONING - HOT WATER - HYDRAULIC

- INTERNATIONAL CODE COUNCIL- INSIDE DIAMETER / DIMENSION - ELECTRICAL ISOLATED GROUND- INCH - INCANDESCENT - INCLUDED / INCLUDING - INFORMATION - INSULATION - INTERIOR - INTERMEDIATE - INVERT - INTERNATIONAL PIPE STANDARD - INVERTED ROOF MEMBRANE ASSEMBLY

- JOIST - JOINT

- KIP (1000 LB) - KICK PLATE - KILOGRAM - KITCHEN - KNOCKOUT

- STRUCTURAL STEEL ANGLE, LONG, LITER - LABORATORY - LANDING - LAMINATE / LAMINATION - LAVATORY - LATERAL- POUND - LINEAR FOOT - LINOLEUM- LOCKER - LIVE LOAD- LONG LEG HORIZONTAL - LONG LEG VERTICAL - LINE - LOW POINT- LIGHT - LOW VOLTAGE - LIGHT WEIGHT CONCRETE

- METER, METRIC - MACHINE - MAINTENANCE - MASONRY - MATERIAL - MAXIMUM - MACHINE BOLT - MARBLE- MOTOR CONTROL CENTER- MEDIUM DENSITY FIBERBOARD - MECHANICAL, ELECTRICAL, PLUMBING - MEDIUM DENSITY OVERLAY PLYWOOD - MECHANICAL - MEMBRANE - METAL - MEZZANINE - MANUFACTURER - MANHOLE - MINIMUM - MISCELLANEOUS - MILLIMETER - MASONRY OPENING - MACHINE SCREW - MOUNTED - MOUNTING - METAL - MULLION

- NORTH, NEWTON - NOT APPLICABLE - NOISE CRITERIA - NOT IN CONTRACT - NUMBER - NOMINAL - NOMINAL PIPE SIZE - NOISE REDUCTION COEFFICIENT- NOT TO SCALE

- OXYGEN- OUTSIDE AIR - ON CENTER - ON CENTER EACH WAY - OUTSIDE DIAMETER/DIMENSION - OWNER FURNISHED, CONTR INSTALLED - OWNER FURNISHED, OWNER INSTALLED - OFFICE - OVER HEAD - OPPOSITE HAND - OPENING - OPPOSITE - OVERFLOW ROOF DRAIN - OUTSIDE - OVERHEAD

- PAINT - PARALLEL- PAVING - PARTITION - PAPER TOWEL DISPENSER - PARTICLEBOARD - PRECAST CONCRETE - POWDER DRIVEN FASTENER - PERFORATED - PERIMETER - PERPENDICULAR - POINT OF FROG - PLATE - PLASTIC LAMINATE - PLASTER - PLUMBING - POUNDS PER LINEAR FOOT - PLYWOOD - PANEL - POLISHED - PAIR - PREFABRICATED - PROJECT - POUNDS PER SQUARE FOOT - POINT - PAINTED - PARTITION- PAPER TOWEL RECEPTACLE

- QUALITY CONTROL- QUARRY TILE - QUANTITY

HB HC HCP HDW HDWDHS HM HNDRL HO HORIZ HPT HRC HR HSS HT HVAC HW HYDR

ICCID IGIN INCAND INCL INFO INSUL INT INTERM INV IPS IRMA

JST JT

K KPL KG KIT KO

L LAB LDG LAM LATLAV LB LF LINLKR LLLLH LLV LN LPT LT LVLWC

M MACH MAINT MAS MATL MAX MB MBL MCCMDF MEP MDO MECH MEMB MET MEZZ MFR MH MIN MISC MM MO MS MTD MTG MTL MULL

N NA NC NIC NO NOM NPS NRCNTS

OOA OC OCEW OD OFCI OFOI OFF OH OPH OPNG OPP ORD OUTS OVHD

P PARPAV PARTN PATD PBD PC PDF PERF PERIM PERP PF PL PLAM PLAS PLBG PLF PLYWD PNL POL PR PREFAB PROJ PSF PT PTDPTN PTR

QCQT QTY

- RELOCATED - RADIUS OR RISER (PIPING) - RETURN AIR - RADIUS - RESILIENT BASE - REFLECTED CEILING PLAN - ROOF DRAIN - RECOMMENDED - RECEPTACLE - RECESSED - REFERENCE - REFLECTED / REFLECTIVE / REFLECT - REFRIGERATOR - REGISTER - REINFORCED / REINFORCING - RELOCATE - REMOVABLE - REQUIRE / REQUIRED - RESILIENT - REVISION / REVISED - ROOM - ROUGH OPENING - RATED - RATING - RAIN WATER LEADER

- SOUTH, ELECTRICAL SWITCH- SUPPLY AIR - SANITARY- SOLID CORE - SCHEDULE - STORM DRAIN / SOAP DISPENSER - SECTION - SQUARE FEET/FOOT - SPRINKLER HEAD - SHEET - SHOWER - SIMILAR - SHEET METAL, SQUARE METER - SHEET METAL SCREW - SANITARY NAPKIN DISPENSER - STANDPIPE - SPECIFICATION - SPRINKLER - SPEAKER - SQUARE - STRUCTURE SLAB ELEVATION - STAINLESS STEEL - SERVICE SINK - STATION - SOUND TRANSMISSION CLASSIFICATION- STANDARD - STEEL - STEEL JOIST- SELF TAP SHEET METAL SCREW - STORAGE - STRINGER - STRUCTURAL - SUBCATEGORY - SUSPENDED - SYMMETRICAL - SYSTEM

- TONGUE AND GROOVE - TREAD, THERMOSTAT - TOWEL BAR - TOP OF CURB - TOP OF CONCRETE - TELEPHONE OR TELECOM - TEMPERATURE - TERRAZZO - TOGGLE BOLT - THICKNESS - THRESHOLD - THROUGH - TACKBOARD - TEMPERED - TOP OF (SEE OTHER WORD) - TOP OF SLAB, TOP OF STRUCTURE - TOP OF STEEL - TOP OF PAVEMENT - TOILET PAPER DISPENSER - TRACTION - STRUCTURAL STEEL TUBE- TELEVISION - TOP OF WALL - TYPICAL

- UNDERWRITERS LABORATORY- UNFINISHED - UNLESS NOTED OTHERWISE - URINAL

- VENTILATION AND AIR CONDITIONING - VINYL COMPOSITION TILE - VERTICAL - VESTIBULE - VAPOR RETARDER - VINYL TILE - VINYL WALL COVERING

- WITH - WIDTH, WEST, STRUCTURAL STEEL WIDE FLANGE - WATER CLOSET - WOOD - WOOD SCREW - WINDOW - WITHOUT - WEATHERPROOFING - WATERPROOF MEMBRANE - WORK POINT - WATER RESISTANT/REPELLANT - WEATHERSTRIPPING - WAINSCOT - WEIGHT - WALL TO WALL- WELDED WIRE FABRIC

(R) R RA RAD RB RCP RD RECOM RECPT REC REF REFL REFR REG REINF REL REM REQ RESIL REV RM RO RTD RTG RWL

S SA SANSC SCHED SD SECT SF SH SHT SHR SIM SM SMS SND SP SPEC SPR SPKR SQ SSE SST SSK STA STCSTD STL STLJST STMSSTOR STRG STRUCT SUBCAT SUSP SYMM SYS

T&G T TB TC TCONC TEL TEMP TER TGB THK THRES THRU TKBD TMPD TO TOS TOSTL TP TPD TRACT TSTV TW TYP

ULUNFIN UNO, UON UR

VAC VCT VERT VEST VR VT VWC

W/W WC WDWDS WDW W/O WP WPM WPT WR WS WSCT WT WWWWF

ARCHITECTURAL / INTERIORS ABBREVIATIONS

VIEW TITLE

VIEW NUMBER

VIEW TITLE

GRAPHIC SYMBOLS

TRUE NORTH

PROPERTY LINE

SHEET REFERENCE SYMBOL

VIEW NUMBER

SHEET NUMBER

CATEGORY

DISCIPLINE

BUILDING / WALL SECTION REFERENCES

SCOPE OFNEW WORK

EXISTING WORK

COLUMN CENTERLINE

COLUMN GRIDLABEL

REFER TO THISSHEET IDENTIFICATION

EXTERIOR ELEVATION

INTERIOR ELEVATION

DETAIL

REFERENCES REFER TO THISSHEET IDENTIFICATION

MATCHLINE: A/A201ROOM NAME / NUMBER SYMBOL

ROOM NAME ROOM IDENTIFICATION

ROOM NUMBER

PARTITION TYPE, DOOR, AND MISC SYMBOLS

PARTITION TYPE TAG

KEYNOTE

REVISION CLOUD

SPOT ELEVATION

DIMENSION POINT

ELEVATION DATUM

ELEVATION SYMBOLS

1TITLE1/8" = 1'-0"

VIEW SCALE

N 1

A201

11

A301

2

A941

MATCHLINE: A/A202

10

101

0' - 0"

DP

FL EL

0' - 0"

45°

1 1/4" 5' - 0"

X

R 3

' -0"

A

1 1.1

DIMENSION LINES

A3A

101A

3

A701

DOOR NUMBER / OPENING IDENTIFIER

ANNOTATION SYMBOLS

A601 2

1

4

3

INDICATES FINISHED SURFACES SHALL ALIGN

DETAIL CALLOUT

INTERIOR DETAIL

REVISION NUMBER

REFER TO THISSHEET IDENTIFICATION

ALIGN

WALL SECTION

BUILDING SECTION

ELEVATION REFERENCES

FINISH TAG

REVISED AREA

1

A501

# EQUIPMENT TAG

11 /A301

TOILET ACCESSORY TAG

T-0

MISCELLANEOUS TAGS

WINDOW TAG

#

101A

#

11

PT

A. GENERAL NOTES:1. THE CONTRACTOR SHALL PROVIDE COMPLETE PROJECT SYSTEMS AND COMPONENTS AND

COMPLY WITH ALL REQUIREMENTS INDICATED ON THE PROJECT DOCUMENTS.

2. WORK WITHIN THE AREA BOUNDARIES INDICATED IN THE PROJECT DOCUMENTS, AND COMPLY WITH ALL APPLICABLE BUILDING CODE, REGULATION, & ORDINANCE REQUIREMENTS. OCCUPANTS ADJACENT TO THE PROJECT AREA BOUNDARIES SHALL CONTINUE UNINTERRUPTED OCCUPANCY DURING CONSTRUCTION OF THE PROJECT

3. VERIFY FIELD CONDITIONS AND COORDINATION WITH THE PROJECT DOCUMENTS PRIOR TO PROCEEDING WITH THE WORK.

4. COORDINATE THE WORK WITH ALL REQUIREMENTS INDICATED IN THE PROJECT DOCUMENTS.

5. PERFORM THE WORK AT THE PROJECT SITE DURING NORMAL BUSINESS HOURS, UNLESS OTHERWISE NOTED.

6. COORDINATE THE WORK WITH EQUIPMENT, FURNISHINGS, AND SYSTEMS PROVIDED BY THE OWNER.

7. NO ASBESTOS, LEAD, FORMALDEHYDE IN MATERIALS.

B. DEFINITIONS:1. "TYPICAL" OR "TYP" INDICATES IDENTICAL COMPLETE SYSTEM SHALL BE PROVIDED FOR EACH

OCCURRENCE OF THE CONDITION NOTED.

2. "SIMILAR" INDICATES COMPLETE SYSTEM AND COMPONENTS SHALL BE PROVIDED COMPARABLE TO THE CHARACTERISTICS FOR THE CONDITION NOTED.

3. "AS REQUIRED" INDICATES COMPONENTS REQUIRED TO COMPLETE THE NOTED, SYSTEM AS INDICATED IN THE PROJECT DOCUMENTS, SHALL BE PROVIDED.

4. "ALIGN" INDICATES ACCURATELY PROVIDE FINISH FACES OF MATERIALS IN STRAIGHT, TRUE, AND PLUMB RELATION TO ADJACENT MATERIALS.

C. DIMENSIONS:1. DIMENSIONS ARE INDICATED TO THE CENTERLINE OF THE STRUCTURAL GRID, FACE OF

CONCRETE WALL, NOMINAL FACE OF CMU WALL, FACE OF PARTITION TYPE AS SCHEDULED, UON

2. ALIGNMENT OF PARTITIONS AND FINISHES AS SCHEDULED SHALL BE STRAIGHT, TRUE & PLUMB. THE PRIORITY FOR PROJECT DIMENSIONS SHALL BE IN THE FOLLOWING ORDER:

A . MIN DIMENSION FOR ACCESSIBILITY CLEARANCE & BUILDING CODE REQUIREMENTB . LARGE SCALE DETAILS C . SMALL SCALE DETAILS D . ENLARGED VIEWS E . FLOOR PLANS AND ELEVATIONS

3. FLOOR ELEVATIONS ARE INDICATED TO THE FACE OF THE STRUCTURAL SLAB, UNLESS OTHERWISE NOTED.

4. VERTICAL DIMENSIONS ARE INDICATED FROM THE FLOOR ELEVATION TO FACE OF FINISHED MATERIAL AT THE DIMENSION POINT, UNLESS NOTED ABOVE FINISH FLOOR -"AFF".

5. CEILING HEIGHTS ARE INDICATED FROM THE FLOOR ELEVATION TO THE FACE OF SUSPENDED CEILING SYSTEM OR FACE OF FINISH MATERIAL AS SCHEDULED.

6. DIMENSIONS SHOWN ON THE DRAWINGS SHALL INDICATE THE REQUIRED SIZE, CLEARANCE, AND DIMENSIONAL RELATIONSHIP BETWEEN PROJECT SYSTEMS AND COMPONENTS. DIMENSIONS SHALL NOT BE DETERMINED BY SCALING THE DRAWINGS.

D. DRAWING SET ORGANIZATION:1. EACH DRAWING SET SHEET IS IDENTIFIED BY THE SHEET NUMBER IN THE LOWER RIGHT HAND

CORNER OF THE DRAWING TITLE BLOCK. THE SHEET TITLE PROVIDES A GENERAL DESCRIPTION OF THE CONTENTS OF THE SHEET. SHEET NUMBER EXAMPLE: A201 "A" INDICATES THE DISCIPLINE THAT CREATED THE DRAWING "2" INDICATES THE DRAWING CATEGORY CONTAINED ON THE SHEET "01" INDICATES THE SHEET NUMBER

2. SHEET NUMBERS MAY INCLUDE SUPPLEMENTAL CHARACTERS TO PROVIDE ADDITIONAL INFORMATION, SUCH AS DRAWING CONTENT, PROJECT SECTOR OR PHASE. REFER TO THE DRAWING INDEX FOR A COMPLETE LIST OF SHEETS INCLUDED IN THE DOCUMENT SET. EXAMPLE: EL201A "EL" INDICATES THE DISCIPLINE THAT CREATED THE DRAWING AND THE DRAWING CONTENT = ELECTRICAL LIGHTING "A" INDICATES SECTOR "A" OF PLAN SHEET "201". REFER TO THE PROJECT KEY PLAN OR

COMPOSITE PLAN INDICATING THE RELATIONSHIP OF THE SECTORS.

3. DRAWING SET INDEX INDICATES THE COMPLETE LIST OF SHEETS CONTAINED IN THE DRAWING SET, INDEXED BY DISCIPLINE, SHEET NUMBER AND SHEET TITLE, IN SEQUENTIAL ORDER. NOTE THAT ALL SEQUENTIAL SHEET NUMBERS MAY BE NOT USED IN THE DRAWING SET.

4. DISCIPLINE IDENTIFICATION, IN ORDER BOUND IN THE DRAWING SET. REFER TO THE DRAWING SET INDEX FOR DISCIPLINE CONTAINED IN THIS DRAWING SET:

G GENERAL INFORMATION Q EQUIPMENT C CIVIL F FIRE PROTECTION L LANDSCAPE P PLUMBING S STRUCTURAL M MECHANICAL A ARCHITECTURAL E ELECTRICAL I INTERIORS T TELECOMMUNICATIONS

5. DRAWING CATEGORY IDENTIFICATION. REFER TO THE DRAWING SET INDEX FOR DISCIPLINES, CATEGORIES, AND SHEET NUMBERS CONTAINED IN THIS DRAWING SET:

GENERAL NOTES

ARCHITECTJohnston, LLC 2603 Augusta Dr., Suite 1500Houston, TX 77057P - 713.244.8300

CIVIL & STRUCTURAL ENGINEERWALTER P MOORE 1301 MCKINNEY, SUITE 1500HOUSTON, TX 77010

MEP ENGINEERJohnston, LLC 2603 Augusta Dr., Suite 1500Houston, TX 77057P - 713.244.8300

UT HEALTH PROFESSSIONAL

BUILDING

VALET & CORRIDOR

UT HEALTH PARKING GARAGE

PHARMACY

VALET DRIVEWAY

MA

IN S

TR

EE

T

FA

NN

IN S

TR

EE

T

MEMORIAL HERMAN POB

MAIN

STR

EET

PROJECT LOCATION

FAN

NIN

STR

EET

N

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROJECT SUBMISSION:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

2:1

1:2

2 P

M

GENERAL NOTES,ABBREVIATIONS,SYMBOLS, INDEX,AND CODESUMMARY

G0.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

JOHNSTON

ADDENDUM #01

2019-12-16

2019-12-16

PROJECT TEAM

DRAWING INDEX

KEY MAPLOCATION MAP

PROJECT INFORMATION

PROJECT ADDRESS:

UNIVERSTIY OF TEXAS PROFESSIONAL BUILDING6410 FANNIN STREET HOUSTON, TX 77030

PROJECT DESCRIPTION:

THIS 9,649 S.F. PROJECT INCLUDES:

1. RENOVATION OF DRIVEWAY BETWEEN THE UT HEALTH PROFESSIONAL BUILDING AND PARKING GARAGE TO REPAIR PLUMBING, UPDATE PEDESTRIAN ROUTE AND ADD FLOOD PREVENTION IMPROVEMENTS.

2. THE VALET FUNCTION WILL MOVE FROM DROP-OFF DRIVE INTO THE BUILDING. A NEW ENTRY WILL BE CREATED WITH A NEW VALET OFFICE, WAITING AREA AND HALLWAY TO THE LOBBY.

3. THE EXISTING PHARMACY WILL BE MODIFIED TO ACCOMMODATE THE NEW HALLWAY. A NEW UNISEX TOILET WILL BE ADDED TO THE PHARMACY.

4. TEMPORARY RELOCATION OF THE VALET FUNCTION TO THE SERVICE DOCK DRIVE.

DRAWING SHEET INDEX

Sh

eet

Nu

mb

er

DRAWING TITLE 2019-1

0-2

5 9

0%

CO

NS

TR

UC

TIO

N D

OC

UM

EN

TS

2019-1

1-1

8 IS

SU

ED

FO

R C

ON

ST

RU

CT

ION

2019-1

2-1

6 A

DD

EN

DU

M #

01

00 GENERAL

G0.00 COVER ● ● ●

G0.01 GENERAL NOTES, ABBREVIATIONS, SYMBOLS, INDEX, AND CODE SUMMARY ● ● ●

G1.00 LIFE SAFETY PLAN ● ● ●

G2.00 TYPICAL MOUNTING HEIGHTS ● ●

G3.00 ADA ACCESSIBILITY ● ●

G4.00 UL ASSEMBLIES ● ●

01 CIVIL

C0.2 TOPOGRAPHIC SURVEY ●

C0.3 GENERAL NOTES ● ●

C1.0 CIVIL SITE DEMOLITION PLAN ● ●

C2.0 CIVIL SITE LAYOUT & GRADING PLAN ● ●

C3.0 CIVIL SITE UTILITY AND DRAINAGE PLAN ● ●

C4.0 STORM WATER POLLUTION PREVENTION PLAN ● ●

C5.0 CIVIL SITE DETAILS ● ●

C5.1 CIVIL SITE DETAILS ● ●

02 STRUCTURAL

S0.1 GENERAL NOTES ● ●

S1.00 PARTIAL PLANS AND DETAILS ● ●

03 DEMOLITION

AD1.01 OVERALL DEMOLITION PLAN ● ●

AD2.01 ENLARGED DEMOLITION FLOOR PLAN & REFLECTED CEILING PLAN - INTERIOR ● ●

AD2.02 ENLARGED DEMOLITION FLOOR PLAN & REFLECTED CEILING PLAN - DRIVEWAY ● ●

04 ARCHITECTURAL

A0.01 OVERALL SITE PLAN ● ●

A1.01 OVERALL FLOOR PLAN ● ● ●

A3.01 ENLARGED FLOOR PLAN & REFLECTED CEILING PLAN - INTERIOR ● ● ●

A3.02 ENLARGED FLOOR PLAN & REFLECTED CEILING PLAN - DRIVEWAY ● ●

A9.01 INTERIOR ELEVATIONS ● ●

A10.00 CASEWORK DETAILS ● ●

A10.01 CASEWORK DETAILS ● ●

A10.02 CEILING DETAILS ● ●

A10.03 INTERIOR DETAILS ● ●

A10.04 PARTITION TYPES ● ● ●

A10.05 RATED PENETRATION DETAILS ● ●

A11.01 OPENING SCHEDULE ● ● ●

A11.02 DOOR/WINDOW DETAILS ● ●

A12.00 3D VIEWS ● ●

AQ1.00 EQUIPMENT PLAN - LEVEL 1 ● ●

05 INTERIORS

IF0.00 FINISH LEGEND AND SCHEDULE ● ●

06 MECHANICAL

M0.00 MECHANICAL LEGEND, INDEX, NOTES & ABBREVIATIONS ● ●

M0.01 MECHANICAL SCHEDULES, CONTROLS AND DETAILS ● ● ●

MD1.01 MECHANICAL DEMOLITION PLAN - LEVEL 1 ● ●

M2.01 MECHANICAL DUCTWORK PLAN - LEVEL 1 ● ● ●

07 ELECTRICAL

E0.00 ELECTRICAL LEGEND, SHEET INDEX, NOTES & ABBREVIATIONS ● ●

ED1.01 ELECTRICAL DEMOLITION PLAN - LEVEL 1 ● ●

E1.01 ELECTRICAL SITE PLAN ● ● ●

E2.01 ELECTRICAL LIGHTING PLAN - LEVEL 1 ● ● ●

E3.01 ELECTRICAL POWER PLAN - LEVEL 1 ● ● ●

E5.01 ELECTRICAL FIRE ALARM PLAN - LEVEL 1 ● ● ●

E7.00 ELECTRICAL ONE-LINE, PANELS ●

E9.00 ELECTRICAL DETAILS ● ●

08 PLUMBING

P0.00 PLUMBING LEGEND, INDEX, NOTES, ABBREVIATIONS & SCHEDULES ● ●

PD1.01 PLUMBING DEMOLITION PLAN - LEVEL 1 ● ●

PU1.01 PLUMBING UNDERSLAB PLAN - LEVEL 1 ● ●

P2.01 PLUMBING PLAN - LEVEL 1 ● ●

P6.00 PLUMBING RISERS & DETAILS ● ●

CODE SUMMARY

1. PROJECT ADDRESSUT HEALTH PROFESSIONAL BUILDING6410 FANNIN STREETHOUSTON, TX 77054

OWNER:UT HEALTH SYSTEMS832 WEST ROADHOUSTON, TX 77054

2. APPLICABLE CODES AND ORDINANCES2015 NFPA 101, LIFE SAFETY CODE2015 NFPA 1, FIRE CODE2015 INTERNATIONAL BUILDING CODE2015 INTERNATIONAL MECHANICAL CODE2015 INTERNATIONAL PLUMBING CODE2010 AMERICAN WITH DISABILITIES ACT2012 TEXAS ACCESSIBILITY STANDARDS2016 ANSI / ASHRAE/ IES 90.1 ENERGY STANDARD FOR BUILDINGS

FIRE-RESISTIVE CONSTRUCTION REQUIREMENTSSTRUCTURAL FRAME UNKNOWN (TO BE DETERMINED)FLOOR CONSTRUCTION UNKNOWN (TO BE DETERMINED)ROOF CONSTRUCTION UNKNOWN (TO BE DETERMINED)

TRAVEL DISTANCE MAX 300 FT.COMMON PATH OF TRAVEL 75 FT.DEAD-END CORRIDOR 50 FT.

MINIMUM CORRIDOR WIDTH44" GENERAL CORRIDORS

INTERIOR FINISH REQUIREMENTSVERTICAL EXISTINS & PASSAGEWAYS BEXIT ACCESS CORRIDORS CROOMS & ENCLOSED SPACES C

GENERAL BUILDING DESCRIPTIONCONSTRUCTION TYPE UNKNOWN (TO BE DETERMINED)OCCUPANCY CLASSIFICATION BNO. OF FLOORS 12NO. OF BASEMENT FLOORS 2PROJECT AREA TOTAL 9,649 S.F.SPRINKLERED YES

NOTE: ARCHITECT HAS REQUESTED AND IS WAITING FOR EXISTING DRAWINGS TO DETERMINE EXISTING BUILDING INFORMATION.

1

1

1

1

1 ADDENDUM #01 2019 12 16

Page 5: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

2 22 2

S SS S

1S 1S1S 1S

2FS 2FS2FS 2FS

1 11 1

ELEV. 6

ELEV. 3

ELEV. 2 ELEV. 1

ELEV. 8 ELEV. 7

STAIR 3

ELEV. 5

SERVICE

panels

ELEV. 8 ELEV. 7

STAIR 3

BUILDING

PHONE ROOM

S SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

S

S SS S S S

EXIT

EXISTING CONSTRUCTION

LIFE SAFETY SYMBOLS LEGEND

2-HOUR MIN FIRE-RESISTANCE RATED FIRE BARRIER90 MIN OPENING PROTECTIVE

SMOKE PARTITION

1-HOUR SMOKE BARRIER WALL45 MIN OPENING PROTECTIVE

2-HOUR FIRE/SMOKE WALL90 MIN OPENING PROTECTIVE

FIRE EXTINGUISHER

1-HOUR MIN FIRE-RESISTANCE RATED FIRE BARRIER45 MIN OPENING PROTECTIVE

14' - 7"

1 2 3 4 5 6 7 8 9 10 11 13

A.1

A

B

12

D

E

F

G

H

I

J

K

35' -

1"

5' -

0"

7' -

4"

12' -

0"

11' -

2"

PHARMACYSCOPE OF PROJECT1,811 S.F.

TRAVEL DISTANCE = 98' - 4"

EX

IT

13' - 2"

EX

IT

EX

IT

EX

IT

EXIT

EX

IT

EX

IT

EXIT

EXIT

UT HEALTH PROFESSIONAL BUILDING

UT HEALTH PARKING BUILDING

MEMORIAL HERMAN POB

FA

NN

IN S

TR

EE

T

MA

IN S

TR

EE

T

PHARMACY

105

UNISEX TOILET

106

EXISTING ELECTRICAL

SWITCHGEAR ROOMWAITING ROOM

101

VALET OFFICE

102

CO

RR

IDO

R

103

PHARMACY

104

EXISTING LOBBY

EX

IT

DRIVEWAYSCOPE OF PROJECT7,838 S.F.

FE

LIFE SAFETY GENERAL NOTES

A. EXISTING CONSTRUCTION FULLY SPRINKLERED.B. NO MODIFICATIONS TO FIRE RATED WALLS ARE INCLUDED IN THE SCOPE OF

THIS PROJECT.C. NO MODIFICATIONS TO THE OCCUPANT LOAD ARE INCLUDED IN THE SCOPE

OF THE PROJECT.D. NO MODIFICATIONS TO SMOKE COMPARTMENT ARE INCLUDED IN THE

SCOPE OF THE PROJECT.

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROJECT SUBMISSION:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

2:1

1:2

4 P

M

LIFE SAFETY PLAN

G1.00

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

JOHNSTON

ADDENDUM #01

2019-12-16

2019-12-16

FIELD VERIFY ALL EXISTING CONDITIONS & DIMENSIONS PRIOR TO BEGINNING OF WORK

NOTE:

3/32" = 1'-0"26LIFE SAFETY PLAN - LEVEL 1

1

1 ADDENDUM #01 2019 12 16

Page 6: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

2 22 2

S SS S

1S 1S1S 1S

2FS 2FS2FS 2FS

1 11 1

1FS 1FS1FS 1FS

ELEV. 6

ELEV. 3

ELEV. 2 ELEV. 1

ELEV. 8 ELEV. 7

STAIR 3

ELEV. 5

SERVICE

panels

ELEV. 8 ELEV. 7

STAIR 3

BUILDING

PHONE ROOM

S SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

S

S SS S S S FLOOR PLAN LEGEND

EXISTING PARTITION TO REMAIN

NEW GYP BD PARTITION AS INDICATED

AREA NOT IN CONTRACT/EXISTING CONSTRUCTION TO REMAIN

NEW DOOR, DOOR IDENTIFIER ASSEMBLY AS INDICATED ON A11.01

101

NEW FIRE EXTINGUISHER CABINET RE: A10.03

FEC

OPENING SCHEDULE RE: A11.01X

NEW FIRE EXTINGUISHER RE: SPECIFICATIONSFE

FIRE RATING LEGEND

2-HOUR MIN FIRE-RESISTANCE RATED FIRE BARRIER90 MIN OPENING PROTECTIVE

SMOKE PARTITION

1-HOUR SMOKE BARRIER WALL45 MIN OPENING PROTECTIVE

2-HOUR FIRE/SMOKE WALL90 MIN OPENING PROTECTIVE

1-HOUR MIN FIRE-RESISTANCE RATED FIRE BARRIER45 MIN OPENING PROTECTIVE

1-HOUR FIRE/SMOKE WALL45 MIN OPENING PROTECTIVE

1 2 3 4 5 6 7 8 9 10 11 13

A.1

A

B

12

D

E

F

G

H

I

J

K

16A3.01

PHARMACY

105

PHARMACY

104

CO

RR

IDO

R

103

WAITING ROOM

101

EXISTINGELECTRICAL

SWITCHGEAR ROOM

EXISTING LOBBY

26A3.02

UNISEX TOILET

106

UT HEALTH PROFESSIONAL BUILDING

UT HEALTH PARKING BUILDING

FA

NN

IN S

TR

EE

T

MA

IN S

TR

EE

T

FE

VALET OFFICE

102

MEMORIAL HERMAN POB

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROJECT SUBMISSION:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

2:1

0:5

4 P

M

OVERALL FLOORPLAN

A1.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

JOHNSTON

ADDENDUM #01

2019-12-16

2019-12-16

GENERAL NOTES - FLOOR PLAN

A SHADED AREA DENOTES AREAS OUTSIDE OF THE LIMITS OF THEPROJECT SCOPE. CONTRACTOR TO COORDINATE WITH OWNERREGARDING DEMOLITION & CONSTRUCTION OUTSIDE OF THEPROJECT SCOPE AREA. ANY WORK DONE OUTSIDE THEPROJECT SCOPE SHOULD BE PATCHED/CONSTRUCTED TOMATCH ADJACENT AREA.

B THE GENERAL CONTRACTOR IS RESPONSIBLE FOR BRACINGAND BLOCKING OF WALLS RECEIVING MILLWORK, SHELVING,EQUIPMENT, ETC. ALL WOOD BLOCKING, GROUNDS, ROUGHBUCKS, AND MISCELLANEOUS BLOCKING IS TO BEFIRE-RETARDANT TREATED.

C THE GENERAL CONTRACTOR SHALL PATCH AND FINISH TOMATCH EXISTING ANY ADJACENT WALLS, FINISHES, ETC.,AFFECTED IN ANY MANNER, BY CONSTRUCTION.

D THE GENERAL CONTRACTOR SHALL FILL AND PATCH ALLOPENINGS AND HOLES LEFT AFTER DEMOLITION, SEAL AROUNDALL PIPING, DUCTS, ETC., AND ENSURE ACCORDANCE WITHAPPLICABLE CODES AND ORDINANCES. RE: SHEET A10.05 FORSEALING PENETRATIONS.

E THE GENERAL CONTRACTOR IS TO NOTIFY ARCHITECT IF FLOORPENETRATIONS CONFLICT WITH STRUCTURAL ELEMENTS,DUCTWORK, ETC., PRIOR TO PROCEEDING WITH WORK.

F PARTITIONS:

F1 DO NOT SCALE DRAWINGS, DIMENSIONS GOVERNING.DIMENSIONS ARE TO FACE OF FINISHED PARTITION U.N.O.(GYPSUM BOARD SURFACE-NOT STUD).

F2 PARTITIONS THAT ALIGN WITH EXISTING BUILDING PARTITIONSSHALL ALIGN WITH FINISHED FACE OF NEW GYPSUM LAYER.

F3 GYPSUM BOARD ABOVE CEILING TO BE TAPED AND FLOATEDONLY.

F4 INSTALL 5/8" WATER RESISTANT GYPSUM BOARD AT ALLPLUMBING CHASES.

F5 REFER TO SHEET A10.04 FOR PARTITION TYPES.

F6 PROVIDE BRACING ABOVE CEILING HEIGHT PARTITIONS WHENLONG UNBRACED WALL LENGTHS OCCUR, AND AT ALL DOORAND GLAZED OPENING JAMBS IN ACCORDANCE WITHMANUFACTURER'S SPECIFICATIONS.

F7 ALL PARTITIONS TO BE A3A, U.N.O.

G THE GENERAL CONTRACTOR SHALL CONFIRM ALL OWNERFURNISHED, OWNER INSTALLED (O.F.O.I.) AND OWNERFURNISHED, CONTRACTOR INSTALLED (O.F.C.I.) ITEMS WITH THEARCHITECT AND THE OWNER PRIOR TO CONTRACTION, TOCONFIRM ALL DIMENSIONAL, ARCHITECTURAL, AND MEPREQUIREMENTS AS CONFIGURED IN THESE DOCUMENTS.

H REFERENCE IDENTIFICATION OF DOORS IS SCHEDULED BY THECORRESPONDING ROOM NUMBER IN WHICH THE OPENINGOCCURS OR GIVES ACCESS TO. REFER TO A11.01 FOR DOORSCHEDULE.

I PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT.

J FOR TYPICAL MOUNTING HEIGHTS REFER TO G2.00.

K EXISTING TO REMAIN RATED WALLS & CONCRETE FLOOR, SEALALL HOLES CAUSED BY THE REMOVAL OF PIPES, CONDUITS,DUCTS, ETC. SEAL OPENINGS IN BARRIERS W/ APPROVED FIRERATED MATERIAL.

L FOR ROOM FINISHES REFER TO "FINISH SCHEDULE" & FINISHPLANS ON IF0.00.

M CLOSE ALL JOINTS BETWEEN PLUMBING FIXTURES,ACCESSORIES & DISSIMILAR MATERIALS W/ SEALANT (I.E. SINKS& ACCESSORIES TO WALL)

N REFER TO MEP DRAWINGS FOR MED GASES LOCATION,RECESSED ALARM PANDS, VALVE BOXES & ELECTRICAL PANELS,U.N.O.

O REFER TO SHEET A11.01 FOR WINDOW SCHEDULE

P WALL MOUNTED GRAB BARS, GRAB BAR FASTENERS ANDMOUNTING DEVICES TO SUPPORT AT LEAST 250 LBS. SEEELEVATION FOR MOUNTING LOCATION AND REFER TOSTRUCTURAL DRAWINGS FOR MOUNTING REQUIREMENTS.

FIELD VERIFY ALL EXISTING CONDITIONS & DIMENSIONS PRIOR TO BEGINNING OF WORK

NOTE:

3/32" = 1'-0"26OVERALL FLOOR PLAN - LEVEL 1

1

1 ADDENDUM #01 2019 12 16

Page 7: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

SD

F

S

W

ELEV. 2

S SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

S

S SS S S S

ELEV. 2

F

SD

SD SD

SD

SD

SD

SD

SD

SD

F

F

F

F

F

F

F

F

S SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

SS

S

S SS S S S

2 22 2

S SS S

1S 1S1S 1S

2FS 2FS2FS 2FS

1 11 1

1FS 1FS1FS 1FS

FLOOR PLAN LEGEND

EXISTING PARTITION TO REMAIN

NEW GYP BD PARTITION AS INDICATED

AREA NOT IN CONTRACT/EXISTING CONSTRUCTION TO REMAIN

NEW DOOR, DOOR IDENTIFIER ASSEMBLY AS INDICATED ON A11.01

101

NEW FIRE EXTINGUISHER CABINET RE: A10.03

FEC

OPENING SCHEDULE RE: A11.01X

NEW FIRE EXTINGUISHER RE: SPECIFICATIONSFE

2' x 2' GRID AND TILE SYSTEM - SEE SPECIFICATIONS

GYPSUM BOARD CEILING AS INDICATED ON PLAN.

SEE FINISH PLAN FOR PAINT SPECIFICATIONS

MATERIALS

FINISHED CEILING HEIGHT AS INDICATED ON PLAN UON.

ACP-1

ANNOTATIONS

RCP LEGEND

LIGHT FIXTURES

UNDER CABINET

LIFE SAFETY

EXIT SIGN, ARROW INDICATES PATH OF TRAVEL

SMOKE DETECTOR

LIFE SAFETY STROBE

DEMO 2' x 2' GRID AND TILE SYSTEM - SEE SPECIFICATIONS

SUPPLY AIR GRILLE

RETURN AIR GRILLE

RECESSED DOWNLIGHT

2' x 2' RECESSED DIRECT/INDIRECT LED

2' x 4' RECESSED LENSED LED

SPEAKER

RECESSED DIMMABLE DOWNLIGHTD

LED COVE LIGHT

WALL SCONCE

CEILING MOUNTED CAMERA

WIRELESS ACCESS POINT

CUSTOM CEILING AS INDICATED ON PLAN. - SEE SPECIFICATIONS

SPRINKLER

9' - 0"TYPE

HEIGHT A.F.F.

FLOOR PLAN GENERAL NOTES

REFER TO SHEET A1.01 FOR FLOOR PLAN GENERAL NOTES

7 8 9

G

H

I

J

K

A9.01 11

A9.01

13

08

A9.01 23

A9.01

26

A9.01 07

06

21

16

A9.01

22

EXISTING

LOBBY

EXISTING

ELECTRICAL

SWITCHGEAR ROOMWAITING ROOM

101

PHARMACY

104

CORRIDOR

103

PHARMACY

105

18

12

3' - 0"

3' -

0"

3' -

0"

ALIGN

VALET OFFICE

102

CLEAR

5' - 0"

1' - 10"

10

' -

6"

ALIG

N

101.1

102.1

W01

W01

24"x

36"

24"x

36"

24"x

36"

24"x

36"

24"x

36"

24"x

36"

24"x

36"

24"x

36"

24"x

36"

24"x

36"

24"x

36"

24"x

36"

21"x

36"

21"x

36"

21"x

36"

OVER HEAD TRACK LENGTH

9' - 0"

4

55

2' -

5"

ALIGNALIGN

6

5' -

7"

4

11' - 3 1/4" 11' - 4 3/4"

EQ

EQ

2' - 1"

2' -

6"

3' -

0"

4' - 1" 9' - 4 1/2" 1' - 1"

11

' -

2"

UNISEX TOILET

106

A9.01 10A9.01

24

19

14

09

EXISTING

LOBBY

EXISTING

ELECTRICAL

SWITCHGEAR ROOM

1' - 0"

8"

105.1

106.1

7' - 0"

ALIGN

C

I

B6

B5

H1

E

A9.0120

F3

I

15

1010

1010

1010

1111

12

13

1414

G3A G3AG3A

G3AG3A

16

G3A

G3A

SA3A

17

17

17

18

18

18

4' -

3 1

/2"

2' - 11 1/4"

15

15

19

ALIG

N

13' - 6"

2' - 0"

ALIGN

F.V

.

2' -

4 3

/4"

20

21

22

2323

25

25

26

26

26

6' - 5 3/4" 10' - 0"

4' -

0"

6' -

11

"

2727

14A11.02

14A11.02

SIM.

01A11.02

D3A

28

SA3A

SA3A

SA6A

SA3A

A9.01

25

30

01A11.02

29

FE

2' - 6"

2' - 1"

ALIGN

1' - 6"

ALIG

N

30

30

3030

30

30

303030

19' - 4" 20' - 0"

20

' -

0"

20

' -

0"

18

' - 1

0"

1' -

2"

31

7 8 9

G

H

I

J

K

WAITING ROOM

101EXISTING ELECTRICAL

SWITCHGEAR ROOM

PHARMACY

104

CORRIDOR

103

PHARMACY

105

7' - 6"

19' - 4" 20' - 0"

20

' -

0"

20

' -

0"

18

' - 1

0"

1' -

2"

VALET OFFICE

102

ALIGNALIGN

ALIGN

5' -

7 1

/2"

3' -

3 1

/4"

1' - 2"

5' -

6 1

/4"

8' - 0"

7' - 8"

6' -

9"

EQ

EQ

2' - 7" 4' - 8"

ALIGN

1

1

2

2

1' -

6"

1' - 6"

1' -

6"

33

03 / A10.02

03 / A10.02

03 / A10.02

1

1

77

2

2

88

UNISEX TOILET

106

8' - 0"7' - 6"

1' -

7"

ALIG

N

ALIGN

9

1' - 0"

7' - 0"

03 / A10.02

22

2

EQ EQ

2' - 6" 2' - 6"

3' -

6"

2' -

0"

04 / A10.0209 / A10.02

09 / A10.02

09 / A10.02

09 / A10.02

09 / A10.02

03 / A10.02

7

2' - 8 1/2"

EQ

EQ

1' - 6 1/2"

2' -

6"

2' - 11"

15

05 / A10.02

24

2' -

5"

1' - 2"

FIRE RATING LEGEND

2-HOUR MIN FIRE-RESISTANCE RATED FIRE BARRIER

90 MIN OPENING PROTECTIVE

SMOKE PARTITION

1-HOUR SMOKE BARRIER WALL

45 MIN OPENING PROTECTIVE

2-HOUR FIRE/SMOKE WALL

90 MIN OPENING PROTECTIVE

1-HOUR MIN FIRE-RESISTANCE RATED FIRE BARRIER

45 MIN OPENING PROTECTIVE

1-HOUR FIRE/SMOKE WALL

45 MIN OPENING PROTECTIVE

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROJECT SUBMISSION:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

2:3

9:5

5 P

M

ENLARGED FLOORPLAN & REFLECTEDCEILING PLAN -INTERIOR

A3.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

JOHNSTON

ADDENDUM #01

2019-12-16

2019-12-16

KEYNOTES LEGEND12 SURFACE MOUNTED ENTRY MAT RE: FINISHES PLAN

13 RECESSED ENTRY MAT RE: FINISHES PLAN AND 11/A10.03

14 EXISTING CANOPY ABOVE (SHOWN DASHED)

15 PROVIDE BACKING/BLOCKING IN WALL AS REQUIRED FOR WALLMOUNTED TV

16 FLOOR DRAIN, SLOPE TO DRAIN, RE: 01/A10.03 & PLUMBINGDRAWINGS

17 PROVIDE BACKING IN WALL AS REQUIRED FOR UPPER CABINETS

18 RADIUS EDGE AT COUNTERTOP

19 EXISTING FURRDOWN ABOVE

20 TRANSACTION WINDOW RE: 28/A11.01

21 FLOOR TRANSITION RE: 18/A10.03

22 TRANSITION/SILL DETAIL RE: 23/A11.02

23 PROVIDE ADDITIONAL SUPPORT AS REQUIRED IN PARTITIONLENGTH OF GRAB BAR TO SUPPORT A MINIMUM WEIGHT OF 200LBS.

24 PROVIDE ACCESS PANEL AS REQUIRED RE: 08/A10.02

25 PROVIDE FINISHED END PANEL SUPPORT

26 PROVIDE UNDER CABINET LIGHTING AT UPPER CABINET RE:ELECTRICAL DRAWINGS

27 NEW HIGH DENSITY STORAGE SYSTEM SHELVING HT. 86.5" A.F.F.

28 FIRE EXTINGUISHER CABINET RE: 03/A10.03

29 WALL MOUNTED FIRE EXTINGUISHER RE: SPECIFICATIONS

30 VERIFY COMPLIANCE OF EXIST. WALLS, DOORS, AND FRAMESWITH INDICATED RATING. UPGRADE AS NECESSARY.

31 SIZE OF COLUMN TO BE VERIFIED DURING CONSTRUCTION.

KEYNOTES LEGEND1 PROVIDE CEILING MOUNTED CAMERA RE: 10/A10.02 AND

COORDINATE WITH OWNER.

2 RE: SHEET A10.02 FOR TYPICAL GYP BD CEILING DETAILS

3 EXISTING CEILING, LIGHTING FIXTURES AND ABOVE CEILINGWORK TO REMAIN. PROTECT IN PLACE, PATCH AND MATCHEXISTING AS NECESSARY FOR RENOVATION. RE: MEP DRAWINGS

4 EXISTING COLUMN AND PIPES TO REMAIN. PROTECT ASREQUIRED.

5 EXISTING DRIVEWAY TO REMAIN RE: AD2.02

6 EXISTING MILLWORK TO REMAIN. PROTECT AS REQUIRED

7 EXISTING FURRDOWN TO REMAIN.

8 WALL SCONCE MOUNTED AT 6'-6" A.F.F., RE: ELECTRICALDRAWINGS

9 VANITY LIGHT, TYP. RE: ELECTRICAL DRAWINGS

10 RELOCATED EXISTING SHELVING

11 LOW WALL WITH SWING DOOR RE: ELEVATIONS AND A10.01

TOILET ACCESSORY SCHEDULE

ID Item Description Model # ResponsibilityB5 1 1/4" Nom Dia SST Grab Bar, Surface Mount, 36"

LengthBobrick - B-6806 CFCI

B6 1 1/4" Nom Dia SST Grab Bar, Surface Mount, 42"Length

Bobrick - B-6806 CFCI

C Mirror Framed, 18"W x 36"H Bobrick - B-290 CFCI

E Toilet Tissue Dispenser, Surface Mount OFCI

F3 Paper Towel Dispenser, Surface Mount OFCI

H1 Toilet Seat Cover Dispenser OFCI

I Soap Dispenser, Surface Mount OFCI

J1 Coat Hook Bobrick - B-7671 CFCI

X

FIELD VERIFY ALL EXISTING CONDITIONS & DIMENSIONS PRIOR TO BEGINNING OF WORK

NOTE:

GENERAL NOTES - RCP

A REFER TO "FINISH SCHEDULE" FOR FURTHER DEFINITION OFCEILING MATERIALS AND FINISHES.

B LOCATE ALL CEILING MOUNTED SMOKE DETECTORS ANDSPEAKERS IN THE CENTER OF FULL PANELS AT LAY-IN CEILING.

C LOCATE ALL SPRINKLER HEADS IN THE CENTER OF FULLPANELS AT LAY-IN CEILINGS. AT GYPSUM BOARD CEILINGS,SYMMETRICALLY SPACE HEADS AND CENTER ON LIGHT ROWSWHERE AREAS LIMITATIONS PERMIT.

D REFER TO CEILING PLANS FOR CEILING HEIGHTS. ALL HEIGHTSARE TO BOTTOM OF GRID SYSTEM OR GYP BOARD ABOVEFINISH FLOOR (AFF RELATIVE TO THE FLOOR THAT THECEILING PLAN IS SHOWN).

E REFER TO ELECTRICAL DRAWINGS FOR LIGHT FIXTURE TYPES.

F ALL CEILING GRIDS ARE TO BE CENTERED IN A ROOM UNLESSDIMENSIONED OTHERWISE.

G REFER TO MECHANICAL DRAWINGS FOR HVAC DIFFUSERGRILLE SIZES AND TYPES.

H SHADED AREA DENOTES AREAS OUTSIDE OF THE LIMITS OFTHE PROJECT SCOPE. CONTRACTOR TO COORDINATE WITHOWNER REGARDING DEMOLITION & CONSTRUCTION OUTSIDEOF THE PROJECT SCOPE AREA. ANY WORK DONE OUTSIDETHE PROJECT SCOPE SHOULD BE PATCHED/CONSTRUCTED TOMATCH ADJACENT AREA.

I ALL CEILINGS TO BE 9'-0" AFF U.N.O. NEW TYPICAL CEILINGHEIGHT TO MATCH EXISTING , VERIFY IN FIELD EXISTINGCONDITION.

J ALL ACOUSTICAL CEILINGS TO BE ACT-1, RE: IF0.00 UNLESSNOTED OTHERWISE

K ALL UPPER CABINETS TO HAVE UNDERCOUNTER LIGHTING,U.N.O.

L ALL GYPSUM FUR DOWNS ARE AT 7'-6" UNLESS NOTEDOTHERWISE. PAINT ALL SIDES & SOFFITS OF FUR DOWN PT-1.FUR DOWN AT WAITING AREA TO BE PAINTED PT-1

1/4" = 1'-0"16

ENLARGED FLOOR PLAN -PHARMACY & VALET SUITE

1/4" = 1'-0"26

ENLARGED REFLECTED CEILING PLAN -PHARMACY & VALET SUITE

X

1

1

1

1 ADDENDUM #01 2019 12 16

1

1

1

1

1

1

1

1

1

Page 8: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

THE "PARTITION TYPE TAG", ILLUSTRATED BELOW, INDICATES THE ASSEMBLY OF THE COMPLETE EXTENT OF EACH PARTITION INDICATED BY THE TAG ON THE FLOOR PLANS, AND OTHER DRAWINGS IN THE PROJECT DOCUMENTS. REFER TO PARTITION TYPE DETAILS INDICATED BY THE "PARTITION TYPE" CHARACTER ON THE TAG, FOR EXAMPLE: PARTITION TAG ID "A" = REFERENCE TO DETAIL "TYPE A".REFER TO THE "FIRE RATING LEGEND" BELOW FOR THE FIRE-RESISTANCE CLASSIFICATION NOTED BY THE "FIRE RATING INDENTIFICATION" ON THE TAG, FOR EXAMPLE: "1" = 60 MIN FIRE-RESISTANCE RATED PARTITION ASSEMBLY. THE "METAL STUD/CMU NOM WIDTH" CHARACTER ON THE TAG, AND AS SHOWN ON PARTITION TYPE DETAILS, INDICATES THE METAL STUD OR CMU NOM WIDTH. OR EXAMPLE: "3" = 3-5/8" METAL STUDS. THE "PARTITION TYPE MODIFIER" CHARACTERS REFER TO THE "PARTITION TYPE MODIFIER" NOTES SHOWN BELOW, WHICH APPLY TO THE COMPLETE EXTENT OF EACH PARTITION WHERE SO TAGGED.THE "PARTITION KEYNOTE" CHARACTERS REFER TO NOTES SHOWN ON DRAWING KEYNOTE LEGENDS, WHICH APPLY TO THE COMPLETE EXTENT OF EACH PARTITION SO TAGGED. FOR EXAMPLE, "S50" = PARTITION SHALL COMPLY WITH SOUND TRANSMISSION CLASS LEVEL STC-50.PARTITION TYPE TAG:

PARTITION (AS INDICATED ON FLOOR PLANS)

FIRE RATING INDICATION

PARTITION TYPE

MET STUD/CMU WIDTH

PARTITION TYPE MODIFIER

PARTITION TYPE MODIFIERS:THE FOLLOWING NOTES APPLY TO THE FULL EXTENT OF EACH PARTN, WHERE "PARTN TYPE MODIFIER" CHARACTER(S) ARE SHOWN ON THE TAG:A. PROVIDE ACOUSTIC BATT INSUL FULL DEPTH OF EACH METAL STUD CAVITYB. PROVIDE ACOUSTIC BATT INSUL FULL DEPTH OF EACH MET STUD CAVITY, AND ACOUSTIC BATT INSUL ABOVE TOP OF PARTN, MIN 24" EACH DIRECTION PERPENDICULAR TO PARTNC. PROVIDE (1) ADDITIONAL LAYER OF 5/8" GYP BD ATTACHED TO (1) SIDE OF SCHED PARTN TYPE AS INDICATED, EXTEND FULL HT OF PARTN, PROVIDE ACOUSTIC BATT INSUL FULL WIDTH OF EACH STUD CAVITYD. PROVIDE (1) ADDITIONAL LAYER OF 5/8" GYP BD ATTACHED TO BOTH SIDES OF SCHED PARTN TYPE, EXTEND FULL HT OF PARTN, PROVIDE ACOUSTIC BATT INSUL FULL WIDTH OF EACH STUD CAVITYH. PROVIDE (1) LAYER OF 5/8" LAM ACOUSTIC GYP BD (TYPE X ON FIRE-RATED PARTN) ATTACHED TO FACE OF MET STUDS ON BOTH SIDES OF SCHED PARTN TYPE IN PLACE OF (1) LAYER OF SCHED GYP BD ON BOTH SIDES, AND PROVIDE ACOUSTIC BATT INSUL FULL DEPTH OF EACH MET STUD CAVITYJ. TERMINATE ADDITIONAL LAYERS OF GYP BD AS SCHED @ 4" ABOVE FINISH CLG, UONL. PROVIDE PARTN TYPE AS SCHED, WITH MIN 20 GA MET STUDS @ 16" OCM. PROVIDE PARTN TYPE AS SCHED, WITH MIN 18 GA MET STUDS @ 16" OCN. PROVIDE PARTN TYPE AS SCHED, WITH MIN 16 GA MET STUDS @ 16" OCP. PROVIDE (1) LAYER 5/8" WR GYP BD IN PLACE OF THE OUTSIDE LAYER OF GYP BD ON SCHED PARTN TYPE, MOUNT ON EACH FACE OF THE PARTN EXPOSED TO MOISTURE - EXTEND FULL HT OF PARTN UONR. TERMINATE BOTTOM RUNNER TRACK OF THE PARTITION TYPE AT THE TOP OF RAISED FLOOR ACCESS PANEL ASSEMBLY. REFER TO ACCESS FLOOR SYSTEM DETAIL/T. PROVIDE THERMAL INSUL BATT FULL HT IN EACH STUD CAVITY, AS SPECIFIEDU. PROVIDE THERMAL INSULATION BATT FULL HEIGHT IN EACH STUD CAVITY, AS SPECIFIED.

PARTITION TYPE GENERAL NOTES

FIRE RATING LEGEND

THE COMPLETE ASSEMBLY OF EACH PARTITION WITH A FIRE RATING INDICATION SYMBOL SHOWN ON THE TAG, SHALL COMPLY WITH ALL REQUIREMENTS OF THE FIRE-RESISTANCE RATING CLASSIFICATION: SYMBOL RATING CLASSIFICATION <OMITTED> NON-RATED PARTITION, UON1 60 MIN FIRE-RESISTANCE RATED FIRE PARTITION1S 60 MIN FIRE-RESISTANCE RATED & SMOKE BARRIER PARTITION 2 120 MIN FIRE-RESISTANCE RATED FIRE BARRIER3 180 MIN FIRE-RESISTANCE RATED FIRE BARRIER4 240 MIN FIRE-RESISTANCE RATED FIRE BARRIER

PARTITION KEYNOTES

THE FOLLOWING NOTES APPLY TO THE FULL EXTENT OF EACH PARTN, WHERE "PARTN KEYNOTE" CHARACTER(S) ARE SHOWN ON THE TAG: S-- KEYNOTE "S" INDICATES THE COMPLETE PARTN ASSEMBLY SHALL COMPLY WITH THE SOUND TRANSMISSION CLASS LEVEL AS INDICATED - FOR EXAMPLE, S50 = STC 50.

2A3A

1/4"

5/8"

BOTTOM OF STRUC

MET TOP RUNNER TRACK, AS INDICATED ON REFERENCED DETAIL

CEILING AS SCHED

MET STUD WIDTH: MET STUDS SHALL BE @ 16" OC, UON

DESIGNATION STUD WIDTH

2

3

4

6

2-1/2"

3-5/8"

4"

6"

5/8" GYP BD, (1) LAYER EA SIDE OF MET STUDS

ACOUSTIC INSULATION BATT WHERE SCHEDULED

MIN 1/8" PDF @ 24" OC, 1-1/4" MIN EMBEDMENT

MET BOTTOM RUNNER TRACK

ACOUSTIC SEALANT BOTH SIDES OF PARTN @ PARTN TYPE SCHED W/ ACOUSTIC INSUL

CONCRETE SLAB

FIRE RATING: NON RATED

01A10.05

STC 45-49

1/4"

MET STUD WIDTH: MET STUDS INDICATED @ 16" OC, UON

DESIGNATION STUD WIDTH

23

2-1/2"3-5/8"

5/8" GYP BD, (1) LAYER ON FINISH SIDE OF PARTN

MIN 1/8" PDF @ 24" OC, 1-1/4" MIN EMBEDMENT

MET BOTTOM RUNNER TRACK

ACOUSTIC SEALANT @ PARTN TYPE SCHED W/ ACOUSTIC INSUL

CONCRETE SLAB

FIRE RATING: NON RATED

5/8"

UO

N BOTTOM OF STRUC

MET TOP RUNNER TRACK, AS INDICATED ON REFERENCED DETAIL

CEILING AS SCHED

ACOUSTIC INSULATION BATT WHERE SCHEDULED

1 1-5/8"

01A10.05

6 6"

4" M

IN

1/4"

5/8"

UO

N

BOTTOM OF STRUC

"NON-RATED PARTITION TO STRUC" DETAILS INDICATE ATTACHMENT TO STRUC

MET TOP RUNNER TRACK, AS INDICATED ON REFERENCED DETAIL

PROVIDE ACOUS INSUL BATT EXTEND MIN 24" EACH SIDE OF PARTN, @ PARTN TYPES SCHED W/ ACOUS INSUL

TERMINATE GYP BD 4" ABOVE CLG

SUSPENDED CEILING AS SCHED

ACOUSTIC INSULATION BATT WHERE SCHEDULED

MET STUD WIDTH: MET STUDS INDICATED @ 16" OC, UON

DESIGNATION STUD WIDTH

2

3

6

2-1/2"

3-5/8"

6"

5/8" GYP BD, (1) LAYER EA SIDE OF METAL STUDS

MIN 1/8" PDF @ 24" OC, MIN 1-1/4" EMBEDMENT

MET BOTTOM RUNNER TRACK

ACOUSTIC SEALANT BOTH SIDES OF PARTN @ PARTN TYPE SCHED W/ ACOUSTIC INSUL

CONCRETE SLAB, UON

FIRE RATING: NON RATED

01A10.05

OFFSET PARTN TIGHT TO BOTTOM OF DUCT, CRACE/SUPPORT AS REQUIRED

PARTN

EXTEND WALL STRAIGHTTO STRUCTURE ABOVE

WHERE NO DUCT OCCURS

EXISTING PARTN

FIN. CEILING

HVAC DUCT WHERE

OCCURS, REFER TOMECH DRWG, MOUNTTIGHT TO STL BEAM

MET BOTTOM RUNNER TRACK

BOTTOM OF STRUC

BOTTOM OF STL BEAM

WHERE OCCURS

OFFSET PARTN

VARIES

DIM INDICATED ON FLOOR PLAN

1/4"

5/8"

BOTTOM OF STRUC

MET TOP RUNNER TRACK, AS INDICATED ON REFERENCED DETAIL

CEILING AS SCHED

MET STUD WIDTH: MET STUDS SHALL BE @ 16" OC, UON

DESIGNATION STUD WIDTH

2

3

4

6

2-1/2"

3-5/8"

4"

6"

5/8" GYP BD, (1) LAYER EA SIDE OF MET STUDS

ACOUSTIC INSULATION BATT WHERE SCHEDULED

MIN 1/8" PDF @ 24" OC, 1-1/4" MIN EMBEDMENT

MET BOTTOM RUNNER TRACK

PROVIDE SEALANT AT BOTH SIDES OF PARTITION

CONCRETE SLAB

FIRE RATING: NON RATED

PROVIDE SEALANT AT BOTH SIDES OF PARTITION

01A10.05

STC 45-49

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

2:1

1:0

0 P

M

PARTITION TYPES

A10.04

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

JOHNSTON

PROJECT SUBMISSION:

2019-12-16

2019-12-16

GENERAL NOTES -PARTITION

A FIRE RESISTANT GYPSUM BOARD.

- PARTITION FIRE AND/OR SMOKE RATINGS ARE INDICATED ONTHE FLOOR PLANS BY DASHED LINE OR SYMBOL. SEE SHEETS GSERIES FOR LEGEND

- FIRE RATED PARTITION CONSTRUCTION MUST CONFORM TOGYPSUM ASSOCIATION (GA) DESIGNS, UNDERWRITERSLABORATORY (UL) TESTED DESIGNS OR OTHER TESTSAPPROVED BY GOVERNING CODE AUTHORITIES. FIRE ASSEMBLYDESIGN NUMBERS (I.E., GA WP1200, UL U419) NOTED ONPARTITION DETAILS SHALL BE FOLLOWED WHEN A FIRE RATEDASSEMBLY IS INDICATED.

- WHEN FIRE RATED PARTITIONS INTERSECT NON-RATEDPARTISIONS, CARRY FIRE RATED ASSEMBLY THROUGHNON-RATED CONSTRUCTION.

- CUTOUTS FOR ELECTRICAL DEVICES ON OPPOSITE SIDES OFPARTITIONS IN SAME STUD SPACE IS NOT ALLOWED.

- PROVIDE UL SYSTEM PENETRATION AT PENETRATIONS ANDTERMINATIONS IN ACCORDANCE WITH DIVISION 7.

- PROVIDE FIRE STOPPING AND FIRE SAFING AT TOP OFPARTITION TERMINATIONS TO COMPLY WITH FIRE RATINGASSEMBLY AND EXTEND RATING TO STRUCTURAL DECK ABOVE.

B INSTALL BACKING PLATES AT ALL WALL-MOUNTED RAILINGS,WALL MOUNTED CASEWORK OR MILLWORK AND WALL MOUNTEDDOOR BUMPERS.

C ALL CORRIDOR PARTITIONS TO TO BE CONSTRUCTED TO RESISTTHE PASSAGE OF SMOKE OR TO MEET THE REQUIRED RATING.

D PROVIDE FOR DEFLECTION OF STRUCTURE AT TERMINATIONSOF PARTITION WITH STRUCTURE ABOVE IN ACCORDANCE TODIVISIONS 4 AND 9.

E PROVIDE ACOUSTIC BATT INSULATION IN ALL PARTITIONSUNLESS NOTED OTHERWISE IN PARTITION TYPE.

3" = 1'-0"06TYPE A: FULL HT PARTN, NON RATED

3" = 1'-0"21TYPE G: FULL HT FURRING

3" = 1'-0"16TYPE D: PARTIAL HT PARTN

1 1/2" = 1'-0"26PARTN OFFSET @ HVAC DUCT

3" = 1'-0"08TYPE SA: FULL HT SMOKE PARTN, NON RATED

1

1

1 ADDENDUM #01 2019 12 16

Page 9: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

NOTE:GLASS LITE DIMENSIONS ARE TO EDGE OF EXPOSED GLASS

DOOR TYPE FFLUSH PANEL

DOOR TYPE S1SLIDING PANEL ASSMBLY

GL-01

6' -

8"

TO

BT

M O

F S

TR

OB

E L

EN

S

5' -

0"

4' -

0"

UO

N

3' -

6"

3' -

2"

UO

N

1' -

6"

UO

N

6" , UON

ALIGN DEVICES VERTICALLYWHERE SHOWN STACKED INPLAN VIEW

LIFE SAFETY DEVICES-CENTERABOVE ELEC DEVICES, SIGNS,OR FEC BELOW

WALL MTD SIGNAGE

DOOR LATCH, PANIC DEVICE

LIGHT SWITCHES, THERMOSTAT, OCCUPANCY SENSOR, CARD READER, DOOR CONTROL DEVICES

TELECOM & FIRE ALARM

DOOR FRAME/WALL OPNG WHERE OCCURS

VOICE/DATA/POWER DEVICES, UON

FIN FLR

LOCATE DEVICES 6" FROM DOOR/WALL OPNG, OR AS DIMENSIONED, WHERE NOT DIMENSIONED, LOCATE @ NEAREST MET STUD FROM LOCATION SHOWN ON FLOOR PLAN

PLAN VIEW

ELEV VIEW

T

CR

DEVICE TYPE MODIFIER AS INDICATED

DEVICE SYMBOL

DEVICE MOUNTING HEIGHT AS INDICATED

F

48 G

DEADLOCK STRIKE

HOSPITAL ARM PULL (LOWER BASE) AND PUSH PLATE

PUSH BAR AND PULL

STRIKE FOR KNOB LOCKS, HANDLE SETS, ROOLER LATCHES & EXIT DEVICES

3' -

4 3

/8"

3' -

6"

3' -

9"

4' -

0"

11

3/4

"1

' -

1"

EQ

EQ

NE

T D

OO

R H

EIG

HT

USE 3 HINGES FOR DOORS UP TO AND INCLUDING 7'-6" ADD 1 HINGE FOR EACH 2'-6" IN HEIGHT OR FRACTION THERE OF

UP

TO

UP

TO

DOOR

U.N.O.

U.N.O.

05/ A11.02

04/ A11.02

FRAME TYPE 01DOOR OPNG

FRAME TYPE 02SLIDING PANEL ASSMBLY

02/ A11.02

GL-01

01/ A11.02

W01 TRANSACTION WINDOW

2' -

7 1

/2"

GL-02

07/ A11.02

08/ A11.02

06/ A11.02

12/ A11.02

11/ A11.02

14/ A11.02

3' -

6"

2' - 1 3/4"

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

2:1

1:0

5 P

M

OPENINGSCHEDULE

A11.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

JOHNSTON

PROJECT SUBMISSION:

2019-12-16

2019-12-16

DOOR SCHEDULE

MARK ROOM NAME

DOORS FRAMES DETAILS

FIRERATING

HARDWAREGROUP COMMENTSTYPE MATERIAL FINISH

GLASSTYPE

SIZE

TYPE MATERIAL FINISHGLASSTYPE HEAD SILL JAMBWIDTH 1 WIDTH 2 HEIGHT

101.1 WAITING ROOM GL AL GL-01 02/A11.02 09/A11.02 01/A11.02 AUTOMATIC SLIDING DOOR

102.1 VALET OFFICE F WD P-LAM - 3' - 0" 7' - 0" 01 HM PT 05/A11.02 04/A11.02 K201

105.1 PHARMACY F WD P-LAM - 3' - 0" 7' - 0" 01 HM PT 05/A11.02 04/A11.02 20 MIN 101

106.1 UNISEX TOILET F WD P-LAM - 3' - 0" 7' - 0" 01 HM PT 05/A11.02 04/A11.02 341

WINDOW SCHEDULE

MARKROOMNAME

ROUGH OPENING GLAZING SILLHEIGHTWIDTH HEIGHT TYPE

W01 VALET OFFICE 2' - 1 3/4" 3' - 6" GL-02 2' - 7 1/2"

W01 WAITING 2' - 1 3/4" 3' - 6" GL-02 2' - 7 1/2"

GENERAL NOTES - DOORS

A DOOR AND FRAME ASSEMBLIES SHALL COMPLY WITH ALLSCHEDULED REQUIREMENTS, GENERAL NOTES & LEGENDS,

DOOR AND FRAME DETAILS, AND PROJECT SPECIFICATIONS.

B "OPENING IDENTIFIERS" INDICATED ON THE SCHEDULEIDENTIFY DOOR-FRAME ASSEMBLY TYPES, WHICH ARE SHOWN

THE DOOR TAG FOR EACH DOOR OPENING ON THE FLOORPLANS.

C "DOOR PANEL TYPES" AND "FRAME TYPES' INDICATED ON THE SCHEDULE REFER TO THE "DOOR TYPE DIAGRAMS" AND

"FRAME TYPE DIAGRAMS", AND "CONSTRUCTION TYPES", "FINISH TYPES", "GLASS TYPES" REFER TO CORRESPONDING

LEGENDS SHOWN ON THE DOOR SCHEDULE SHEET.

D DOOR WIDTH AND DOOR HEIGHT INDICATE THE NOMINALDIMENSIONS OF EACH DOOR LEAF (SHOWN IN INCHES). DOORWIDTH FOR ASSEMBLIES WITH A SINGLE DOOR LEAF ISINDICATED BY "DOOR WIDTH 1." ACTUAL DOOR DIMENSIONSSHALL COMPLY WITH HEAD - JAMB - MULLION - SILL DETAILS

AND DOOR SPACING AND CLEARANCES AS SPECIFIED. NOTE THAT ALL DOOR THICKNESSES ARE 1-3/4", UON.

E FRAME ASSEMBLIES SHALL COMPLY WITH "HEAD - JAMB -MULLION - SILL" DETAILS AS SCHEDULED. DETAIL NUMBERSREFERENCE SHEET A11.02, UON.

F "FIRE RATING" SYMBOL INDICATES THE FIRE RATING MINUTESFOR EACH ASSEMBLY, AS INDICATED BY THE "FIRE RATINGLEGEND" ON THE DOOR SCHEDULE SHEET.

G "HARDWARE GROUP" NUMBER REFERS TO GROUPS SHOWN ON THE DOOR SCHEDULE SHEET, AND REQUIREMENTS

INDICATED BY THE "INTERIOR HARDWARE TYPE" LIST, "HARWARE TYPE NOTES", AND PROJECT SPECIFICATIONS.

REFER TO SHEET: A11.02 FOR HARDWARE SCHEDULE

H "TYPE REMARKS" REFER TO REQUIREMENTS INDICATED BY THE "TYPE REMARK LEGEND" ON THE DOOR SCHEDULE SHEET

I DOOR UNDERCUT FOR RATED DOORS TO BE 3/4" MAX.

J DOOR UNDERCUT FOR NON-RATED DOORS TO BE 1" MAX.

K REFER TO SHEET: A11.02 FOR DOOR/WINDOW TYPES &DETAILS

L REFER TO SHEET: A11.01 FOR HARDWARE SETS

M THE HARDWARE SETS REPRESENT THE DESIGN INTENT ANDDIRECTION OF THE OWNER AND ARCHITECT. THEY ARE AGUIDELINE ONLY AND SHOULD NOT BE CONSIDERED ADETAILED HARDWARE SCHEDULE. DISCREPANCIES,CONFLICTING HARDWARE AND MISSING ITEMS SHOULD BEBROUGHT TO THE ATTENTION OF THE ARCHITECT WITHCORRECTIONS MADE PRIOR TO THE BIDDING PROCESS.OMITTED ITEMS NOT INCLUDED IN A HARDWARE SET SHOULDBE SCHEDULED WITH THE APPROPRIATE ADDITIONALHARDWARE REQUIRED FOR PROPER APPLICATION ANDFUNCTIONALITY.

DOOR TYPE LEGEND

F FLUSH PANEL DOOR

S1 SLIDING DOOR ASSEMBLY

FRAME TYPE LEGEND

01 STANDARD 3-PIECE DOOR FRAME

02 SLIDING DOOR ASSEMBLY

NOTE A SUFFIX MODIFIER (AL, GL, HM, SS, WD) DENOTES FRAMEMATERIAL

FINISH TYPE LEGEND

AA ANODIZED ALUMINUM

PL PLASTIC LAMINATE

SSM SOLID SURFACE MATERIAL

CONSTRUCTION TYPE LEGEND

AL ALUMINUM

GL GLASS - GLASS TYPE AS SCHEDULED

GLASS TYPE LEGEND

GL-01 1/4" TEMPERED GLASS, CLEAR

GL-02 3/4" IMPACT RESISTANT SECURTY GLASS, CLEAR

GL-03 1/4" TEMPERED SPANDREL GLASS

3/8" = 1'-0"27DOOR TYPE DIAGRAM

3/8" = 1'-0"06GENERAL DEVICE ALIGNMENT DIAGRAM

3/8" = 1'-0"26DOOR TYPE DIAGRAM

3/8" = 1'-0"28WINDOW TYPE DIAGRAM

S1 AL AA8' - 0" 7' - 8" 02 GL-01 900

HARDWARE GROUP NO. 101FOR USE ON DOOR #: 105.1 PROVIDE EACH SGL DOOR WITH THE FOLLOWING: QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 (3 EA. @ DOORS UNDER 90") 652 IVE1 EA OFFICE/ENTRY LOCK 70-8255-OB 626 SAR1 EA PERMANENT CORE MATCH EXISTING KEY SYSTEM BES1 EA SURFACE CLOSER 4040XP RW/PA TBSRT (MTG PLT, SPCR AS REQ) 689 LCN1 EA WALL STOP WS406/407CCV 630 IVE1 EA GASKETING 188FSBK PSA (SR64 SILENCERS @ NON-RATED DOORS) BK ZER

HARDWARE GROUP NO. 341FOR USE ON DOOR #: 106.1 PROVIDE EACH SGL DOOR WITH THE FOLLOWING: QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 (3 EA. @ DOORS UNDER 90") 652 IVE1 EA PRIVACY W/INDICATOR 49(OCC/VAC @ OUTSIDE)-8265 X B LEVER 626 SAR1 EA SURFACE CLOSER 4040XP RW/PA TBSRT (MTG PLT, SPCR AS REQ) 689 LCN1 EA WALL STOP WS406/407CCV 630 IVE1 EA GASKETING 188FSBK PSA (SR64 SILENCERS @ NON-RATED DOORS) BK ZER

HARDWARE GROUP NO. 900FOR USE ON DOOR #: 101.1 PROVIDE EACH SGL DOOR WITH THE FOLLOWING: QTY DESCRIPTION CATALOG NUMBER FINISH MFR

ALL HARDWARE BY AUTOMATIC SLIDING DOOR SUPPLIER

HARDWARE GROUP NO. K201FOR USE ON DOOR #: 102.1 PROVIDE EACH SGL DOOR WITH THE FOLLOWING: QTY DESCRIPTION CATALOG NUMBER FINISH MFR

3 EA HINGE 5BB1 4.5 X 4.5 BBLK IVE1 EA TRILOGY KEYPAD LOCK DL27-00-IC US26D TRI1 EA PERMANENT CORE MATCH EXISTING KEY SYSTEM BES1 EA WALL STOP WS406/407CCV 630 IVE1 EA GASKETING 188FSBK PSA (SR64 SILENCERS @ NON-RATED DOORS ) BK ZER

1

1 ADDENDUM #01 2019 12 16

Page 10: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

KEY:

TYPE "B" UNLESS OTHERWISE INDICATED.

INLET DUCT SIZE SCHEDULE

6" 0-100 CFM 8" 100-220 CFM 10" 225-330 CFM 12" 330-510 CFM 14" 510-700 CFM

AIR DEVICE SCHEDULE NOTES:

1. PROVIDE SQUARE TO ROUND TRANSITION FOR TYPE A CEILING DIFFUSERS FOR DUCT SIZE AND CFM INDICATED (SEE INLET DUCT SIZE CHART, THIS SCHEDULE).

2. PROVIDE FINISH AS SPECIFIED ON ARCHITECTURAL DRAWINGS..3. PROVIDE VOLUME DAMPER AT BRANCH DUCT TAP ABOVE ACCESSIBLE

CEILINGS.

LAY - IN CEILING DIFFUSER 01

SECURE FLEX DUCT INNER SLEEVE TO AIR DEVICE NECK WITH STAINLESS STEEL CLAMP AND VAPOR SEAL

LAY-INPANEL

SEE AIR DISTRIBUTION DEVICESCHEDULE FOR AIR DISTRIBUTIONDEVICE MODEL, SIZE & CFM RANGE

ADJUSTABLE AIR DEFLECTORS ONPERFORATED FACE FOR TYPE CDCEILING DIFFUSER SUPPLY ONLY

PREFORMEDINSULATION &VAPORBARRIERINSULATION

INSULATED FLEXIBLEDUCT SEE AIRDISTRIBUTIONDEVICE SCHEDULEFOR FLEX DUCTSIZES

INVERTED T-BAR

SECURE FLEX DUCT INNER SLEEVE TOSPIN-IN WITH STAINLESS STEEL CLAMP AND VAPOR SEAL

SUPPLY/RETURN EXHAUSTDUCT WITH INSULATION

PULL INSULATION UP TO DUCT ANDVAPOR SEAL

SPIN-IN FITTING WITH VOLUME DAMPERFLEXMASTER #

NOTE: 1. PROVIDE TWO SS CLAMPS FOR EACH CONNECTION ONE FOR INNER SLEEVE AND ONE FOR VAPOR BARRIER SEAL.

DUCT ELBOW DETAIL 03

DOUBLE THICKNESS TURNING VANES (RE: SPECIFICATIONS)

RECTANGULAR SQUARE ELBOW

(NON-TRANSITION)

AIR

FLO

W

W

W

1.25W MAX. EXPANSION0.75W MAX. CONTRACTION

DEPTH REMAINS CONSTANT

RECTANGULAR SQUARE ELBOW

(TRANSITION)

AIR

FLO

W

W

RECTANGULAR OR ROUND RADIUS ELBOW

(NON-TRANSITION)

AIR

FLO

W

W

R=1.5W

R

1.25W MAX. EXPANSION0.75W MAX. CONTRACTION

RECTANGULAR RADIUS ELBOW

(TRANSITION)

AIR

FLO

W

W

R=1.5W

R

W

EQ

EQ

DEPTH REMAINS CONSTANT

1. PROVIDE SINGLE THICKNESS TURNING VANE WHEN DUCTVELOCITY IS BELOW 2000 FPM.

2. PROVIDE AIRFOIL TYPE TURNING VANE WHEN DUCT VELOCITY ISABOVE 2000 FPM.

NOTES:

FLEX DUCT SUPPORT DETAIL 02

1. SUPPORT SYSTEM MUST NOT DAMAGE DUCT OR CAUSE OUT OF ROUND SHAPE

2. DUCT IS FLEXIBLE WITH EXTERNAL INSULATION AND VAPOR BARRIER JACKETING

3. MINIMUM CENTER LINE BEND RADIUS IS ONE DIAMETER (OR INSIDE RADIUS OF D/2)

4. DUCT SHOULD EXTEND STRAIGHT FOR SEVERAL INCHES FROM A CONNECTION BEFORE BENDING

5. MAXIMUM SAG OF 1/2" PER FOOT OF SUPPORT SPACING

NOTES

1" MIN.

WIRE HANGER

1" MIN.

1" BAND CLAMP

SEENOTE 1

SEENOTE 1

SPIN IN FITTING -REFER TO SPIN-INFITTING DETAIL

4' - 0" MAX

INSULATION NOTSHOWN

RECTANGULARDUCTWORK SHOWN

FLEX DUCT SAG -SEE NOTE 5

08TERMINAL UNIT W/ELECTRIC HEAT CONTROL SCHEMATIC

C

SEQUENCE OF OPERATION

1. GENERAL REQUIREMENTS

A. TERMINAL UNITS SHALL BE CONTROLLED, AND MONITORED VIA A TERMINAL UNIT CONTROLLER FOR EACH TERMINAL UNIT.

B. TERMINAL UNIT CONTROLLERS SHALL MONITOR THE STATUS OF THE ASSOCIATED AIR HANDLING UNIT TO DETERMINE ITS OPERATING MODE.

C. THE TERMINAL UNIT CONTROLLER SHALL MONITOR AND REPORT OVER THE NETWORK THE FOLLOWING ITEMS AS A MINIMUM: SPACE TEMPERATURE, SPACE TEMPERATURE SETPOINT, SETPOINT AS SET AT THE THERMOSTAT, CONTROL DAMPER STATUS, AND REHEAT COIL STATUS.

D. THE SPACE TEMPERATURE SETPOINT SHALL BE ADJUSTABLE OVER THE HVAC CONTOL NETWORK AND THE CONTROLLER SHALL BE CAPABLE OF OVERRIDING THE THERMOSTAT SETPOINT.

2. OFF MODE

A. WHEN THE ASSOCIATED AHU IS IN STOP MODE, THE VAV CONTROL DAMPER SHALL BE IN ITS FULLY OPEN POSITION.

3. OCCUPIED MODE OPERATIONS

A. THE SPACE TEMPERATURE SHALL BE CONTROLLED BY MODULATING THE DAMPER IN THE TERMINAL UNIT BETWEEN MAXIMUM AND MINIMUM SET POINTS. IF AT A

MINIMUM AIRFLOW AND THE SPACE IS BELOW SETPOINT, THE TERMINAL UNIT SHALL GO TO THE HEATING CFM AND THE ELECTRIC DUCT HEATER SHALL BE STAGED TO MAINTAIN SETPOINT.

B. THE SPACE TEMPERATURE SETPOINT SHALL BE 75° F FOR COOLING AND 70° F FOR HEATING. A SEPERATE ADJUSTABLE SETPOINT SHALL BE MAINTAINED FOR BOTH HEATING AND COOLING.

4. UNOCCUPIED MODE OPERATIONS

A. IN UNOCCUPIED MODE THE VAV TERMINAL UNIT CONTINUE TO OPERATE AS FOR OCCUPIED MODE OPERATIONS EXCEPT THAT SEPERATE UNOCCUPIED MODE TEMPERTURE SETPOINTS SHALL BE MAINTAINED.

B. THE UNOCCUPIED MODE TEMPERATURE SETPOINT FOR COOLING SHALL 76° F. (ADJUSTABLE) THE SPACE TEMPERATURE SETPOINT FOR HEATING SHALL BE 68° F. (ADJUSTABLE)

S.A.

FACTORY MOUNTED DDC CONTROLLER

T

PRIMARYAIR

VARIABLE VOLUME TERMINAL BOX

ELECTRIC HEATER

TO OTHER TERMINAL UNIT CONTROLLERSTO DDC NETWORK

SINGLE DUCT VAV - ELECTRIC HEAT 05

NOTES:

1. THIS DETAIL REFERS TO VAV AND CONSTANT VOLUME ELECTRIC REHEAT BOXES AND VAVBOXES WITHOUT REHEAT.

2. FLEX DUCT TO ALLOW ONE BEND WITH CENTERLINE RADIUS NOT LESS THAN 1 1/2 DUCTDIAMETERS.

3. TAP FITTING TO RECTANGULAR MEDIUM PRESSURE DUCT MAY ALSO BE RECTANGULAR 45°ENTRY, SIZED PER SMACNA RECOMMENDATIONS, AND THEN TRANSITIONING TO ROUND.

4. MEDIUM PRESSURE ROUND TRUNK DUCT TO HAVE CONICAL TEE FITTING, WITH OTHERREQUIREMENTS AS SHOWN.

5. BOXES 1,400 CFM OR LESS TO BE SUPPORTED WITH 1"x18 GA. GALVANIZED BAND IRON ONFOUR CORNERS. BOXES GREATER THAN 1,400 CFM SHALL HAVE TRAPEZE SUPPORT OF REINFORCING ANGLE WITH 3/8" GALVANIZED ALL THREAD ROD HANGERS.

6. COORDINATE REQUIREMENT FOR CEILING ACCESS PANELS WITH DIVISION 8.

TRANSITION FROM BOX CONNECTION SIZE TO DUCT SIZE INDICATED ON DRAWINGS OR BOX SCHEDULE

RUN MIN. 4'-0" STRAIGHT DUCT, I.C.FLANGE CONNECTION SIZE OF BOX PRIORTO ANY TRANSITION OR TAKE OFF

RECTANGULAR MEDIUMPRESSURE TRUNKDUCT

LOWPRESSUREDUCT

ROUNDTO ROUNDREDUCERROUND DUCT AND FLEX.

REFER TO BOX SCHEDULE FOR RUNOUT DUCT SIZE

BOXES WITH ELECTRIC REHEAT COILS TO HAVE 3'-6" MIN. WORKING CLEARANCE ON TERMINAL BOX SIDE IN ADDITION TO CLEAR ACCESS FOR MAINTENANCE & INSPECTION

CONICALTAP FITTING

4'-0" MAX.LENGTH FLEXDUCT.

DUCT HANGER DETAIL 04

TWIST 90° ANDCONNECT TOSTRUCTUREABOVE (TYP)

3"

18 GA. X 1-1/4"GALVANIZEDDUCT HANGER

(3) SHEET METALSCREWS PER DUCTHANGER (TYP)

TRANSFER DUCT WITH GRILLES 06

D

CAULK AND SEAL ALL AROUND DUCT AT WALL BOTH SIDES

THROUGH-WALL TRANSFER DUCT, ACOUSTICALLY LINED

SHEETMETALDUCTWORK

CEILING

UNDERSIDEOF STRUCTURE ABOVE

1" ACOUSTICAL LINER

WALL, FLOOR TOSTRUCTURE

D

D

DU

CT

DE

PT

HD

=

SMOKE DAMPER 07

SUPPLY OR RETURN AIR DUCT

RUSKIN MODEL SD-60 1 1/2 HOUR SMOKE DAMPER OR EQUAL

SMOKE BARRIER, REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION SPECIFICATIONS

SEAL WITH FIRE RATED NON-HARDENING SEALER AIR TIGHT (TYPICAL)

CEILING

DUCT INSULATION

ACCESS PANELS

IN DUCT

NO JOINTS

CLASS 1 SMOKE DAMPER PER U. L. 555S REQUIREMENTS

U. L. LISTED ELECTRONIC OPERATOR OUT OF AIR STREAM

MAX. 12"

1. LAYERS OF GYPBOARD SLEEVE MUST MATCH LAYERS OF WALLGYPBOARD.

2. INSTALL DAMPER AND SLEEVE IN ACCORDANCE WITHMANUFACTURER'S INSTRUCTIONS NOT TO VOID U.L. LISTING

NOTES:

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROJECT SUBMISSION:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12/1

3/2

019 8

:14:5

2 A

M

MECHANICALSCHEDULES,CONTROLS, ANDDETAILS

M0.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

ADDENDUM #01

2019 12 16

Author

AIR DEVICE SCHEDULE

Key name TYPE TYPE DESCRIPTION MANUFACTURER MODEL MODULE SIZE MATERIAL FINISH DESCRIPTION

A-24x24 CEILINGSUPPLY

A SUPPLY DIFFUSER TITUS OMNI-AA 24 x 24 ALUMINUM BAKEDENAMEL

SQUARE PANEL FACE LAY-IN HIGH CAPACITY CEILING DIFFUSER. 24x24 FACE UNLESSOTHERWISE SPECIFIED. NECK DIAMETER SPECIFIED IN SCHEDULE NOTES. PROVIDE AIRPATTERN CONTROLLER.

B-24x24 CEILINGRETURN/EXHAUST

B CEILING RETURN /EXHAUST GRILLE

TITUS PAR-AA 24 x 24 ALUMINUM BAKEDENAMEL

24x24 PERFORATED FACE GRILLE. PLENUM RETURN GRILLE WITH 22x22 NECK UNLESSNOTED OTHERWISE IN PLANS. DUCTED EXHAUST GRILLE WITH NECK DIAMTER SPECIFIEDIN SCHEDULE NOTES AND RUN-OUT DUCT SIZE AS SPECIFIED ON PLANS.

X - EXISTING X EXISTING AIR DEVICE TITUS EXISTING PER PLANS EXISTING EXISTING EXISTING AIR DEVICE.

VAV BOX SCHEDULE - ELECTRIC HEAT

UNITINLETSIZE

MAX. AIRFLOW

MIN. AIRFLOW

HEATINGCFM

HEATINGKW VOLTS/PH/HZ

VAV-1-1 10" 830 CFM 275 CFM 830 CFM 11 480/3/60

NOTES:

1. PROVIDE TOP AND BOTTOM ACCESS PANEL FOR SERVICE.2. PROVIDE SINGLE POINT ELECTRICAL CONNECTION WITH FAN DISCONNECT.3. ELECTRIC HEATER SHALL BE 4 STAGES.

1 ADDENDUM #01 12/16/2019

1

Page 11: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

RE

F.

ELEV. 2 ELEV. 1

8 9

G

H

I

J

K

WAITING ROOM

101

PHARMACY

104

CORRIDOR

103

EXISTING

ELECTRICAL

SWITCHGEAR

ROOM

112

ELEV. 2

109

EXISTING

CLOSET

108

EXISTING BREAK

ROOM

107

PHARMACY

105

ELEV. 2

109

8 9

G

H

I

JK

VALET OFFICE

102

UNISEX TOILET

106

B

125X

X

340A

150A

14"x12" SA

24"x12" SA

100B

X X

24"x10" EA

X

X

X

125X

340A

(E)VAV

12"x14" SA

VAV-1-1

8"ø

EA

T

X

M05

M08

M07

M10

M10

SD

SD

14"x10" RA

M09

M09

M10

M10

SD

SD

SD

REBALANCE DIFFUSER TO CFM SHOWN

REBALANCE DIFFUSER TO CFM SHOWN

14"x10" RA

14"x10" RA

1

1

1

M12

M12

M12

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12/1

3/2

019 8

:14:5

7 A

M

MECHANICALDUCTWORK PLAN -LEVEL 1

M2.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

PROJECT SUBMISSION:

2019 12 16

Author

1/4" = 1'-0"1

MECHANICAL ENTRY LEVEL

MECHANICAL GENERAL NOTES

1. DRAWINGS ARE PROVIDED TO SHOW INTENT OF THE SYSTEM LAYOUT AND AREDIAGRAMMATIC ONLY.

2. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND LOCATION OF EXISTINGEQUIPMENT, DUCTWORKS, DIFFUSERS, ETC. TO REMAIN BEFORE COMENCING ANY WORKS.

3. CONTRACTOR SHALL COORDINATE RENOVATION WORK WITH OWNER AND WITH OTHERCONTRACTORS.

4. CLEAN ALL CONSTRUCTION DEBRIS AFTER ALL EQUIPMENT, DUCTWORKS, DIFFUSERS, ETCHAVE BEEN INSTALLED. CONTRACTOR SHALL PROTECT OWNER PROPERTIES FROMDAMAGES AND DUSTS.

5. THE AIR SYSTEM, EACH AIR DISTRIBUTION DEVICES SHALL BE ADJUSTED TO WITHIN 10% OFDESIGN AIR FLOW.

6. PROVIDE SPACE FOR OPERATION AND MAINTENANCE AS RECOMMENDED BY THEMANUFACTURER.

7. DUCTWORK INSULATION REQUIREMENTS SHALL MEET OR EXCEED ALL IECC MINIMUM.

8. ALL 2'x2' SUPPLY AIR GRILLES ARE FOUR-WAY THROW PATTERN UNLESS OTHERWISE NOTED.

9. AT ALL SUPPLY AIR DUCTWORK, PROVIDE TURNING VANES OR FULL-RADIUS ELBOWS AT ALLTURNS. PROVIDE DUCT TAKE-OFFS WITH BALANCING DAMPERS.

10 SEAL AROUND DUCTWORK AIR TIGHT AT ALL WALL PENETRATION.

11. COORDINATE AIR DEVICE COLOR WITH ARCHITECT.

12. ALL HVAC EQUIPMENT AND CONTROLS SHALL BE LABELED FOR IDENTIFICATION.LABELING/IDENTIFICATION SHALL BE LEGIBLE AND MECHANICALLY SECURED TO THEEQUIPMENT WITH NON-CORODING FASTENERS.

13. CONTRACTOR SHALL PREPARE AND INSTALL ALL NEW MCHANICAL EQUIPMENT ANDDUCTWORK INSTALLATION BEFORE SWITCHING INTO NEW SYSTEM.

(KEYNOTES SHOWN FOR THIS SPECIFIC SHEET ONLY)

MECHANICAL KEYNOTES

M05 INSTALL NEW VAV. RE-BALANCE EXISTING AHU TO ACCOMMODATE NEW VAV BOX. REF:SCHEDULE.

M07 BALANCE EXHAUST RISER.

M08 TAKE PRE-READINGS AND REBALANCE-TERMINAL UNIT. AFTER SETTING AIRFLOW ATDIFFUSER IN CORRIDOR. RELOCATE THERMOSTAT IF NECESSARY

M09 RELOCATE EXISTING DIFFUSER TO NEW LOCATION, EXTEND DUCT AS NECESSARY. REF:M2.01.

M12 INSTALL SMOKE DAMPER INTO EXISTING DUCTWORK.

1 ADDENDUM #01 12/16/2019

1

Page 12: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

RE

F.

ELEV. 6ELEV. 2 ELEV. 1

1 2 3 4 5 6 7 8 9 10 11 1312

G

H

I

J

K

2-B

PHARMACY

105

PHARMACY

104

CO

RR

IDO

R

103

WAITING ROOM

101

EXISTINGELECTRICAL

SWITCHGEAR ROOM

112

EXISTING LOBBY

113

UNISEX TOILET

106

FA

NN

IN S

TR

EE

T

MA

IN S

TR

EE

T

UT HEALTH PROFESSIONAL BUILDING

UT HEALTH PARKING BUILDING

D1

EX

D1D1D1D1D1D1

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

D1 D1 D1 D1 D1

D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1

L03

L02 L02

L08

L08

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 3

:21

:21

PM

ELECTRICAL SITEPLAN

E1.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

PROJECT SUBMISSION:

2019 12 16

Author

3/32" = 1'-0"1ELECTRICAL SITE PLAN

(KEYNOTES SHOWN FOR THIS SPECIFIC SHEET ONLY)

ELECTRICAL KEYNOTES

L02 LIGHT FIXTURES ARE EXISTING TO REMAIN UNLESS NOTEDOTHERWISE. (TYPICAL)

L03 VERIFY THAT A PORTION OF THE CANOPY LIGHTS ARESERVED FROM AN EMERGENCY CIRCUIT. IF NONE ARESERVED FROM EMERGENCY CIRCUIT(S), PROVIDE NEWEMERGENCY CIRCUIT(S) AS REQUIRED TO SERVE CANOPYLIGHTS, AND SERVE INDICATED FIXTURES FROMEMERGENCY CIRCUIT(S). NEW LIGHT FIXTURES ARE TO BEREPLACED IN LOCATION CURRENTLY OCCUPIED BYEXISTING FIXTURES.

L08 REPAIR, PATCH AND PAINT CANOPY TO RESTORE TOORIGINAL CONDITIONS.

1 ADDENDUM #01 12/16/2019

1

16 DEC 2019

Page 13: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

RE

F.

ELEV. 6ELEV. 2 ELEV. 1

OS

OS

OS

OSOS

OS

6 7 8 9

G

H

I

J

K

AAA

A

A

A

AA

AA

AA

AA

D D D

D D

D

D

D

D

D

D

D

D

DD

D D

D D

D

D

D

D

D D D

B B

B

U

U

3

3

U

U

U

M

CC

X

X

X

X

D

D

D

EX-1 EX-1

L04

D

L05

L06

L06

WAITING ROOM

101

PHARMACY

104

CORRIDOR

103

PHARMACY

105

EXISTING

ELECTRICAL

SWITCHGEAR

ROOM

112

EXISTING LOBBY

113

ELEV. 2

109

EXISTING

CLOSET

108

EXISTING BREAK

ROOM

107

VALET OFFICE

102

Room

114

UNISEX TOILET

106

X

1

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

1:5

2:3

4 A

M

ELECTRICALLIGHTING PLAN -LEVEL 1

E2.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

PROJECT SUBMISSION

2019 12 16

Author

1/4" = 1'-0"1ELECTRICAL LIGHTING PLAN - LEVEL 1

(KEYNOTES SHOWN FOR THIS SPECIFIC SHEET ONLY)

ELECTRICAL KEYNOTES

L04 MATCH EXISTING EXTERIOR DOWNLIGHT AND CONNECTTO EMERGENCY CIRCUIT.

L05 CONNECT TO EXISTING EMERGENCY CIRCUIT SERVINGLIGHT FIXTURES IN THIS AREA

L06 CONNECT TO EXISTING NORMAL POWER CIRCUIT SERVINGLIGHT FIXTURES IN THIS AREA

1 ADDENDUM #01 12/16/2019

16 DEC 2019

Page 14: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

RE

F.

ELEV. 6ELEV. 2 ELEV. 1

J

6 7 8 9

G

H

I

J

K

+72"TV

REF

+42"CM

REFGF

+42"GF

+42"

+42"GF

+42"GF

1HA

VAV-1-1

1HA - 30,32,34

30/3/NF

E02

(TYP.)

1LC 1LB

E02

(TYP.)

1LB - 12

1LB - 8

1LB - 10

1LC - 33

1LC - 38

1LC - 40

1LC - 35

ELL1-10

1LC - 42

1LC - 39

1LC - 37

WAITING ROOM

101

PHARMACY

104

CORRIDOR

103

PHARMACY

105

EXISTING

ELECTRICAL

SWITCHGEAR

ROOM

112

EXISTING LOBBY

113

ELEV. 2

109

EXISTING

CLOSET

108

EXISTING BREAK

ROOM

107

VALET OFFICE

102

Room

114

UNISEX TOILET

106

+42"GFI

(TYP.)

E02

TV

E03

1

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

1:5

2:3

6 A

M

ELECTRICALPOWER PLAN -LEVEL 1

E3.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

PROJECT SUBMISSION:

2019 12 16

Author

1/4" = 1'-0"1ELECTRICAL POWER PLAN - LEVEL 1

(KEYNOTES SHOWN FOR THIS SPECIFIC SHEET ONLY)

ELECTRICAL KEYNOTES

E02 VOICE/DATA OUTLET. INSTALL OUTLET BOX . PROVIDE 1''CONDUIT WITH PULL STRING AND GROMMET TO LOCATIONABOVE ACCESSIBLE CELLING

E03 VERIFY EXISTING RECEPTACLE AND DATA OUTLET ATAPPROXIMATELY 72" AFF. OTHERWISE, PROVIDERECEPTACLE AND DATA OUTLET AT 72" AFF, CONNECTRECEPTACLE TO CIRCUIT CURRENTLY SERVINGTELEVISION.

1 ADDENDUM #01 12/16/2019

16 DEC 2019

Page 15: UTPB – Valet and Driveway Reno...utpb – valet and driveway reno page 2 mechanical 1. m0.01: mechanical schedules, controls, and details ... fab fb fc fd fdc fdn fe fec ff&e ffel

RE

F.

ELEV. 6ELEV. 2 ELEV. 1

S

S

S

S

S

S

S

S

S

6 7 8 9

G

H

I

J

K

75cd

30cd

WAITING ROOM

101

PHARMACY

104

CORRIDOR

103

PHARMACY

105

EXISTING

ELECTRICAL

SWITCHGEAR

ROOM

112

EXISTING LOBBY

113

ELEV. 2

109

EXISTING

CLOSET

108

EXISTING BREAK

ROOM

107

VALET OFFICE

102

Room

114

UNISEX TOILET

10615cd

30cd

1

1

1

1

30cd

1

1

30cd

1

75cd

11

1

30cd

1

1

F1

REVISION/ISSUE NO. YYYY MM DD

PROJECT NO.

PROJECT TITLE:

PROFESSIONAL SEAL:

SHEET TITLE:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET:

CLIENT:

PLAN KEY:

DATE:

DRAWN BY

CIVIL & STRUCTURAL ENGINEERING

MEP ENGINEERING

PLAN KEY:

12

/16/2

01

9 1

1:5

2:3

7 A

M

ELECTRICAL FIREALARM PLAN -LEVEL 1

E5.01

19-00032-00

UTPB - VALET &DRIVEWAYRENOVATION

PROJECT SUBMISSION:

2019 12 16

Author

1/4" = 1'-0"1ELECTRICAL FIRE ALARM PLAN - LEVEL 1

1 ADDENDUM #01 12/16/2019

16 DEC 2019