up-mp 31dc - master battery
TRANSCRIPT
01
Polígono industrial La DehesaC/ Dehesa Vieja,nº2 Nave 1628052 Madrid (Spain)Tel. (+34) 918 021 649Fax. (+34) 917 750 [email protected]
DEEP CYCLE BATTERIES
SPECIFICATIONS
Nominal Voltage
Rated Capacity
Plate Technology
Separator
Electrolyte
Standards
12V
110 Ah (at C20 and 25°C)
Antimony / Calcium
Polyethylene + glass mat
Sulphuric acid; analytical grade
IEC 60254; IEC 61427
Polypropylene
Double
Top / Automotive
Available
More than 400 cycles
More than 800 cycles
Case / Lid Material
Lid Type
Terminal Type
Carrying Handles
Cycles at 75% DoD
PVES Applications
PERFORMANCE CHARACTERISTICS
Battery Discharge Performance at 25°C
Temperature Correction Factor of Discharge C20 (20h) Capacity
Discharge Rate
End of discharge voltage
Discharge capacity
C5 (5h)
10,20 V
90 Ah
C20 (20h)
10,50 V
110 Ah
C100 (100h)
10,80 V
115 Ah
Capacity at 25 A
10,50 V
220 min / 92 Ah
Temperature
Correction factor
-10°C
0.83
0°C
0.87
10°C
0.92
15°C
0.94
20°C
0.97
30°C
1.03
40°C
1.09
SI Units
336 mm
173 mm
235 mm
28,40 kg
US Units
13,20 inch
6,80 inch
9,20 inch
62,60 lbs
Length
Width
Height
Typical Weight
PHYSICAL CHARACTERISTICS
12V 110 Ah (C20)
www.masterbattery.es
UP-MP SERIES
UP-MP 31DC
UP-MP 31DC
Polígono industrial La DehesaC/ Dehesa Vieja,nº2 Nave 1628052 Madrid (Spain)Tel. (+34) 918 021 649Fax. (+34) 917 750 [email protected]
www.masterbattery.es
02
Battery Charge Conditions
Charging Profiles: WaW0 and IUIa Charge Factor: 1.10 - 1.20
WaW0 – (double slope taper) characteristics for flooded batteries
Charging times with WaW0 - characteristics in hours
IUIa – characteristics for flooded batteries Charging times with IUIa - characteristics in hours
Main Charge Time Final Charging
Voltage
Current
20-30A/100Ah
8A/100Ah
4A/100Ah
2.65 Vpc
2.40 Vpc
2.00 Vpc
Main Charge Time Final Charging
Voltage
Current
14-20A/100Ah
5A/100Ah
2.65 Vpc
2.40 Vpc
2.00 Vpc
Charging Factor
Cha
rgin
g T
ime
(h)
20A/100Ah
30A/100Ah
20A/100Ah
30A/100Ah
20A/100Ah30A/100Ah
with pneumetic electrolyte mixing Standard charge
80% DoD
60% DoD
40% DoD
10
9
8
7
6
2
5
4
3
1.02 1.04 1.06 1.08 1.10 1.141.12 1.16 1.18 1.20 1.22
Charging Factor
Cha
rgin
g T
ime
(h)
14A/100Ah
20A/100Ah
14A/100Ah
20A/100Ah
14A/100Ah
20A/100Ah
with pneumetic electrolyte mixing Standard charge
80% DoD
60% DoD
40% DoD
10
9
8
7
6
2
5
4
3
1.02 1.04 1.06 1.08 1.10 1.141.12 1.16 1.18 1.20 1.22