University College Cork
Energy Review
2016/17
Student: Pat Mehigan.
Word count: 3ing Executive Summary
UCC Energy Review 2016/17
Page 2 of 18
EXECUTIVE SUMMARY 3
1 PAST AND PRESENT ENERGY USE 6
1.1 Electrical 6
1.2 Natural Gas 7
2 SIGNIFICANT ENERGY USERS ELECTRICAL 8
3 SIGNIFICANT ENERGY USERS NATURAL GAS 9
4 ENERGY BASELINE & ACTION PLAN 10
4.1 Electrical 10
4.2 Natural Gas 14
UCC Energy Review 2016/17
Page 3 of 18
EXECUTIVE SUMMARY
This document records the results of an energy review, undertaken in Q3 2017, of the
operations at University College Cork (UCC). The scope was to review the electrical and
natural gas users and to determine the significant energy users (SEU’s), identify the variables
and people that impact them, identify areas for maintaining and improving energy
performance. The results were obtained from metering information available on the site
metering package and the available billing data. From the review the site SEU’s were
determined based on:
The amount of energy they use.
And / or
The ability to reduce the energy consumption through the register of energy saving
opportunities.
The approach to energy management for 2016/17 focussed on housekeeping measures and
engaging with the SEU’s through the saver saves scheme, where applicable, to understand
how the buildings are used by the departments.
The objective for 2016/17 was to maintain the existing consumption levels for UCC, despite
the planned increases in occupied space, namely the Western Gateway and Food Science
Building. Through ongoing investment, monitoring and engagement with the SEU’s, UCC
achieved a 0.6% decrease in electrical energy and a 8.5% decrease in natural gas
consumption.
16 electrical energy saving projects were completed in 2016/17 and resulted in savings of
440,000 kWh/year. (See appendix III for details).
8 out of 13 electrical SEU’s reported a drop in annual consumption levels totalling 0.6
GWh/year while the remaining 5 SEU’s saw a total increase of 0.3 GWh/year, with the WGB
alone accounting for an increase of 0.16 GWh/year.
Natural gas reduction is mainly attributable to the reduced operating hours of the CHP’s
(discussed further in appendix II) as well as slight savings in other SEU’s.
10 natural gas energy saving projects were completed in 2016/17 and resulted in savings of
55,000 kWh/year. (See appendix III for details).
UCC Energy Review 2016/17
Page 4 of 18
CAUL are excluded from the scope of this review as well as Tyndall National Institute and the
Mardyke Arena as both areas operate their own independent ISO50001 process.
The objective for 2017/18 is to expand the saver saves scheme, using the Boole Library as the
template and to reduce the existing consumption levels for UCC, despite the planned
increases in occupied space, namely the Western Gateway and Food Science Building.
Based on this energy review and the action plan, the predicted Oct 2017 to Sept 2018
consumption levels are:
19,520,000 kWh of electrical energy and 17,650,000 kWh of natural gas.
The 2017/18 SEU’s and the appropriate EnPI’s for electrical and gas consumption are detailed
in the tables below.
Table of Electrical SEU’s and their EnPIs for 2017/18 at UCC
SEU % of Electrical Energy across UCC
EnPI ( in term) weekly kWhr EnPI (out of term) weekly kWhr
WGB 20.2 82,147 82,147
Food Science 10.6 39,842 39,842
Kane 10.5 41,224 36,850
Boole 8.6 34,604 22,817
Bioscience 8.4 31,376 31,376
Brookfield 6.7 27,140 22,690
Pharmacy 5.1 18,792 15,667
ORB 3.9 15,419 12,476
Student Centre 2.5 8,965 5,822
BSU 2.3 8,798 8,798
ERI 2 8,742 6,710
Aula Maxima 1.7 6,895 5,635
Glucksman 1.6 6,450 5,042
The above SEU’s account for 84.1% of the electricity consumed across UCC.
UCC Energy Review 2016/17
Page 5 of 18
Table of Thermal SEU’s and their EnPIs for 2017/18 at UCC
SEU Why EnPI 2017/18
kWh/week
CHP Significant natural gas user, producing electricity and using the waste heat for building heating as well as steam for heating and process requirements – accounts for 53% of NG use
Note1
Main Campus Boilers
Significant natural gas user, producing steam for heating and process requirements – accounts for 13.5% of NG use
Base load of
20,388 kWh with 2965 kW per HDD (13)
Brookfield Significant natural gas user for heating– accounts for 4% of NG use
Base load of
3,082 kWh with 1010 kW per HDD (13)
WGB Significant natural gas user for heating– accounts for 4% of NG use
Base load of
1092 kWh with 467 kW per HDD (17)
Food Science Significant natural gas user for heating– accounts for 3.2 % of NG use
Base load of
4,4407 kWh with 647 kW per HDD (12)
Pharmacy Significant natural gas user for heating– accounts for 2.9 % of NG use
Base load of
4,148kWh with 616 kW per HD (13)
BSU Significant natural gas user for heating– accounts for 2.9 % of NG use
Base load of
5,123 kWh with 360 kW per HDD (15)
ORB Significant natural gas user for heating– accounts for 2.2% of NG use
Base load of
682 kWh with 617 kW per HDD (13)
Bioscience Significant natural gas user for heating– accounts for 2.1 % of NG use
Base load of
4,709 kWh with 361 kW per HDD (13)
The above SEU’s account for 88.8 % of the natural gas consumed across UCC.
Note 1: No valid EnPI available.
UCC Energy Review 2016/17
Page 6 of 18
1 PAST AND PRESENT ENERGY USE
1.1 Electrical
The table below shows the annual electrical energy use (GWh/a) since 2008/9
Area 08/9 09/10 10/11 11/12 12/13 13/14 14/15 15/16 16/17
UCC- all 21.3 20.8 20.7 20.63 20.10 19.79 19.91 19.78 19.65
WGB 1.2 1.41 2.13 2.97 2.74 3.02 3.20 3.81 3.97
FSB 2.11 2.19 2.06 2.09 2.15 2.26 2.27 2.36 2.1
Kane 2.48 2.54 2.40 2.32 2.15 2.03 2.09 2.01 2.0
Boole 2.60 2.63 2.40 2.13 1.99 1.99 1.91 1.82 1.69
Bio 1.81 1.90 1.76 1.74 1.72 1.63 1.63 1.60 1.64
BHSC 1.3 1.27 1.25 1.17 1.19 1.21 1.29 1.28 1.32
Pharm NA NA 1.11 1.18 1.15 1.17 1.01 0.98 1.01
ORB 0.99 0.96 0.72 0.85 0.85 0.85 0.88 0.82 0.77
Student 0.64 0.63 0.56 0.59 0.56 0.62 0.56 0.54 0.48
ERI 0.50 0.48 0.46 0.44 0.43 0.42 0.42 0.41 0.40
BSU 0.40 0.43 0.43 0.43 0.44 0.53 0.44 0.40 0.44
Aula 0.35 0.36 0.31 0.36 0.36 0.34 0.34 0.35 0.33
Glucksman 0.45 0.25 0.42 0.13 0.42 0.42 0.44 0.40 0.30
The electrical energy consumption for 2016/17 was compared with degree day data (cooling
and heating) and no meaningful correlation was found between the two.
UCC Energy Review 2016/17
Page 7 of 18
1.2 Natural Gas
The table below shows the annual natural gas use (GWh/a), where available, since 2008/9.
Year 08/9 09/10 10/11 11/12 12/13 13/14 14/15 15/16 16/17
UCC- all 23.00 23.2 23.44 19.20 21.90 19.32 28.59
note 1
37.26
note 1
34.1
CHP NA NA NA NA NA NA 11.2
note 1
21.59
note 1
17.79
Campus
Boilers
5.3 5.93 6.96 4.48 4.76 4.07 4.58 3.85 4.45
BHSC 1.65 1.53 1.48 1.53 1.48 1.31 1.40 1.43 1.35
East skid 2.35 2.20 1.95 1.68 2.06 1.88 1.94 1.59 1.66
Pharm NA NA NA NA NA 1.16 1.02 0.92 0.98
FSB NA NA NA NA NA 0.90 0.96 0.91 1.01
Bio NA NA NA NA NA 0.94 0.87 0.80 0.69
WGB 0.74 0.60 0.68 0.52 0.87 0.68 0.89 1.08 1.35
BSU 0.83 1.04 0.96 0.87 1.09 0.84 0.99 0.91 0.96
Note 1: Increase in the CHP gas consumption associated with the change of ownership from third party vendor to UCC in April 2015.
UCC Energy Review 2016/17
Page 8 of 18
2 SIGNIFICANT ENERGY USERS ELECTRICAL
From the 2016/17 energy review, the SEU’s were selected based on the amount of energy
they use or the ability to reduce their energy consumption.
SEU Description % of Site
energy use
WGB WGB building, located on the Western Road houses
lecture rooms, offices, conferencing facilities, Labs.
20.2
Food Science
Building
A research intensive building, FSB houses labs, dairy
processing, brewery, meat processing areas as well as
office spaces.
10.6
Kane Building The Kane building is home to research labs, IT data
centre, Lecture theatres and offices.
10.5
Boole Library Main Campus library. 8.6
Bioscience The building accommodates scientific labs, seminar
rooms and office rooms.
8.4
Brookfield Teaching rooms, medical simulation labs, offices and lecture halls.
6.7
Pharmacy Houses Labs, lecture halls, cleanroom and café. 5.1
ORB Home to offices, classrooms and café. 3.9
Student Centre UCC student centre, i.e. shops, computer rooms, halls, bar and café.
2.5
BSU Home to research labs 2.3
ERI Environmental Research Building, offices, heat pump, research labs.
2.0
Aula Located in the Quad, home to offices , conference rooms.
1.7
Glucksman UCC art gallery. 1.6
Others Other sites (91) account for the remaining 15.9% of energy use.
15.9
Appendix I gives a summary of the electrical SEU’s, detailing their 2016/17 performance,
2017/18 targets, operational controls etc.
UCC Energy Review 2016/17
Page 9 of 18
3 SIGNIFICANT ENERGY USERS NATURAL GAS
From the 2016/17 energy review, the SEU’s were selected based on the amount of natural
gas they consume and/or the ability to reduce their consumption.
Area Description % of Site gas
use
CHP 2 off CHP units used to generate steam and LPHW. 53
Main Campus Steam boilers
2 off Natural Gas fired shell & tube boilers that generate steam at 7 bar gauge.
13.5
Brookfield Gas feed for boilers / café. 4
WGB Gas feed for boilers / café. 4
Food Science Gas feed for boilers 3.2
Cavanagh building
Gas feed for boilers / café. 2.9
BSU Gas feed for boilers BSU research building 2.9
ORB Gas feed for boilers / café. 2.2
Bioscience Gas feed for boilers / café. 2.1
Others Other sites (34) account for the remaining 12.2 % of energy use.
12.2
Appendix II gives a summary of the natural gas SEU’s, detailing the 2016/17 performance, 2017/18 targets, operational controls etc.
UCC Energy Review 2016/17
Page 10 of 18
4 ENERGY BASELINE & ACTION PLAN
4.1 Electrical
The baseline for electrical usage is from October 2016 to September 2017. Based on this energy review the estimated reduction associated with
the SEU’s for 2017/18 will be 102,500 kWh
SEU 2017/18
Annual Target
(GW/h/year)
Predicted
annual savings
(kW/h/year)
Action plan 2017/18
WGB 4.177 +200,000 Assess suitability for sustainability campaign, assess suitability for LED replacement, building
management approach to be documented as template for Capital Projects. Extend the no of
meters on the resourcekraft metering package. Continue to closely manage the BSU area.
FSB 2.02 -70,000 The savings from the ESO completed in the summer of 2017 will carry forward to 2017/18,
reducing the expected annual consumption by 20,000 kWh. With the upcoming planned
collaboration with the school for the saver saves scheme we have set a target of saving a
further 50,000 kWh over the year. The following actions are planned for the 2017/18:
Communicate weekly to user on energy usage. Undertake trial of the saver saves scheme.
Connect up PV array to metering load. Undertake energy audit of Block A and C.
UCC Energy Review 2016/17
Page 11 of 18
SEU 2017/18
Annual Target
(GW/h/year)
Predicted
annual savings
(GW/h/year)
Action plan 2017/18
Kane 2.1 0 The following actions are planned for the 2017/18: Continue to monitor weekly energy
consumption. Audit the building services (24% of total energy consumption) to ensure correct
operation.
Boole 1.6 -90,000 The savings from the ESO completed in the summer of 2017 will carry forward to 2017/18,
reducing the expected annual consumption by 90,000 kWh The following actions are planned
for the 2017/18: Communicate weekly to College on energy usage. Investigate suitability for
chilled water system replacement. Lighting management protocols to reduce PGL lighting for
summer term. Review occupancy patterns verses opening times.
Bioscience 1.630 -12,000 The following actions are planned for the 2017/18: Sign up College to the saver saves scheme.
Investigate suitability for lighting replacement and / or upgrade and start roll out. Investigate
suitability for replacement and rationalisation of LPHW systems. Cost up metering plan for the
building and agree implementation plan.
BHSC 1.32 0 The following actions are planned for 2017/18: Assess suitability for sustainability campaign.
Assess suitability for LED replacement and commence. Extend the no of meters on the
resourcekraft metering package.
UCC Energy Review 2016/17
Page 12 of 18
SEU 2017/18
Annual Target
(GW/h/year)
Predicted
annual savings
(GW/h/year)
Action plan 2017/18
Pharmacy 0.97 -38,000 Installation of new air compressor. Upgrade lighting controls in the atrium. Fumehood sash
speed control project. Roll out of building awareness campaign. Upgrade the BMS platform.
ORB 0.74 -29,000 Continue to monitor weekly energy consumption. Investigate causes of nightload, which
achieve an annual reduction of 2%. Extend the metering plan in the building.
Student
Centre
0.4 -81,000 Continue to monitor weekly energy consumption. Investigate the investment required to
upgrade the existing Siemens and Trend BMS. Verify lighting savings. Cost proposal for
extending the metering plan in the building. Investigate suitability of divorcing the radio room
from the Hall AHU. Detailed audit on building services equipment to identify SEU’s within the
building and the night load consumers,
BSU 0.4 -22,000 Conduct detailed energy audit and building awareness campaign to achieve a 5% reduction in
annual energy consumption.
ERI 0.39 -20,500 Continue to monitor weekly energy consumption. Roll out building awareness campaign.
Extend the metering plan in the building. Review feasibility of dry cooling loop for cooling
circuit. Assess suitability of ESCO model for PV array/ battery storage. Conduct energy review
and achieve a 5% reduction in annual savings.
UCC Energy Review 2016/17
Page 13 of 18
SEU 2017/18
Annual Target
(GW/h/year)
Predicted
annual savings
(GW/h/year)
Action plan 2017/18
Aula
Maxima
0.33 0 Continue to monitor weekly energy consumption. Replace the failed BMS system.
Investigate extending the no of meters on the resourcekraft metering package.
Glucksman 0.35 +60,000 Continue to monitor weekly energy consumption. Verify lighting savings. Extend the metering
plan in the building.
Total 16.427 -102,500
UCC Energy Review 2016/17
Page 14 of 18
4.2 Natural Gas
The baseline for gas usage is from October 2016 to September 2017. Based on this energy review and action plan the total estimated reduction
associated with the SEUs for 2017/18 will be 16.43 GWh for the year.
SEU 2017/18
Target
(GW/h/year)
Predicted annual
savings
(GW/h/year)
Action plan 2017/18
CHP 0 -17.79 Shutdown of the CHP units
Campus
Boilers
5.36 +1.5 Development of plan for FSB steam supply Progress tendering of the ESCO for the district
heating project. Review operating sequence in the absence of CHP, i.e. which boiler will
lead.
BHSC 1.35 0 Assess ESO for installation of dedicated DHW boiler.
WGB 1.35 0 Assess ESO for installation of dedicated DHW boiler.
FSB 1 -0.055 Replace failed BMS controller. Rationalisation of LPHW systems
Pharmacy 0.98 -0.02 Roll out of fumehood sash speed control. Assess need for dedicated DHW boiler.
BSU 0.96 0 Continue to monitor
ORB 0.70 -0.02 Repair BMs controller
Bioscience 0.69 -0.07 10% saving from rationalisation of LPHW systems
UCC Energy Review 2016/17
Page 15 of 18
Total -16.455
UCC Energy Review 2016/17
Page 16 of 18
APPENDIX I
SUMMARY OF ELECTRICAL SEU’S, TARGETS, CONTROL & ACTION PLANS
UCC Energy Review 2016/17
Page 17 of 18
APPENDIX II
SUMMARY OF NATURAL GAS SEU’S, TARGETS, CONTROL & ACTION PLANS
UCC Energy Review 2016/17
Page 18 of 18
APPENDIX III
SUMMARY OF ENERGY SAVING OPPORTUNITIES COMPLETED 2016/17