universal grille - halton · awe/awu - universal grille halton awe/awu ... measurement and...

8
1 20/AWE,AWU/3500/0606/EN AWE/AWU - Universal Grille Halton AWE/AWU Universal Grille • Horizontal air supply, suitable also for exhaust • Fixed front vanes, stable throw pattern with vertical 15° deflection: AWE, no deflection: AWU • Adjustable rear vanes for horizontal deflection of the air jet • Aluminium construction with elegant outlook • Detachable grille enables cleaning of the grille and ductwork • Continuous grilles available with modular construction Accessories • Airflow adjustment damper • Plenum options with measurement and adjustment functions • Installation frame MATERIAL AND FINISHING PART MATERIAL FINISHING NOTE Frame Aluminium Anodised, Polyester-painted, White RAL 9010 50% gloss, Mill finished Special colours available Epoxy-painting (100 %) available Vanes Aluminium Anodised, Polyester-painted, White RAL 9010 50% gloss, Mill finished Special colours available Epoxy-painting (100 %) available Installation frame Galvanised steel Plenum box / spigot Galvanised steel ACCESSORIES ACCESSORY CODE DESCRIPTION Balancing plenum PRI For balancing & equalising the airflow and attenuating the duct noise Plenum BDR Plenum for duct connection (with or without attenuation material) Airflow measurement and adjustment unit MSM For supply installation Sound attenuation IN Mineral wool for the BDR plenum box. Polyester fiber for the PRI plenum box. Flow adjustment damper OD Aluminium opposite blade damper~for airflow adjustment Installation frame IF For installation without plenum Concealed screw fastening CC For installation with BDR plenum or IF frame

Upload: vuonghuong

Post on 04-May-2018

222 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Universal Grille - Halton · AWE/AWU - Universal Grille Halton AWE/AWU ... measurement and adjustment module. ... 66 238 40 46 50 49 43 37 29 23 25 40 35 34

1

20

/AW

E,A

WU

/35

00

/06

06

/EN

AWE/AWU - Universal Grille

Halton AWE/AWU Universal Grille

• Horizontal air supply, suitable also for exhaust

• Fixed front vanes, stable throw pattern with

vertical 15° deflection: AWE, no deflection: AWU

• Adjustable rear vanes for horizontal deflection of

the air jet

• Aluminium construction with elegant outlook

• Detachable grille enables cleaning of the grille and

ductwork

• Continuous grilles available with modular

construction

Accessories

• Airflow adjustment damper

• Plenum options with measurement and adjustment

functions

• Installation frameMATERIAL AND FINISHING

PART MATERIAL FINISHINGNOTE

Frame Aluminium Anodised, Polyester-painted, White RAL 9010 50% gloss, Mill finished

Special colours available Epoxy-painting (100 %) available

Vanes Aluminium Anodised, Polyester-painted, White RAL 9010 50% gloss, Mill finished

Special colours availableEpoxy-painting (100 %) available

Installation frame Galvanised steel

Plenum box / spigot Galvanised steel

ACCESSORIES

ACCESSORY CODE DESCRIPTION

Balancing plenum PRI For balancing & equalising the airflow and attenuating the duct noise

Plenum BDR Plenum for duct connection (with or without attenuation material)

Airflow measurement and adjustment unit MSM For supply installation

Sound attenuation IN Mineral wool for the BDR plenum box. Polyester fiber for the PRI plenum box.

Flow adjustment damper OD Aluminium opposite blade damper~for airflow adjustment

Installation frame IF For installation without plenum

Concealed screw fastening CC For installation with BDR plenum or IF frame

Page 2: Universal Grille - Halton · AWE/AWU - Universal Grille Halton AWE/AWU ... measurement and adjustment module. ... 66 238 40 46 50 49 43 37 29 23 25 40 35 34

2

L2

L1

H2

H1

18

18

5

48

AWE

AWU

NS L1 L2 H1 H2

200x50 212 176 62 26

200x100 212 176 112 76

300x100 312 276 112 76

400x100 412 376 112 76

500x100 512 476 112 76

600x100 612 576 112 76

800x100 812 776 112 76

1000x100 1012 976 112 76

600x150 612 576 162 126

800x150 812 776 162 126

1000x150 1012 976 162 126

1200x150 1212 1176 162 126

1500x150 1512 1476 162 126

600x200 612 576 212 176

800x200 812 776 212 176

1000x200 1012 976 212 176

1200x200 1212 1176 212 176

1500x200 1512 1476 212 176

AWE/AWU - Universal Grille

20

/AW

E,A

WU

/35

00

/06

06

/EN

DIMENSIONS

With flow control damper OD total depth = 48 mm +

45 mm.

Special dimensions

In addition to standard sizes, other sizes can be

specially ordered. The maximum size is 1500x500 mm

(LxH).

It is possible to have a continuous grille of modular

design when the installation length is greater than

1500 mm. The maximum total length is 20 m.

Function

Supply air is supplied with vertical 15° angle deflection

and with horizontal deflection (rear vanes) through the

vanes into the space, mixing with room air in front of

the grille.

The flow pattern is adjusted by changing the angle of

the adjustable rear vanes.

Wall installation for horizontal supply or ceiling

installation for vertical supply.

In wall installations, the recommended distance from

the ceiling is 200 mm, when the supply air is directed

to the ceiling.(AWE)

The grille can also be used as an exhaust unit.(AWU)

Page 3: Universal Grille - Halton · AWE/AWU - Universal Grille Halton AWE/AWU ... measurement and adjustment module. ... 66 238 40 46 50 49 43 37 29 23 25 40 35 34

3

20

/AW

E,A

WU

/35

00

/06

06

/EN

AWE/AWU - Universal Grille

Installation

The grille is connected to the circular duct using

either a PRI balancing plenum or a BDR plenum or

alternatively directly to the rectangular duct using the

IF installation frame.

Clips fastening (standard)

Installation frame (IF) PRI balancing plenum BDR plenum box

The grilles are supplied with clips fastening as

standard.

Clips fastening is used with PRI, BDR and IF.

Concealed screw fastening (option)

Concealed screw fastening is possible when the grille

is installed with an installation frame (IF) or a BDR

plenum, though not with a PRI balancing plenum.

Holes for screws are provided in the BDR.

For ceiling installation concealed screw fastening is

recommended.

Visible screw fastening is not possible due to the

reduced width of the frame (18 mm).

Size of the installation hole is LxH when installation

frame is used, and (L-5)x(H-5) without installation

frame.

Page 4: Universal Grille - Halton · AWE/AWU - Universal Grille Halton AWE/AWU ... measurement and adjustment module. ... 66 238 40 46 50 49 43 37 29 23 25 40 35 34

4

q = k pv m ∆*

BDR >6xD min 3xD

100 6 7

125 10 12

160 19 22

200 28 32

250 49 51

315 77 83

ØD PRI/S >8xD min 3xD

125 200x100 10.1 12.6

160 300x100 17.0 21.7

160 400x100 17.0 21.7

200 500x100 27.7 33.9

200 300x150 27.8 33.9

250 400x150 47.2 55.5

250 500x150 46.2 50.1

250 600x150 45.8 51.1

315 800x150 80.8 83.3

250 400x200 51.2 55.5

315 500x200 92.9 83.3

315 600x200 82.7 93.1

315 800x200 79.3 83.3

AWE/AWU - Universal Grille

20

/AW

E,A

WU

/35

00

/06

06

/EN

Adjustment

In order to enable airflow adjustment and

measurement of airflow rate it is recommended that

you connect the diffuser to the BDR plenum or PRI

balancing plenum equipped with the MSM module.

The supply flow rate is determined by using the MSM

measurement and adjustment module.

Detach the grille and pass the tubes and control

spindle through the grille.

Measure the differential pressure using a manometer.

The flow rate is calculated using the formula below.

Adjust the airflow rate by rotating the control spindle

until the desired setting is achieved.

Lock the damper position with a screw.

Replace the tubes and spindle in the plenum and

replace the grille.

K factor for installations with different safety distances

(D= duct diameter)

Airflow adjustment damper OD

The airflow rate is adjusted by turning the damper

blades behind the grille using a screwdriver. The

measurement is carried out when grille is installed.

Page 5: Universal Grille - Halton · AWE/AWU - Universal Grille Halton AWE/AWU ... measurement and adjustment module. ... 66 238 40 46 50 49 43 37 29 23 25 40 35 34

5

500x100, 600x100, 800x100, 600x200

1000x100, 800x150, 1000x150, 800x200, 1000x200 1200x150, 1500x150, 1200x2000, 1500x200

200x50, 200x100, 300x100, 400x100 20

/AW

E,A

WU

/35

00

/06

06

/EN

AWE/AWU - Universal Grille

Pressure drop, throw pattern and sound data

AWE or AWU, wall installation at a distance of 200

mm from the ceiling (with Coanda effect)

Note :

• When there is no coanda effect (installation greater than 200 mm from ceiling) the throw pattern must be multiplied by 0.7.• For exhaust use, adjust supply data by adding + 5 dB(A) and DPs= DPs x 1.2.

Page 6: Universal Grille - Halton · AWE/AWU - Universal Grille Halton AWE/AWU ... measurement and adjustment module. ... 66 238 40 46 50 49 43 37 29 23 25 40 35 34

6

AWE/AWU - Universal Grille

20

/AW

E,A

WU

/35

00

/06

06

/EN

Sound power level with OD damper

Use of an OD opposite blade damper, will result in

increased pressure loss. The resulting increase in

sound level is computed from the selection chart value

and the formula below:

LpA = DLp + LpA

Kp= Adjusted pressure dropPressure drop in selection chart

Example :

ALE-1000x150 + OD/ALE

qv = 300 l/s

LpA = 31 dB(A) without damper OD/ALE

DPs= 50 Pa (desired pressure drop)

Kp = 50/11 = 4.5

LpA = 31 + 14 = 45 dB(A)

Throw length correction factor

When the throw length is adjusted with the rear

vanes, the actual throw length is obtained by

multiplying the value obtained from the selection chart

by the correction coefficient K1.

L0.2 (a) = K1 x L0.2

The correction coefficient K1 is the average for the

various grille sizes.

Pressure drop correction factor

When the throw length is adjusted with the rear

vanes, the actual pressure drop is obtained by

multiplying the value obtained from the selection chart

by the correction coefficient K2.

DPs (a) = K2 x DPs

The sound level increases when pressure drop is

increased. The correction coefficient K2 is the average

for the various grille sizes.

Angle between vanes

Angle between vanes

Page 7: Universal Grille - Halton · AWE/AWU - Universal Grille Halton AWE/AWU ... measurement and adjustment module. ... 66 238 40 46 50 49 43 37 29 23 25 40 35 34

7

20

/AW

E,A

WU

/35

00

/06

06

/EN

AWE/AWU - Universal Grille

SOUND LEVEL DATA, SUPPLY

AWE-AWU qv DPst DPtot F (Hz) LpA NR NC

(l/s) (m3/h) (Pa) (Pa) 125 250 500 1000 2000 4000 8000 [dB(A)]

200x50 17 61 16 18 34 33 27 21 13 7 9 25 19 1721 76 25 28 39 38 32 26 18 12 14 30 24 2326 94 38 42 44 43 37 31 23 17 19 35 29 2833 119 58 65 49 48 42 36 28 22 24 40 35 33

200x100 35 126 11 13 34 33 27 21 13 7 9 25 19 1744 158 17 20 39 38 32 26 18 12 14 30 24 2354 194 26 30 44 43 37 31 23 17 19 35 30 2866 238 40 46 50 49 43 37 29 23 25 40 35 34

300x100 51 184 9 11 34 33 27 23 15 7 9 25 19 1764 230 15 17 39 38 32 27 19 12 14 30 24 2378 281 22 26 44 43 37 32 24 17 19 35 30 2897 349 34 40 50 49 43 37 29 23 25 40 35 34

400x100 64 230 8 9 35 34 28 22 14 8 10 25 19 1780 288 12 15 40 39 33 27 19 13 15 30 24 2399 356 19 23 45 44 38 32 24 18 20 35 30 28124 446 30 36 50 49 43 37 29 23 25 40 35 34

500x100 78 281 7 9 35 34 28 22 14 8 10 25 19 1797 349 11 13 40 39 33 27 19 13 15 30 24 23121 436 17 21 45 44 38 32 24 18 20 35 30 28151 544 27 33 50 49 43 37 29 23 25 40 35 34

600x100 92 331 7 8 35 34 26 22 14 8 8 25 19 16114 410 11 13 40 39 32 27 19 13 14 30 25 22141 508 16 20 45 44 37 32 24 18 19 35 30 28176 634 25 31 50 49 42 37 29 23 24 40 35 33

800x100 117 421 6 7 35 34 28 21 13 8 10 25 19 18145 522 9 11 40 39 33 26 18 13 15 30 24 23181 652 15 18 45 44 38 32 24 18 20 35 30 28224 806 23 27 50 49 43 37 29 23 25 40 35 34

1000x100 145 522 6 7 34 33 27 21 13 7 9 25 19 17178 641 9 11 39 38 32 26 18 12 14 30 24 22220 792 14 17 44 43 37 31 23 17 19 35 29 28272 979 22 26 49 48 42 36 28 22 24 40 35 33

800x150 175 630 6 7 34 33 27 21 13 7 9 25 19 17216 778 8 10 39 38 32 26 18 12 14 30 24 23267 961 13 16 44 43 37 31 23 17 19 35 30 28328 1181 20 24 49 48 42 36 28 22 24 40 35 33

1000x150 210 756 5 6 34 33 27 21 13 7 9 25 19 17259 932 8 10 39 38 32 26 18 12 14 30 24 22321 1156 12 15 44 43 37 31 23 17 19 35 29 28397 1429 18 23 50 48 42 37 29 23 24 40 35 33

1200x150 243 875 5 6 34 33 27 21 13 7 9 25 19 17298 1073 7 9 39 38 32 26 18 12 14 30 24 22369 1328 11 13 44 43 37 31 23 17 19 35 29 28459 1652 17 21 49 48 42 36 28 22 24 40 35 33

1500x150 290 1044 4 5 34 33 27 21 13 7 9 25 19 17361 1300 7 8 39 38 32 26 18 12 14 30 24 23446 1606 10 13 44 43 37 31 23 17 19 35 29 28551 1984 15 19 49 48 42 37 29 22 24 40 35 33

600x200 290 1044 4 5 34 33 27 21 13 7 9 25 19 17361 1300 7 8 39 38 32 26 18 12 14 30 24 23446 1606 10 13 44 43 37 31 23 17 19 35 29 28551 1984 15 19 49 48 42 37 29 22 24 40 35 33

800x200 178 641 6 7 34 33 27 21 13 7 9 25 19 17220 792 9 11 39 38 32 26 18 12 14 30 24 23271 976 13 16 44 43 37 31 23 17 19 35 29 28334 1202 20 25 49 48 42 37 28 22 24 40 35 33

1000x200 225 810 5 6 35 33 27 22 14 7 9 25 19 17280 1008 8 10 40 38 32 27 19 12 14 30 24 22343 1235 12 14 45 43 37 32 24 17 19 35 29 27426 1534 18 22 50 48 42 37 29 22 24 40 34 33

1200x200 272 979 5 6 35 33 27 22 14 7 9 25 19 17336 1210 7 9 40 38 32 27 19 12 14 30 24 22414 1490 11 13 45 43 37 32 24 17 19 35 29 27512 1843 16 20 50 48 42 37 29 22 24 40 34 33

1500x200 385 1386 4 5 34 33 27 21 13 7 9 25 19 17475 1710 6 8 39 38 32 26 18 12 14 30 24 23583 2099 9 11 44 43 37 31 23 17 19 35 29 28721 2596 14 17 49 48 42 36 28 22 24 40 35 33

LpA values presented with room attenuation 4 dB (red 10m2 - sab). When using room attenuation 8 dB (red 25m2 - sab): LpA - 4dB.NR/NC noise criteria

Page 8: Universal Grille - Halton · AWE/AWU - Universal Grille Halton AWE/AWU ... measurement and adjustment module. ... 66 238 40 46 50 49 43 37 29 23 25 40 35 34

8

AWE/AWU - Universal Grille

20

/AW

E,A

WU

/35

00

/06

06

/EN

Servicing

Remove the grille by gently drawing it out by the

frame. Use a screwdriver if necessary.

Clean the parts by wiping then with a damp cloth.

Push the grille back into place so that the clips lock (or

fix by tightening the concealed screws).

Option: with balancing plenum PRI or BDR + MSM

Remove the measurement and adjustment module by

gently pulling the shaft (NB. not the control spindle or

measurement tubes!).

Wipe the parts with a damp cloth, instead of

immersing in water.

Reassemble the measurement and adjustment

module by pushing the shaft until the module meets

the stopper.

Push the grille back into place so that the clips lock.

Suggested Specifications

The grille shall have horizontal fixed vanes with a 15°

angle deflection:AWE, no deflection: AWU and vertical

adjustable rear vanes, and an 18 mm wide flat frame,

anodised or epoxy-painted with a white (RAL 9010)

colour.

Flow pattern shall be adjustable by rear vanes.

Option 1

The grille shall be connected to the ductwork using

a plenum with mineral wool as sound insulation

material.

Option 2

The grille shall be connected to the ductwork using

a balancing plenum, which comprises polyester

fibre with a washable surface as sound attenuation

material.

The plenum shall comprise an airflow measurement

and adjustment unit.

The grille shall be removable in order to provide

access to the measurement and adjustment module

in the plenum.

Product Code

AWE-L-H

AWU-L-H

L = Length

200,+1,..,20000

H = Height

50,+1,..,500

Specifics and accessories

FS = Fastening

CL Clips

CC Concealed screw fastening

FI = Finishing

AN Anodised

MF Mill finished

PN Painted

CO = Colour

W White

X Special colour

N No painting

Code example

ALE-200-50, FS=CL,FI=AN,CO=N

Sub products

BDR Plenum

PRI Plenum

IF Installation frame (Grilles)

OD Opposed blade damper (Grilles)