unistar nuclear energy - nuclear regulatory commissiontanks for water storage”; aci 350.3,...

38
FIRE PROTECTION SYSTEM CLASSIFICATION RAI 378 MARCH 6, 2013 UNISTAR NUCLEAR ENERGY

Upload: others

Post on 18-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • FIRE PROTECTION SYSTEM CLASSIFICATION RAI 378 MARCH 6, 2013

    UNISTAR NUCLEAR ENERGY

  • FIRE PROTECTION SYSTEM CLASSIFICATION

    Introductory Remarks and Summary of RAI 378

    Fire Protection Buildings and Tanks Performance Requirements

    Codes and Methodology

    Fire Protection System System Classification and Performance Requirements

    Codes and Methodology

    RAI 378 Response schedule and Conclusion

    Agenda

    2

  • FIRE PROTECTION SYSTEM CLASSIFICATION

    Background

    In CCNPP Unit 3 COLA Rev 8, to address the requirement of RG 1.189, UniStar had classified portions of the Fire Protection System (FPS) as Seismic Cat II-SSE.

    To address RAI 253, UniStar removed the Cat II-SSE and changed it to be consistent with DC FSAR classification.

    This change raised the question of how the design would meet the requirement of RG 1.189

    Objective of the presentation

    Explain the seismic classification method and design criteria that is used to meet the requirement of RG 1.189

    Go through the RAI 378 questions, describe the basis for our response and solicit NRC feedback

    Introduction

    3

  • FIRE PROTECTION SYSTEM CLASSIFICATION

    Fire Protection Buildings and Tanks Performance Requirement

    Codes and Methodology

    Agenda

    4

  • RAI 378 QUESTION 03.07.02-75

    • The applicant is requested to expand the description in CCNPP Unit 3 FSAR Section 3.7.2.3.4 to include directly or by reference the design requirements for the FPB, FWSTs and any other CS structures which have requirements over and above those stated in U.S. EPR FSAR Section 3.7.2.3.4.

    Item B - Requirements for Fire Protection Building (FPB) and Fire Water Storage Tanks (FWSTs)

    5

  • RAI 378 QUESTION 03.07.02-75

    • US EPR classification: - U.S. EPR Section 3.7.2.8, Fire Protection Building (FPB) and Fire

    Water Storage Tanks (FWSTs) are Conventional Seismic (CS) structures

    • US EPR requirements:

    Item B – CLASSIFICATION OF FIRE PROTECTION BUILDING AND FIRE WATER STORAGE TANKS

    6

    COL ITEM 3.7.2.8 A COL applicant that references the U.S. EPR design certification will provide the seismic design basis for the sources of fire protection water supply for safe plant shutdown in the event of a Safe Shutdown Earthquake (SSE).

    U.S. EPR FSAR Section 3.7.2.3.4. The analysis and design of Conventional Seismic building structures will be in accordance with the applicable requirements of the International Building Code (IBC) (Reference 4) and other codes, as appropriate (see Section 3.2.1.4 for description of CS structures).

  • RAI 378 QUESTION 03.07.02-75

    • Fire Protection Building • UniStar will design the FPB to meet a seismic

    performance consistent with the CCNPP Unit 3 SSE, with the use of conventional seismic codes - Methodologies to determine seismic forces for the FPB

    are based on: • ASCE 7, “Minimum Design Loads for Buildings and other

    Structures” • Seismic force magnitude consistent with SSE demands

    7

    Item B - Requirements for Fire Protection Building (FPB) and Fire Water Storage Tanks (FWSTs)

  • • Fire Water Storage Tanks - UniStar will design the FWSTs to meet a seismic performance

    consistent with the CCNPP Unit 3 SSE, with the use of conventional seismic codes

    - Methodologies to determine seismic forces for the FWSTs are based on:

    • ASCE 7, “Minimum Design Loads for Buildings and Other Structures” (American Water Works Association (AWWA) D-100, “Welded Steel Tanks for Water Storage”; ACI 350.3, “Seismic Design of Liquid-Containing Concrete Structures and Commentary” for calculation of seismic forces;

    • Verify SSE performance target with TID-7024, "Nuclear Reactors and Earthquakes,“ (SRP Section 3.7.3, Item 14), and ASCE 4, “Seismic Analysis of Safety-Related Nuclear Structures and Commentary”

    8

    RAI 378 QUESTION 03.07.02-75 Item B - Requirements for Fire Protection Building (FPB) and

    Fire Water Storage Tanks (FWSTs)

  • 9

    RAI 378 QUESTION 03.07.02-75 Item B - Requirements for Fire Protection Building (FPB) and

    Fire Water Storage Tanks (FWSTs) Preliminary Preliminary

  • RAI 378 QUESTION 03.07.02-75

    • A fixed based equivalent static lateral force methodology will be used to analyze the FPB - The FPB is a one story structure with a Single Degree of

    Freedom (SDOF) behavior. - The FPB will be founded on competent engineered fill that will

    be subject to Inspection Tests Analysis and Acceptance Criteria (ITAAC) equivalent to those of the CCNPP Unit 3 Category I structures.

    - The methodology delineated in conventional seismic codes (ASCE 7) with SSE performance targets and elastic design will result in a conservative approach.

    10

    Item B - Requirements for Fire Protection Building (FPB) and Fire Water Storage Tanks (FWSTs)

  • 11

    RAI 378 QUESTION 03.07.02-75 Item B - Requirements for Fire Protection Building (FPB) and

    Fire Water Storage Tanks (FWSTs)

    • Subsurface conditions impact code parameters

    • Subsurface conditions are well defined for the FPB and FWSTs

  • 12

    RAI 378 QUESTION 03.07.02-75 Item B - Requirements for Fire Protection Building (FPB) and

    Fire Water Storage Tanks (FWSTs)

    • Subsurface conditions impact code parameters

    • Subsurface conditions are well defined for the FPB and FWSTs

  • • The FPB is a one story building, Risk Category IV, founded over a stiff soil site - Site Class D, VS ≥ 600 fps (ASCE 7) - Importance factor Ie = 1.50 (ASCE 7)

    • The elastic lateral seismic force (R = 1.0), based on the total weight of the FPB (W) for the CCNPP Unit 3 is:

    13

    𝐹 =𝑆𝑆𝑀𝑀𝑀𝑅𝐼𝑒�

    𝑊 =0.45

    11.50�

    𝑊 = 0.675 𝑊

    RAI 378 QUESTION 03.07.02-75 Item B - Requirements for Fire Protection Building (FPB) and

    Fire Water Storage Tanks (FWSTs)

  • • The applicant is requested to provide, in addition to the applicable references, the specific analysis methods, seismic models, seismic input, and acceptance criteria that will be used to seismically qualify the FWSTs and include this information in Section 3.7.3 of the FSAR. - The FWSTs are projected as above ground steel tanks - Methodologies to determine seismic forces for the FWSTs are based

    on: • ASCE 7, “Minimum Design Loads for Buildings and Other Structures”

    (American Water Works Association (AWWA) D-100, “Welded Steel Tanks for Water Storage”; ACI 350.3, “Seismic Design of Liquid-Containing Concrete Structures and Commentary” for calculation of seismic forces;

    • Verify SSE performance target with TID-7024, "Nuclear Reactors and Earthquakes,“ (SRP Section 3.7.3, Item 14), and ASCE 4, “Seismic Analysis of Safety-Related Nuclear Structures and Commentary”

    14

    RAI 378 QUESTION 03.07.02-75 Item E - Requirements for Fire Water Storage Tanks (FWSTs)

  • • Design codes - National Fire Protection Association (NFPA), “Standard for

    Water Tanks for Private Fire Protection,” NFPA 22 - American Water Works Association (AWWA) D-100, “Welded

    Steel Tanks for Water Storage”

    15

    RAI 378 QUESTION 03.07.02-75 Item E - Requirements for Fire Water Storage Tanks (FWSTs)

  • RAI 378 QUESTION 03.07.02-75

    • In Enclosure 2, page 15 of 38, it states that the FPB and the FWSTs are designated as SC II. For the FPB and FWSTs this statement does not agree with the seismic classification provided in Table 3.2-1. The applicant is requested to resolve this discrepancy throughout the CCNPP FSAR so it is clear as to what seismic classification the FPB and FWSTs belong. - FPB and FWSTs are classified as Conventional Seismic structures.

    The change (from the RAI 253 response) will be made in response to RAI 378 and the FSAR markup will be provided.

    Item F - CLASSIFICATION

    16

  • RAI 378 QUESTION 03.07.02-75

    • The applicant is requested to justify why shear wave velocity information is not required for the FPB which, according to page 30 of 38, is required to remain functional during and after an SSE. The applicant is also requested to address why the ITAAC requirements of the FPB are also not applicable to the FWSTs.

    - Engineered fill in the area of the FPB and FWSTs will be placed with

    same materials and specifications as for Category I structures. - UniStar has provided a response to RAI 344, which indicates that

    the shear wave velocity and compaction ITAACs used for Category I structures will also be required for the FPB and FWSTs.

    Item J - FPB and FWSTs ITAAC

    17

  • FIRE PROTECTION SYSTEM CLASSIFICATION AGENDA

    Fire Protection System System Classification and Performance Requirements

    Codes and Methodology

    18

  • RAI 378, QUESTION 03.07.02-75 Items A & N – FPS Seismic Classification

    A. In Enclosure 2, page 14 of 38, it states that Section 3.2.1 categorizes Fire Protection SSC into two categories:

    1) SSC that must remain functional during and after an SSE; and

    2) SSC that must remain intact after an SSE without deleterious interaction with any Seismic Category I SSC.

    In the revised markup of Section 3.2.1 the staff could not find where the FPS was divided into these two categories. Therefore, the applicant is requested to identify each portion of the CCNPP Unit 3 FPS along with its seismic classification that come under these categories, and include this information in the FSAR.

    19

  • RAI 378, QUESTION 03.07.02-75

    N. Provide a table which identifies the seismic classification for each portion of the FPS to include:

    - Safety classification - Seismic category - Applicable design codes - Design requirement (no seismic requirement/must remain structurally intact

    under an SSE/must maintain its pressure boundary under an SSE/must remain functional during and after an SSE)

    UniStar Response: Item A: The site-specific SSCs of the Fire Protection system are seismically classified as shown in the following conceptual flow diagram. Item N: The handout describes the applicable design codes and design requirements for each site-specific SSC.

    Items A & N – FPS Seismic Classification

    20

  • RAI 378, QUESTION 03.07.02-75 Item I – FPS Nuclear Island Loop

    In Enclosure 2, Table 3.2-1 of the response, a portion of SSCs in component code SGA are designated as SC II and are required to provide safe shutdown equipment protection following an SSE. This is inconsistent with the definition of SC II provided on response page 5 of 38, which only requires that SC II SSCs be designed to withstand SSE seismic loads without incurring a structural failure that permits deleterious interaction with any Seismic Category I SSC. The applicant is requested to resolve this discrepancy.

    UniStar Response: COLA FSAR Table 3.2-1 will be updated to describe the site-specific portion of Fire Protection system. The site-specific SSCs providing safe shutdown equipment protection following a safe shutdown earthquake (SSE), which are required to remain functional, will be classified as Conventional Seismic (Note 1). COLA FSAR Section 3.2.1.4, Conventional Seismic will be supplemented to include the additional design criteria.

    21

  • RAI 378, QUESTION 03.07.02-75 Item K – Seismic Input & Method of Seismic Qualification

    In Enclosure 2, the ITAAC of Tables 2.4-21, 2.4-24 and 2.4-25 identify seismic qualification reports as Acceptance Criteria for the FPB ventilation system, FW distribution system, and Fire Suppression Systems, respectively. The applicant is requested to identify the source(s) of the seismic input and the method of seismic qualification for the FPB ventilation system, FW distribution system, and Fire Suppression Systems and include this information in Section 3.7.3 of the FSAR. For the FPB ventilation system and other portions of the Fire Protection System supported within the FPB and other structures, the applicant is requested to identify how the seismic input for these SSCs will be developed.

    UniStar Response: COLA ITAAC Tables 2.4-21, -24 and -25 will be updated to reflect the correct seismic classification of the associated systems, which is to remain functional following a safe shutdown earthquake (SSE). COLA FSAR Section 3.7.3 will be updated to add the seismic input and the method of seismic qualification for the FPB ventilation system, FW distribution system and fire suppression systems of the FPS in the FPB and other areas. (Refer to Handout for Item O regarding details of the sources of seismic input and method of seismic qualification for the site-specific FPS SSCs)

    22

  • RAI 378, QUESTION 03.07.02-75 Item L – ITAAC: Fire Protection Building Ventilation

    In Enclosure 2, the ITAAC of Table 2.4-21 provide Commitment Wording, Inspections, Tests or Analysis, and Acceptance Criteria for portions of the UHS Fire Protection Building System piping and ducting implying that portions of the system are SC I. However, in CCNPP FSAR Table 3.2-1 there is no system identified by this name nor is any part of the Fire Protection System in Table 3.2-1 designated as SC I. The applicant is requested to provide additional details regarding this system including its description, location, design requirements and include this information in the CCNPP FSAR Table 3.2-1 and FSAR Section 3.7. UniStar Response: ITAAC Table 2.4-21 Commitment Wording inadvertently refers to UHS Fire Protection Building. The correct name of the building is Fire Protection Building (FPB). There are no SC I SSCs in the FPB. This ITAAC wording will be corrected in Part 10 of the COLA (ITAAC).

    23

  • RAI 378, QUESTION 03.07.02-75 Item M – ITAAC: FPS Ventilation

    In Enclosure 2, ITAAC Table 2.4-21 for item c under the column “ Inspection Test or Analysis” it states in part that type tests, analyses or a combination of tests and analyses will be performed on the piping identified as SC II using analytical assumptions or under conditions which bound the SC I design requirements As this piping has been designated as SC II under the Commitment Wording Column, the applicant is requested to explain this apparent disagreement in the designation of the Fire Water Distribution System seismic classification.

    UniStar Response: As described in the response to Item L, ITAAC Table 2.4-21 Item c & d, Commitment Wording, inadvertently refers to UHS Fire Protection Building. The correct name of the building is Fire Protection Building (FPB). There are no SC I SSCs in the FPB. ITAAC Table 2.4-21 Items c & d will be revised for FPS ventilation system ducting classified as Convention Seismic (Note 1) that is required to be functional following an SSE. This ITAAC wording will be corrected in Part 10 of the COLA (ITAAC).

    24

  • RAI 378, QUESTION 03.07.02-75

    In Enclosure 2, page 5 of 38, CCNPP Unit 3 FSAR Section 3.2.1.2 markup states that SSCs classified as SC II are designed to withstand SSE seismic loads without incurring a structural failure that permits deleterious interaction with any SC I SSC or that could result in injury to main control room occupants. However, on page 18 of 38, which addresses buried pipe and pipe ducts it states that in accordance with Section 3.2.1, Fire Protection piping to Seismic Category (SC) I structures that is classified as: 1) SC II is designed to maintain its pressure boundary after an SSE event; and 2) is designed to remain functional during and following an SSE event. 1) First, as written it is not clear whether all FP piping connected to SCI structures is classified as SC II and is designed to maintain its pressure boundary and remain functional during and after an SSE event.

    2) Second, Section 3.2.1 does not reflect these additional requirements. FSAR Section 3.2.1 should be revised to identify the specific seismic requirements applicable to the FPS and the sentence on page 18 of 38 should be rewritten to make clear what the seismic requirements are for FP piping connected to SC I structures.

    Item C - FP Piping Connected to SC I Structures

    25

  • RAI 378, QUESTION 03.07.02-75

    UniStar Response:

    1) Seismic classifications of site-specific FP piping have been modified and are identified with design requirements described in response to Item N of this RAI. Revised classifications for FP piping are CS (Note 1), and NSC. CS (Note 1) requires piping to remain functional during and after an SSE.

    Site-specific FP piping connected to SC I structures is classified as CS (Note 1). Seismic analysis and design of CS (Note 1) buried piping will follow the same requirements as of SC I piping, outlined in FSAR Section 3.7.3.12, Section 3.8.4.4.5, and Section 3.10 of the AREVA NP Topical Report ANP-10264NP-A.

    2) FSAR Section 3.2.1 will be revised to include Seismic Category CS (Note 1) and design requirements applicable to this classification. • Applicable Sections of FSAR, will be revised to identify the specific seismic

    requirements of the FP piping attached to SC I structures.

    Item C - FP Piping Connected to SC I Structures

    26

  • RAI 378, QUESTION 03.07.02-75

    1) In Enclosure 2, page 15 of 38, it states that the buried FP SSC identified in Table 3.2-1 are seismically analyzed using the design response spectra identified in 3.7.1.1.1.4. It states “These piping mains will be designed according to ASCE 4-98, 1983 ASCE Report “Seismic Response of Buried Pipes and Structural Components”, and the AREVA Topical Report ANP 10264, ‘US. EPR Piping Analysis and Pipe Support Design Topical Report’.” The 1983 ASCE report is not identified in FSAR Section 3.7.3.12 which addresses the analysis of buried FP pipe. The applicant is requested to explain this omission and describe what additional requirements from the 1983 ASCE report will be applied to the analysis and design of buried FP pipe and to include this information in Section 3.7.3 of the FSAR.

    2) In addition, the AREVA Topical Piping Report only addresses the qualification of ASME III piping (safety class 1,2, and 3). According to Table 3.2-1 of the markup, the FP piping is qualified using the provisions of ANSI/ASME B31.1. The applicant is requested to explain how the AREVA Topical Piping Report is applicable to seismic qualification of the FP piping.

    3) Lastly, buried FP SSC are not explicitly identified in Table 3.2-1 even though this is indicated to be the case in the applicant’s response. The applicant is requested to revise Table 3.2-1 to include the identification of buried FP SSC.

    Item H – FP Buried Piping

    27

  • RAI 378, QUESTION 03.07.02-75

    UniStar Response: Site-specific buried FP piping will be classified as CS (Note 1), and NSC in Table 3.2-1. Seismic analysis and design of CS (Note 1) buried piping will follow the same requirements as of SC I piping, outlined in FSAR Section 3.7.3.12, Section 3.8.4.4.5 and supplemented by response to RAI 333, Q 03.08.04-29.

    1. ASCE 1983 Report (Seismic Response of Buried Pipes and Structural Components), & ASCE 4-98, are specifically used to evaluate the effects of seismic waves traveling through surrounding soil. Seismic responses of long, straight buried pipe sections, remote from bends or anchor points, are taken as equal to those of the ground as defined in the 1983 ASCE report. Upper bound maximum axial and bending strains due to seismic wave propagation are calculated using equations provided in ASCE 1983 Report. ASCE 1983 Report will be included in FSAR Section 3.7.3.12.

    2. AREVA NP Topical Report ANP-10264NP-A, Section 3.10 describes detailed step by step method of analysis and design of ASME Class 2 & 3 SC I buried piping and is based on among others ASCE 4-98, ASCE 1983 Report and ASME III 2004 and ANSI/ASME B31.1 standards.

    3. Table 3.2-1 will be revised to explicitly include buried FP SSC (N handout).

    Item H – FP Buried Piping

    28

  • RAI 378, QUESTION 03.07.02-75

    In addition to addressing the staff concerns in Items A through M above, applicant is requested to provide the following additional information regarding the seismic design for the CCNPP Unit 3 FPS:

    For each SSC that must remain structurally intact under an SSE; must maintain its pressure boundary under an SSE; or must remain functional during and after an SSE the applicant is requested to provide the seismic inputs, type of seismic model, methods of analysis, and the acceptance criteria that are imposed which ensure that the SSC will meet its applicable design requirement and to include this information in the appropriate section of the FSAR.

    Item O - Fire Protection SSC

    29

  • RAI 378, QUESTION 03.07.02-75

    UniStar Response: • Seismic classification of Site-specific FP SSC have been re-defined & identified

    including seismic design requirements in the handout for Item N, as: i) CS (Note 1) and ii) NSC

    FP SSC are grouped as follows, and are listed in the handout for Item O:

    i) CS (Note 1) Structures - buried pipes. ii) CS (Note 1) Subsystems - HVAC ducts, cable trays, conduits and tubing

    distribution systems and supports. iii) CS (Note 1) Components - Mechanical and Electrical Equipment. iv) CS (Note 1) above ground piping supports.

    • All site-specific FP CS (Note 1) SSC are designed per requirements of respective SC I SSC, as described in appropriate Section of US EPR FSAR using site-specific SSE or envelope of site-specific SSE and CSDRS. Seismic input, seismic model, analysis methods are described in the handout for Item O.

    Item O - Fire Protection SSC

    30

  • FIRE PROTECTION SYSTEM CLASSIFICATION

    CONCLUSIONS

    Conclusions

    31

  • FIRE PROTECTION SYSTEM CLASSIFICATION

    • RAI 378 response is being prepared based on these

    slides.

    • Submittal date is March 31 with FSAR mark-ups.

    • CC3 COLA Revision 10 will incorporate RAI 378.

    • Previous responses to RAI 375 and 253 will be superseded as required.

    Conclusions

    32

  • USG

    USG

    UHS MAKEUP WATER INTAKE STRUCTURE

    NUCLEAR ISLAND FIRE MAIN LOOP

    JOCKEYPUMP

    FIREPROTECTION

    BUILDINGSPRINKLER

    SYSTEM

    TURBINE ISLANDFIRE MAIN LOOP

    TO SECURITYBUILDING

    TO WAREHOUSEBUILDING

    RAW WATERMAKEUP LINE

    A

    C A

    A B

    * B

    * B

    DESIGNAREA

    A

    B NSCNS-AQ

    NS-AQ CS (NOTE 1)

    SAFETYCLASSIFICATION

    SEISMICCATEGORY

    LEGEND:

    - OUTDOOR HYDRANT

    - POST INDICATOR VALVE

    - ANGLE GLOBE VALVE

    - HOSE REEL

    - PUMP

    - CHECK VALVE

    - DESIGN AREA BREAKSB A

    STAND-PIPE, FOR MULTIPLE HOSE STATION SERVING SC-I, SSCs

    FIRE WATERSTORAGE TANKS

    2 x 300,000 GALLONS

    FIRE PROTECTION BUILDING

    DIESELFIREPUMP

    (1 x 100%)

    ELECTRIC FIREPUMP (1 x 100%)

    TURBINEISLAND

    COOLINGTOWERAREA

    DIESELFIREPUMP

    (1 x 100%)

    PROPOSED CONCEPTUAL FIRE PROTECTION FLOW DIAGRAM

    NUCLEAR ISLANDBUILDINGS:

    RB*, SB,EPGB, ESWB

    * CONTAINMENT PENETRATION

    PIPING AND VALVES ARE

    SEISMIC CATEGORY I.

    CS NOTE 1 - SSC MUST REMAIN FUNCTIONAL FOLLOWING AN SSE.ENCOMPASSES THE U.S. EPR SEISMIC CATEGORY II.

    C

    U.S. EPRFSAR IBR

    *U.S. EPRFSAR IBR

    C NSCNS

    A *

    A *

    A/G U/G

    U/GA/G

    B A

    - ABOVE GROUND / UNDERGROUND PIPE BREAK

    U/GA/G

    U/GA/G

    P

    P

    P

    P

    P

    P

    P

    P

    P P

    P

    PP

    PP

    P

    P P

    P P

    P P

    P

    PP

    P

    PP

    P

    P

    - ISOLATION VALVE

    A *

    A *

    A *

    B A

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewLine

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

    jatracewOval

  • RAI 378, Question 03.07.02-75 Handout - Item N

    Fire Protection System Input for FSAR Table 3.2-1

    Note 1 – SSC must remain functional during and after an SSE, encompassing the U.S. EPR Seismic Cat II. * - ASME Section III for seismic analyses methodology only **- ASCE 1983, Seismic Response of Buried Pipe and Structural Components report ***- AISI 2001, North American Specification for the Design of Cold-Formed Steel Structural Members, 2001 Edition Page 1 of 3

    SSC DESCRIPTION SAFETY CLASSIFICATION

    SEISMIC CATEGORY

    10CFR50 APPENDIX B PROGRAM

    CODE(S) DESIGN REQUIREMENTS

    Diesel Engine Driven Fire Pumps, Drivers and supporting subsystems, including diesel fuel oil supply

    NS-AQ CS (Note 1) YES

    NFPA 20 NFPA 25

    NFPA 804 ANSI/ASME B31.1

    IEEE 344

    Must remain functional during and

    after an SSE.

    Electric Motor Driven Fire Pump and Driver NS-AQ NSC YES

    NFPA 20 NFPA 25

    NFPA 804 IEEE 344

    No Seismic requirement.

    Electric Motor Driven Fire Jockey Pump and Driver NS-AQ NSC YES

    NFPA 20 NFPA 25

    NFPA 804

    No Seismic requirement.

    Fire Protection Tank Makeup Water Piping and Valves From Raw (Desalinated) Water Supply System

    NS NSC NO NFPA 22 NFPA 25

    No Seismic requirement.

    Fire Water Distribution System Aboveground Piping, including valves and suppression system inside the Fire Protection Building NS-AQ CS (Note 1) YES

    NFPA 13 NFPA 25

    NFPA 804 ANSI/AISC 360

    ANSI/ASME B31.1 ASME III*

    Must remain functional during and

    after an SSE.

    Fire Water Distribution System, Conventional Area (Safe Shutdown Equipment Protection) U/G Loop

    U.S. EPR FSAR IBR

    U.S. EPR FSAR IBR

    U.S. EPR FSAR IBR

    U.S. EPR FSAR IBR

    U.S. EPR FSAR IBR

  • RAI 378, Question 03.07.02-75 Handout - Item N

    Fire Protection System Input for FSAR Table 3.2-1

    Note 1 – SSC must remain functional during and after an SSE, encompassing the U.S. EPR Seismic Cat II. * - ASME Section III for seismic analyses methodology only **- ASCE 1983, Seismic Response of Buried Pipe and Structural Components report ***- AISI 2001, North American Specification for the Design of Cold-Formed Steel Structural Members, 2001 Edition Page 2 of 3

    SSC DESCRIPTION SAFETY CLASSIFICATION

    SEISMIC CATEGORY

    10CFR50 APPENDIX B PROGRAM

    CODE(S) DESIGN REQUIREMENTS

    Fire Water Distribution Underground Piping System, including valves & hydrants, to UHS Makeup Water Intake Structure, Protecting Safe Shutdown Equipment following an SSE NS-AQ CS (Note 1) YES

    NFPA 24 NFPA 25

    NFPA 804 ANSI/ASME B31.1

    ASME III* ASCE 4-98

    ASCE 1983**

    Must remain functional during and

    after an SSE.

    Fire Water Distribution Underground Piping System, including valves & hydrants, Turbine Island Loop and Cooling Tower Loop, Not Protecting Safe Shutdown Equipment following an SSE

    NS-AQ NSC YES

    NFPA 24 NFPA 25

    NFPA 214 NFPA 804

    IBC

    No Seismic requirement.

    Fire Water Aboveground Piping and Valves of Standpipes and Hose Stations for UHS Makeup Water Intake Structure NS-AQ CS (Note 1) YES

    NFPA 14 NFPA 25

    NFPA 804 ANSI/ASME B31.1

    ASME III*

    Must remain functional during and

    after an SSE.

    Fire Water Aboveground Piping and Valves of suppression systems, Standpipes and Hose Stations for Site Specific Buildings, other than UHS Makeup Water Intake Structure

    NS-AQ NSC YES

    NFPA 13 NFPA 14 NFPA 25

    NFPA 804

    No Seismic requirement.

    Ventilation Equipment and Ductwork, Supporting Diesel Driven Fire Pumps

    NS-AQ CS (Note 1) YES

    NFPA 20 NFPA 90A

    ASME AG-1 ASME N509

    ANSI/AISC N690 AISI 2001 ***

    IEEE 344

    Must remain functional during and

    after an SSE.

    Ventilation Equipment and Ductwork, Except Supporting Diesel Driven Fire Pumps NS-AQ NSC YES

    NFPA 20 NFPA 90A

    IBC

    No Seismic requirement.

  • RAI 378, Question 03.07.02-75 Handout - Item N

    Fire Protection System Input for FSAR Table 3.2-1

    Note 1 – SSC must remain functional during and after an SSE, encompassing the U.S. EPR Seismic Cat II. * - ASME Section III for seismic analyses methodology only **- ASCE 1983, Seismic Response of Buried Pipe and Structural Components report ***- AISI 2001, North American Specification for the Design of Cold-Formed Steel Structural Members, 2001 Edition Page 3 of 3

    SSC DESCRIPTION SAFETY CLASSIFICATION

    SEISMIC CATEGORY

    10CFR50 APPENDIX B PROGRAM

    CODE(S) DESIGN REQUIREMENTS

    Instrumentation and Controls in the Fire Protection Building support the fire protection system NS-AQ CS (Note 1) YES IEEE 344

    Must remain functional during and

    after an SSE. Fire Protection System Electrical Distribution System NS NSC NO IBC

    No Seismic requirement.

  • RAI 378, Question 03.07.02-75 Handout – Item O

    1 of 2

    Site-Specific FP CS (Note 1)

    SSC

    Seismic Input Seismic Model Methods of Seismic Analysis

    Acceptance Criteria Codes and Standards

    Buried FP Piping (Per response to RAI 333 Question 03.08.04-29)

    See response to RAI No. 333 Question 03.08.04-29

    See response to RAI No. 333 Question 03.08.04-29

    See response to RAI No. 333 Question 03.08.04-29

    See response to RAI No. 333 Question 03.08.04-29

    See response to RAI No. 333 Question 03.08.04-29

    FP HVAC Ducts and Supports- (Per Section 3A.2 of US EPR FSAR)

    CCNPP 3 Site-specific SSE

    Per US EPR FSAR Appendix 3A.2: [Equivalent beam elements, Shell elements.]

    Per US EPR FSAR Appendix 3A.2: [1. Response Spectrum, 2. Time History, OR 3. Equivalent Static Method. ]

    Per US EPR FSAR Appendix 3A.2: [HVAC Duct & Supports stress allowables per Para AA-4321 of ASME AG-1]

    Per US EPR FSAR Appendix 3A.2: [ASME AG-1, ANSI/AISC N690, AISI 2001, SMACNA, ANSI/AISC 360.]

    FP Cable Tray, Conduit & Supports- (Per Section 3A.3 of US EPR FSAR)

    CCNPP 3 Site-specific SSE

    Per US EPR FSAR Appendix 3A.3: [Equivalent beam element, braces as truss elements]

    Per US EPR FSAR Appendix 3A.3: [1. Response Spectrum, 2. Time History, OR 3. Equivalent Static Method. ]

    Per US EPR FSAR Appendix 3A.3: [AISI 2001, ANSI/AISC N690.]

    Per US EPR FSAR Appendix 3A.3: [ANSI/AISC N690, AISI 2001, ANSI/AISC 360. ]

    FP Mechanical & Electrical Equipment and supports- (Per Section 3.10 of CCNPP 3 FSAR)

    CCNPP 3 Site-specific SSE

    Per CCNPP 3 FSAR Section 3.10: [Analytical: Simple Frame (columns and beams), or plate & shell elements. Testing: Individual equipment or Combined equipment and support.]

    Per CCNPP 3 FSAR Section 3.10: [Qualify by analysis: 1. Response Spectrum, 2. Time History, OR 3. Equiv. Static Method. Qualify by testing. Qualify by a combination of analysis and testing. Qualify by similarity. (Qualify by experience not used)]

    Per CCNPP 3 FSAR Section 3.10: [Capable of performing its function under all loads using allowable stresses from applicable codes. OR Functions as designed following the test.]

    Per CCNPP 3 FSAR Section 3.10: [IEEE Std 344-2004 ASME QME-1-2007 ANSI/AISC N690, AISI 2001, ANSI/AISC 360.]

  • RAI 378, Question 03.07.02-75 Handout – Item O

    2 of 2

    Site-Specific FP CS (Note 1)

    SSC

    Seismic Input Seismic Model Methods of Seismic Analysis

    Acceptance Criteria Codes and Standards

    Above Ground FP Piping Supports- (Per AREVA Topical Piping Report ANP-10264NP-A)

    CCNPP 3 Site-specific SSE

    Per CCNPP 3 FSAR Section 3.9.3.1 as ASME Class 3 equivalents. [Analytical: Simple columns, beams and frames, or Plate & shell elements. Testing: Standard components.]

    Per CCNPP 3 FSAR Section 3.9.3.1 as ASME Class 3 equivalents.

    [Equiv. Static Method. Qualify by testing.]

    Per CCNPP 3 FSAR Section 3.9.3.1 as ASME Class 3 equivalents.

    [Subsection NF of ASME Code. ANSI/AISC N690]

    Per AREVA Topical Piping Report ANP-10264NP-A. [Subsection NF of ASME Code. ANSI/AISC N690]

    Above Ground FP Piping- (Per AREVA Topical Piping Report ANP-10264NP-A)

    CCNPP 3 Site-specific SSE

    Per AREVA Topical Piping Report ANP-10264NP-A, Section 4.0

    Per AREVA Topical Piping Report ANP-10264NP-A, Section 4.0

    Per AREVA Topical Piping Report ANP-10264NP-A, Table 3-3

    Per AREVA Topical Piping Report ANP-10264NP-A, Table 3-3

    Fire Protection System Classification�RAI 378�March 6, 2013Fire Protection System ClassificationFire Protection System ClassificationFire Protection System ClassificationRAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75RAI 378 Question 03.07.02-75Fire Protection System Classification�AGENDARAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75�RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75RAI 378, Question 03.07.02-75Fire Protection System ClassificationFire Protection System Classification