underground standard u772.2 in the meter base
TRANSCRIPT
Conductor having highest voltageto ground in 4-wire delta systemmust be connected to the righthand terminal and marked withorange tape at the pedestal andin the meter base.
Meter Base281086
Plastic bushing required for steelconduit to protect cable.
Schedule 40 PVC or betterFurnished and Installedby Consumer.
Service laterals furnishedand installed by OG&E.
NOTES:1. Place identifying tag on service conductors with
information relating to where service is coming from(pedestal, transformer, pipe or no pipe underdriveway.) Refer to U16
Seenote 1
Placeinstructions as towhere service iscoming from.
Sig
natu
res o
n F
ile
AP
PR
OV
ED
UNDERGROUND STANDARDOG&E Electric Services©
U772.2
CONNECTION DIAGRAMFOR SELF-CONTAINED THREE PHASE FOUR WIRE METER
208Y/120 OR 240 /120 VOLT 200-AMPERE MAXIMUMΔ
SEP 2007S
UP
ER
SE
DE
S J
UN
2005 IS
SU
E
Meter Base200A1Ø 2810653Ø 281086
48 to 6
6-in
60-in p
refe
rred
Schedule 40 PVCor better(3-inch conduit for200-Ampere MeterBase)
5
42
1
6
3
30-in (
min
)
1 Service Lateral X X
2 Service Lateral Raceway X X
3 Meter Base X X
4 Service Raceway X X
5 Service Equipment X X
6 Meter X X
DESCRIPTION
FURNISHED BY INSTALLED BY
O.G.& E. CONSUMER O.G.& E. CONSUMER
ITEMNUMBER
Notes:1. When foundation obstructions exist, the use of schedule 40 (minimum) conduit with
(2) 45-degree elbows to clear obstructions is permissible. The top 45-degree elbowis to be at or below ground level.
2. OG&E equipment is to be installed on outside surface of structure and is not to be recessed.
3. Refer to U16 for proper identification and marking.
See note 1
7 Grounding Electrode &Grounding ElectrodeConductor
X X
* Not Shown
*
Sig
natu
res o
n F
ile
AP
PR
OV
ED
UNDERGROUND STANDARDOG&E Electric Services©
U772
METER INSTALLATIONFOR SELF-CONTAINED SINGLE PHASE OR THREE PHASE METER
208Y/120 OR 240 /120 OR 240/120 VOLTSD
200-AMPERES MAXIMUM
SU
PE
RS
ED
ES
M
AR
2014 IS
SU
EAUG 2014