ultrasonic level transmitters
DESCRIPTION
The materials included in this compilation are for the use of Dwyer Instruments, Inc. potential customers and current employees as a resource only. They may not be reproduced, published, or transmitted electronically for commercial purposes. Furthermore, the Company’s name, likeness, product names, and logos, included within these compilations may not be used without specific, written prior permission from Dwyer Instruments, Inc. ©Copyright 2014 Dwyer Instruments, Inc.TRANSCRIPT
Ultrasonic Level Transmitters
The materials included in this compilation are for the use of Dwyer Instruments, Inc. potential customers and current employees as a resource only. They may not be reproduced, published, or transmitted electronically for commercial purposes. Furthermore, the Company’s name, likeness, product names, and logos, included within these compilations may not be used without specific,
written prior permission from Dwyer Instruments, Inc. ©Copyright 2014 Dwyer Instruments, Inc.
Overview
ULTMULT UTC/UTS
ULL
ULL Introduction
Designed for non-contact measurement of liquid levelsSophisticated algorithms are used to overcome acoustic interferences and false echoes
ULL - Specifications
Wetted Materials: Sensor: Polypropylene; Acoustic window: ECTFERanges:
ULL-1XXX: 0.25 to 5 m (0.82 to 16.4 ft )ULL-2XXX: 0.6 to 15 m (1.96 to 49.2 ft)
Accuracy: 0.25% of max. range (at 20°C)Enclosure: Plastic enclosure: ABS & UV resistant bodyEnclosure Rating: NEMA 4 (IP65)
ULL- FeaturesUltrasonic technology paired with automatic temperature compensation to provide reliable and accurate measurements in virtually all conditionsSophisticated algorithms are used to overcome acoustic interferences and false echoesLCD screen and four push buttons allow for quick and easy programming on a simple menu structureDiagnostic capabilities and a fail-safe output signal
ULT - Introduction
Provides reliable, accurate, non-contact measurement of liquid levelsNeeds only a 7.6 cm diameter column for effective measuring surfacePurchase by range
ULT - Specifications
Wetted Materials: Sensor: PVDF; Process connection: 303 SS; O-ring: fluoroelastomerRanges: 7.5 m (24.6´) , 10 m (32.8´) Accuracy: ±0.2% of max rangeOutput Signal: 4 to 20 mA or 20 to 4 mA (Two-wire)Enclosure Rating: Weather-proof meets NEMA 4X (IP66), explosion-proof rated Class I, Div. 1, Groups B, C, D; Class II/III, Div. 1, Groups E, F, GAgency Approvals: CE, FM
ULT Features Weatherproof & Explosion Proof
Weather-proof meets IP 67 FM Approved Explosion-proof Housing
Rated Class I, Div. 1, Groups B, C, D; Class II/III, Div. 1, Groups E, F, G.
6 digit local LCD display w/ Push ButtonsNo handheld or laptop required for programmingUnits selectionTank dimensionsEasy Programming
ULTM - Introduction
Ultrasonic level transmitterHas embedded cellular communications and can send SMS alerts
ULTM - Specifications
Wetted Materials: PVDFRange:
Liquids: 8 m (26.25´) ;Solids: 6 m (19.69´) .
Accuracy: ±0.5 cm (±0.2˝) or 0.2% of max. rangeRepeatability: 0.2% of measured rangeEnclosure Material: Plastic PC/ABS+UV.Enclosure Rating: IP65/IP67, IP68 (96 hours at 1.8 m (5.91’) water depth).
ULTM - Features
Embedded and external temperature sensor for any conditionCellular Transmission dataUSB for quick set up and local monitoringHourly alerts Low Power consumption (battery powered)
UTC/UTS – Introduction
Reliable, accurate, non-contact measurement of liquid level and open channel flow even under extremely harsh conditionsNo moving parts to wear or jamModbusDesigned to be used with UTS sensors
UTC - Specifications
Ranges: 0.6 to 25 m (2 to 82 ft) Accuracy: 0.25% of max. rangeSwitch Type: 5 SPDT relaysEnclosure Material: ECTFEEnclosure Rating: NEMA 4X (IP65)Units: m, in, ft, m3/hr, GPM interchangeable
UTS - Specifications
Wetted Materials: PolypropyleneTransducer Frequency: 25 kHzRange: 0.6 to 25 m (2 to 82 ft) Enclosure Rating: NEMA 4 (IP65)
UTC/UTS – Features
Withstands extreme conditions 6-digit LCD displaySimple programming menu 5 SPDT relaysEasy to InstallModbus RTU communication protocolRS-232 4 to 20 mA communications
ULL - Applications
Continuous Level Monitoring for:Fuel Tank LevelDigester Tank LevelChemical Tank LevelCooling Tower Level
ULT - Application
Continuous Level Monitoring for:Fuel Tank LevelDigester Tank LevelPump Lift StationsWet Well Level Chemical Tank LevelCooling Tower Level
Beam path
ULTM - Applications
Remote Level
Fuel Tank Monitoring Fuel Theft PreventionLeakage Detection Identification of overflowWastewater MonitoringRiver flood Alerts
UTC/UTS - Applications
Used as a flow monitor for open channels and Level Monitoring
Designed to be mounted above open channels such as:
FlumesWeirs