ultrasonic level sensor sigma · 2017-07-06 · 7.4.2 to achieve the optimal sensor operation,...

55
1 Ultrasonic level sensor "SIGMA" ULSx-yy models Installation Manual ULS.0000-EN IM _v.170515_

Upload: others

Post on 29-Jul-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

1

Ultrasonic level sensor

"SIGMA"

ULSx-yy models

Installation Manual

ULS.0000-EN IM

_v.170515_

Page 2: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

2

CONTENTS

Page

1 GENERAL INSTRUCTIONS ................................................................................... 2

2 BASIC DEVICE INFORMATION ........................................................................... 3

3 BASIC TECHNICAL CHARACTERISTICS ........................................................... 4

4 DEVICE MARKINGS ................................................................................................ 5

5 GENERAL VIEW AND CONTENTS OF DELIVERY ........................................... 5

6 SAFETY REQUIREMENTS ..................................................................................... 8

7 PREPARATION FOR INSTALLATION AND MOUNTING PLACE

PRESELECTION ............................................................................................................ 8

8 SENSOR ELECTRICAL CONNECTION .............................................................. 11

9 FINAL SELECTION OF MEASURING PART MOUNTING PLACE ................ 13

10 SENSOR INSTALLATION AND SETTING ....................................................... 14

11 SENSOR PARAMETERS SETTING ................................................................... 19

12 SENSOR SETTING AND ADJUSTMENT WITH "uS_Install" PROGRAM ..... 21

13 TRANSPORTATION AND STORAGE ............................................................... 23

APPENDIX A SENSOR OPERATION MODES ...................................................... 24

APPENDIX B "uS_Install" APPLICATION PROGRAM......................................... 28

APPENDIX C LAYOUTS FOR SENSOR CONNECTION TO PC ......................... 35

APPENDIX D FIRMWARE UPDAITING, CONFIGURATION DATA SAVING

AND RESTORING ....................................................................................................... 36

APPENDIX E DATA EXCHANGE PROTOCOL .................................................... 39

APPENDIX F CALIBRATION TABLE CALCULATION ...................................... 45

APPENDIX G QUICK GUIDE FOR “US20 Install Service” PROGRAM .............. 47

The present manual is intended to provide information necessary for users to

install and maintain ultrasonic level sensor "SIGMA" ULS-20, ULS2-20 and ULS4-20

models (hereinafter – Sensor or Product).

1 GENERAL INSTRUCTIONS

Only personnel that acknowledged the present manual is allowed to install the

sensor.

During the fuel level sensor installation, organizational and technical actions

that ensure the occupational safety with autogas systems, control and measuring

equipment, ancillary equipment and consumable materials have to be carried out (see

Section 6).

Page 3: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

3

2 BASIC DEVICE INFORMATION

Ultrasonic level sensor “SIGMA” is purposed for noninvasive liquified petroleum

(propane/butane) gas (LPG) level measurement in horizontally positioned gas tanks of

vehicles.

a b

Fig. 2.1 – Typical LPG fuel containers layout and recommended position for

sensor measuring part installation in passenger cars

(a – toroidal container, b – cylindrical container)

It is also possible to use sensor for gasoline, diesel and other fluids level

measuring.

Sensor consists of two parts – measuring part and transducer with indicator

(hereinafter – Transducer).

Transducer calculates fuel level by processing data from the measuring part and

outputs result to the indicator. Calibration procedure is performed to indicate fuel

volume instead of fuel level. After the calibration, fuel level (in centimeters) is

recalculated into volume (liters). Measuring results are demonstrated on the indicator;

they can be also transferred to the GPS tracking device for further processing.

See Appendix A for indicator use description with different operation modes and

settings.

Measuring part is installed on the container bottom from outside by using fixing

mechanism – cable with traction device.

Sensor can transfer data to vehicle information system.

There are 3 modifications of SIGMA ULS sensors, which have different data

transfer interface:

SIGMA ULS - no data transfer interface;

SIGMA ULS2 - RS-232 digital interface;

SIGMA ULS4 - RS-485 digital interface.

To protect the sensor from mechanical influences and unauthorized access to the

sensor and its mounting system, a ULM.4000 protection device can be used

(optionally) on horizontally located fuel gas ballons up to 450 mm in diameter

mounted outside the vehicle.

Sensor installation does not interfere with the tank structure or influence autogas

equipment operation.

Sensor can be used with equipment that supports unified communication

protocol Epsilon Data Exchange (see Appendix E).

Page 4: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

4

3 BASIC TECHNICAL CHARACTERISTICS

Table 3.1 – Basic technical data

Parameter or characteristic name Unit Value Note

General

Type of measured fuel LPG

Allowed tilt angle of vehicle when measuring

level, max degrees 12

Container wall thickness mm 1,5…4,0

Operational temperature range С – 40 … + 70

Measuring part ingress protection rating IP67

Transducer ingress protection rating IP50

Mode of operation Continuous

Measurement

Indicator resolution capability liters 1*

Measurement range mm 20…600**

Averaging period sec. 30

Code length of presentation of measurement

results bit

10/12/16 level

8 temperature

Exchange rate through the serial port bps

2400, 4800,

9600, 19200,

38400,

57600,

115200

Programmed,

default setting -

19200

Power supply

Power supply voltage, operational range V +9 …+36 Nominal value

Current consumption, max mA 70

Interface

Digital RS-232 ULS2 model

RS-485 ULS4 model

Dimensions

- transducer, max mm 62х38х16

- measuring part, max mm Ø26х11

* - Indicator readings are considered adequate in 30 seconds after the filling-in if the vehicle

stays in horizontal position.

** - When level of fuel in tank is lower than the minimal measuring range of sensor, readings can

be incorrect. It is recommended to fill in before fuel reaches lower measuring range of sensor.

Page 5: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

5

4 DEVICE MARKINGS

Fig. 4.1 – Device markings legend

5 GENERAL VIEW AND CONTENTS OF DELIVERY

Fig. 5.1 – Measuring part components

Fig. 5.2 – General view of transducer with indicator

(Button 1- to change the operation mode, Button 2 – to browse the menu entries; see

Appendix A)

ULS 4 - GW - xxxx

Model

Interface type

4 - RS-485

2 - RS-232 - no interface

Additional modifications (blank field for standard devices)

blank

Indicator color

B - black

- dark-grey

- grey

T

G

Y

Display glow color

W - white

G - green-yellow

- beige

Button 1

Button 2

Page 6: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

6

Table 5.1 – Basic delivery kit

Name q. Note

Measuring part 1 Assembled with 7 m cable

Transducer with indicator 1

Assembled with cables: power supply

(~1 m), interface and signal (~0,2 m

each), fuse holder with fuse SI 0,1 А,

two heat shrinkable cambrics (Ø3 and

Ø6 mm).

Measuring part fixing kit 1 See fig. 5.3

Transducer mounting holder 1 With mounting kit

Passport 1

1 – Half-bushing ( 5)

2 – Half-bushing (М5)

3 – Clamp cover – to press

measuring part

4 – Bushing (cable protection)

5 – Measuring part gasket (attached

to the measuring part)

6 – Cable. 2 m long

7 – Container vibration isolator

8 – Sensor vibration isolator

9 – Cable double clamp

10 – Screw М5 х 35

11 – Grower washer

12 – U-washer (inner 5)

13, 14 – Polyethylene bag

15 – TSIATIM-221 lubricant - 5 g

Fig. 5.3 – Measuring part mounting kit

Page 7: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

7

Table 5.2 – Optional items, documentation and software

Name Note

Indicator tilting holder ULS.4200 For comfortable angle-wise indicator mounting

Protection device for sensor

ULM.4000 (Optionally)

For mechanical protection and restriction of

access to the sensor (See Fig. 5.4)

Installation manual ULS.0000 IM. -

User Software CD ULS.0000 CD3.

CD contains:

- "US20_Install" and "US20 Install Service"

programs for sensor installation and calibration;

- "US20_AppLoader" loader program for firmware

updating, configuration data saving and restoring.

- "US20 Calibration table calculation for automotive

LPG containers" program for calibration table

generation according to LPG container dimensions.

Fig 5.4 – ULM.4000 - Measuring part protective cover with traction device

Page 8: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

8

6 SAFETY REQUIREMENTS

Requirements of fire safety regulations, according to ГOCT (GOST) 12.1.004-

91 "Occupational safety standards system. Fire safety. General requirements," and

electrical safety, according to ГOСT (GOST) 12.1.019-91 "Occupational safety

standards system. Electrical safety. General requirements" or other requirements in

force within the territory of the consumer have to be observed on the working site.

Requirements of occupational health and safety rules have to be observed on

road transport at the working sites according to НПАОП (NPAOP) 0.00-1.62-12

"Occupational safety and health rules on road transport", autogas occupational safety

requirements or other requirements in force within the territory of the consumer.

The responsibility for the implementation of security measures lies with the

technical staff involved in the installation of the fuel level sensor, as well as the

employees responsible for the equipment at the working site.

7 PREPARATION FOR INSTALLATION AND MOUNTING PLACE

PRESELECTION

7.1 Unpack and check the specification according to Table 5.1

7.2 Prepare equipment, instruments and consumables according to Table 7.1:

Table 7.1

Name

Wrench with mouth size of 10 mm.

Electric drill with 6,5 mm drill

Gasket lubricant (included in delivery kit) – 5 gram

Automotive sealant (recommended: ABRO RTV Silicone Gasket Maker, part

No.12AB or analogue) – 2 - 3 grams

Highlighter to mark possible place of measuring part installation

Measuring tape to measure fuel container before calibration

Rubber roller to press the vibration isolator

Note – to install sensor, rubber spacers with 20 mm thickness may be necessary

to use. Spacers can be from any nonmetal elastic material with enough rigidity to

withstand the weight of fuel container. Spacers should be inserted under the fuel

container to insure the required space for measuring part installation.

7.3 Fill the container not less than 2/3 of its volume.

Page 9: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

9

7.4 Select the installation place for measuring part beforehand. To do this:

7.4.1. Place the vehicle on flat horizontal surface, fuel container must be in

horizontal position too.

7.4.2 To achieve the optimal sensor operation, measuring part must be installed

in the lower point underneath the container, right in the middle, as demonstrated

on fig. 2.1, 7.1, 7.2.

Fig. 7.1 – Correct and incorrect installation positions for cylindrical container

7.4.3 The best places for measuring part installation are cavities and hollow

spaces in the vehicle trunk bottom. Distance between the bottom, trunk walls

and measuring part must be no less than 5 mm (see fig. 7.2). To achieve this,

rubber spacers may be used. Spacers must be positioned in a way that container

remains in horizontal position.

Fig. 7.2 – Measuring part position in the vehicle trunk hollow space

Another solution for installation can be cutting Ø 40 – 50 mm hole in the trunk

bottom, where the measuring part can be placed. Hole can be hermetically

sealed afterwards with a slab of rubber sheet or with matching blanking plug

(user-supplied).

Page 10: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

10

!

There must be no division walls or other container construction

elements (float gauge, nozzles, etc.) inside, under the measuring

part installation place. Measuring part installation on welded

seams or other surface irregularities is forbidden.

Measuring part working surface should be parallel to fuel surface, in other

words – horizontally.

Fig .7.2 – Potential installation place of measuring part on a toroidal container

7.4.4 Considering information above, chose two, three potential installation

places of measuring part, clean them from dirt and rust, degrease and mark

them.

Page 11: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

11

8 SENSOR ELECTRICAL CONNECTION

8.1 Sensor electrical connection involves connecting cable wires of the measuring part

and transducer, connecting power supply cables to vehicle electrical system and, if

needed, connecting RS-232/RS-485 interface cables to GPS tracking device

(according to color markings, demonstrated on fig. 8.1).

Fig. 8.1 – Sensor electrical connection layout

8.2 Sensor wires electrical connection is performed as follows:

8.2.1 Connect shielded cables from the measuring part to transducer by twisting

them (step by step instruction is in table 8.1).

8.2.2 Connect power supply wires to vehicle electrical system.

Red power supply wire must be connected after the ignition switch for

sensor to operate only when ignition is ON.

0,1 A fuse with holder (in the delivery kit) must be installed in place of sensor

connection to "+" vehicle electrical system (fig. 8.1).

8.3 If it is necessary to remove the sensor, perform wire disconnection in reverse

order.

Page 12: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

12

Table 8.1 – Cable wires connection method

Step 1. Pull heat-shrinkable tubing 6 x 30 mm on

one of cables for connection.

Step 2. Perform (check) cable stripping according to

figure on the right.

Step 3. Twist corresponding (same color)

conductors and shields of two cables to each other.

Step 4. Lay down twisted conductors of red and

white wires alongside the isolation. Contact between

signal conductors and shield conductors is

forbidden.

Step 5. Pull on the heat-shrinkable tubing 2 х 8 mm

on red and white conductors and heat them.

Step 6. Coil twisted shield conductors on the heat-

shrinkable tubing of signal (red) wire. Lay down

cables in line.

Step 7. Additionally, make sure that there is no short circuits between signal

conductors and shield conductors.

Step 8. Move (put on) heat-shrinkable tubing 6 х 30

mm onto the connection place and heat it.

Page 13: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

13

9 FINAL SELECTION OF MEASURING PART MOUNTING PLACE

The following sensor installation actions can be performed both by using

indicator and with personal computer or laptop (hereinafter – PC) with preinstalled

"uS_Install" program (see Appendix B). The latter variant is recommended for

installation at autogas vehicle service stations.

Prior to sensor installation with nondefault settings, make sure

that container height settings in sensor are correct. Container

height value in sensor shouldn’t be lower than the actual

container height. Container height settings in sensor can be

changed in menu n6 (Appendix A) or by using "uS_Install"

program (Appendix B). Container height value is 99 cm by the

default.

Required actions according to first variant (with indicator) are described

below.

To determine final place of measuring part installation it is necessary to select

one of previously marked places according to maximum echo signal power, which is

controlled by indicator.

To do this:

9.2 Lubricate (lubricant in table 7.1) the measuring part clamp surface, which is

constrained by a gasket.

Lubricant is purposed to create an acoustic contact between the measuring part

and container.

9.3 Apply the voltage to sensor.

9.4 Enter the transducer service mode (see appendix A) and select section n1 of

service menu.

9.5 Press measuring part to previously marked places one by one and select the most

suitable installation place according to the maximum values on indicator. Slightly vary

the measuring part position to achieve the maximum signal value.

!

Make sure there is enough lubricant on the measuring

part before each pressing (measuring part won’t work

without lubricant)!

Foreign objects or sand grains must not enter the region

of acoustic contact!

!

Page 14: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

14

9.6 The best place for measuring part installation is the place with the highest signal

value.

9.7 Turn the sensor power supply OFF.

10 SENSOR INSTALLATION AND SETTING

10.1 Select installation variant. Depending on gas container type, several installation

variants are used (fig. 10.1):

in case of cylindrical container, cable with traction device wraps container in the

selected installation place;

in case of toroidal container, cable with traction device can contact container

from one side and pass through container construction elements from the other

side.

10.2 Installation is performed as follows:

10.2.1 Attach the vibration isolator in place of measuring part installation. Clean

the container surface from dirt, rust and degrease it beforehand. Remove a

protection cover from the isolator and attach it to the container, then press it

with the rubber roller.

10.2.2 Extend cable through the measuring part clamp cover.

a b

Fig.10.1 – Measuring part installation variants (a –toroidal container, b – cylindrical container)

Page 15: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

15

10.2.3 Drill a hole Ø 6,5 mm if necessary (in case of measuring part installation

on the toroidal container), to allow cable passing through container mounting

hardware. Insert bushing from the delivery kit into the hole and clamp it with U-

washer. Pass the cable through bushing as demonstrated on fig. 10.2:

Fig. 10.2 – Cable passes through the container mounting hardware

10.2.4 Pass cable ends through holes in half bushings of traction device.

Unscrew the traction device screw to the maximum possible length. Insert cable

into clamps and slightly screw clamp nuts.

Fig. 8.3 – Traction device

10.2.5 Holding the whole construction, pull cable ends to the extent, that the

distance between clamp cover and container surface was approximately 20 mm.

Screw up tightly one of the clamps.

10.2.6 Fill the measuring part cavity (restricted by gasket) with lubricant from

Table. 7.1:

Fig. 10.3 – Filling the measuring part cavity with lubricant

ø6,5

Page 16: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

16

There must be no air bubbles or foreign particles, such as dust

or sand inside the lubricant.

10.2.7 Insert the measuring part inside the clamp cover and press it to the

container surface in the selected place (it is allowed to press measuring part with

lubricant only once).

While pressing measuring part to the container, pull cable end through

loosened clamp and taunt the cable. Screw tight the second cable clamp.

Tighten the cable under container by spinning the traction device screw. While

tightening the cable, lubricant surplus will squeeze from under the gasket.

Gasket is purposed to seal hermetically the operating region. Cable should be

tightened until the surplus lubricant stops squeezing through the gasket, which

indicates that measuring part is fastened tightly.

Paste sensor vibration isolator from the delivery kit (fig. 5.2) around the

measuring part and clamp cover.

10.2.8 If measuring part installation is performed outside vehicle body, it is

necessary to seal hermetically the outer diameter of measuring part and

container contact zone with an automotive sealant (indicated in table 7.1).

Before sealing, it is necessary to remove the lubricant surplus and degrease the

surface.

10.2.9 Energize the sensor. Make sure that the signal level had not decreased

or decreased slightly by using service menu (see Appendix A). Otherwise, it is

necessary to repeat place selection and sensor installation, starting from section

9.

10.2.10 Perform transducer automatic parameters setup (see section 11.1) and

confirm its successful completion by using service menu.

Otherwise, it is necessary to repeat place selection and sensor installation,

starting from section 9 (or consult the technical support).

10.2.11 Turn OFF sensor power supply and perform electrical disconnection

according to section 8.

Upon successful measuring part installation, disconnect sensor

from power supply!

!

!

Page 17: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

17

10.3 Install transducer in a convenient place for driver. For example, on the

vehicle dashboard, as demonstrated on fig. 10.4, or on the suitable horizontal

surface by using mounting holder from the delivery kit or with tilting holder

which can be ordered optionally (see table 5.3 and fig. 10.5).

Fig. 10.4 –Usual placement for transducer with indicator

Fig. 10.5 – Transducer with indicator mounting options

10.4 Lay cable from the measuring part to the transducer through service openings of a

vehicle, attach it with zip ties to the stationary parts every 50-60 cm.

Transducer with

indicator

Page 18: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

18

If cable is laid outside the vehicle interior, this section should be fitted with

split corrugated tube to protect cable from mechanical damage. In case of damaging

wire ends, isolation or conductors, while laying shielded cable, damaged section must

be removed and a new connection established according to section 8.2.

10.5 Shielded cable can be reduced in length if the following connection is performed

according to section 8.2.

10.6 Perform sensor electrical connection according to fig. 8.1.

10.7 Energize the sensor by turning an ignition key and check its operational status

(see Appendix A).

Page 19: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

19

11 SENSOR PARAMETERS SETTING

Sensor setting consists of several steps:

- Transducer parameters setting;

- Fuel type selection;

- Container type selection;

- Container calibration;

- Container height setting.

11.1. Transducer parameters setting.

Container must be filled not less than 2/3 of its volume for automatic transducer

parameters setting.

Select n2 entry in the service menu. Results storage menu will appear on

indicator after parameter setting. It is necessary to select “YE” to save the automatic

setting results or “no” to cancel.

Error code will be demonstrated on the display if error occurred. Error E1

indicates that there is not enough fuel to perform automatic parameter setting. If E2-E5

errors occur, it is necessary to repeat setting procedure several times. In case of

permanent error, consult the service center.

11.2. Fuel type selection

Fuel type selection is performed in n3 entry of the menu. It is necessary to select

fuel type according to table (see Appendix A). If user-defined fuel type is selected,

setting can be performed by using end-user software only (see Appendix B).

11.3. Container type selection

User-defined fuel container selection is performed in n4 entry of the menu. It is

necessary to select container type according to table (see Appendix A).

11.4. User-defined container calibration

When selecting user-defined container, it is necessary to calibrate it. User-

defined container calibration is performed in n5 entry of the menu.

Container must be drained of fuel before calibration start.

Select a calibration unit in t1 entry of the menu, then select t2. Total fuel

amount will be demonstrated on the display (0 liters, since the container is empty).

Press Button 1 30 - 40 seconds after fuel is filled into container to record the

fuel unit. Doing this, indicator readings will increase by the unit value.

Page 20: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

20

If after shutdown valve activation the last filled unit is smaller than the required,

it is necessary to select new unit in t1 menu entry and continue calibration in t2 entry.

If there is an error, indicator will enter a flickering mode. In that case, it is

necessary to wait 1 minute and, if flickering continues, add unit by pressing Button 1,

but this last unit will not be added to calibration table.

Calibration results saving menu will appear on the indicator after closing t3

entry.

11.5. Container height setting

Container height setting is performed in n6 entry of the menu. It is necessary to

enter previously measured container height in range of 10-99 cm.

Page 21: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

21

12 SENSOR SETTING AND ADJUSTMENT WITH "uS_Install" PROGRAM

It is possible to use PC with installed "uS_Install" program (delivered

optionally) for sensor setting apart from using indicator. This setting variant is

recommended to use for installation at autogas vehicle service stations, if using sensor

for fuels and liquids different from LPG, diesel or gasoline (e.g. water) and also for

more convenient sensor installation.

"uS_Install" program is used as following:

12.1 Prepare equipment, instruments and consumables according to tables 7.1 and 12.1

Table 12.1

Name q.

Laptop (PC), minimum requirements: Pentium 500 MHz, 64 MB

RAM, MS Windows XP / 7 / 8 / 10, MS Office, at least 20MB of

free hard disk space, "mouse" manipulator and free USB-port.

1 pc.

USB/RS-485 converter (for ULS4 model setting) or USB/RS-232

(for ULS2 model setting) according to the sensor model. It is

recommended to use MOXA UPort 1130 model or MOXA UPort

1110 respectively.

1 pc.

12.2 Connect interface cables to PC and install software according to Appendix B,

where program interface and operation is described.

12.3 Execute all steps from sections 7 – 10, but using PC readings instead of indicator

according to Appendix B.

12.4. Further sensor setting is performed by using "uS_Install" program.

Setting consists of following steps:

- Transducer parameters setting;

- Fuel type selection;

- Container type selection;

- Container calibration (only for user-defined container);

- Container height setting.

12.4.1 Transducer parameters setting

Container must be filled not less than 2/3 of its volume for automatic

transducer parameters setting.

Find «Autotuning» field in «Oscilloscope» property page and press “Step

2” button:

Page 22: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

22

Fig. 12.1

Installation progress will be demonstrated on the screen. Upon setting

completion, successful Autotuning finishing message or error message will

appear on the screen. Error E1 indicates that there is not enough fuel to perform

automatic parameters setting. If E2-E5 errors occur, it is necessary to repeat

procedure in manual mode according to Appendix G.

12.4.2. Fuel type selection

Fuel type selection is performed in “Fuel” field at «Oscilloscope»

property page. It is necessary to select fuel type according to table (see

Appendix B). If user-defined fuel type is selected, it is necessary to set

following parameters:

“Speed of sound” – sound speed in fuel at a temperature 25 °C, m/sec.;

“Temperature coefficient” – change of sound speed if the temperature

fluctuates by 1 °C, m/sec./ °C.

Fig. 12.2

12.4.3. Container type selection

Selection of user-defined or pre-defined fuel container is performed in

“Container type” field at «Calibration» property page. It is necessary to select

container type according to table (see Appendix B).

12.4.4. User-defined container calibration

When selecting user-defined container, it is necessary to calibrate it. User-

defined container calibration is performed by pressing “Table” button on

“Calibration” property page. Calibration procedure is described in Appendix B.

12.4.5. Container height setting

Container height setting is performed in “Container height” field on

“Calibration” property page.

12. 5 Disconnect sensor from power supply and PC, perform electrical connection

according to Section 8.

Page 23: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

23

13 TRANSPORTATION AND STORAGE

Transportation of the sensor in avenue packing of the manufacturer is allowed

by all types of covered land and sea transport (in railway cars, containers, closed-top

cars, holds, etc.). Transportation in the pressurized compartments of planes is allowed.

When transporting products in an original packaging by uncovered transport,

they must be protected from dust, dirt and influence of an atmospheric precipitation.

During transportation and storage, requirements of the markings, indicated on

avenue packing must be applied.

Page 24: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

24

APPENDDIX A

SENSOR OPERATION MODES

Fig. А.1 – n1 operation mode as demonstrated on the display

(Button 1- changes operation modes, Button 2 – shifts the menu entries)

Sensor operation modes:

Basic operation mode

When using basic operation mode, indicator demonstrates current fuel

volume in liters or fuel level in centimeters, depending on fuel container

selection.

Refueling/drain mode

When using refueling/drain mode, indicator demonstrates fuel level change

compared to reference value. In that case, indicator operates in flickering

mode.

To switch between basic operation mode and refueling/drain mode, press

Button 1. To set the reference fuel value, press Button 2.

Service menu mode

To enter service menu mode, press and hold both Buttons simultaneously

during ~ 5 seconds.

To switch menu entries, press Button 2, to enter – Button 1.

Кнопка 1

Кнопка 2Button 2

Button 1

Page 25: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

25

n1

Automatic

setting

step 1

n2

Automatic

setting

step 2

n3

Fuel

type

n4 Contai-

ner ID

n5 Cali-

bration

n6 Container

height

Fig. А.2 – Service menu

3.1. n1 entry of service menu. Automatic setting, step 1.

This menu entry is used to determine the most suitable location for measuring

part installation. Indicator demonstrates signal level of the measuring part (see

table below).

Signal level Signal level evaluation

None There is no signal or insufficient level, it is necessary to find

another location for measuring part installation.

| Insufficient signal level, it is necessary to find another

location for measuring part installation.

|| The minimal sufficient signal level. It is recommended to

find more suitable location for measuring part installation.

||| Sufficient signal level, suitable location for measuring part

installation.

|||| Good signal level, suitable location for measuring part

installation.

||||| Good signal level, suitable location for measuring part

installation.

E1 Not enough fuel in container for measuring part installation.

E2 Place is not suitable for measuring part installation.

3.2. n2 menu entry. Automatic setting, step 2.

This menu entry is used to perform transducer automatic parameters setting.

Indicator demonstrates setting process.

Results saving menu will be displayed on the indicator in case of successful

automatic setting completion. In case of failure – error code.

Page 26: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

26

YE

Save and exit

no

Exit without

saving

Fig. А.3 – Saving menu

Error codes:

Error code Error description

E1 Not enough fuel in container for measuring part installation

E2

Place is not suitable for measuring part installation, consult

the service center or technical support.

E3

E4

E5

3.3. n3 menu entry. Fuel Type

This menu entry is used to determine fuel type according to table:

№ Fuel type

0 User-defined type. Sound speed and temperature coefficient

values are specified by user software.

1 LPG

2 Gasoline

3 Diesel

3.4. n4 menu entry. Container ID.

This menu entry is used to determine user fuel container.

№ Container ID

0 Container is not selected. When using basic operation mode,

indicator demonstrates current fuel level in centimeters.

1 User-defined fuel container. Calibration is performed buy

user.

Page 27: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

27

3.5. n5 menu entry. Calibration.

This menu entry is used for user-defined fuel container calibration. This

menu entry is available only if user-defined container (ID 1) was selected in

previous menu entry.

t1

Unit, liters

t2

Add unit

t3

Exit

Fig. А.4 – n5 menu

Press Button 2 for 30 - 40 seconds after fuel is filled into container to record the

fuel unit. Doing this, indicator readings will increase by the unit value. If the last filled

unit is smaller than the required after shutdown valve activation, it is necessary to

select new unit in t1 menu entry and continue calibration in t2 entry.

If there is an error, indicator will enter a flickering mode. In that case, it is

necessary to wait 1 minute and, if flickering continues, add unit by pressing Button 1,

but this last unit will not be added to calibration table. Calibration results saving menu

will appear (fig. A3) on the indicator after closing t3 entry.

3.6. n6 menu entry. Container height.

This menu entry is used for fuel container height setting. Height is set in

centimeters, possible height range is 10 – 99 centimeters.

Page 28: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

28

APPENDIX B

"uS_Install" APPLICATION PROGRAM

«uS Install» application program (hereinafter – Program) is purposed for fuel

level sensor Sigma ULSx-20 setting.

Program is included in user software package on CD, which is present in

delivery kit. To install program on PC it should be copied into required directory file.

Moreover, PC should be equipped with RS-232 or RS-485 port.

Use USB/Serial adapters MOXA UPort 1110 for RS-232 and MOXA UPort

1130 for RS-485 interface if there are no such ports on PC.

Before launching the program it is necessary to perform sensor electrical

connection in accordance with sensor to PC connection scheme in Appendix C.

Software has an adaptive user interface. Depending on model or/and firmware

version, software interface can change (only options for the current model and

firmware version are displayed).

After starting the program, it is necessary to select the port number, baud rate

and device address in the “Port settings” field (fig. B 1). Default sensor setting are

19200 bps for baud rate and device address – 1.

Fig. B.1 - «Program» property page

Press “Open” button to start working. If baud rate parameters and device

address are unknown, “Device search” button can be used. When “Device search”

button is pressed, software sends an enquiry with a broadcast address into the port.

Page 29: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

29

ATTENTION! “Device search” option is not recommended if several sensors

are connected to the network.

Port status is indicated in the lower part of the window.

- Port closed – means that COM port is closed; press “Open” or “Device

search” button to start working with device;

- Port open – means that COM port is open and operates properly;

- Open error – means that COM port is opening with error; also, error

message will be displayed (fig. B 2). In this case, it is necessary to check if

port is blocked with other application programs and diagnose port operability

on the software and hardware levels.

Fig. B.2 - Port opening error

If program settings and sensor connection are correct, “Oscilloscope” property

page (fig. B.3) will appear in working window. Parameters are read automatically

when property page is selected.

Page 30: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

30

Fig. B.3 - «Oscilloscope» property page

Fuel type selection, measuring part installation place and transducer automatic

parameters setting are performed on this property page.

Signal transformation error code is demonstrated in “Autotuning” field. See the

error code legend in Table B.1:

Table B.1 Code Description Recommendation

0 Correct signal

transformation Suitable place for measuring part installation

1 No return signal Check measuring part acoustic contact. Try

another place for measuring part installation

2,3,5,11 Insufficient return signal

range

Check measuring part acoustic contact. Try

another place for measuring part installation

4,6-10,16-19 Distorted return signal Try another place for measuring part

installation

12,13,15 Incorrect measuring

result Wait several seconds until error resets

Page 31: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

31

20

Measured fuel level

exceeds preset container

height

Check container height settings.

Check the vibration isolator and its proper

installation at the measuring part region.

Level icon demonstrates fuel level in millimeters, T, °C icon – measuring part

temperature in degrees Celsius.

To enter mode for measuring part installation place, press “Step 1” button in

“Autotuning” field. To initiate measuring part automatic parameters setting, press

“Step 2” button.

Fuel type selection and user-defined fuel parameters setting are performed in

“Fuel” field. To save fuel and fuel parameters, press “Write” button.

“Calibration” property page is purposed for container type selection, user-

defined container calibration, calibration tables uploading and container height setting

(fig. B.4).

Fig. B.4 - «Calibration» property page

Container type selection is performed in “Tank ID” icon;

If container type 0 is selected (container not selected), container calibration

table is unavailable.

Manual calibration is available if container type 1 is selected.

Page 32: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

32

Container calibration table is available for reading only if container types 2-99

(pre-defined types) are selected.

Container height setting is performed in “Tank height” icon.

“Data output in liters” parameter sets scale division of low bit data, which is

transferred by the sensor. If container type 0 is selected, data outputs in millimeters.

Press “Set” button to save container type and calibration tables.

To export calibration tables into Excel file format (*.xls, *.xlsx), press “Export

of tables”, to import – press “Import of tables” in “Import/Export of tables” field.

!

Calibration tables’ import and export can be

performed only with the pre-defined containers. User-

defined calibration table import/export can be

performed in “Calibration table” work window.

To open calibration table work window, press “Calibration table” button.

Calibration table work window will appear after pressing (fig. B.5).

Fig. B.5 - «Calibration table» work window

(Entered records will be confirmed after pressing “OK” button)

Page 33: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

33

Manual calibration:

To add calibration table manually, press button or by using right-click

menu. Calibration table record adding window will appear on the screen (fig. B.6). To

delete record from the calibration table, press button or by using right-click menu.

Fig. B.6 - «Add record» window

Automatic calibration:

To add record into calibration table in automatic mode, press “Add” button.

Portion of fuel to add is defined by “Portion” parameter. When performing calibration

by adding, “Portion” parameter must have positive value, when performing calibration

by draining – negative value.

“Sensitivity” parameter defines minimal change in code value when fuel

portion is added. If value is lower than defined, record will not be added in calibration

table. The following message will be displayed:

Fig. B.7

To perform calibration table import of Microsoft Excel (*.xls, *.xlsx) format

files, press button, to perform export - button or by using right-click menu.

Calibration table generation for cylindrical container described in Appendix E.

Page 34: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

34

“Settings” property page is purposed for manufacturing data viewing and data

parameters setting, which are displayed by the sensor (fig. B.8). Manufacturing data

and displayed data parameters reading are performed automatically when opening

property page. To write parameters, press “Set” button.

Fig. B.8 - «Settings» property page

Manufacturing data:

Date – sensor production date;

S/N – sensor serial number;

Model – sensor model;

SW version – firmware version;

HW revision – sensor board revision number.

Output data parameters:

Data resolution – data resolution for reading from sensor;

Response to the 255 address – Sensor response on broadcast query:

With 255 address – Sensor answers with a broadcast address;

With own address – Sensor answers with the defined address.

Address – Sensor network address;

Baud rate – Baud rate speed

«US20_AppLoader» program is purposed for firmware updating,

configuration data saving and restoring (see Appendix D).

Page 35: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

35

APPENDIX C

LAYOUTS FOR SENSOR CONNECTION TO PC

Fig. C.1 ULS2 model connection to PC layout

Fig. C.2 ULS4 model connection to PC layout

Page 36: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

36

APPENDIX D

FIRMWARE UPDAITING, CONFIGURATION DATA SAVING AND

RESTORING

D.1 To update firmware, save and restore configuration data, «US20_AppLoader»

software is used. For this purpose, it is necessary to perform the following steps:

D.1.1 Turn OFF transducer power supply. Connect sensor transducer to RS-

232 (RS-485) port of PC. Launch «US20_AppLoader» program (fig. D.1):

Fig. D.1

D.1.2 Select COM port. During network connection of two or more sensors -

specify device network address in “485 N” field.

D.1.3 Press button in «US20_AppLoader» program.

D.1.4 Power the sensor. After ~1 second technological parameters will be

acquired from sensor:

,

Page 37: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

37

After that, button becomes active again.

D.1.5 Then, select the firmware file by pressing button (fig. D.2):

Fig. D.2

D.1.6 Upload firmware into device by pressing

button.

Uploading process is indicated in percent:

.

Message will appear after uploading.

D.2 Configuration data saving and restoring.

D.2.1 Press button to save configuration data into file.

D.2.2 Select folder for saving and file name in appeared window, then press

button (fig. D.3):

Page 38: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

38

Fig. D.3

D.2.3 Calibration data saving is performed similar to configuration saving, but

instead of “Save configuration” button it is necessary to press “Save calibration”.

D.2.4 Configuration (calibration) data restoring is performed similar to firmware

uploading, but instead of firmware file it is necessary to select configuration

(calibration) file.

D.3 Firmware activation.

D.3.1 To activate new firmware, press

button or turn OFF and resupply indicator power.

D.3.2 To exit application loader program, press button or close program

work window.

D.4 Note.

D.4.1 «US20_AppLoader» works with COM1 … COM9 communication ports.

D.4.2 Availability and number of ports can be checked here:

«My computer\Properties\Device Manager\Ports (COM and LPT)».

D.4.3 To assign the necessary number to the COM port among available, go to:

«My computer\Properties\Device Manager\Ports (COM and LPT)\

Communications port (COMx)\Utilities\Port parameters\Advanced\COMport

number».

Page 39: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

39

APPENDIX E

DATA EXCHANGE PROTOCOL

E.1 General

This section describes data exchange protocol of the ultrasonic fuel level sensor

SIGMA with external devices.

E.2 Physical level

Exchange with external device is carried out by RS-232 or RS-485 interfaces.

Baud rate can be chosen from following values: 2400, 4800, 9600, 19200 (by

the default), 38400, 57600, 115200 bps;

Data width – 8 bps;

Evenness – disabled;

Stopping bit – 1;

Flow control – disabled.

E.3 Logical level

Data exchange is carried out by data packets according to “Request/Response”

principle. External device is a Master (exchange initiator).

Network address is assigned to each sensor. Range of valid addresses is 0x00 –

0xFE, 0xFE address is used for broadcast requests, to which sensor replies

independently of established address. Default address – 0x01.

Following data packets are used in the protocol:

- “Request” data packet – contains command and transferred by the external device

- “Response” data packet – contains command response and transferred by the

identifier.

"Request" packet format

Prefix

Reader

network

address

Command

code

Parameters

CRC

0x31 0х00..0xFF

See

command

description

see. E4 Calculated according to

Application note 27 from Dallas

Page 40: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

40

"Response" packet format

Prefix

Reader

network

address

Command

code

Device

response CRC

0x3E 0х00..0xFЕ

See

command

description

See command

description

Calculated according to

Application note 27 from Dallas

Multibyte parameters are transferred in order of precedence from lowest byte to

high byte ("Little endian").

Following intervals are used in the protocol:

- Timeout between bytes – the maximum interval between transferred bytes inside the

data packet.

- Response transmission delay – minimal interval between the end of “Request” data

packet receipt and start of “Response” data packet transfer.

- Response timeout – the maximum interval between “Request” data packet receipt

and start of “Response” data packet transfer.

- Delay before the transmission start of “Request” data packet after “Response” data

packet receipt (or unidentified data packet) – minimal interval between end of

“Response” data packet receipt (or unidentified data packet) and start of “Request”

data packet transmission.

The parameters of above-mentioned values listed in table 3.

Sequence of bytes, which don’t have data packet format or which exceed the

maximum allowed interval between bytes or packet with data field that exceeds 150

bytes or data packet with incorrect CRC is considered unidentified and is ignored by

the sensor.

Time intervals Parameter Value for different baud rates, ms

2400 4800 9600 19200 38400 57600 115200

Timeout between bytes 15 8 4 2

Response transmission delay 15 8 4 2

Response timeout 100

Delay before the transmission

start of “Request” data packet

after “Response” data packet

receipt

15 8 4 2

Page 41: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

41

E.4 Commands description

E.4.1 Single data readout (command 06h)

Command is used for current data reading: user value of fuel level (10 or 12

bits), technological value of fuel level (16 bits) and temperature (8 bits).

Command format

Offset,

byte Field size, byte Value Description

0 1 31h Prefix

+1 1 00h…FFh Recipient network address

+2 1 06h Command code

+3 1 00h…FFh CRC8

Response format

Offset,

byte Field size, byte Value Description

0 1 3Eh Prefix

+1 1 00h…FFh Sender network address

+2 1 06h Command code

+3 1 -128…127 Temperature, °C

+4 2 0000h…03FFh

or 0000h…0FFFh

User value of fuel level

+6 2 0000h…FFFFh Technological value of fuel

level

+8 1 00h…FFh CRC8

E 4.2 Technological parameters reading (command 41h)

This command is used to read the technological parameters of the sensor: issue

date, serial number, model code, firmware version, data output mode.

Command format

Offset,

byte Field size, byte Value Description

0 1 31h Prefix

+1 1 00h…FFh Recipient network address

+2 1 41h Command code

+3 1 00h…FFh CRC8

Page 42: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

42

Response format

Offset,

byte Field size, byte Value Description

0 1 3Eh Prefix

+1 1 00h…FFh Sender network address

+2 1 41h Command code

+3 1 00h…FFh Year of issue:

00h corresponds to 2000

year

+4 1 00h…0Bh Month of issue:

00h – January, 0Bh -

December

+5 1 01h…1Fh Day of issue: 1 … 31

+6 3 000001h…FFFFFFh Serial number

(1 … 16777215)

+9 1 01h…02h Model code

(see the following table)

+10 1 01h…FFh Firmware version

+11 6 - Reserved

+17 1 00h…FFh Network address

+18 2 - Reserved

+20 1 00h…FFh Data output mode

(see command 55h)

+21 1 00h…FFh CRC8

Sensor model code

Model code (HEX) Model name

01 ULS4-уу

02 ULS2-уу

E.4.3 Serial number and date of issue reading (command 42h).

Command is used for reading the following FLS parameters: date of issue, serial

number, model code and firmware version.

Command format

Offset,

byte Field size, byte Value Description

0 1 31h Prefix

+1 1 00h…FFh Recipient network address

+2 1 42h Command code

+3 1 00h…FFh CRC8

Page 43: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

43

Response format

Offset,

byte Field size, byte Value Description

0 1 3Eh Prefix

+1 1 00h…FFh Sender network address

+2 1 42h Command code

+3 1 00h…FFh Year of issue:

00h corresponds to 2000 year

+4 1 00h…0Bh Month of issue:

00h – January, 0Bh -

December

+5 1 01h…1Fh Day of issue: 1 … 31

+6 3 000001h…FFFFFFh Serial number

(1 … 16777215)

+9 1 01h…02h Model code

+10 1 01h…FFh Firmware version

+11 1 00h…FFh CRC8

E.4.4 Setting the data output mode (command 55h).

This command is intended to set the following parameters: output data width

(10 or 12 bit), baud rate through serial port (2400...115200 bps) and response

parameters on broadcast request.

Command format

Offset,

byte Field size, byte Value Description

0 1 31h Prefix

+1 1 00h…FFh Recipient network address

+2 1 55h Command code

+3 1 00h…FFh See the table of transcripts

below

+4 1 00h…FFh CRC8

Response format

Offset,

byte Field size, byte Value Description

0 1 3Eh Prefix

+1 1 00h…FFh Sender network address

+2 1 55h Command code

+3 1 00h Return code

+4 1 00h…FFh CRC8

Page 44: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

44

Code identification of data output mode

Bits Use Description Default

value

7 Output data width 0: 10 bit

1: 12 bit 1

6 Reserved - 0

5 Response to the

broadcast request

0: respond with own

address

1: Respond with 255

address

0

4,3,2 Baud rate through the

serial port, bps

000 – Rate is constant;

001 – 2400;

010 – 4800;

011 – 9600;

100 – 19200

(default setting);

101 – 38400;

110 – 57600;

111 – 115200

100 (19200 bps)

1 Reserved - 0

0 Reserved - 0

E.4.5 Setting the network address (command 56h)

This command is intended to set sensor network address for simultaneous

operation of several sensors.

Command format

Offset,

byte Field size, byte Value Description

0 1 31h Prefix

+1 1 00h…FFh Recipient network address

+2 1 56h Command code

+3 1 00h…FFh Sensor new network address

+4 1 00h…FFh CRC8

Response format

Offset,

byte Field size, byte Value Description

0 1 3Eh Prefix

+1 1 00h…FFh Sender network address

+2 1 56h Command code

+3 1 00h Return code

+4 1 00h…FFh CRC8

Page 45: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

45

APPENDIX F

CALIBRATION TABLE CALCULATION

Calibration procedure is applied to transform current sensor readings into fuel

volume values if using external device.

Container calibration is performed by using “US20 Calibration table

calculation for vehicle autogas containers.xls” program, which opens in MS Excel

(Macros feature must be allowed to work with file):

Fig. F.1

Page 46: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

46

It is necessary to perform below mentioned measurements for cylindrical autogas

container (see fig. F.2):

Fig. F.2

where L1 – Container length, mm;

L2 – Container girth (perimeter), mm;

L3 – Length of bulge part semi-ellipse, mm;

T – Container wall thickness, mm.

This data is entered in corresponding boxes I4-I7.

The necessary number of records in calibration table is entered in N field (I9

box). Recommended number of records is no less than10 records. More records means

higher accuracy. Maximum records number – 50.

Calibration table calculation is performed after pressing “Calculate” button.

Result is stored in A-B columns:

Column A – Fuel level, l;

Column B – Fuel level height, mm;

Т

L1

L3

L2

Page 47: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

47

APPENDIX G

QUICK GUIDE FOR “US20 Install Service” PROGRAM

Sigma ULS4-20 setting is performed using US20_Install_Sevice v.2.0.0.x

program or later version.

After launching the program, select required port, baud rate and device address

in “Port settings” field.

Default sensor setting are 19200 bps for baud rate and device address – 1.

Press “Open” button to start working.

If baud rate parameters and device address are unknown, “Device search” button can

be used. When “Device search” button is pressed, software sends an enquiry with a

broadcast address into the port.

Mounting place preselection

Perform the mounting place preselection on Oscilloscope/Autotuning property

page.

To start search it is necessary to press Step 1 button and to monitor signal level

according to Signal level scale. The best place for installation is the place with

maximum Signal level value. When search is concluded, press Step 1 button again.

Page 48: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

48

.

Sensor setting

Further sensor setting is performed after vibration isolation fitting and final

measuring part mounting.

To determine operation signal frequency it is necessary to build sensor-tank

AFC system. Before building AFC, set Frequency– 2000 kHz and Pulse – 20 periods

on Oscilloscope/Pulse property page. Atten parameter set as “On”; adjust

amplification factor so that first echoed signal amplitude will be in 5000-20000 range.

After that, select WideBand on Filtr property page.

Page 49: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

49

AFC generation is performed on AFC property page. It is necessary to determine first

echoed signal range and enter initial echoed signal value in Pulse begin field; enter

echoed signal width value in Pulse width field. Enter echoed signal width and initial

value with margin of 100-300 points from the signal threshold.

To build AFC, press AFC button, selecting AFC displaying on the oscillogram

beforehand.

Page 50: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

50

AFC build completion is signaled by «AFC Plot complete» message.

If diagram exceeds 20000 mark, it is necessary to lessen amplification factor

(each Ku step alters amplification factor approximately by 1,5) and generate another

AFC.

Chose frequency with the maximum signal amplitude according to AFC

diagram.

If there are several AFC “peaks” with similar amplitude (in 30% range), specific

peak is selected according to minimal after-ring (see next step).

If there is the same after-ring level on different “peaks”, frequency closest to

2000 kHz should be selected.

Page 51: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

51

Enter selected frequency in Freq field on Pulse property page. Also, switch

oscillogram into Oscill mode.

To minimize after-ring, select “Source” mode, set Ku parameter to “24” and

Atten in “Off”.

Page 52: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

52

It is necessary to achieve after-ring minimization by changing Pulse parameter in

range of 10-20 periods.

Dead zone adjustment is performed on Integrator property page. It is necessary

to set Atten parameter in “On” position before dead zone adjustment.

DeadZone parameter is defined by after-ring width on X-direction.

Minimum permissible value of DeadZone parameter is 400 points. Acceptable

value is 500-700 points.

If after-ring exceeds 700 points, lower Ku parameter (but no less than 18 points)

until after-ring value becomes 500-700 points.

If after-ring parameter exceeds 700 points, when Ku parameter is 18, such value

is entered in DeadZone parameter. To record DeadZone value, press Set button.

Page 53: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

53

After that, it is necessary to limit maximum amplification factor MaxKu.

To do that, enter current Ku or Unlim (if current Ku equal to 24) value in

MaxKu field

Then, perform filter adjustment on Filtr property page. Filtr parameter value is

selected as close as possible to Freq parameter value on Pulse property page.

Then, it is necessary to set Ku parameter in Auto and visually estimate

oscillogram in Envelope mode.

Oscillogram should look like the figure (periodical sequence of fading echoed

signals).

Page 54: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

54

Go to Calibration property page.

Calibration is performed separately according to installation manual.

Tank ID - “0”, if calibration table wasn’t uploaded into Sigma ULSx sensor.

Tank ID - “1” if calibration table was uploaded into Sigma ULSx sensor.

Tank height is measured by measuring tape.

ATTENTION! Do not forget to press “Set” button!

Page 55: Ultrasonic level sensor SIGMA · 2017-07-06 · 7.4.2 To achieve the optimal sensor operation, measuring part must be installed in the lower point underneath the container, right

55

Go to Settings property page.

It is necessary to select Fuel type; adjust other settings if required.

Press Write button.