u to telecom design and construction specifications

Upload: zelite

Post on 07-Jul-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/19/2019 u to Telecom Design and Construction Specifications

    1/34

    University Technology OfficeTelecommunication Design Standards

    And Construction Specifications

    Version 1.4February 13, 2014

  • 8/19/2019 u to Telecom Design and Construction Specifications

    2/34

    ii

    Table of Contents

    1 GENERAL !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!! .62 CODES AND STANDARD REFERENCES .............................................................. 73 REFERENCE DOCUMENTATION .......................................................................... 7

    3.1 FCC Regulations ......................................................................................... 73.1.1 FCC Documentation ........................................................................ 73.2 NFPA Codes ................................................................................................ 7

    3.2.1 NFPA Documentation ...................................................................... 83.3 ANSI/TIA/EIA Telecommunication Building Wiring Standards .................... 8

    3.3.1 ANSI Documentation ....................................................................... 83.4 BICSI Methodologies ................................................................................... 83.5 ANSI/NECA/BICSI 568-2001 ....................................................................... 8

    3.5.1 BICSI Documentation ...................................................................... 84 DEFINITION OF TERMS, ACRONYMS AND ABBREVIATIONS ............................ 9

    4.1 Equipment Room (ER) ................................................................................. 9

    4.2 Entrance Facility (EF) .................................................................................. 94.3 Telecommuncation Room (TR) .................................................................... 94.4 Acronyms ..................................................................................................... 9

    5 DESIGN STANDARDS .......................................................................................... 116 TELECOMMUNICATION ROOMS ......................................................................... 12

    6.1 Telecommunication Room/Building Equipment Rooms ............................. 126.2 General !!!!!!!!!!!!!!!!!!!!!!!!!!!! ..126.3 Location ..................................................................................................... 136.4 Electromagnetic Interference ..................................................................... 136.5 Access !! .. ........................................................................................ ! ..13

    7 DESIGN !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!! ...13

    7.1 Architectural ............................................................................................... 137.2 Size !! ..................................................................................................... 137.3 Walls ! . ..................................................................................................... 137.4 Plywood Backboards ................................................................................. 137.5 Ceiling Height ............................................................................................ 137.6 Treatment .................................................................................................. 147.7 Ceiling.. ...................................................................................................... 147.8 Door ! .. ..................................................................................................... 147.9 Floor Loading ............................................................................................. 147.10 Signage .................................................................................................... 14

    8 ENVIRONMENTAL ................................................................................................ 14

    8.1 Contaminants ............................................................................................. 148.2 Heating, Ventilation and Air Conditioning (HVAC) ..................................... 148.3 Continuous Operation ................................................................................ 148.4 Equipment Placement ................................................................................ 148.5 Standby Operation ..................................................................................... 148.6 Operational Parameters ............................................................................. 148.7 Positive Pressure ....................................................................................... 158.8 Vibration ..................................................................................................... 15

  • 8/19/2019 u to Telecom Design and Construction Specifications

    3/34

    iii

    8.9 Other Mechanical Fixtures ........................................................................ 159 ELECTRICAL ........................................................................................................ 15

    9.1 Lighting ...................................................................................................... 159.2 Power ........................................................................................................ 159.3 General ..................................................................................................... 15

    9.4 Equipment 110V Outlets ........................................................................... 159.5 Equipment 208V Outlets ........................................................................... 169.6 Emergency 110V and 208V Outlets .......................................................... 169.7 Convenience 110V Outlets ....................................................................... 169.8 Location of Power Conditioning Systems (UPS) ....................................... 169.9 Bonding and Grounding ............................................................................ 16

    10 MISCELLANEOUS .............................................................................................. 1910.1 Fire Protection ......................................................................................... 1910.2 Water Infiltration ...................................................................................... 20

    11 CABLE PATHWAYS ............................................................................................ 2011.1 General ................................................................................................... 20

    11.2 Ladder Rack ............................................................................................ 2011.3 Sleeves/Conduits .................................................................................... 2011.4 Horizontal Pathway ................................................................................. 2011.5 Vertical Pathway ..................................................................................... 2011.6 Horizontal Backbone Inter-building Pathway .......................................... 2111.7 Horizontal Backbone Intra-building Pathway .......................................... 2111.8 General Telecommunication Room Design ............................................ 21

    12 EQUIPMENT ROOMS AND SERVICE ENTRANCES ........................................ 2112.1 General ................................................................................................... 21

    13 INTERIOR COMMUNICATION PATHWAYS ...................................................... 2113.1 General ................................................................................................... 2113.2 Cable Tray ............................................................................................... 2113.3 Conduit .................................................................................................... 2213.4 Intra-building Backbone Conduits ........................................................... 2213.5 Outlet/Conduit Location ........................................................................... 2213.6 New Construction Wall Outlet ................................................................. 2213.7 New Construction Floor Outlet ................................................................ 2313.8 Renovations ............................................................................................ 2313.9 Sleeves ................................................................................................... 2313.10 Bonding and Grounding ........................................................................ 23

    14 EXTERIOR COMMUNICATION PATHWAYS ..................................................... 2314.1 General ................................................................................................... 2314.2 Exterior Pathways ................................................................................... 2414.3 General ................................................................................................... 2414.4 Conduit .................................................................................................... 24

    14.4.1 Conduit Depth Requirements ..................................................... 2414.5 Maintenance Vaults ................................................................................. 24

    14.5.1 General ....................................................................................... 2414.5.2 Conduit Entry Points ................................................................... 2514.5.3 Covers ........................................................................................ 25

  • 8/19/2019 u to Telecom Design and Construction Specifications

    4/34

    iv

    14.5.4 Encasement ................................................................................ 2514.5.5 Conduit Orientation ..................................................................... 2514.5.6 Trace Wire and Safety Tape ....................................................... 2514.5.7 Separation from Other Utilities .................................................... 2514.5.8 Innerducts .................................................................................... 25

    14.6 Interior Hardware ..................................................................................... 2514.6.1 Identifying Covers ........................................................................ 2614.6.2 Concrete Strength ....................................................................... 26

    14.7 Handhole ................................................................................................. 2614.7.1 General ........................................................................................ 2614.7.2 Conduit Entry Points .................................................................... 2614.7.3 Covers ......................................................................................... 2614.7.4 Identifying Covers ........................................................................ 27

    15 BACKBONE CABLING ......................................................................................... 2715.1 General .................................................................................................... 27

    16 HORIZONTAL CABLING ..................................................................................... 28

    16.1 General .................................................................................................... 2816.2 Telecommunication Outlet Types, Configurations and Placement .......... 2816.3 SYSTIMAX Components ......................................................................... 28

    16.3.1 Identification ................................................................................ 2816.3.2 Standard Work Area Outlet ......................................................... 2916.3.3 Standard Residence Work Area Outlet ....................................... 3016.3.4 Coax Outlet ................................................................................. 3016.3.5 Wall Phone Outlet ....................................................................... 31

    17 SPECIAL SYSTEM DEVICES .............................................................................. 3117.1 Area Refuge Phone ................................................................................. 3117.2 Blue Light Phones .................................................................................... 3117.3 Elevator Phones ...................................................................................... 3117.4 Wireless Access Point ............................................................................. 31

    18 TYPICAL OUTLET PLACEMENT ........................................................................ 3218.1 Standard Office ........................................................................................ 3218.2 Classrooms (Typical) ............................................................................... 3218.3 Conference Rooms .................................................................................. 3218.4 Lab Areas, Computer Rooms and Other ................................................. 3218.5 Student Living Spaces ............................................................................. 32

    18.5.1 Living Area/Living Room ............................................................. 3218.5.2 Bedroom ...................................................................................... 3218.5.3 Open, Lounge, Common and Other Areas .................................. 3218.5.4 Tables, Desks and Study Carrels ................................................ 32

    19 TESTING, IDENTIFICATION AND ADMINSTRATION ........................................ 3219.1 Testing ..................................................................................................... 32

    20 ASU CABLE ID SCHEME ! ..................................................................................3320.1 Fiber Cable ID Scheme !!!!!!!!!!!!!!!!!!!! ..3320.2 Copper Cable ID Scheme !!!!!!!!!!!!!!!!!!! ..34

    21 AMENDMENTS .................................................................................................... 35

  • 8/19/2019 u to Telecom Design and Construction Specifications

    5/34

    v

    Table of Figures

    1 FLOOR PLAN SYMBOLS LEGEND ......................................................................... 112 TELECOMMUNICATIONS ROOM (TYPICAL) ......................................................... 123 TELECOMMUNICATIONS GROUNDING BUSBARS .............................................. 17

    4 TELECOMMUNICATIONS BONDING BACKBONE ................................................. 195 CABLE TRAY SUPPORT ......................................................................................... 226 EXAMPLE OF A MAINTENANCE JOB .................................................................... 267 EXAMPLE OF A HANDHOLE ................................................................................... 278 FACEPLATE CONFIGURATIONS ........................................................................... 29

  • 8/19/2019 u to Telecom Design and Construction Specifications

    6/34

    6

    1 GENERAL The purpose of the University Technology Office Telecommunication Design Standards andConstruction Specifications (Design Standards) is to describe and specify the minimumbuilding infrastructure required to support the voice, data and other special systems at ASU.

    Architects, engineers and designers should use these Design Standards to incorporate theinformation provided into Construction Documents. This document is based on industrystandards and codes. This document does not replace any national or local standards,regulations or codes, but enhances them. If the standards and practices of the UniversityTechnology Office (UTO) exceed national or local standards, regulations or codes, ASU UTO’spractices shall take precedence.

    The scope of this document includes the design and installation of Telecommunication Rooms(TRs), cabling distribution systems work area outlet locations, cable specifications, testing,documentation and administration. The cabling contractor is responsible for obtaining theCommScope/SYSTIMAX Solutions specifications. This document is intended to serve as aguideline and therefore is subject to change on a project-by-project basis. It is theresponsibility of the Design Team and/or contractor to identify inconsistencies in thespecific project drawings and request clarification from ASU UTO Design designatedpoint of contact.

    In order to achieve and maintain the technology offering throughout the many campus’ andsatellite learning centers ASU UTO has developed strategic partnerships with specificmanufacturers as it relates to the telecommunications infrastructure. The following tableoutlines those partners and their product offering:

    Manufacturer Product TypeCommScope SYSTIMAX Solutions All Copper, Fiber, Lightning Protection

    and Coax ProductsChatsworth/CPI Metal ProductsOberon WAP EnclosuresWiremold/legrand Floor Boxes, Poke Thru’s & Raceway

    SystemsCirca Copper Cable ProtectorsPyramid Industries InnerductSuperior Essex OSP Copper (ANMW) & (ARMM)Fluke Network Test Equipment for Fiber & Copper

    It is further required that the installation contractor is certified in the state of Arizona to installand extend to ASU all performance and product warranties offered by the individualmanufacturer.

    Furthermore, the installation contractor must meet the minimum requirements:

    • BICSI accredited RCDD on staff• SYSTIMAX Solutions D&E Certified Estimator & Project Manager on Staff• 50% of onsite technical staff must be certified as BICSI & SYSTIMAX Installers.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    7/34

    7• Proof of BICSI & SYSTIMAX certifications must be made available upon request.

    2 CODES & STANDARD REF ERENCES The following codes and standards contain provisions that, through reference in this text,constitute provisions of document. At the time of publication the editions indicated were valid.

    All equipment, construction practices, design principles and installations must conform to thelatest version of any or all of the following standards and codes, published by the followingorganizations, where applicable:

    • Federal Communications Commission (FCC)• Institute of Electrical and Electronics Engineers, Inc (IEEE)• National Fire Protection Association (NFPA)• National Electrical Code (NEC)• American National Standards Institute (ANSI)• Telecommunications Industry Association (TIA)• Electronic Industries Alliance (EIA)• Building Industry Consulting Service International (BICSI)•

    National Electrical Contractors Association (NECA)• International Building Code (IBC)

    3 REFERENCE DOCUMENTAT ION All ASU UTO staff, architects, engineers, contractors and vendors involved in the design,installation, and specification of structured cabling systems must have access to the followingreferenced documentation. They will be held accountable to the standards set forth in thisdocument. The standards, codes, and regulations referenced may have corrections, additions,technical service bulletins, and addendums that are not specifically called out in this section. Inall cases, the latest versions are to be referenced regardless of versions stated in thisdocument. Questions, problems or comments concerning this document or the referenced

    document should be directed to the University Technology Office. 3.1 FCC RegulationsFCC Part 68 Regulations for connecting premise cabling and customer provided equipment toregulated networks.

    3.1.1 FCC DocumentationFCC Documentation is available at the following Web site:http://www.fcc.gov/Bureaus/Engineering_Technology/Documents/cfr/1999/47cfr68.pdf

    3.2 NFPA CodesThese NFPA documents are related to telecommunication:

    • NFPA-70 National Electrical Code Chapter 8- Communication Systems• NFPA-71 Central Signaling Systems• NFPA-72 National Fire Alarm Code• NFPA-75 Protection of Electronic and Computer Data Processing Equipment• NFPA-780 Lightning Protection Code• NFPA-101 Life Safety Code

  • 8/19/2019 u to Telecom Design and Construction Specifications

    8/34

    8

    3.2.1 NFPA Documentation NFPA documentation is available from the following:

    National Fire Protection Association1 Batterymarch ParkQuincy, MA 02269-9101Telephone: (617) 770-3000Fax: (617) 770-0700

    3.3 ANSI/TIA/EIA Telecommunication Building Wiring Standards (latest version)There are several documents that make up the ANSI/TIA/EIA Commercial BuildingTelecommunication Cabling Standards. These include:

    • ANSI/TIA/EIA - 568-B Commercial Building Telecommunication Cabling Standard• ANSI/TIA/EIA -569-A Commercial Building Standard for Telecommunication

    Pathway and Spaces• EIA/TIA-606-A Administration Standard for the Telecommunication Infrastructure of

    Commercial Buildings• EIA/TIA-607 Commercial Building Grounding and Bonding requirements for

    Telecommunication• ANSI/NESC 1997 National Electrical Safety Code

    3.3.1 ANSI Documentation ASNI documentation is available from the following:

    Global Engineering Documents15 Inverness Way EastEnglewood, CO 80112-5776(800) 854-7179 ext. 7931

    3.4 BICSI Methodologies

    • BICSI Telecommunication Distribution Methods Manual (TDMM - 11 th edition)• BICSI Telecommunication Cabling Installation Manual (2 nd edition)• BICSI Customer Owned Outside Plant Design Manual (2 nd edition)

    3.5 ANSI/NECA/BICSI 568-2001Installing Commercial Building Telecommunication Cabling

    3.5.1 BICSI DocumentationBICSI documentation is available from the following:

    BICSI 8610 Hidden River ParkwayTampa, FL 33637-1000(800) 242-7405http://www.bicsi.org

  • 8/19/2019 u to Telecom Design and Construction Specifications

    9/34

    94 DEFINITION OF TERMS, ACRONYMS AND ABBREVI ATIONS This section contains definitions of terms, acronyms, and abbreviations that have a specialmeaning or that are unique to the technical content of this document. The terms that are usedin only one clause may be defined within, and at the beginning of, that clause.

    4.1 Equipment Room (ER) An ER Room is a special purpose room designed to serve as a campus point of demarcation. AnER Room may service multiple TRs in a campus design. In large campuses, multiple ERs maybe required and interconnected. This room will only contain Network & Telecommunicationhardware and CATV. Other utilities and special systems must be pre-approved by ASU UTODesign.

    4.2 Entrance Facility (EF) An EF is a special purpose room designed to serve a single building with multiple TRs. The EFmay also contain the necessary equipment to function as a TR for the floor it is located on. Thisroom will only contain Network & Telecommunication hardware and CATV. Any other utilitiesmust be approved by ASU UTO Design.

    4.3 Telecommunication Room (TR) A TR is a special purpose room designed to serve a single floor. In buildings with multiple floors,TRs shall be vertically stacked to form a backbone pathway. The TR is the point in the Data,Voice and CATV infrastructure that the backbone and horizontal distribution systems areconnected to each other. This room will only contain Network, Telecommunication and CATVhardware. Other utilities and special systems must be approved by ASU UTO Design.

    4.4 Acronyms

    • AFF Above Finished Floor• BICSI Building Industry Consultants Service International• CAT Category• CATV Community Antenna Television (cable television)• EF Entrance Facility• ER Equipment Room• HH Handhole• IDF Intermediate Distribution Frame• MDF Main Distribution Frame• MV Maintenance Vault• PBX Private Branch Exchange (Phone Switch)• QA Quality Assurance•

    SMB Surface Mount Box• TMB Telecommunication Mounting Board• TMBB Telecommunication Mounting Back Board• TO Termination Outlet• TR Telecommunication Room (Formally the IDF)• TGB Telecommunications Grounding Busbar• TMGB Main Telecommunication Grounding Busbar• TDMM Telecommunication Distribution Methods Manual (BICSI Publication)• UTO University Technology Office

  • 8/19/2019 u to Telecom Design and Construction Specifications

    10/34

    10

    • UTP Unshielded Twisted Pair• WAP Wireless Access Point

    See “Codes and Standards References” for additional codes and standards Acronyms. Or visitwww.webopedia.com for additional definitions.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    11/34

    115 DESIGN STANDARDS Figure 1: Floor Plan Symbols Legend

    Symbol Function

    Typical Telecommunications Outlet (TO)mounted flush on wall at 15” AFF. X denotescable quantity.

    Typical wall phone outlet mounted flush onwall at 48” AFF.

    Typical TO in ceiling. Terminated cables arehoused in a SMB.

    Typical TO intended to support Wireless Access Points.

    Typical TO in floor box.X denotes cable quantity.

    Typical 120VAC Duplex Electrical Outlet

    Typical 120VAC Quad Electrical Outlet

    Typical 208VAC Electrical OutletVerify 20amp or 30amp configuration

    Typical Relay Rack 19”

    Typical Cable Runway

    X

    W

    C

    WAP

    X

    L 6- 30 R

    RELAY RACK

  • 8/19/2019 u to Telecom Design and Construction Specifications

    12/34

    12

    6 TELECOMMUNICATION RO OMS

    6.1 Telecommunication Room/Building Equipment Rooms

    6.2 GeneralThe following section will outline the location, design and pathway requirements for a typicalEntrance Facility (EF) or Telecommunication Rooms (TR). Figure 2 references a general EF orTR layout.

    Chatsworth Products (Typical): ( See Sample Communications Submittal Package )

    • 12” & 18” Universal Cable Runway• Cable Runway Accessories• 19” x 6”deep Standard Rack• Vertical Cable Manager•

    Universal Horizontal Cable Manager• Horizontal Rack-Mount Power Strips 120VAC and/or 208VAC• Grounding & Bonding Accessories• Elevation Kits Overhead

    Figure 2: Telecommunications Room (Typical)

    W

    17'

    1 4 '

    RELAY RACKRELAY RACKRELAY RACKRELAY RACK

    RELAY RACKRELAY RACKRELAY RACKRELAY RACK

    L6-30R(Typical)

    L5-20R(Typical)

    Active ActivePassive Pas sive

    Active ActivePassive Passive

    5-20

    5-20

    5-20

    +84"

    Door Access ControlUTO Segment

    L6-30R(Typical)

    L5-20R(Typical)

    L6-30R(Typical)

    L5-20R(Typical)

    L6-30R(Typical)

    L5-20R(Typical)

  • 8/19/2019 u to Telecom Design and Construction Specifications

    13/34

    136.3 LocationEF and TR locations must meet the following requirements:

    • Location shall be selected so that the room may be expanded.• Shall be located as close as practicable to the center core of the building to minimize

    horizontal cable distance (Maximum cable length is 250’ from TR to TO.)• Shall be accessible through common-use corridors that will allow the delivery of

    large cable reels and equipment and access for repairs 24x7.• In multiple floor applications, EF and TRs shall have all 4 walls vertically stacked.

    The EF and TRs shall not be part of a server, mechanical, equipment, electrical, washroom,storage area, or a janitor closet. All room locations must be approved in writing by ASU UTODesign prior to construction.

    6.4 Electromagnetic InterferenceThe EF and TRs shall be located away from sources of electromagnetic interference. Specialattention shall be given to electrical power supply transformers, motors and generators, x-rayequipment, elevator equipment, and induction devices.

    6.5 Access Access to the Rooms shall be 24 hours-per-day, 365 days-per-year basis (24x7). Access shallbe through common use corridors and not accessed by way of any other room. At a minimumall doors to TR’s will be equipped with a lock and ISSAC access system if available.Preferably, they shall be on the UTO ISSAC segment.

    7 DESIGN

    7.1 Architectural

    7.2 SizeRooms shall have a minimum inside dimension of 10ft x 12ft dependent on specificTelecommunication requirements. If these rooms require additional square footage based onadditional requirements, the size shall be determined on a case-by-case basis. ASU UTODesign must approve all room dimensions in writing.

    7.3 Walls All four (4) walls shall be floor to deck and have a 2-hour fire rating.

    7.4 Plywood Backboards All four (4) walls shall be covered with " in. fire retardant plywood with fire rating stamp visible

    on all plywood. Plywood will be rated to meet applicable codes and must be LEED compliant.To reduce warping, fire-rated plywood shall be kiln-dried to maximum moisture content of 15%.Plywood will not be painted. Mount plywood 2” above the top of the electrical outlets orsurface raceway and must be installed vertically. Top of plywood shall be level with the top ofthe cable tray but shall not exceed 9’6” AFF.

    7.5 Ceiling HeightThe height between the finished floor and the lowest point of the ceiling should be a minimumof (14 ft).

  • 8/19/2019 u to Telecom Design and Construction Specifications

    14/34

    14

    7.6 TreatmentFloors, walls, and ceiling shall be treated to eliminate dust. Finishes shall be light in color toenhance room lighting. Floor covering shall be sealed concrete.

    7.7 CeilingRoom shall not have a false or drop ceiling to permit maximum use of cable pathways bothvertically and horizontally. In such cases where fireproofing may be sprayed onto the exposedceiling, the fireproofing shall be treated to mitigate airborne dust.

    7.8 DoorDoors shall be a minimum of (42 in) wide and (80 in) high, without doorsill, hinged to openoutward (code permitting) or be removable. Consideration should be given to using doubledoors with a removable center-post. The door(s) shall be fitted with a lock, which is keyed andISSAC access system if available.

    7.9 Floor LoadingThe EFs shall be located on floor areas designed with a minimum floor loading of 4.8 kPa

    (100 lbf/ft 2). The TRs shall be located on floor areas designed with a minimum floor loading of2.4 kPa (50 lbf/ft 2). The project structural engineer shall verify that concentrations of proposedequipment do not exceed the floor-loading limit.

    7.10 SignageSignage, if used, should be developed within the signage plan of the building.

    8 ENVIRONMENTAL

    8.1 ContaminantsThe rooms shall be protected from contaminants and pollutants that could affect operation and

    material integrity of the installed equipment.8.2 Heating, Ventilation and Air Conditioning (HVAC)

    8.3 Continuous OperationHVAC shall be available on a 24 hours-per-day, 365 days-per-year basis. A stand-alone ordedicated unit shall be considered for all Telecommunication Rooms.

    8.4 Equipment PlacementHVAC unit shall not be located in the TR. When the HVAC unit must be located in the TR thelocation needs to be approved by ASU UTO Design.

    8.5 Standby OperationIf a standby power source is available in the building, consideration should be given to alsoconnecting the HVAC system serving the Communications Rooms to the standby supply.

    8.6 Operational ParametersThe temperature and humidity shall be controlled to provide continuous operating ranges of18 ° C (64 ° F) to 24 ° C (76 ° F) with 30% to 55% relative humidity.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    15/34

    15BTU rating requirements shall be calculated on a room-by-room basis due to the nature ofthe equipment that is being hosted.

    The ambient temperature and humidity shall be measured at a distance of 1.5 m (5 ft) abovethe floor level, after the equipment is in operation, at any point along an equipment aislecenterline.

    8.7 Positive Pressure A positive pressure differential with respect to surrounding areas should be provided with aminimum of one air change per hour.

    8.8 VibrationMechanical vibration coupled to equipment or the cabling infrastructure can lead to servicefailures over time. A common example of this type of failure would be loosened connections. Ifthere is a potential for vibration within the building that will be conveyed to the TR via thebuilding structure, the project structural engineer should design safeguards against excessiveTR vibration.

    8.9 Other Mechanical FixturesMechanical fixtures (e.g., piping, ductwork, pneumatic tubing, electrical conduits) not related tothe support of TR/EF shall not be installed in, pass through, under or enter the TR/EF. Inaddition, the area adjacent to the exterior of the TR/EF walls shall remain clear for cablepathways entering the TR/EF.

    9 ELECTRICAL

    9.1 LightingLighting shall be a minimum of 500 lx (50 foot candles) measured 1 m (3 ft) above the finishedfloor, mounted 12” minimum above the elevation of the cable tray. Light fixtures shall not be

    directly over the equipment racks. Light fixtures should be hung in parallel with the equipmentracks in the front and back. Light fixtures must be independently supported from the buildingstructure. Light fixtures shall not be mounted to, or supported by the cable tray.NOTE - Lighting fixtures should not be powered from the same electrical distribution panel asthe TR/EF. Dimmer switches shall not be used and emergency lighting and signs should beproperly placed such that an absence of primary lighting will not hamper emergency exit.

    9.2 PowerEF, ER and TRs power shall be approved by ASU UTO Design.

    9.3 GeneralMinimum dedicated 120VAC and 208VAC circuits that are fed from a panel not located in theTR.

    9.4 Equipment 110V OutletsTRs shall be equipped with a minimum of one dedicated 120V, 20A (L5-20R) circuit. Theoutlets should be above equipment racks depending on room configuration and mounted onunistrut and supported by elevation kit. All outlets shall have a computer generated labelaffixed to it indicating the panel room number, panel ID and circuit number. ASU UTO Designmay specify additional outlets on a case-by-case basis.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    16/34

    16

    9.5 Equipment 208V OutletsTRs shall be equipped with a minimum of one dedicated 208V, 30A (L6-30R) circuit. Theoutlets should be above equipment racks depending on room configuration and mounted onunistrut and supported by elevation kit. All outlets shall have a computer generated labelaffixed to it indicating the panel room number, panel ID and circuit number. ASU UTO Designmay specify additional outlets on a case-by-case basis.

    9.6 Emergency 110V and 208V OutletsThese outlets will be requested by ASU UTO Design on a case-by-case basis. All outlets shallhave a computer generated label affixed to it indicating the panel room number, panel ID andcircuit number. ASU UTO Design may specify additional outlets on a case-by-case basis.

    9.7 Convenience 110V OutletsEFs/ TRs shall be equipped with convenience outlet placed on each wall of the TR for usesother than network equipment (i.e. power tools, testing equipment). This outlet shall be runfrom a separate electrical panel. All outlets shall have a computer generated label affixed to itindicating the panel room number, panel ID and circuit number. ASU UTO Design may specifyadditional outlets on a case-by-case basis.

    9.8 Location of Power Conditioning Systems (UPS)Where applicable, dedicated environmental control equipment, such as power conditioningsystems, and UPS up to 30 kVA shall be permitted in the TR. All UPS equipment larger than30kVA shall be located in a separate room. All UPS equipment will have a wall mountedprimary feed disconnect switch and a power transfer switch that will be included in the designof the room. This must be approved in writing by ASU UTO Design.

    9.9 Bonding and GroundingProvide Telecommunication Grounding/Bonding System in accordance with NFPA-70 Article-

    250 and ANSI-J-STD-607A using approved Grounding Hardware and methods.

    Provide a suitable Telecommunication Bonding Backbone (TBB) that connects TMGB to otherTGB’s utilizing a minimum 2/0 insulated copper bonding conductor and double-bolted,Compression style, Grounding Lugs using Table A below. In addition, provide aninterconnecting-bonding conductor between telecommunication rooms and equipment roomsSTD-607A. This conductor equalizes the potential between grounding planes within thetelecommunication rooms and equipment room.

    Provide Telecommunication Main Grounding Busbar (TMGB), and Grounding Busbar (TGB) inEntrance Facilities (EF), Telecommunications Rooms (TR) and Equipment Server Room.

    The Telecommunication Main Grounding Busbar (TMGB) installed in the EF/MDF shall be 20inches long and 4 inches wide by # inch thick with pre drilled NEMA bolt hole sizing, dual lugand spacing, example; Chatsworth Products, Inc. Busbar Assemblies w/ Lug Kit part number40158-020. CADWELD Bonding method with a 2/0 AWG insulated copper bonding conductorshould be used for connection to Building Steel or electrical ground. Alternate connectionpoints must be approved by ASU UTO Design.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    17/34

    17Table A

    TBB Length (Linear m [ft]) TBB Size (AWG)Less than 4m (13ft) 6 AWG4 to 6m (13 to 20ft) 4 AWG6 to 8m (20 to 26ft) 3 AWG8 to 10m (26 to 33ft) 2 AWG10 to 13m (33 to 44ft) 1 AWG13 to 16m (44 to 52ft) 1/0 AWG16 to 20m (52 to 66ft) 2/0 AWGGreater than 20m (66ft) 3/0 AWG

    Figure 3: Telecommunication Grounding Busbars

    The Telecommunication Grounding Busbar (TGB) installed in the TR shall be 12 inches longand 2 inches wide by # inch thick with pre drilled bolt hole sizing and spacing, ChatsworthProducts, Inc. part number 40153-012. All TGB Connections should utilize 2/0 AWG insulatedcopper bonding conductor using a double hole lug, bolted, compression style, grounding Lugs.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    18/34

    18

    All cable tray, ladder rack, access floors and telecommunication racks and/or cabinetscontained within the ER/TR shall be grounded/bonded to the Busbar (TGB), per Table A. Allconnections to be made with double-hole lug, bolted, compression style, grounding lugs.

    The Telecommunication Grounding Systems shall have non-metallic labels attached to eachbusbar and bonding conductor. Refer to ANSI/TIA/EIA 606A for additional labelingrequirements.

    The labels shall be located on conductors as close as practicable (ie. ease of access to readthe label) to their point of termination. The labeling scheme will be coordinated with ASU UTODesign prior to installation.

    Chatsworth Products Required. ( See Sample Communications Submittal Package )

  • 8/19/2019 u to Telecom Design and Construction Specifications

    19/34

    19Figure 4: Telecommunications Bonding Backbone

    Mid-Rise Building Example

    10 MISCELLANEOUS REQUIR EMENTS

    10.1 Fire ProtectionFire protection of the TR, if required, shall be provided as per applicable code. If sprinklers arerequired within the spaces, the heads shall be provided with wire cages to prevent accidentaloperation. Drainage troughs shall be placed under the sprinkler pipes to prevent leakage ontothe equipment within the room. As required, consideration should be given to the installation ofalternate fire-suppression systems, confirm requirements with ASU UTO Design.

    #6 AWG Minimum toRacks & Runway

    TMGB

    #40158-020

    4 th

    flr

    3 rd

    flr

    2 nd

    flr

    1 st

    flr

    4S

    3S

    2S

    1S

    4N

    3N

    2N

    1NMER

    (Main Electrical Room)

    TMB#40153-012

    #6 AWG Minimum toRacks & Runway

    See Table A

    2/0AWG BondingConductor

  • 8/19/2019 u to Telecom Design and Construction Specifications

    20/34

    20

    10.2 Water InfiltrationThe TR shall be free of water or drain pipes not directly required in support of the equipmentwithin the room.

    11 CABLE PATHWAYS

    11.1 GeneralConduits and sleeves should extend 4-6” into the TR. If the conduits or sleeves are subject towater intrusion they must drain away from the room and be watertight. All conduits and sleevesmust have the ends plugged upon installation. Basket tray shall not be run through walls.Conduits and sleeves must have bushings installed at all ends and at all pull boxes. Thecontractor responsible for the installation of the pathway system is also responsible forproviding segmented pull strings. In hard lid or inaccessible ceiling spaces the use of conduit isrequired. Final design of the Telecommunication pathway must be approved by ASU UTODesign.

    Conduit pathways built for telecommunication cabling have more stringent bending and pull

    box requirements than electrical cabling and must be adhered to (i.e. a telecommunicationsconduit can have no more than 180 degrees of cumulative bends between pull points).

    11.2 Ladder RackThe ladder rack shall be installed around the inside perimeter of the TR room for thedistribution of communication cabling. A ladder rack shall also be installed over the top of anyfree-standing racks with an overhead elevation kit. The runway shall be mounted 7’6” fromfinished floor to the bottom of the tray. There shall be no other equipment, lights, conduits,fixtures etc. attached to, mounted on, running through or on the ladder rack except thoseneeded to support the ladder rack systems or those approved by ASU UTO Design, i.e. powerdistribution to support Network equipment.

    • An 18” ladder rack (typical) will be installed in the ER/MDF.• A 12” ladder rack (typical) will be installed in the TR/IDF.• Ladder Rack may not be run through walls.

    Chatsworth Products Required: ( See Sample Communications Submittal Package )

    11.3 Sleeves/Conduits

    11.4 Horizontal PathwayThe quantity of horizontal sleeves installed in each TR/EF for horizontal cabling shall be a

    minimum of three (3) 4" sleeves. The sleeves shall be a minimum 8’-0” AFF to the bottom ofthe sleeves. Sleeves that are installed above 9’-0” AFF must have vertical ladder rackinginstalled from the bottom of the sleeve to the top of the cable tray for lashing of cables in thevertical run.

    11.5 Vertical PathwayIn a multi-story building where TRs are stacked to form a riser, a minimum of six (6) 4” sleevesshall be installed between the stacked TRs. The minimum quantity will be determined on acase-by-case basis.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    21/34

    2111.6 Horizontal Backbone Inter-building PathwayThe horizontal backbone pathway shall consist of a minimum of six (6) 4” conduits between theEF/MDF of each building and the nearest designated maintenance vault servicing that facility.Cable tray can be used for Inter-building Backbone distribution only with the use of properlysized innerduct or by the installation of a physical separation for the protection of the Backbonecables from general cable installation.

    11.7 Horizontal Backbone Intra-building Pathway• If the TRs are not vertically stacked on the EF/MDF, backbone pathway shall consist of

    a minimum of six (6)-4” conduits installed between the EF/MDF of the building and eachTR. All conduits and inner-ducts shall contain a mule tape with footage makers. In multi-story building where TRs are stacked to form a riser, a minimum of six (6) 4” conduitsshall be installed between the EF/MDF and the first TR in the stack. ASU UTO Designmust approve use of cable tray as a backbone distribution system. Conduit will be at40% capacity of the conduits maximum fill.

    11.8 General Telecommunication Room Design

    Telecommunication Room design shall follow BICSI TDMM design recommendations. ASUUTO Design must approve all final TR design. A detailed telecommunication drawing shall beforwarded for approval by ASU UTO Design.

    12 EQUIPMENT ROOMS AND SERVICE ENTRANCES

    12.1 GeneralEquipment Rooms / PBX and Service Entrance Rooms shall be located and designed on acase-by-case basis with ASU UTO Design.

    13 INTERIOR COMMUNICATI ON PATHWAYS

    13.1 GeneralThe Interior Communication and Special Systems Pathways shall provide a distribution systemfor all system cabling that will be served by the building. The pathways for a building mayinclude all or some of the following, cable tray, continuous conduit systems, conduit stubs,sleeves, and cable hangers. All pathways must be approved by ASU UTO Design prior todesign completion. Interior pathway design shall follow all BICSI TDMM designrecommendations and TIA568-B, TIA569-A and NEC Article 200 standards. A detailed T1 andPathway Logical drawing shall be required for all pathway plans.

    13.2 Cable Tray

    A continuous cable tray system shall be installed on each floor as required. The tray shall be abasket style with a minimum size of 6" W x 2" D. The cable tray shall be supported by atrapeze style support. A solid bottom liner shall be installed in all open areas 8’ or below. Allcable tray shall be grounded per manufactures specification. The use of “T” support isprohibited .

    B-Line/GS Metals & Chatsworth Products Required: (See Sample Communications SubmittalPackage)

  • 8/19/2019 u to Telecom Design and Construction Specifications

    22/34

    22

    Figure 5: Cable Tray Support

    Floors with fewer TOs than (50) may be supported with an approved “J” Hook solution withauthorization from ASU UTO Design. When making turn and elevation changes theappropriate tray accessories, having the proper bend radius, must be used. For access to, andinstallation of, cables in the cable tray, the following clearances are required around the cabletray. The cable tray system shall have 1’-0” clearance measured from the top most surface ofthe tray. Access from the sides shall be 6" to 1’. Access to the cable tray from below shall beunobstructed its entire length. There shall be no other equipment, lights, conduits, fixtures etc.attached to, mounted on, installed through or on the cable tray except those needed to supportthe tray systems. Cable tray shall not be installed through walls. The tray shall stop at all wallsand sleeves or conduits shall be installed. The tray shall continue on the other side of the wallas required. Support system for tray shall be detailed in submittals.

    13.3 Conduit• Sizes indicated for conduits are trade sizes in all cases. Conduits shall have an

    insulated bushing installed prior to the installation of telecommunications cabling.Conduits must have the ends plugged upon installation to keep debris from enteringthem. Conduit shall be installed in the most direct route possible, usually parallel withbuilding lines. Conduit shall not contain continuous sections longer than 100 feet. Iflengths total more than 100 feet, pull points or pull boxes shall be inserted. Conduit shallhave no more than 180 degrees of cumulative bends between pull points or more than90 degrees of bends at any one point. Electrical Metallic Tubing shall be electro-galvanized steel. Conduit will be at 40% capacity of the conduits maximum fill.(See ASU UTO Design to request specifications section for conduit detail.)

    13.4 Intra-building Backbone Conduits

    See TR pathway requirements.

    13.5 Outlet/Conduit Location

    13.6 New Construction Wall OutletConduit stubbed above ceiling shall be a minimum of 1” with bushing. Each 1” conduit willservice only one wall outlet location. (NO DAISY CHAIN) The conduit will be terminated in a 4”x 4” x 2.75” deep metal box with a pull string. The box shall be fitted with a single gang mudring or a double gang mud ring when applicable.

    UNISTRUT

    3 / 8 ” All - Thread

    CPI

  • 8/19/2019 u to Telecom Design and Construction Specifications

    23/34

    23

    Outlets are (typically) located at the following heights to top of wall outlet:

    Desks 18” AFF Above Counter 42” AFFWall Phones 48” AFF Lab Bench 42” AFFPay Phones 48” AFF Overhead 80” AFF

    13.7 New Construction Floor OutletConduit from the cable tray to a typical floor outlet shall be a minimum of 1”. Each 1” conduitwill service only one floor outlet location. (NO DAISY CHAIN) Confirm all floor outlets meetFire Code and will accommodate SYSTIMAX inserts, bezels and/or faceplates.

    13.8 RenovationsFor areas being renovated, the minimum requirement is for horizontal wiring to be properlysupported and secured in the work area in either surface raceway, communication power pole

    raceway, enclosed within the wall or furniture and not exposed to possible damage. The cableshall be supported from cable tray to outlet location by CAT 6 approved cable hangersmounted a minimum of 6 inches above the ceiling at a maximum distance of 5’ betweenhangers.

    13.9 SleevesSizes indicated for sleeves are trade sizes in all cases. Sleeves shall have an insulatedbushing installed prior to the installation of telecommunications cabling. Sleeves must have theends plugged upon installation to keep debris from entering them. Sleeves used at walltransition points for cable tray systems shall be 4 inches. Quantity of sleeves shall be equal tothe capacity of the cable tray. Sleeves for distribution of horizontal cable in renovated areas

    not having conduits to the cable tray shall be sized so that when all cables have been installedat the completion of the project, the sleeve will be at 40% capacity of the sleeves maximum fill.

    Sleeves shall be UL listed at the rating of the wall or floor. If the wall or floor has a fire ratinggreater than 2 hours the sleeve shall have an equal rating in all cases. The minimum sleevesize installed for any penetration shall be 2 inches.

    13.10 Bonding and Grounding All ladder rack, cable tray and conduits shall be bonded to the TGB in the TR.

    14 EXTERIOR COMMUNICATI ON PATHWAYS

    14.1 GeneralThe Exterior Communication Pathways shall provide a campus distribution system for allsystem cabling that will be served by the building. The pathways for a campus distributionsystem may include all or some of the following; maintenance vault, Handhole, inner-duct,conduit, multi-cell conduits. All pathways must be approved by ASU UTO Design prior toimplementation. Exterior pathway design shall follow all BICSI TDMM and BICSI CustomerOwned Outside Plant Design Manual design recommendations and TIA568B and 569A

  • 8/19/2019 u to Telecom Design and Construction Specifications

    24/34

    24

    standards. ASU UTO Design must approve all final design. A detailed telecommunicationdrawing and pathway logical drawing will be required.

    (Conduit pathways built for telecommunication cabling have more stringent bendingand pull box requirements than electrical cabling and must be adhered to (i.e. atelecommunications conduit can have no more than 180 degrees of cumulative bends

    between pull points).

    14.2 Exterior Pathways

    14.3 GeneralSizes indicated for conduits and innerduct are trade sizes in all cases. For quantities seeBackbone Inter-Building section.

    14.4 Conduit

    • All conduits shall be a minimum of 4 inches for inter-building pathway.•

    Conduits must have the ends plugged upon installation to keep debris from enteringthem.• Conduit lengths shall contain no continuous sections longer than 300 feet. If conduit

    lengths total more than 300 feet, pull points shall be provided.• Conduit shall have no more than 180 degrees of cumulative bends between pull points

    or more than 90 degrees of bends at any one point. All bends must be long, sweepingbends with a radius not less than six times the internal diameter of conduits 50 mm (2in) or smaller, or ten times the internal diameter of conduits larger than 50 mm (2 in). 48inches sweeps preferred.

    • The use of pull boxes for 90 degree bends is prohibited.• All conduits must be mandreled prior to turning over to ASU UTO.•

    All ends of conduit must be reamed.• All conduits entering a building must be pitched to drain away from the building to avert

    water intrusion. To prevent conduit shearing, conduits entering through walls shall bemetallic and extend to undisturbed earth, particularly where such backfill is susceptibleto load bearing tension.

    • All conduits that do not have inner-duct shall be threaded with mule tapes with footagemarkers.

    • Rigid Galvanized Steel Conduit shall be hot-dipped galvanized steel, including threads.Extra-Heavy wall conduit: Schedule 80, constructed of polyvinyl chloride, rated for usewith 90 degree C conductors, and UL listed for direct burial and normal above grounduse.

    • Heavy wall conduit: Schedule 40, constructed of polyvinyl chloride, rated for use with 90degree C conductors, and UL listed for direct burial and concrete encasement.

    • Conduit will be at 40% capacity of the conduits maximum fill.• (See ASU UTO Design to request the specifications for exterior conduit detail)

    14.4.1 Conduit Depth RequirementsTop of conduit must be buried at least 24 inches below finished grade.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    25/34

    2514.5 Maintenance Vaults

    14.5.1 GeneralJoint Use Maintenance Vaults (MVs) are permitted. The vaults shall be 4’ x 6’ minimum.

    14.5.2 Conduit Entry PointsConduits entering the MV are to be placed at opposite ends of a MV.

    14.5.3 CoversCovers shall always be round and centrally located on single cover maintenance vault. Framesand covers used in roads or driveways shall be rated to withstand vehicular traffic. For MVover 3.7 m (12 ft) long, follow these guidelines:

    • Between 3.7 m (12 ft) and 6 m (20 ft) use two covers.• Over 6 m (20 ft), use three covers.

    14.5.4 Encasement All underground conduits shall be slurry capped sealed.

    14.5.5 Conduit OrientationManufactured conduit spacer shall be used for all conduits in the duct bank so conduits canmaintain the same orientation at all points of access. The installer shall provide photographsand a site inspection to UTO Design.

    14.5.6 Trace Wire and Safety TapeTelecommunication pathways underground shall have a trace wire for locating the route andan identifying tape to reduce the risk of damage if excavation intersects the conduit.

    14.5.7 Separation from Other UtilitiesPower up to 1KVA:

    • 12 in. of well- packed earth• 4 in. of masonry• 3 in. of concrete

    Gas, Oil, Water, etc.:• 12 in. when parallel• 6 in. when crossing

    14.5.8 Innerducts

    • Innerducts shall have both ends plugged upon installation.• All innerducts shall be threaded with mule tapes with footage markers.• Innerduct shall not be directly buried or concrete incased as a replacement to conduits.• All innerducts shall be marked with a unique identifier indicating that origin and

    destination.• There shall be a minimum of 3 - 1 # Inches ribbed, orange, PVC innerduct installed per

    4 inches conduit. (Typical)

    14.6 Interior Hardware All hardware in MVs must be galvanized. MVs shall be equipped with the following:

  • 8/19/2019 u to Telecom Design and Construction Specifications

    26/34

    26

    • Bonding inserts and struts for racking.• Pulling eyes at least 22 mm (7/ 8 in) in diameter.• A sump drywell of at least 200 mm (8 in) in diameter.• An entry ladder (required). • Appropriate grounding points.

    14.6.1 Identifying Covers All covers shall have COMMUNICATIONS pre-marked on the cover for easy identification.

    14.6.2 Concrete StrengthThe strength of concrete used for MVs shall be at least 24 kPa (3500 psi). NOTE: Strongerconcrete may be stipulated in certain installations.

    Figure 6: Example of a Maintenance Vault

    14.7 Handhole

    14.7.1 General

    Handholes (HHs) are smaller than maintenance vault (MVs), but the covers provide full accessto the entire space inside the hole. HH shall be used as pull- through points only. HHs shall notbe used as splice points, unless specified by ASU UTO Design. HH shall not be used inconduit runs that have more than three (3) 4 inch conduits.

    Joint Use HHs is not permitted.

    14.7.2 Conduit Entry PointsConduits entering the HH are to be aligned on opposite walls of the HH at the same elevation.

    SUMP

    12'

    6 ' 6 "

    GROUNDRODS

    Eye Bolt Eye Bolt

    (6) 4" conduitstypical 3-over-3

    Cast Iron Frame and Lid(H20 Loading)30" TYPE “A”

    UNISTRUT

  • 8/19/2019 u to Telecom Design and Construction Specifications

    27/34

    2714.7.3 CoversCovers shall always be round and centrally located on HH.Frames and covers used in roads or driveways shall be rated to withstand vehicular traffic.

    14.7.4 Identifying Covers All covers shall have COMMUNICATIONS pre-marked on the cover for easy identification.

    Figure 7: Example of a Handhole

    15 BACKBONE CABLING

    15.1 GeneralBackbone cabling is the media over which Voice, Video, Data, Audio, Community antennatelevision (CATV) signals will be transmitted to the TRs. The media used for the transmissionof the signals will be copper, fiber and coax. Backbone cables are broken into two types, inter-building and intra-building. Inter-building cabling has very strict requirements when entering abuilding. Cable insulation type, lightning protection and termination methods are importantconsiderations when designing outside plant (OSP) cabling. SYSTIMAX lightning protection

    solutions shall be utilized on all copper multi-pair cables and all copper and fiber optic cableswill be grounded.

    Sizing of backbone cabling for support of a building is directly related to the building’s functionsboth during initial occupancy and future use. There is no generic backbone installation that willfit all applications. Design of the building’s backbone cabling will be on a case-by-case basis.Generally, Optical Fiber, High Pair Count Copper and Coaxial cable will be installed forbackbone applications.

    4'

    Eye Bolt

    4'

    SUMP

    (2) 4" conduits

    TypicalHandhole

    Cast IronFrame and Lid

  • 8/19/2019 u to Telecom Design and Construction Specifications

    28/34

    28

    Backbone cable design shall follow all current BICSI TDMM design recommendations andTIA568B standards. ASU UTO Design must approve all final design. A detailedCommunication site plan and Backbone logical drawings will be required for all Backbonecabling Plans.

    Product Requirement: ( See Sample Communications Submittal Package) • OSP & Riser Fiber SYSTIMAX Armored LazrSpeed (50mm Multi-mode) &

    SYSTIMAX (Single-mode)• OSP Copper Superior Essex ANMW Armored• Riser Copper Superior Essex ARMM• OSP & Riser Coax CommScope .5/.75• Fiber Terminations – SYSTIMAX pre-radius LC connectors on all Multi-mode and

    Single-mode fiber• Fiber Optic Shelf (LIU) – Rack mount enclosures shall be used for fiber terminations,

    sized accordingly• CommScope VisiPatch shall be used for Copper OSP & Riser terminations• 110 Blocks shall be used for transition from wall to CommScope VisiPatch in a rack

    16 HORIZONTAL CABLING

    16.1 General The following will describe the minimum work area outlet requirements for areas such as; astandard office, classroom, conference room, special locations and residence halls. The use ofplenum cable is required unless home run conduits are installed in ASU facilities. The exactplacement and quantities of outlets and pathways must be approved by ASU UTO Design.

    Detailed communications floor plans for backbone cable design shall follow all current BICSITDMM design recommendations and TIA568B standards. ASU UTO Design must approve allfinal designs in writing.

    In general, install one (1) TO in each office on the wall opposite of the door. Larger offices forDirector Level and above should receive two (2) TOs.

    A minimum of one duplex electrical outlet should be installed within 16 inches, but not closerthan 8 inches, of every work area outlet.

    Cable ID label shall be a minimum 3 inches from termination point at patch panel and T.O.s.

    16.2 Telecommunication Outlet Types, Configurations and Placement

    16.3 (To be comprised of all SYSTIMAX components. See Sample CommunicationsSubmittal Package)

    16.3.1 IdentificationIdentification of cabling, pathways and hardware shall conform to TIA 606-A. The labelingscheme for the structured cabling system shall be submitted to ASU UTO Design for approvaland inclusion in all matrices for building operations prior to trim/finish. Faceplate, insert anddust cover shall be same color. Dust covers shall be installed on all faceplates.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    29/34

    29

    Figure 8: Faceplate Configurations

    16.3.2 Standard Work Area Outlet A Standard work area outlet is comprised of two SYSTIMAX 4-pair Category 6 twisted paircables, inserted into a single gang 3-port faceplate. The faceplate, insert, and dust covers shallbe the same color. Dust covers shall be installed on all faceplates. The jack identifierdesignated window (label holder) shall be printed or typed in black on white.

    X-Y-Z

    X-Y-Z

    SYSTIMAX SYSTIMAX

    SYSTIMAXSYSTIMAX

    SYSTIMAX SYSTIMAX

    1 2

    3 4

    5 6

    TR#“SINGLE DIGIT FORMAT”

    FLOOR OF TRLOWER LEVEL – 0

    FIRST -1

    SECOND – 2THIRD -3

    CABLE I.D.001 - 999

    LABELING SCHEME SAMPLE

    Jack ID #”s

    SYSTIMAX

    SYSTIMAX

    Jack ID #”s

    1

    2

    3SYSTIMAX

  • 8/19/2019 u to Telecom Design and Construction Specifications

    30/34

    30

    16.3.3 Standard Residence Work Area Outlet A residence work area outlet is comprised of 4-pair SYSTIMAX Category 6 twisted pair cables.The number of CAT6 cables shall be determined on a case-by-case basis.

    16.3.4 Coax Outlet A Coax outlet is comprised of one CommScope quad-shielded RG-6 or RG-11 coax cabledepending on length from TR to distribution point. The RG-6 shall be used for lengths less than200’ and the RG-11 shall be used for lengths over 200’. The location of a coax outlet will belocated on a case-by-case basis. The faceplates shall be a single gang one port or a singlegang two-port type. The coax cable will be for video distribution.

    Jack ID #”s

    SYSTIMAX

    SYSTIMAX

    Jack ID #”s

    1

    2

    3SYSTIMAX

    DATA

    DATA

    VOICE

    Coax ID # Coax ID #

    SYSTIMAX

    The Coax is

    labeled:Floor-Closet-CXXX

  • 8/19/2019 u to Telecom Design and Construction Specifications

    31/34

    31

    16.3.5 Wall Phone Outlet A Wall Phone outlet is comprised of one SYSTIMAX 4-pair Category 6 twisted pair voice cable. All wall phone locations shall be ADA compliant. The faceplates shall be a plastic single gangtype.

    17 SPECIAL SYSTEM DEVIC ES

    17.1 Area Refuge PhoneThe phone outlet is comprised of one SYSTIMAX 4-pair Category 6 twisted pair voice cable.

    All locations shall be ADA compliant. The cable shall be terminated on a TIA-568B CAT6 jackby the cabling contractor responsible for the installation.

    17.2 Blue Light PhonesThe phone outlet is comprised of one SYSTIMAX 4-pair Category 6 twisted pair voice cable.The cable shall be terminated on a TIA-568B CAT6 jack by the cabling contractor responsiblefor the installation.

    17.3 Elevator PhonesThe phone outlet is comprised of one SYSTIMAX 4-pair Category 6 twisted pair voice cable.The cable shall be terminated on a TIA-568B CAT6 jack by the cabling contractor responsiblefor the installation.

    17.4 Wireless Access Point A wireless access point is comprised of four (4) SYSTIMAX 4-pair Category 6 data cables. TheWireless enclosure for a drop ceiling shall be an Oberon enclosure (Model 1064-00) andtermination shall be within the enclosure with fire-stop on a SYSTIMAX M102SMB modularoutlet. The locations for these cables shall be determined by ASU UTO. Contact and arrangefor these engineering services on a per project basis and coordinate closely with ASU UTODesign.

    SYSTIMAX

    Jack ID #”s

  • 8/19/2019 u to Telecom Design and Construction Specifications

    32/34

    32

    18 TYPICAL OUTLET PLACE MENT

    18.1 Standard office Each office shall have a minimum of one TO, on opposite wall of entry. The TO should be

    three feet from the back wall (furthest from the door) and shall contain a minimum of (2)SYSTIMAX 4-pair Category 6 cables.

    18.2 Classrooms (Typical)The specific cabling requirements shall be determined on a case-by-case basis. However,please us the following as a classroom base; one TO located in the ceiling for video projectionand camera containing (2) Category 6 cables. One floor box at the front of the classroomcontaining up to (6) Category 6 cables for lectern. One TO containing (2) Category 6 cables,per location, for wireless access points or as required.

    18.3 Conference Rooms

    The specific cabling requirements shall be determined on a case-by-case basis. However,please us the following as a classroom base; TO located in the ceiling for video projection andcamera containing (2) Category 6 cables. Floor box beneath conference room table containingup to four Category 6 cables. TO containing (2) Category 6 cables per location for wirelessaccess points. Lab Areas, Computer Rooms and Other The specific cabling requirementsshall be determined on a case-by-case basis.

    18.5 Student Living Spaces

    18.5.1 Living Area / Living RoomEach living area or room shall have a minimum of (1) outlet with coax cable and one work areaoutlet with (1) Category 6 cable.

    18.5.2 BedroomThere shall be (1) SYSTIMAX CAT6 for voice per room and (1) SYSTIMAX CAT6 for data perpillow.

    18.5.3 Open, Lounge, Common and Other AreasThe specific cabling requirements shall be determined on a case-by-case basis.

    18.5.4 Tables, Desks and Study CarrelsThe specific cabling requirements shall be determined on a case-by-case basis.

    19 TESTING, IDE NTIFICATION AND ADMI NISTRATION

    19.1 TestingTesting of Copper UTP cables shall conform to the requirements of ANSI/TIA 568-CStandards. Channel link for Cat6 cable shall be a minimum of 6db headroom. Permanent linkfor Cat6 cable shall be a minimum of 3db headroom.Testing of Optical Fiber cables shall conform to the requirements of TIA 568-C Tier II. Inaddition, OTDR Traces will be provided for all fiber testing bi-directional and power meter.

  • 8/19/2019 u to Telecom Design and Construction Specifications

    33/34

    3320 ASU CABLE ID SCHEME

    20.1 Fiber Cabling Scheme:

    Intra-building:

    Building #, Cable #

    306B-X

    Example: From ER to TR, Building # - Cable #.

    306B-2, 306B-3, 306B-4, ETC !! .

    Inter-building:

    Building #, Building #, Cable #

    168-170-X

    Example: To - From, Building # - Building # - Cable #.

    In Building #168, Cable shall read, 170-168-1 .

    In Building #170, Cable shall read, 168-170-1 .

    LIU Labeling:

    ROOM # - LIU #

    250U1-L1

    Example:

    ROOM # 250U1, LIU #1 = 250U1-L1ROOM # 250U1, LIU #2 = 250U1-L2ROOM # 250U1, LIU #3 = 250U1-L3

  • 8/19/2019 u to Telecom Design and Construction Specifications

    34/34

    34

    20.2 Copper Cabling Scheme:

    Intra-building:

    Building #, Floor #, Cable #, Pair Cont

    306B-1-001-1-100

    Example: From ER to TR, Building #, Floor #, Cable #, Pair Count

    306B-2-2-1-100, 306B-3-3-1-100, 306B-4-4-1-100, ETC

    Inter-building:

    Building #, Building #, Floor #, Cable #, Pair Count

    168-170-1-001-1-100

    Example: To - From, Building # - Building # - Floor# - Cable # - Pair Count

    In Building #168, Cable shall read, 170-168-1-001-1-100 .

    In Building #170, Cable shall read, 168-170-1-001-1-100 .