tutorial 6 application of pilot scheme
DESCRIPTION
Application of Pilot Scheme DobleTRANSCRIPT
-
Application of Pilot Schemes
J. GosaliaDoble Engineering Company
Presentation Topics
2
Pilot Schemes
What is Pilot
protection scheme?
Basic Principle
Types of pilot
schemes
Comparison of different schemes
10th India Doble Power Forum Conference 119
Doble E
ngineering
Company
-
End Zone Faults
Zone 1 setting at A & B = 80% of the line length Fault at F1: seen in Zone 1 at A & B. Cleared instantaneously Fault at F2:
Cleared inst. at station B but in with Zone 2 time delay at A. Fault remains on the line for Zone 2 time delay
End Zone fault it is not cleared instantaneously
CA BF2
G GF1
End Zone Faults : Pilot Scheme
Fault on the protected line should be cleared instantaneously : Continuity of supply Limit the Damage & shock to electrical system Stability of the system Minimize Revenue loss $$$$........
Faults on the protected line including end zone fault can be cleared by employing pilot scheme Each end communicates with the other end to clear faults
on the protected line instantaneously
10th India Doble Power Forum Conference 120
Doble E
ngineering
Company
-
Direct Transfer Trip Scheme : DTT
21
Z1
TripZ2
Z321
Z1
TripZ2
Z3
G G
SignalingChannel
SignalingChannel
Direct Transfer Trip Scheme : Logic
21
Z1
TripZ2
Z3
Signal ReceiveSignal Send
Mal operation of the signaling equipment may result in an unnecessary tripping
To avoid mal operation, signal receive can be supervised by the distance element Z2 before issuing trip command
10th India Doble Power Forum Conference 121
Doble E
ngineering
Company
-
Permissive Under Reach TT Scheme
21
Z1
TripZ2
Signal Receive Signal Send
&
Z2t
Signal is sent to remote terminal if Z1 operates.If signal is received from remote terminal then tripping is issued instantaneously if local Zone 2 see the fault
G GZ1
Z2Z1
Permissive Under Reach TT Scheme
21
Z1
TripZ2
Signal Receive Signal Send
&
Z2t
For end Zone fault with the remote breaker open, fault will not be cleared inst.Use 52b contact to send the cont. permissive signal to remote end for open breaker.
G G
52bComm
10th India Doble Power Forum Conference 122
Doble E
ngineering
Company
-
PUTT Scheme : Caution
Fault near terminal A is not seen by Zone 1 at terminal B No current flows through terminal B Fault is seen as Zone 1 Fault at terminal A
Breaker at A trips instantaneously Now the fault current is fed via line CD and through B. Protection at B now sees the fault in Zone 2 but has no
permissive signal from terminal A to trip Fault is cleared after Zone 2 timer times out.
G
A
C
B
D
PUTT Scheme : Solution
As breaker A opens the permissive signal to B resets Now the fault is fed through breakers C,D and B Zone 2 at B picks up but has no permission from A to trip Solution : Add a time delay on drop out on a permissive
signal receive The drop out delay >= Zone 2 pick up time + safety margin
G
C D
A B
10th India Doble Power Forum Conference 123
Doble E
ngineering
Company
-
PUTT : Logic
21
Z1
TripZ2
Signal Receive Signal Send
&
Z2t
52b
td
PUTT : Limitation
For Short line followed by a long line: Fault with the fault resistance may not be seen in Zone 1 PUTT scheme fails to clear the fault on the line Fault is cleared in Zone 2 time
ZR
Zs
Zone 1
Zone 2
10th India Doble Power Forum Conference 124
Doble E
ngineering
Company
-
POTT Scheme
21
Z1
Z2
Z3
G G
&Trip 21
Z1
Z2
Z3
&Trip
SignalingChannel
SignalingChannel
POTT : Logic
21
Z1
Z2
Z3
&Trip
Signal Receive
Signal Send
10th India Doble Power Forum Conference 125
Doble E
ngineering
Company
-
POTT : Fault Resistance Coverage
Zs
Zone 1
Zone 2
Permissive Overreach TT Scheme
G
A
C
B
D
G
C sees Zone 2 fault, B sees zone 1 fault Fault current flows C-D-B D receives permission to trip from C but D sees reverse fault Breaker B opens as it sees the fault in Zone 1 Now the fault current reverses and flows through D-C-A D sees Zone 2 fault, C does not see fault and zone 2 resets and
stop sending permissive signal to D If D Zone 2 picks up before Zone 2 at C resets, D can trip If C Zone 2 is slow to reset it can trip for a fault on parallel line
10th India Doble Power Forum Conference 126
Doble E
ngineering
Company
-
POTT : Solution
21
Z1
Z2
Z3
&Trip
Signal Send
Signal Receive
tp
Adding a time delay tp in Signal Send will prevent mal operationtp > Fast PU local Z2 time slowest reset time of remote Z2 time
POTT Scheme :Remote Breaker Open
G G
A sees Zone 2 fault, B does not see fault as it is open A can not trip instantaneously as it does not receive the
permissive signal from B If the local breaker is open and receives permissive signal from
remote end, the permissive signal can be Echoed back to remote breaker
Now the breaker A can trip to clear the fault on the line
A B
10th India Doble Power Forum Conference 127
Doble E
ngineering
Company
-
POTT : Signal Echo Logic
T1 & T2 &Signal Send
Signal Receive
52b
T1 timer avoid sending Echo if breaker is tripped by other protection
T2 avoids continuous Echo
POTT : Logic
Signal Receive
Signal Send
21
Z1
Z2
Z3
& Trip
FSK logicTrip and
Guard Freq. When Permissive signal is
received from Remote End guard frequency is lost and trip freq is received
Permissive Trip is issued by signaling equipment to protection when guard frequency is lost and trip frequency is received
PLCC equipment transmit guard and trip freq. over power line
10th India Doble Power Forum Conference 128
Doble E
ngineering
Company
-
POTT : Caution
Line TrapG
FSK logicTrip and
Guard Freq.
Coupling cap
G
FSK logicTrip and
Guard Freq.
Coupling cap
Guard as well as trip frequency can not be transmitted or attenuated due to fault on the power line
Line Trap
Un Blocking Scheme
POTT scheme Trip frequency must be received & guard
frequency must be lost to issue permissive signal Un Blocking Scheme
Enhanced POTT scheme If guard frequency is lost then permissive trip
signal is issued only for 100-150 mSecs. If Z2 is picked up protection trip during this time After this time permissive trip signal is only issued
if guard frequency is lost & trip frequency received Very secure and reliable scheme
10th India Doble Power Forum Conference 129
Doble E
ngineering
Company
-
POTT Scheme : Weak In feed
Fault near the remote terminal is seen as Zone 2 at local terminal Needs permissive trip signal from remote end to clear
the fault Remote end has a week source contributing to the
fault : Z2 at remote end does not pick up and no permissive signal is sent at local end
Fault on the line is not cleared instantaneously
G
G
Z1
Z2
POTT : Weak In Feed
G
G
Z1
Z2
Z3
Signal Receive
Z3&
Echo Signal Send
Trip local Br.
10th India Doble Power Forum Conference 130
Doble E
ngineering
Company
-
Blocking Scheme
Simple scheme Very popular in N. America Comm. channel only sends the blocking signal to
remote end to block tripping Unlike POTT scheme where guard signal is sent
continuous Z3 is set reverse looking
Z3 Picks up and sends the blocking signal indicating fault is beyond the protected line section
Blocking Scheme
G
G
Z1
Z2
Z3
Fault near the remote terminal is seen as Zone 2 at local terminal Remote Z3 does not see the fault No blocking signal is sent Trip is issued after a time delay tp to clear fault
For fault beyond remote terminal Z3 reverse looking picks up & send block signal No trip at local terminal
10th India Doble Power Forum Conference 131
Doble E
ngineering
Company
-
Blocking Scheme : Logic
Z3&
Signal Send
Signal Receive
Z2
&Trip local Br.
tp
G
G
Z1
Z2
Z3
Blocking Vs. Permissive Scheme
Signal Receive: Blocks local inst. Z2 tripping
Signaling channel is normally OFF. only ON when Z3 picks up
When Z2 picks up, it waits for a time delay tp before issuing trip to ensure remote terminal has a time to send block signal
Signal Receive trips Z2 instantaneously
Signaling channel is ON all the time sending Guard frequency and changes to trip freq. if Z2 picks up
No intentional time delay for tripping if permissive signal is received
10th India Doble Power Forum Conference 132
Doble E
ngineering
Company
-
Blocking Vs. POTT : Comparison Intentional time delay
added to avoid over tripping
Failure of the communication channel may results in over tripping for an external fault
Blocking scheme is more dependable
Single On/Off signaling channel in use operating at single frequency in both direction
No intentional time delay on trip for a fault on the line
Failure of the communication channel may results in a failure to trip for a fault on the line
POTT scheme is more secure
Separate signaling channel for each direction of signaling
Un Blocking scheme combines security of POTT scheme &Dependability of Blocking scheme
Selection of Pilot Scheme?
Deciding factors Reliability of signaling channels
N. America for 115/230 kV lines, blocking scheme is used frequently
Reliability is quite good
Operating speed Fault clearing time requirement
System operating practice
10th India Doble Power Forum Conference 133
Doble E
ngineering
Company
-
Special Schemes
Zone 1 extension scheme No communication channel is used Economical, Simple Used along with Auto Reclosing protection 95% of all the faults are transient fault
Phase distance and time over current protection in blocking scheme Phase distance works like any other blocking scheme Ground distance protection has limited fault resistance coverage Little or not fault coverage for short line and/or strong source Time over current protection for ground fault provides higher fault
resistance coverage
Zone 1 Ext. Scheme
Zone 1 is set to over reach by setting Z1x Z1x reach of AB is set to 20% in to the line section CD If the fault occurs in line section CD, breaker A and C trips High speed Auto Reclose protection closes the breakers
A & C During the same time, the Z1x reach is pulled back to Z1 If the fault is permanent on the next line section only
breaker C will trip and breaker A does not trip If the fault is transient, interruption in power transfer is
minimal
G GZ1
Z1x
21/79
A B C D
10th India Doble Power Forum Conference 134
Doble E
ngineering
Company
-
Zone 1 Ext. Scheme : Logic
Auto RecloseIn progress
Z1
& Z1 trip.Z1x
&
79
Zone 1 Ext. Scheme: Pros & Cons
Transient faults on the line are cleared instantaneously without the need for elaborate communication equipment
Permanent end Zone faults are cleared in Zone 2 time
Transient faults in the next line section will create unnecessary tripping and reclosing of the circuit breaker This is the main disadvantage when interconnected
high voltage power system when several feeders can terminate at a single bus
10th India Doble Power Forum Conference 135
Doble E
ngineering
Company
-
Pilot Scheme: 21P and 50/51G
Protection A and B: Block signal is sent to remote end by high speed non dir. ground
time over current element The block signal is cancelled by the ground directional element Block signal is received, 50 HS with directional element picked up. Wait for a time delay tp to see if block signal is cancelled Once the block signal is cancelled protection A and B trips to clear
the fault on the line
G GZ1
21P50/51G
A B C D
21P50/51G
Ground Fault
36
Z1A B
GG
50
67&
tp
50
67&
tp
10th India Doble Power Forum Conference 136
Doble E
ngineering
Company
-
Pilot Scheme: 21P and 50/51G Blocking scheme : 21P as discussed earlier Ground over current uses 50/51 and directional protection 67
Local End: (Forward fault) Block signal is sent to remote end by non directional ground
time over current element (50 HS) The block signal is cancelled by the ground directional
element sees the forward fault. Remote End: (Forward Fault)
High set is picked up (50 HS) and directional element picked up & block signal is received
Wait for a time delay tp for block signal to be removed from the remote end
Block signal from the local end is cancelled by the directional element of the local end
Once the block signal is cancelled remote end trips.
10th India Doble Power Forum Conference 137
Doble E
ngineering
Company