TrueZONE® for Hydronic ControlWiring Diagrams
2
Hot Water Zone Valve or Circulator Relay Panel Control
TrueZONE HZ322 with Hot Water Zone Valve or Circulator Relay Panel ...................................................................4
Hot Water Zone Valves with A/C Dampers
TrueZONE HZ311 with Hot Water Zone Valves and A/C Dampers ...........................................................................4
TrueZONE HZ432 with Hot Water Zone Valves and A/C Dampers ...........................................................................4
Hot Water Zone Valve or Circulator Relay Panel with A/C Dampers
TrueZONE HZ311 with Hot Water Zone Valve or Circulator Relay Panel and A/C Dampers .....................................5
TrueZONE HZ322 with Hot Water Zone Valve or Circulator Relay Panel and A/C Dampers .....................................5
TrueZONE HZ432 with Hot Water Zone Valve or Circulator Relay Panel and A/C Dampers .....................................5
Hydro-air Applications
TrueZONE HZ311 with Hydro-air Application ............................................................................................................6
TrueZONE HZ322 with Hydro-air Application ............................................................................................................6
Honeywell’s TrueZONE® panels can control zone valves and circulator
relays in hydronic heating applications. This document provides helpful
wiring diagrams to assist you in a variety of installation scenarios.
HZ311 HZ322 HZ432
3
Wireless Zone Valve Control
Wireless TrueZONE HZ322 with Hot Water Zone Valve control .................................................................................6
Wireless TrueZONE HZ432 with Hot Water Zone Valve control .................................................................................6
Wireless Circulator Control
Wireless TrueZONE HZ322 with Hot Water Circulator control ...................................................................................7
Wireless TrueZONE HZ432 with Hot Water Circulator control ...................................................................................7
Wireless Relay Panel Control
Wireless TrueZONE HZ432 with Hot Water Relay Panels .........................................................................................7
When used with our RedLINK-enabled TrueZONE® panels, our Wireless
Adapter and Wireless FocusPRO® Thermostat you can easily – and
wirelessly – add hydronic zoning to a home or add more zones to an
existing system. In addition, wireless hydronic zoning introduces the
opportunity to increase profit with add-on accessories such as the
Portable Comfort Control and Wireless Outdoor Sensor – for the ultimate
in convenience and control.
TM
Wireless FocusPRO Thermostats TrueZONE Panel Wireless Adapter
+
Portable Comfort Control
Optional Wireless Accessories
Wireless Outdoor Sensor
4
Hot Water Zone Valve or Circulator Relay Panel Control
RHRC
W1/EW2Y1Y2GOB
DS/BK
HZ322
HEAT 1HEAT 2COOL 1COOL 2
FANPURGE
EM HEAT
ZONE 1
ZONE 2
ZONE 3
EMERGENCYHEAT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
SE
NS
OR
DATSDATS
EQ
UIP
ME
NT
RC
PO
WE
R
M1M4M6
RC
W1/EW2Y1Y2G
O/BL
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
Zone 1 Thermostat
Power-closedSpring-open
ARD or ZD Damper
Wire zones 1-2 the same as zone 3.
Rc
WG
YR
h
Zone valve or circulator relay panel
Zo
ne
1 T
( R
)
T
( W
)
HZ322 zone panel controlling a zone valve or circulator relay panel.
Remove the Rh/Rc jumper on the equipment terminals of the HZ322
C7735A1000
Fan Relay
Compressor Relay
Cooling Transformer
C
RL1
L2
24 volt transformer
TrueZONE HZ322 with Hot Water Zone Valve or Circulator Relay Panel
Hot Water Zone Valves with A/C Dampers
There are different ways to wire zone valves to the aquastat. For complete wiring instructions on any of the zone valve and aquastat refer to the product data sheets for those controls.
M1M4M6RCWYG
M1M4M6RCWYG
M1M4M6RCWYG
RhRcWYG
RC
DATSDATS
PURGE OVERRIDE
HZ311
HEATCOOLFAN
PURGE
ZONE 1ZONE 2ZONE 3
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
EQ
UIP
ME
NT
PO
WE
RS
EN
SO
R
Zone 1 Thermostat
Rc
WG
YR
h
Power-closedSpring-open
ARD or ZD Damper
Th T
r
Wire zones 2 and 3 the same as zone 1.
(Yellow wires)Compressor Relay
Fan Relay
Cooling Transformer
The thermostats used must have separate Rh andRc (or R and Rc) terminals with jumper removed.
C7735A1000
HZ311 zone panel controlling air-conditioning zoned with dampers and heating zoned with hot water zone valves.
V8043 zone valve
24 volt transformer CR
L1 L2
C
RL1
L2
24 volt transformer
TrueZONE HZ311 with Hot Water Zone Valves and A/C Dampers
HZ432 zone panel controlling air-conditioning zoned with dampers and heating zoned with hot water zone valves.
HZ432
HEAT 1HEAT 2HEAT 3COOL 1COOL 2PURGE
FANEM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCYHEAT
M1M4M6
RC
W1/EW2W3Y1Y2G
O/BL
M1M4M6RCW1/EW2W3Y1Y2GO/BL
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
M1M4M6RC
W1/EW2W3Y1Y2G
O/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2W3Y1Y2GO/BL
RC
PO
WE
RA
CC
ES
SO
RIE
S
AZ1AZ2
OTOT
SE
NS
OR
S
DATSDATS
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne
4D
AM
PE
RT
HE
RM
OS
TA
TR
F P
OR
T
RHRC
W1/EW2W3Y1Y2GOB
DS/BK
EQ
UIP
ME
NT
HOMECONFIG
CHECK OUT
ADJUST SETTING
C7735A1000
Fan Relay
Compressor Relay
Cooling Transformer
Power-closedSpring-open
ARD or ZD Damper
Zone 1 Thermostat
Rc
WG
YR
h
Th
Tr(Yellow wires)
V8043 zone valve
*There are different ways to wire zone valves to the aquastat. For complete wiring instructions on any of the zone valve and aquastat refer to the product data sheets for those controls.
Wire zones 2 -4 the same as zone 1.
The thermostats used must have separate Rh and Rc (or R and Rc) terminals with jumper removed.
C
RL1
L2
24 volt transformer
C R
L1L2
24 volt transformer
TrueZONE HZ432 with Hot Water Zone Valves and A/C Dampers
5
Hot Water Zone Valve or Circulator Relay Panel with A/C Dampers
M1M4M6RCWYG
M1M4M6RCWYG
M1M4M6RCWYG
RhRcWYG
RC
DATSDATS
PURGE OVERRIDE
HZ311
HEATCOOLFAN
PURGE
ZONE 1ZONE 2ZONE 3
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
EQ
UIP
ME
NT
PO
WE
RS
EN
SO
R
Zone 1 Thermostat
Rc
WG
YR
h
Power-closedSpring-open
ARD or ZD Damper
Compressor Relay
Fan Relay
Cooling Transformer
C7735A1000
HZ311 zone panel controlling air-conditioning zoned with dampers and heating zoned with a zone valve or circulator relay panel.
M1M4M6RCWYG
M1M4M6RCWYG
M1M4M6RCWYG
RhRcWYG
RC
DATSDATS
PURGE OVERRIDE
HZ311
HEATCOOLFAN
PURGE
ZONE 1ZONE 2ZONE 3
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne
2D
AM
PE
RT
HE
RM
OS
TA
T
EQ
UIP
ME
NT
PO
WE
RS
EN
SO
R
ARD or ZD Damper
Wire zones 2 and 3 the same as zone 1.
Thermostats need to be configured to energize fan in heat.
C7735A1000
HZ311 zone panel controlling a hydro-air application * Remove the Rh/Rc jumper on the equipment terminals of the HZ311
Wire zones 2 and 3 the same as zone 1.
The thermostats used must have separate Rh and Rc (or R and Rc) terminals with jumper removed.
Zone valve or circulator relay panel
Zo
ne 1
T ( R
) T ( W
)
Aquastat
T (
R )
T (
W )
Fan relay center
G
Y
R
Zone 3 Thermostat
Rc
WG
YR
h
*
C
RL1
L2
24 volt transformer
C
RL1
L2
24 volt transformer
TrueZONE HZ311 with Hot Water Zone Valve or Circulator Relay Panel
and A/C Dampers
HZ432
HEAT 1HEAT 2HEAT 3COOL 1COOL 2PURGE
FANEM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCYHEAT
M1M4M6
RC
W1/EW2W3Y1Y2G
O/BL
M1M4M6RCW1/EW2W3Y1Y2GO/BL
Zo
ne 3
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RC
W1/EW2W3Y1Y2G
O/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2W3Y1Y2GO/BL
RC
PO
WE
RA
CC
ES
SO
RIE
S
AZ1AZ2
OTOT
SE
NS
OR
S
DATSDATS
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne
4D
AM
PE
RT
HE
RM
OS
TA
TR
F P
OR
T
RHRC
W1/EW2W3Y1Y2GOB
DS/BK
EQ
UIP
ME
NT
HOMECONFIG
CHECK OUT
ADJUST SETTING
HZ432 zone panel controlling air-conditioning zoned with dampers and heating zoned with a zone valve or circulator relay panel.
Wire zones 2 and 3 the same as zone 1.
The thermostats used must have separate Rh and Rc (or R and Rc) terminals with jumper removed.
C7735A1000
Fan Relay
Compressor Relay
Cooling Transformer
Power-closedSpring-open
ARD or ZD Damper
Zone 1 Thermostat
Rc
WG
YR
h
Zone valve or circulator relay panel
Zon
e 1
T ( R
) T ( W
)
C
RL1
L2
24 volt transformer
TrueZONE HZ432 with Hot Water Zone Valve or Circulator Relay Panel
and A/C Dampers
RHRC
W1/EW2Y1Y2GOB
DS/BK
HZ322
HEAT 1HEAT 2COOL 1COOL 2
FANPURGE
EM HEAT
ZONE 1
ZONE 2
ZONE 3
EMERGENCYHEAT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
SE
NS
OR
DATSDATS
EQ
UIP
ME
NT
RC
PO
WE
R
M1M4M6
RC
W1/EW2Y1Y2G
O/BL
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
HZ322 zone panel controlling air-conditioning zoned with dampers and heating zoned with a zone valve or circulator relay panel.
Wire zones 2 and 3 the same as zone 1.
The thermostats used must have separate Rh and Rc (or R and Rc) terminals with jumper removed.
C7735A1000
Fan Relay
Compressor Relay
Cooling Transformer
Power-closedSpring-open
ARD or ZD Damper
Zone 1 Thermostat
Rc
WG
YR
h
Zone valve or circulator relay panel
Zo
ne 1
T ( R
) T ( W
)
C
RL1
L2
24 volt transformer
TrueZONE HZ322 with Hot Water Zone Valve or Circulator Relay Panel
and A/C Dampers
6
M1M4M6RCWYG
M1M4M6RCWYG
M1M4M6RCWYG
RhRcWYG
RC
DATSDATS
PURGE OVERRIDE
HZ311
HEATCOOLFAN
PURGE
ZONE 1ZONE 2ZONE 3
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
EQ
UIP
ME
NT
PO
WE
RS
EN
SO
R
Zone 1 Thermostat
Rc
WG
YR
h
Power-closedSpring-open
ARD or ZD Damper
Compressor Relay
Fan Relay
Cooling Transformer
C7735A1000
HZ311 zone panel controlling air-conditioning zoned with dampers and heating zoned with a zone valve or circulator relay panel.
M1M4M6RCWYG
M1M4M6RCWYG
M1M4M6RCWYG
RhRcWYG
RC
DATSDATS
PURGE OVERRIDE
HZ311
HEATCOOLFAN
PURGE
ZONE 1ZONE 2ZONE 3
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne
2D
AM
PE
RT
HE
RM
OS
TA
T
EQ
UIP
ME
NT
PO
WE
RS
EN
SO
RARD or ZD Damper
Wire zones 2 and 3 the same as zone 1.
Thermostats need to be configured to energize fan in heat.
C7735A1000
HZ311 zone panel controlling a hydro-air application * Remove the Rh/Rc jumper on the equipment terminals of the HZ311
Wire zones 2 and 3 the same as zone 1.
The thermostats used must have separate Rh and Rc (or R and Rc) terminals with jumper removed.
Zone valve or circulator relay panel
Zo
ne 1
T ( R
) T ( W
)
Aquastat
T (
R )
T (
W )
Fan relay center
G
Y
R
Zone 3 Thermostat
Rc
WG
YR
h
*
C
RL1
L2
24 volt transformer
C
RL1
L2
24 volt transformer
Hydro-air Applications
TrueZONE HZ311 with Hydro-air Application
Wireless Zone Valve Control
ABCD
THM4000R
RHRC
W1/EW2Y1Y2GOB
DS/BK
HZ322
HEAT 1HEAT 2COOL 1COOL 2
FANPURGE
EM HEAT
ZONE 1
ZONE 2
ZONE 3
EMERGENCYHEAT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
SE
NS
OR
DATSDATS
EQ
UIP
ME
NT
RC
PO
WE
R
M1M4M6
RC
W1/EW2Y1Y2G
O/BL
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
ABCDW
IRE
LE
SS
WIRELESSHOME
CONFIGCHECK OUT MODE
BACK NEXTADJUST SETTING
Wireless HZ322 zone panel controlling zone valves.
Transformer
Remove the Rh/Rc jumper at the panel.
C7735A1000
TH
TR
End sw
itch
V8043 zone valve(or equivalent)
Fan center
C
R
If the Honeywell valve has yellow and red wires instead of terminal connections, the red wires are the end switch, the yellow wires are the TH and TR.
C
G
Y
R
Outdoor condenser
TH
TR
End
sw
itch
TH
TR
End
sw
itch
Wire the end switch from each valve in parallel to the R and W or T and T at the aquastat or boiler.
D
D
C
B
A
A
If cooling is zoned, the dampers (not shown), are wired as normal to the Truezone panel.
B
C
B
B
C
Wireless adaptor*
Parts needed:1. Wireless Truezone panels: (Verify the box has a Redlink sticker on it)HZ322K - 3-zones, 2 heat/2 cool.
2. Wireless thermostats with adaptor for zone 1: Option 1: YTH6320R1023 is a kit that includes a TH6320R wireless programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.Option 2: YTH5320R1025 is a kit that includes a TH5320R wireless non-programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.
3. Wireless thermostats without adaptor for zones 2-3: Option 1: TH6320R1004 - Wireless programmable thermostat without adaptor.Option 2: TH5320R1002 – Wireless non- programmable thermostat without adaptor.
Accessories: (optional)REM5000R1001 - Remote Controller (Can control up to 16 thermostats)C7089R1013 - Wireless Outdoor Sensor.
Aquastat
T(R
) T
(W)
Wireless TrueZONE HZ322 with Hot Water Zone Valve control
HZ432
HEAT 1HEAT 2HEAT 3COOL 1COOL 2PURGE
FANEM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCYHEAT
M1M4M6
RC
W1/EW2W3Y1Y2G
O/BL
M1M4M6RCW1/EW2W3Y1Y2GO/BL
Zo
ne 3
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RC
W1/EW2W3Y1Y2G
O/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2W3Y1Y2GO/BL
RC
PO
WE
RA
CC
ES
SO
RIE
S
AZ1AZ2
OTOT
SE
NS
OR
S
DATSDATS
Zo
ne
1D
AM
PE
RT
HE
RM
OS
TA
T
Zo
ne
4D
AM
PE
RT
HE
RM
OS
TA
T
RHRC
W1/EW2W3Y1Y2GOB
DS/BK
EQ
UIP
ME
NT
HOMECONFIG
CHECK OUT
ADJUST SETTING
ABCDW
IRE
LE
SS
ABCD
THM4000R
Wireless HZ432 zone panel controlling zone valves.
Transformer
Remove the Rh/Rc jumper at the panel.
Aquastat
T(R
) T
(W)
C7735A1000
TH
TR
End sw
itch
V8043 zone valve(or equivalent)
Fan center
C
R
If the Honeywell valve has yellow and red wires instead of terminal connections, the red wires are the end switch, the yellow wires are the TH and TR.
C
G
Y
R
Outdoor condenser
TH
TR
End
sw
itch
TH
TR
End
sw
itch
Wire the end switch from each valve in parallel to the R and W or T and T at the aquastat or boiler.
D
D
C
B
A
A
If cooling is zoned, the dampers (not shown), are wired as normal to the Truezone panel.
B
B
C
B
C
Wireless adaptor*
Parts needed:1. Wireless Truezone panel: (Verify the box has a Redlink sticker on it)HZ432K - 4-zones, 3 heat/2 cool. 2. Wireless thermostats with adaptor for zone 1: Option 1: YTH6320R1023 is a kit that includes a TH6320R wireless programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.Option 2: YTH5320R1025 is a kit that includes a TH5320R wireless non-programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.3. Wireless thermostats without adaptor for zones 2-4: Option 1: TH6320R1004 - Wireless programmable thermostat without adaptor.Option 2: TH5320R1002 – Wireless non- programmable thermostat without adaptor.
Accessories: (optional)REM5000R1001 - Remote Controller (Can control up to 16 thermostats)C7089R1013 - Wireless Outdoor Sensor.
E When a THM4000R is used you cannot expand beyond 4 zones.
E
TH
TR
End
sw
itch
B
C
Wireless TrueZONE HZ432 with Hot Water Zone Valve control
RHRC
W1/EW2Y1Y2GOB
DS/BK
HZ322
HEAT 1HEAT 2COOL 1COOL 2
FANPURGE
EM HEAT
ZONE 1
ZONE 2
ZONE 3
EMERGENCYHEAT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
SE
NS
OR
DATSDATS
EQ
UIP
ME
NT
RC
PO
WE
R
M1M4M6
RC
W1/EW2Y1Y2G
O/BL
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
HZ322 zone panel controlling a hydro-air application.
ARD or ZD Damper
Wire zones 2-3 the same as zone 1.
Zone panel needs to be configured to energize fan in heat.
R
C
L1
L2
Transformer
* Remove the Rh/Rc jumper on the equipment terminals of the HZ322
Aquastat
T (
R )
T (
W )
Fan relay center
G
Y
R
Zone 3 Thermostat
Rc
WG
YR
h
*
C7735A1000
TrueZONE HZ322 with Hydro-air Application
Remove the Rh/Rc jumper at the panel.
If the Honeywell valve has yellow and red wires instead of terminal connections, the red wires are the end switch, the yellow wires are the TH and TR.
Wire the end switch from each valve in parallel to the R and W or T and T at the aquastat or boiler.
If cooling is zoned, the dampers (not shown), are wired as normal to the TrueZONE panel.
See parts needed section on page 7.
D
C
B
A
Remove the Rh/Rc jumper at the panel.
If the Honeywell valve has yellow and red wires instead of terminal connections, the red wires are the end switch, the yellow wires are the TH and TR.
Wire the end switch from each valve in parallel to the R and W or T and T at the aquastat or boiler.
If cooling is zoned, the dampers (not shown), are wired as normal to the TrueZONE panel.
When a THM4000R is used you cannot expand beyond 4 zones.
See parts needed section on page 7.
D
C
B
A
E
7
14
36
14
36
1 4
3 6
ABCD
THM4000R
RHRC
W1/EW2Y1Y2GOB
DS/BK
HZ322
HEAT 1HEAT 2COOL 1COOL 2
FANPURGE
EM HEAT
ZONE 1
ZONE 2
ZONE 3
EMERGENCYHEAT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2Y1Y2GO/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
SE
NS
OR
DATSDATS
EQ
UIP
ME
NT
RC
PO
WE
R
M1M4M6
RC
W1/EW2Y1Y2G
O/BL
Zo
ne
3D
AM
PE
RT
HE
RM
OS
TA
T
ABCDW
IRE
LE
SS
WIRELESSHOME
CONFIGCHECK OUT MODE
BACK NEXTADJUST SETTING
Wireless HZ322 zone panel controlling circulators.
Transformer
Remove the Rh/Rc jumper at the panel.
C7735A1000
R8222D1014Fan center
C
R
Wire the 1 and 3 from each relay in parallel to the T and T (or R and W) terminals at the boiler or aquastat.
C
G
Y
R
Outdoorcondenser
C
C
B
A
A
If cooling is zoned, the dampers (not shown), are wired as normal to the Truezone panel.
Wireless adaptor*
Parts needed:1. Wireless Truezone panels: (Verify the box has a Redlink sticker on it)HZ322K - 3-zones, 2 heat/2 cool.
2. Wireless thermostats with adaptor for zone 1: Option 1: YTH6320R1023 is a kit that includes a TH6320R wireless programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.Option 2: YTH5320R1025 is a kit that includes a TH5320R wireless non-programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.
3. Wireless thermostats without adaptor for zones 2-3: Option 1: TH6320R1004 - Wireless programmable thermostat without adaptor.Option 2: TH5320R1002 – Wireless non- programmable thermostat without adaptor.
4. R8222D1014 relays (or other relay with low volt coil, and line volt rated double-pole normally-open switches)
Accessories: (optional)REM5000R1001 - Remote Controller (Can control up to 16 thermostats)C7089R1013 - Wireless Outdoor Sensor.
Circulator
It is up to the installing contractor to determine what voltage is required to power the transformer primary and circulators.
Line Voltage power
Aquastat
T(R
) T(W
)
D
E Each circulator circuit would be wired to the corresponding zone’s relay. This circuit is shown on zone 3 of this diagram.
B
C D E
C D E
L2
L1
Wireless Circulator Control
Wireless TrueZONE HZ322 with Hot Water Circulator control
Wireless Relay Panel Control
Wireless TrueZONE HZ432 with Hot Water Circulator control
14
36
14
36
14
361 4
3 6
Wireless HZ432 zone panel controlling circulators.
Remove the Rh/Rc jumper at the panel.
Wire the 1 and 3 from each relay in parallel to the T and T (or R and W) terminals at the boiler or aquastat.
Outdoor condenser
C
B
A
If cooling is zoned, the dampers (not shown), are wired as normal to the Truezone panel.
Parts needed:1. Wireless Truezone panels: (Verify the box has a Redlink sticker on it)HZ432K - 4-zones, 3 heat/2 cool.2. Wireless thermostats with adaptor for zone 1: Option 1: YTH6320R1023 is a kit that includes a TH6320R wireless programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.Option 2: YTH5320R1025 is a kit that includes a TH5320R wireless non-programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.3. Wireless thermostats without adaptor for zones 2-3: Option 1: TH6320R1004 - Wireless programmable thermostat without adaptor.Option 2: TH5320R1002 – Wireless non- programmable thermostat without adaptor.4. R8222D1014 relays (or other relay with low volt coil, and line volt rated double-pole normally-open switches)
Accessories: (optional)REM5000R1001 - Remote Controller (Can control up to 16 thermostats)C7089R1013 - Wireless Outdoor Sensor.
Circulator
It is up to the installing contractor to determine what voltage is required to power the transformer primary and circulators.
Aquastat
T(R
) T(W
)
D
E Each circulator circuit would be wired to the corresponding zone’s relay. This circuit is shown on zone 4 of this diagram.
B
ABCD
THM4000R
HZ432
HEAT 1HEAT 2HEAT 3COOL 1COOL 2PURGE
FANEM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCYHEAT
M1M4M6
RC
W1/EW2W3Y1Y2G
O/BL
M1M4M6RCW1/EW2W3Y1Y2GO/BL
Zo
ne 3
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RC
W1/EW2W3Y1Y2G
O/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2W3Y1Y2GO/BL
RC
PO
WE
RA
CC
ES
SO
RIE
S
AZ1AZ2
OTOT
SE
NS
OR
S
DATSDATS
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne
4D
AM
PE
RT
HE
RM
OS
TA
T
RHRC
W1/EW2W3Y1Y2GOB
DS/BK
EQ
UIP
ME
NT
HOMECONFIG
CHECK OUT
ADJUST SETTING
ABCDW
IRE
LE
SS
C
G
Y
R
A
Wireless adaptor*
F
C7735A1000
TransformerC
R
L2
L1
Fan center
Line Voltage power
F When a THM4000R is used you cannot expand beyond 4 zones.
C D E
C D E
C D E
C
1
3
Zone 1 of relay panel
T(R
)
T(W
)
C
1
3
Zone 3 of relay panel
T(R
)
T(W
)
C
1
3
Zone 2 of relay panel
T(R
)
T(W
)
C
1
3
Wireless HZ432 zone panel controlling a hot water relay panel.
Remove the Rh/Rc jumper at the panel.
Outdoor condenser
C
B
A
If cooling is zoned, the dampers (not shown), are wired as normal to the Truezone panel.
Parts needed:1. Wireless Truezone panels: (Verify the box has a Redlink sticker on it)HZ432K - 4-zones, 3 heat/2 cool.2. Wireless thermostats with adaptor for zone 1: Option 1: YTH6320R1023 is a kit that includes a TH6320R wireless programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.Option 2: YTH5320R1025 is a kit that includes a TH5320R wireless non-programmable thermostat, and THM4000R1000 wireless adaptor. You would need 1 of these per zone panel.3. Wireless thermostats without adaptor for zones 2-3: Option 1: TH6320R1004 - Wireless programmable thermostat without adaptor.Option 2: TH5320R1002 – Wireless non- programmable thermostat without adaptor.4. R8222B1067 relays (or other relay with low volt coil, and low-voltage rated normally-open switches)
Accessories: (optional)REM5000R1001 - Remote Controller (Can control up to 16 thermostats)C7089R1013 - Wireless Outdoor Sensor.
It is up to the installing contractor to determine what voltage is required to power the transformer primary and circulators.
Zone 4 of relay panel
T(R
) T(W
)
ABCD
THM4000R
HZ432
HEAT 1HEAT 2HEAT 3COOL 1COOL 2PURGE
FANEM HEAT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
EMERGENCYHEAT
M1M4M6
RC
W1/EW2W3Y1Y2G
O/BL
M1M4M6RCW1/EW2W3Y1Y2GO/BL
Zo
ne 3
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RC
W1/EW2W3Y1Y2G
O/BL
Zo
ne 2
DA
MP
ER
TH
ER
MO
ST
AT
M1M4M6RCW1/EW2W3Y1Y2GO/BL
RC
PO
WE
RA
CC
ES
SO
RIE
S
AZ1AZ2
OTOT
SE
NS
OR
S
DATSDATS
Zo
ne 1
DA
MP
ER
TH
ER
MO
ST
AT
Zo
ne
4D
AM
PE
RT
HE
RM
OS
TA
T
RHRC
W1/EW2W3Y1Y2GOB
DS/BK
EQ
UIP
ME
NT
HOMECONFIG
CHECK OUT
ADJUST SETTING
ABCDW
IRE
LE
SS
C
G
Y
R
A
Wireless adaptor*
F
C7735A1000
TransformerC
R
L2
L1
Fan center
Line Voltage power
D When a THM4000R is used you cannot expand beyond 4 zones.
C
B
Wireless TrueZONE HZ432 with Hot Water Relay Panels
Remove the Rh/Rc jumper at the panel.
It is up to the installing contractor to determine what voltage is required to power the transformer primary and circulators.
If cooling is zoned, the dampers (not shown), are wired as normal to the TrueZONE panel.
Wire the 1 and 3 from each relay in parallel to the T and T (or R and W) terminals at the boiler or aquastat.
Each circulator circuit would be wired to the corresponding zone’s relay. This circuit is shown on zone 3 of this diagram.
See parts needed section on page 7.
D
C
B
A
ERemove the Rh/Rc jumper at the panel.
It is up to the installing contractor to determine what voltage is required to power the transformer primary and circulators.
If cooling is zoned, the dampers (not shown), are wired as normal to the TrueZONE panel.
Wire the 1 and 3 from each relay in parallel to the T and T (or R and W) terminals at the boiler or aquastat.
Each circulator circuit would be wired to the corresponding zone’s relay. This circuit is shown on zone 4 of this diagram.
When a THM4000R is used you cannot expand beyond 4 zones.
See parts needed section on page 7.
D
C
B
A
E
F
Remove the Rh/Rc jumper at the panel.
It is up to the installing contractor to determine what voltage is required to power the transformer primary and circulators.
If cooling is zoned, the dampers (not shown), are wired as normal to the TrueZONE panel.
When a THM4000R is used you cannot expand beyond 4 zones.
See parts needed section on page 7.
D
C
B
A
Parts needed for wireless installation:
Verify the TrueZONE box has a RedLINK sticker on it.
Wireless Zoning Adaptor Kit: You would need 1 of these per zone panel
Programmable Wireless Zoning Adaptor Kit (YTH6320R1023)
Non-Programmable Wireless Zoning Adaptor Kit (YTH5320R1025)
*Wireless Adaptor (THM4000R): Connects to your choice of wireless thermostats
Programmable Wireless FocusPRO (TH6320R1004)
Non-Programmable Wireless FocusPRO (TH5320R1002)
Optional Wireless Accessories:
Portable Comfort Control (REM5000R1001)
Wireless Outdoor Sensor (C7089R1013)
TM
8
Automation and Control Solutions
In the US:
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422-3992
In Canada:
Honeywell Limited
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
67-7219 PRFebruary 2009© 2009 Honeywell International Inc.
Illustrated in this paper are the most common wiring diagrams for hydronic
application of the TrueZONE® control panel. It is the contractor's choice on
what options make most sense for their business and customer. With the
introduction of wireless hydronic zoning, this document will help create new
installation solutions, as well as opportunity to earn more profit with add-on
wireless accessories.
For questions, please contact the Honeywell Zoning Hotline toll-free at
1-800-828-8367