transmitter calibration

2
Isolator Calibration Example Input is 4-20mA and output is 4-20m A 1. Input 4mA into the unit and adjust the output with the OFFSET (zero) control until the output is also 4mA. 2. Input 20mA into the unit and adjust the output with the SPAN (gain) control until the output is also 20mA. 3. Repeat step 1 and 2 if necessary. 4. Check the output at half scale. Input 12mA and check that the output is 12mA. Transmitter Cali bration, Offset ( Ze ro), Span Most transm itters have two adjustments in common which are termed OFFSET (z ero) and SPA N (gain). These adjustments allow the output signal to be varied considerably, generally 20% of the transmitter range. Offset This adjustment sets what is in effect the value of output when the input is zero. Figure 1 shows the effect of altering the offset on a transmitter. Span  As can be se en from Figure 2, altering the SPAN changes the slope of the relationship between input and output signals. Calibration Principles The principle used in the calibration of transmitters is that if two points on a straight line are established then the line itself is established. By examining Figure 2 it can be seen that at low magnitudes of input signal the effect of span adjustment is very small. Consequently the first calibration point should be selected close to the bottom of the input range. The offset adjustment is then used to give the required output signal for the input signal being fed to the transmitter. Because alteration of the span results in a higher output deviation at the top end of the input range it follows that the second calibration point should be at this top end, say in the top 25%. Thus the calibration at this point is achieved by imposing an input signal of suitable magnitude and adjusting the span potentiometer to give the correct output. In practice it is sometimes difficult to eliminate the interaction effects between offset and span so it is recommended that the procedure for setting these two points be repeated until both points are obtained without the need for further adjustments.  Ana lo gue Process C ontro l Se rvices is a di vision of NESS Corporation

Upload: deborah-malanum

Post on 17-Oct-2015

13 views

Category:

Documents


0 download

DESCRIPTION

Calibration

TRANSCRIPT

  • Isolator Calibration Example

    Input is 4-20mA and output is 4-20mA

    1. Input 4mA into the unit and

    adjust the output with the

    OFFSET (zero) control until the

    output is also 4mA.

    2. Input 20mA into the unit and

    adjust the output with the SPAN

    (gain) control until the output is

    also 20mA.

    3. Repeat step 1 and 2 if

    necessary.

    4. Check the output at half scale.

    Input 12mA and check that the

    output is 12mA.

    T r a n s mi t t e r C a l ib r a t io n , O f fs e t ( Ze r o ) , S p a n

    Most transmitters have two adjustments in common which are termed OFFSET (zero) and SPAN(gain). These adjustments allow the output s ignal to be varied considerably, generally 20% of

    the transmitter range.

    Offset

    This adjustment sets what is in effect the value of output

    when the input is zero. Figure 1 shows the effect of

    altering the offset on a transmitter.

    Span

    As can be seen from

    Figure 2, altering the

    SPAN changes the

    slope of therelationship between

    input and output s ignals.

    Calibration Principles

    The principle used in the calibration of transmitters is that

    if two points on a straight line are established then the

    line itself is established. By examining Figure 2 it can be seen that at low magnitudes of input s ignal

    the effect of span adjustment is very small. Consequently the firs t calibration point should be selected close to the bottom of the input

    range. The offset adjustment is then used to give the required output s ignal for the input s ignal being fed to the transmitter.

    Because alteration of the span results in a higher output deviation at the top end of the input range it follows that the second calibration

    point should be at this top end, say in the top 25%. Thus the calibration at this point is achieved by imposing an input s ignal of suitable

    magnitude and adjusting the span potentiometer to give the correct output.

    In practice it is sometimes difficult to eliminate the interaction effects between offset and span so it is recommended that the procedure for

    setting these two points be repeated until both points are obtained without the need for further adjustments.

    Analogue Process Control Services is a division of NESS Corporation