transmittal of addendum - wylie · transmittal of addendum ***** instructions: acknowledge receipt...
TRANSCRIPT
j:\clerical\wylie\2015-155 nortex gsr\specs\re-bid\addendum\add-3 (re-bid).docx - 1 - Addendum No. 3
TRANSMITTAL OF ADDENDUM ************************************************************************************
INSTRUCTIONS:
Acknowledge receipt of Addenda in Proposal, on outer envelope of bid, AND WITH THE FORM
BELOW FAXED TO (214) 461-8390 or EMAIL TO: [email protected] upon receipt.
************************************************************************************
Addendum Acknowledgment FAX to (214) 461-8390 OR Email to: [email protected]
I Acknowledge the receipt of Addendum No. 3
City of Wylie, Texas
Project Name: Nortex 1.0-MG Ground Storage Reservoir (Bid #W2018-33-B)
By Facsimile Transmission on this date: January 15, 2018
Contractor’s Signature Company Name
E-Mail Address:
“PLEASE SIGN & FAX THIS PAGE BACK TO (214) 461-8390”
OR
“EMAIL A STATEMENT ACKNOWLEDGING RECEIPT”
(Indicate Date Received as verification that you received this Addendum)
Total Number of Fax Pages: 38
Note: This Addendum is being sent in PDF format with
page sizes being 8½” x 11” and/or 11” x 17” (or a
combination of both sizes). To print an 11” x 17”
PDF sheets, your print settings should be set at:
“Choose Paper Source by PDF Page Size”.
j:\clerical\wylie\2015-155 nortex gsr\specs\re-bid\addendum\add-3 (re-bid).docx - 2 - Addendum No. 3
CITY OF WYLIE, TEXAS
NORTEX 1.0-MG GROUND STORAGE RESERVOIR
Project No. W2018-33-B
ADDENDUM NO. 3
Plans and specifications for the Nortex 1.0-MG Ground Storage Reservoir (Project No. W2018-33-B),
for the City of Wylie, Texas, on which bids are to be received until 3:00 p.m., Friday, January 19,
2018, are hereby modified as follows:
1. CLARIFICATION QUESTIONS & ANSWERS:
The following questions and answers do not require any revision to the plans, specifications or
contract documents and are provided for clarification and information purposes:
A. (Q) There is no bid item for Mobilization, Bonds & Insurance. Where would you like for
us to include the costs?
(A) It is not unusual for there to be no separate bid item for these costs. The contractor is
solely responsible for including these subsidiary costs to the bid item or items as they
deem appropriate.
B. (Q) Can you clarify the excavation of the existing tank based on the bid items?
(A) Bid Item #4 includes the excavation of the first 4 feet of soil below the existing steel
tank and ring beam, whether contaminated (oiled sand) or not. There is approximately
800 cubic yards of material included in the excavation for this bid item. Bid Item #5 is
a contingency in case the contaminated soil extends beyond 4 feet below the existing
tank. The quantity for Bid Item #21 has been revised to account for the increased total
excavation quantity minus the amount for tank removal in Bid Item #4. A revised
geotechnical report issued with this addendum clarifies design parameters for the slab
and footing and increased the overall depth of excavation by 1 foot.
2. BID SCHEDULE
Please delete the Bid Schedule attached to the original specifications and contract documents and
replace it with the attached revised Bid Schedule (Pages BS-2A through BS-8A). The following
summarizes the revisions made to the attached Bid Schedule:
• Refer to Bid Item 21 – “Unclassified Excavation for GSR Minus Existing Tank Removal
(Plan Quantity)”:
The total overall quantity of excavation for the ground storage reservoir, including existing
tank removal is approximately 4,210 cubic yards. The approximate quantity of excavation
for the first 4 feet below the existing tank is 800 cubic yards. The revised plan quantity is
therefore, 3,410 cubic yards.
• Refer to Bid Item 22 – “Furnish & Install Flexible Base for Foundation and 3-foot Perimeter
Backfill for GSR (Plan Quantity)”:
The revised geotechnical report increased the thickness of the foundation by 1-foot
increasing the quantity of this item by 310 cubic yards.
Item
No.
Estimated
Quantity Unit
Price in
Figures
Extended
Amount
1 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
2 146 S.Y.
complete in place, the sum of
Dollars
and
Cents per
3 400 L.F.
complete in place, the sum of
Dollars
and
Cents per
4 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
5 4 V.F.
complete in place, the sum of
Dollars
and
Cents per
Project No. 2018-33-B
Remove & Properly Dispose of Additional
Contaminated Soil > 4-Ft. Below Existing Tank
Foundation
Vertical Foot
Linear Foot
Lump Sum
Lump Sum
Square Yard
Description and Price in Words
BID SCHEDULE
CITY OF WYLIE, TEXAS
Nortex 1.0-MG Ground Storage Reservoir
AWWA D110, Type III
Furnish & Install New Electrical Conduits &
Wiring from Existing Electrical Control
Building to Existing Pump Station Building
Construct Temporary Access Drive and
Temporary Gate to Existing Pump Station
Remove & Properly Dispose of Existing 917,500
Gallon Bolted Steel Tank, Ring Beam and Soil
(Net Cost)
Remove and Replace Existing 8-foot Security
Fence (Wood or Chain Link)
J:\CLERICAL\Wylie\2015-155 Nortex GSR\Specs\Re-Bid\Tech-Spec\06-P&BS-2.xlsx
BS-2A
Addendum No. 3
Item
No.
Estimated
Quantity Unit
Price in
Figures
Extended
Amount Description and Price in Words
6 317 S.Y.
complete in place, the sum of
Dollars
and
Cents per
7 418 S.Y.
complete in place, the sum of
Dollars
and
Cents per
8 26 L.F.
complete in place, the sum of
Dollars
and
Cents per
9 30 L.F.
complete in place, the sum of
Dollars
and
Cents per
10 104 L.F.
complete in place, the sum of
Dollars
and
Cents per
11 2 Ea.
complete in place, the sum of
Dollars
and
Cents per
Linear Foot
Each
Linear Foot
Linear Foot
Remove & Dispose of Existing 14" Discharge
Pipe
Remove & Dispose of Existing 24" Discharge
Pipe
Remove & Dispose of 14" Gate Valves
Remove & Dispose of Existing 14" Supply Pipe
Square Yard
Square Yard
Remove Existing 12' Wide, 6-inch Thick
Reinforced Concrete Access Drive on
Compacted Subgrade
Construct 12' Wide, 6-inch Thick Reinforced
Concrete Access Drive on Compacted Subgrade
J:\CLERICAL\Wylie\2015-155 Nortex GSR\Specs\Re-Bid\Tech-Spec\06-P&BS-2.xlsx
BS-3A
Addendum No. 3
Item
No.
Estimated
Quantity Unit
Price in
Figures
Extended
Amount Description and Price in Words
12 1 Ea.
complete in place, the sum of
Dollars
and
Cents per
13 30 L.F.
complete in place, the sum of
Dollars
and
Cents per
14 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
15 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
16 50 L.F.
complete in place, the sum of
Dollars
and
Cents per
17 1 Ea.
complete in place, the sum of
Dollars
and
Cents per Each
Remove & Dispose of 24" Butterfly Valves
Lump Sum
Each
Connect to Existing 14" Supply Piping
Linear Foot
Construct 14" Yard Supply Pipe Including
Bends & Fittings (Outside GSR Piping)
Connect to Existing 24" Discharge Piping
Lump Sum
Construct 24" Yard Discharge Pipe including
Bends & Fittings (Outside GSR Piping)
Furnish & Install 24" Butterfly Valve with
Extended Operator (Discharge Side)
Linear Foot
J:\CLERICAL\Wylie\2015-155 Nortex GSR\Specs\Re-Bid\Tech-Spec\06-P&BS-2.xlsx
BS-4A
Addendum No. 3
Item
No.
Estimated
Quantity Unit
Price in
Figures
Extended
Amount Description and Price in Words
18 1 Ea.
complete in place, the sum of
Dollars
and
Cents per
19 63 L.F.
complete in place, the sum of
Dollars
and
Cents per
20 1 Ea.
complete in place, the sum of
Dollars
and
Cents per
21 3,410 C.Y.
complete in place, the sum of
Dollars
and
Cents per
22 1,910 C.Y.
complete in place, the sum of
Dollars
and
Cents per
23 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
Cubic Yard
Lump Sum
Furnish & Install 6" PVC Pipe Underdrain,
Manhole and Duplex Sump Pumps
Furnish & Install 8" Gate Valve with Extended
Operator (Drain Line)
Unclassified Excavation for GSR Minus
Existing Tank Removal (Plan Quantity)
Each
Linear Foot
Construct 8" Yard Drain Line (Outside GSR
Piping)
Cubic Yard
Furnish & Install Flexible Base for Foundation
and 3-Foot Perimeter Backfill for GSR (Plan
Quantity)
Furnish & Install 14" Butterfly Valve with
Extended Operator (Supply Side)
Each
J:\CLERICAL\Wylie\2015-155 Nortex GSR\Specs\Re-Bid\Tech-Spec\06-P&BS-2.xlsx
BS-5A
Addendum No. 3
Item
No.
Estimated
Quantity Unit
Price in
Figures
Extended
Amount Description and Price in Words
24 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
25 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
26 2 Ea.
complete in place, the sum of
Dollars
and
Cents per
27 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
28 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
29 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
Lump Sum
Lump Sum
Each
For Preparing and Submitting an Excavation
Safety Plan that is in conformance to latest
OSHA Standards
Furnishing and Installing a Complete Excavation
Safety and Support System in full accordance
with latest OSHA Standards
Lump Sum
Site Work/Grading Including Overflow Flume
Lump Sum
Furnish & Install SolarBee Model SB500PWc
v20 Tank Mixers
For Constructing a 1,000,000 Gallon, AWWA
D110, Type III, Prestressed Concrete Ground
Storage Reservoir, Internal Piping, Backfill and
all related appurtenances
Furnish & Install All Electrical & SCADA for
entire GSR Project
Lump Sum
J:\CLERICAL\Wylie\2015-155 Nortex GSR\Specs\Re-Bid\Tech-Spec\06-P&BS-2.xlsx
BS-6A
Addendum No. 3
Item
No.
Estimated
Quantity Unit
Price in
Figures
Extended
Amount Description and Price in Words
30 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
31 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
32 146 S.Y.
complete in place, the sum of
Dollars
and
Cents per
33 225 L.F.
complete in place, the sum of
Dollars
and
Cents per
34 40 L.F.
complete in place, the sum of
Dollars
and
Cents per
35 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
Linear Foot
Lump Sum
Lump Sum
Restore Healthy Stand of Grass for All
Disturbed Areas
Remove Temporary Access Drive to Pump
Station and Restore Fence After GSR
Construction is Completed
Square Yard
Remove and Replace Existing 6-Foot Wood
Privacy Fence
Design & Implement Storm Water Pollution
Prevention Plan
Remove and Replace Existing 6-Foot Chain
Link Fence
Linear Foot
Construct Temporary Drive for Access to
Construction Easements
Lump Sum
J:\CLERICAL\Wylie\2015-155 Nortex GSR\Specs\Re-Bid\Tech-Spec\06-P&BS-2.xlsx
BS-7A
Addendum No. 3
Item
No.
Estimated
Quantity Unit
Price in
Figures
Extended
Amount Description and Price in Words
36 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
37 1 L.S.
complete in place, the sum of
Dollars
and
Cents per
38 1 L.S. 45,000.00$ 45,000.00$
complete in place, the sum of
Dollars
and
Cents per
TOTAL AMOUNT BID (Items 1 Through 38)
Bid Allowance
No
Lump Sum
Owner's Contingencies Allowance
Forty Five Thousand
Restore Irrigation Sysytem and Landscaping for
Temporary Access Easement
Lump Sum
Remove Temporary Drive for Access to
Construction Easements
Lump Sum
J:\CLERICAL\Wylie\2015-155 Nortex GSR\Specs\Re-Bid\Tech-Spec\06-P&BS-2.xlsx
BS-8A
Addendum No. 3
The seal appearing on this
document was authorized by
James F. Phipps, P.E. 84778
on August 15, 2016.
geotechnical and construction materials consultants
August 15, 2016 Report No. 15841G REVISED
Birkhoff, Hendricks & Carter, LLP 11910 Greenville Avenue, Suite 600 Dallas, Texas 775243 ATTN: Mr. Joe R. Carter, P.E., C.F.M. Phone: 214-361-7900 Email: [email protected]
RE: Geotechnical Investigation
Nortex Ground Storage Reservoir Towngate Drive Wylie, Texas
Gentlemen:
Presented herein is the report of a geotechnical investigation conducted by Henley-Johnston &
Associates, Inc. for the above referenced project.
We appreciate the opportunity to provide this report to you. If we can be of further service or if
you desire any additional information, please do not hesitate to call.
Signed,
HENLEY-JOHNSTON & Associates, Inc.
James F. Phipps, P.E.
Vice President
Firm Registration No.: F-1238
Copies submitted (1) Birkhoff, Hendricks & Carter, LLP – Mr. Joe R. Carter, P.E., C.F.M.
INDEX
INVESTIGATION AND ANALYSIS 1
Introduction 1
Field and Laboratory Investigation 1
Surface and Subsurface Conditions 2
Tank Pad Preparation 4
Excavations 5
Foundation Recommendations 6
Construction Considerations 6
Paving Recommendations 6
Earthwork Recommendations 8
Construction Testing and Observations 9
PLATES
Report No. 15841G REVISED August 15, 2016
- 1 -
INVESTIGATION AND ANALYSIS
Introduction
This report presents the results of a subsurface investigation performed for a proposed 1.0 million
gallon, concrete ground storage tank (GST) at the Nortex station located off Towngate Drive in
Wylie, Texas. At the time of this investigation, it was understood the proposed ground storage
tank would measure 74.56 feet in diameter, with a side water depth of 30.88 feet. The anticipated
contact pressure for this tank was estimated to be less than 2.1 ksf below the tank floor, and less
than 4 ksf beneath the tank perimeter. The finished floor elevation of the tank is anticipated to be
at least 1 foot above finished grade. Differential movements related to soil heave are to be
limited to 1 inch.
The purpose of this investigation was to identify and evaluated the subsurface conditions in the
area of the proposed tank. It was anticipated that a shallow foundation as described in ACI
372R-03 as consisting of a membrane floor slab with a monolithic perimeter wall footing would be
used for this project. Additionally, potential vertical movements due to soil heave are to be limited
to 1-inch. Per ACI, maximum differential settlement is to be limited to 0.7-inches or less from tank
center to tank edge for a 6-inch thick slab, and 0.35-inches for a 12-inch thick floor. Maximum tilt
is to be limited to 2.8-inches. Total uniform settlement is not to exceed 6 inches.
This report is specific to this project. Persons using the recommendations and information herein
for projects and/or designs not covered by this report do so at their own risk.
Field and Laboratory Investigation
As requested, subsurface conditions for this ground storage tank were evaluated with a single
core boring at the location staked in the field by the client. This location is presented on Plate 1.
The boring was drilled using a truck-mounted rig equipped with continuous flight augers and wet
rotary techniques. Drilling and sampling were done in general accordance with ASTM methods
and standards. Relatively undisturbed samples of cohesive soil and weathered shale were
obtained with three-inch diameter thin-walled Shelby tubes. Upon encountering the unweathered
strata, the hole was flushed of all cutting, temporary casing inserted and the rock cored near
continuous using an Nx-size, carbide tipped bit.
Core Recovery and Rock Quality Designation (RQD) were measured and recorded. The RQD value
provides an estimate of the variation of rock mass properties. RQD is calculated by summing the
length of all pieces of intact rock core greater than twice the diameter and dividing by the total length
drilled. Pieces shorter than twice the diameter broken mechanically (drilling) or by handling were
fitted together and considered as one piece. RQD is recorded on the "Log of Boring" illustration.
Water levels were estimated during drilling and upon completion of the boring. The water levels
noted during drilling are presented on the “Log of Boring” illustration. A shallow piezometer was
installed post-investigation to a depth of 15 feet adjacent to the location of Boring 1.
Observations from this piezometer are presented in the Surface and Subsurface Conditions
section.
Report No. 15841G REVISED August 15, 2016
- 2 -
All samples were transported to the central laboratory for visual classification and testing. Soils
were visually classified according to the Unified Soil Classification System (USCS). Rock
materials were described using standard geological nomenclature. The Boring Log and a key to
terms and symbols used on the log are attached.
To aid in the classification process, Atterberg Limits (ASTM D-4318) and Moisture Content
determinations (ASTM D-2216) tests were performed on representative samples. All of the
above test data are summarized on Plate 2.
The potential for heave was also evaluated using the Absorption Pressure-Swell test. This test
involves placing a 1-inch thick sample of soil in a 2.5-inch ID confining ring into a consolidation
machine and inundating it with water. Weight is added in appropriate increments to maintain the
original height and volume of the sample. Once the sample has “balanced”, the weight is
reduced to approximately 200 psf and the soil allowed to swell. Results of these tests are
summarized on Plate 3.
The strength of each cohesive sample was estimated using a hand penetrometer. The results of
these estimates are recorded graphically on the "Log of Boring" illustrations. The strength properties
of selected soil samples were investigated by Unconfined Compression tests. In the Unconfined
Compression test, axial load is applied to a laterally unsupported cylindrical sample until failure
occurs within the sample. This test is conducted fairly rapidly (failure within about 10 minutes) and
generally conforms to ASTM D 2166 for soil samples and D 7012 for rock core. Results of the
Unconfined Compression tests performed are summarized on Plate 3.
Unconsolidated-undrained multi-stage triaxial compression tests were performed on selected
samples of the clay and weathered shale materials. In this test, performed in general accordance
with ASTM D 2850, a cylindrical sample is enclosed in a membrane and subjected to a confining
pressure of about one-half the estimated overburden pressure. The sample is loaded axially to
incipient failure while not permitting drainage from the specimen. Upon reaching incipient failure, the
confining pressure is doubled and the specimen again loaded to incipient failure. This process is
repeated a third time and the sample is loaded past failure. The results of this test are presented
graphically on Plates 4 and 5 as stress-strain curves and Mohr’s diagrams.
The potential for settlement of the subgrade materials was evaluated using the consolidation test
(ASTM D- 2435). In this test a 1-inch thick sample of soil is placed into a 2.5-inch ID confining
ring and inserted into a consolidation machine and loaded to approximately 100 psf. Water is
then supplied to the sample and additional weight is added to ensure the clay sample does not
swell and change volume. After enough load has been applied to ensure the soil does not swell,
additional loads are added incrementally to consolidate the soil. Once the consolidation is
achieved, the sample is decrementally unloaded until the initial weight is achieved. Graphical
representation of changes in void ratio versus changes in vertical stress, and the change in height
of the samples for each applied load compared to elapsed time are presented on Plates 6
through 11.
Report No. 15841G REVISED August 15, 2016
- 3 -
Surface and Subsurface Conditions
Surface Conditions
At the time of the field investigation the area of the proposed tank was occupied by an existing,
ground-supported steel tank. Surface grades in this area were relatively flat.
Geologic Setting
Review of geologic maps indicates the proposed ground storage tank is located within the Lower
Ozan Formation, which is of the Cretaceous age and consists of dark to medium gray shale in the
unweathered state. The Ozan is calcareous in nature and upon weathering becomes lighter in
appearance and develops the properties of highly plastic (CH) clay. Progressive weathering
produces both CH and moderately plastic (CL) residual clays.
The residual soils are known to be expansive, while the activity of the weathered strata varies.
Subsurface Conditions
The specific type, depth, and thickness of materials penetrated by the borings are reflected on the
individual “Log of Boring” illustrations, which follow the illustrations for this report.
Dark brown, grading with depth to brown and light brown clays were encountered at the surface
and extended to a depth of 14 feet at the boring location. Olive-brown and light gray weathered
shale was present directly below the upper clays and continued to a depth of 54 feet. This shale
was calcareous and soft (rock hardness classification), and contained some gypsum seams
below a depth of 39 feet.
Slightly weathered shale was present at an elevation of 54 feet from the surface. This layer was
gray in appearance and soft, and contained some iron staining. Firm, gray unweathered shale
was noted at a depth of 60 feet. This shale material was fossiliferous and extended through the
termination depth of 70 feet.
The residual clays varied from dry to moist with depth at the time of sampling, while the
weathered shale was generally dry.
Ground water was noted a depth of 50 feet below existing grades during drilling. Just prior to
coring the water level had risen to 5 feet from the ground surface. Observations of the shallow
piezometer are presented in Table 1.
Table 1 Piezometer Readings for Nortex Ground Storage Reservoir
Towngate Drive – Wylie, Texas
Date Read Depth to Ground Water from Surface (ft.)
3/28/16 Installed / Dry
4/04/16 13.9
Rain 4/09/16 and 4/11/16
4/11/16 6.9
Rain 4/17/16
4/18/16 3.7
4/25/16 4.7
Report No. 15841G REVISED August 15, 2016
- 4 -
Based on this information, ground water should be anticipated as shallow as 3.7 feet from existing elevations during construction. Seismic Classifications
Based on the materials encountered within the borings and the geologic setting, this site may be -
classified as Seismic Class B according to the 2015 International Building Code and ASCE 7-10
as the soils and rock formations most closely match that designation.
Tank Pad Preparation
Ground supported storage tanks constructed over expansive soils will experience both heave as
a result of swelling from the clays, and also settlement due to foundation loads imposed by the
perimeter footing and contents of the tank.
Soil movements were evaluated using the TxDOT Method Tex-124-E “Method for Determining
Potential Vertical Rise of Soils”, and the results of the consolidation and absorption pressure-
swell tests. The TxDOT method is based on the results of a series of pressure-swell tests
performed on samples of varying moisture content and Plasticity Indices (PI), and uses the PI and
measured moisture contents of the samples in question.
In an open environment, movement within residual clay soils is generally seasonal in nature.
Heave occurs during periods of increased rainfall as a result of the clays gaining in moisture and
swelling. During hotter, drier months these same soils will lose moisture and subsequently
shrink. Soil movements are typically manifested as a gradual and sustained heave as the
subgrade clays gain moisture because of lack of evaporation. Also contributing to this heave can
be the infiltration of water from the exterior or from utility leaks and seepage from the tank.
Based on the heave analysis, total soil movements related to the underlying clays and weathered
shale were estimated to be on the order of 5 inches, or more, if soil supported elements are
placed over a relatively dry subgrade. If placed over a relatively moist subgrade, soil movements
were estimated to be on the order of 1 inch. Under current moisture conditions, the potential for
heave was estimated to be in the order of 4 inches.
The potential for settlement was evaluated based on the results of the consolidation test and the
anticipated applied loads from the tank footing and floor slab. Based on this analysis, total
settlement on the order of 1 inch at the tank center, and 2 inches at the perimeter are possible.
Anticipated total differential settlement between the center and tank edge is estimated to be on
the order of 1-1/2 inches.
In order to reduce the potential for heave to the order of 0.7-inch or less, it is recommended that a
minimum of 6 feet of granular fill be placed beneath the tank pad. The depth of the granular fill
should extended at least 5 feet below the perimeter footing.
The area of the tank should be excavated to a depth of 6 feet below the interior floor and 5 feet
below the perimeter footing. This excavation should extend a minimum of 5 feet beyond the
perimeter of the tank. The depth of excavation should be uniform across the area of the tank.
Report No. 15841G REVISED August 15, 2016
- 5 -
The sidewalls of the excavation should be constructed using an approximate 2-foot wide step and
bench.
The exposed subgrade at the base of the excavation should be ripped to a depth of 6 inches and
compacted per the Earthwork Recommendations section. A minimum 30-mil thick plastic liner
should be placed over the base of the excavation. This is to limit the infiltration of water into the
clay subgrade. The plastic liner should extend up the sidewalls of the excavation as well.
Granular fill used below the storage tank, this material should meet the gradation requirements of
ASTM C33, Size 357. A below grade drainage system should be placed around the perimeter of
the tank pad and below the depth of the granular fill, or the tank excavation sloped to drain to a
central sump. Water that collects within this drainage system should be discharged away from
the tank.
Proper placement of granular fill beneath the tank pad is estimated to limit the potential for heave
to the order of 1 inch over the life of the structure. Total settlement of the perimeter footing is also
estimated to be on the order of 1 inch for a properly compacted subgrade and footings sized
according to the Foundations Recommendations section of this report. Total differential
settlement between the tank center and edge is anticipated to not exceed 0.7 inch.
If construction of the tank pad will be delayed for more than 30 days after it is recommended that
a plastic barrier be placed over the conditioned soils to limit the loss of moisture within the
modified subgrade. This will also limit the infiltration of water from the tank into the subgrade
materials.
All existing foundations and utilities within the proposed tank pad should be removed and the
excavations backfilled using on-site soils or similar. Materials should be placed as outlined in the
Earthwork Recommendations section.
Excavations
Per Federal regulations, any excavation over 20 feet in depth will require an engineered
excavation and safety plan prepared by a licensed engineer. Soils encountered at this site
consisted of CH clays and weathered shale. It is recommended that these materials be treated
as Type B materials per OSHA Excavation Standards CFR 29, Part 1926, Sub-Part P, Appendix
A. For these soils, temporary excavations should be sloped back on a temporary maximum slope
of 1H:1V.
For any temporary retention system design, the clays and shale may be considered to exert an
equivalent fluid pressure of 50 pcf considering drained and active conditions against any shielding
or temporary shoring.
All spoils and construction materials should be kept a minimum of 4 feet from the edge of the
trench. Water should not be allowed to pond along the edge of or within the bottom of any
excavation.
Report No. 15841G REVISED August 15, 2016
- 6 -
Foundation Recommendations
It is anticipated that a shallow foundation, as described in ACI 372R-03, consisting of a
membrane floor slab with monolithic perimeter wall footings, would be used for support of the
tank. For this site, an allowable net bearing pressure of 4,000 psf may be used when evaluating
the foundation. This value includes a Factor of Safety of at least 3 with respect to the shear
strength of the underlying soils. All foundations should bear a minimum of 36 inches below
existing or finished grade, whichever is deeper.
The tank floor should be designed to not exceed a contact pressure of 3.0 ksf, while the perimeter
footing should not exceed an allowable contact pressure of 5.0 ksf. The footing should have a
minimum width of 3 feet and a maximum width of 5 feet. This office should be allowed to
evaluate the allowable contact pressure in the event the footing width will exceed 5 feet.
The footing and floor slab should bear directly on compacted granular fill as described in the
Tank Pad Preparation and Earthwork Recommendations sections of this report.
Construction Considerations
The foundation should be placed in proper plan location and the excavation cleared of all loose or
soft materials prior to concrete placement. Reinforcing steel cages should be prefabricated in a
rigid manner to allow expedient placement of both steel and concrete into the excavation. It is
essential that excavation of foundation elements and the placement of reinforcing steel and
concrete be carried out in a continuous operation. No portion of the stratum providing structural
support should be exposed to atmospheric conditions for more than eight (8) hours following the
completion of excavation and backfilling operations. If this time requirement cannot be met, it is
recommended that the base of any completed excavation be protected by placing a thin seal slab
of lean concrete or an approved alternate method of protection. Excavation for the tank should
be made with attention to drainage to keep the base of the excavation from collecting water
during wet weather periods. Permanent drainage should be maintained to provide the means of
removing water from the backfill materials during and after construction of the tank. It is
recommended that the subgrade below any granular material beneath the tank be sloped to drain
by gravity to a central collection sump and then collected and discharged away from the structure.
A minimum 30-mil thick plastic sheeting is recommended between the subgrade and granular
material.
In order to confirm compliance with specifications and acceptability of the bearing stratum, a
qualified and experienced geotechnical observer from this office should be present during
foundation installation.
Paving Recommendations
Asphalt Pavement:
Flexible asphalt pavement may be used for parking and drives. The upper six inches of subgrade
below asphalt pavement should be stabilized using approximately 8% hydrated lime (32 pounds
per square yard) to achieve a treated soil with a Plasticity Index of 15 or less. It is recommended
that site specific testing of the subgrade be performed to evaluate the actual amount of lime
required to provide a stabilized subgrade. Lime should be placed in general accordance with
Report No. 15841G REVISED August 15, 2016
- 7 -
Item 301.2 LIME TREATMENT the North Central Texas Council of Government (NCTCOG)
Standard Specifications for Public Works Construction published in 2004. Lime treated soils
should be compacted to a minimum of 95% of the maximum dry unit weight (ASMT D-698) with
moisture contents at or above optimum.
For light truck and car traffic the following section is recommended:
1” Type D Asphalt Surface Course over,
2” Type A or B Coarse Graded Base Course.
For heavy truck traffic the following section is recommended:
2” Type D Asphalt Surface Course over,
4” Type A or B Coarse Graded Base Course.
All asphalt should be placed in accordance with Item 302 of the NCTCOG standard. Compaction
tests and air void verification should be conducted to evaluate the in-place density of the asphalt
pavement.
All joints within asphalt pavements should be sealed and maintained to limit water infiltration into
the subgrade soils.
Concrete Pavement:
Sections for reinforced concrete paving were evaluated using the Interim AASHO and PCA
methods1. Considering light vehicular traffic and less than six, fully loaded trucks per day, the
following sections are recommended for a 20-year life span.
For light truck and car traffic the following section is recommended:
5” of 3,000 psi Portland Cement Concrete over,
6” of recompacted subgrade.
For heavy truck traffic up to 6 vehicles per day the following section is recommended:
6” of 3,000 psi Portland Cement Concrete over,
6” of recompacted subgrade.
Subgrade soils below concrete pavements should be compacted to a minimum of 95% (ASTM D-
698) with moisture contents between 0 and +4 percentage points.
1 Yoder, E.J., and Witczak, M.W., Principles of Pavement Design, 2nd Ed., John Wiley & Sons, Inc., New
York, NY, pp 605 to 608.
Report No. 15841G REVISED August 15, 2016
- 8 -
Concrete pavement should be reinforced with No. 3 deformed bars on 18-inch centers. No. 4
smooth dowels should be used at expansion and construction joints on 12-inch centers.
Control joints should be installed in the pavement within four hours after concrete has been
placed, not after completion of the pour. Joint spacing and depth should conform to the
recommendations presented in the latest version of Joint Design for Concrete Highways and
Street Pavements, produced by PCA. Spacing between control joints should not exceed 15-feet.
All joints should be sealed and periodically maintained. This will limit the potential for water to
infiltrate into the subgrade.
Expansion joints should consist of doweled keyways, thickened sections, or steel dowels
supported on a non-deteriorating medium such as bituminous mastic or bituminous impregnated
cellulous2. All expansion joints should be filled completely with sealant to the pavement surface.
Earthwork Recommendations
Areas that will receive fill should be stripped of all organic materials and ripped to a depth of 6
inches. The exposed subgrade should then be wetted as necessary and compacted to a
minimum of 95% of the maximum dry unit weight as determined by ASTM D-698. Moisture
content should be a minimum of +2% above the optimum moisture content.
On-site soils used as backfill against the tank or for utility trenches should be placed in maximum
eight-inch loose lifts and compacted to a minimum of 95% of the maximum unit dry weight as
determined by ASTM D-698. Moisture content should be a minimum of +2% above optimum
moisture content.
Any excavated weathered shale used for backfill against the tank or for utility trenches should be
reduced to a nominal diameter of 3 inches and wetted thoroughly to produce a uniform moisture
content throughout the material. Weathered shale should be placed in maximum 8-inch loose lifts
and compacted to a minimum of 95% of the maximum dry unit weight as determined by ASTM D-
698. Moisture contents should be a minimum of +2% of optimum as determined by ASTM D-698.
Granular fill used below the storage tank, this material should meet the gradation requirements of
ASTM C33, Size 357. This material should be placed in maximum 10 inch loose lifts and
compacted to a minimum of 95% of the maximum dry unit weight as determined by ASTM D
4253, Maximum Index Density and Unit Weight of Soils Using a Vibratory Table. Crushed
concrete, crushed stone or crushed pit-run gravel may be used. Material types may not be
mixed.
Granular fill should be tested for density using portable nuclear gauges set in the back-scatter
mode.
2 Guide for Design and Construction of Concrete Parking Lots, ACI Committee 330, NRMCA Publication
MSP 34, January 1988, p 330R-8.
Report No. 15841G REVISED August 15, 2016
- 9 -
Construction Testing and Observation
It is recommended that all backfill materials within a trench be tested for moisture and density at a
rate of one test per foot of fill for every 100 linear feet of excavation. Field density tests should be
conducted during placement of fill. Provisions should be made to permit safe access to the utility
trench during placement of fill to allow for testing of the backfill materials for adequate moisture
and density.
Density testing beneath the tank pad should be conducted at a rate of one test per lift for every
1,500 square feet of area. This equates to three tests per lift for a 95-foot diameter tank. Field
testing is to be conducted during placement of fill materials.
Periodic inspection of shallow foundations is recommended to ensure adherence with the
recommendations of this report.
PLATE
1
LEGEND
SOIL BORING
HJA No.:
DATE:
15841G
FEBRUARY 2016
TEXAS FIRM REGISTRATION NO. F-1238
BORING LOCATION PLAN
235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
1
NORTEX 1.0MG GROUND STORAGE TANK
TOWNGATE DRIVE
WYLIE, TEXAS
GEOTECHNICAL INVESTIGATION REPORT NO. 15841G
NORTEX 1.0 MG STORAGE TANK TOWNGATE DRIVE
WYLIE, TEXAS
Plate 2
SUMMARY OF INDEX PROPERTIES
BORING NUMBER
DEPTH (ft.)
LIQUID LIMIT (%)
PLASTIC INDEX
DUW
(pcf)
FINER #200 (%)
MOISTURE CONTENT
(%)
UNIFIED SOIL CLASSIFICATION
1 0.0 – 1.0 22.4
1 1.0 – 2.0 32.8
1 2.0 – 3.0 32.5
1 3.0 – 4.0 68 42 89.7 28.2 CH
1 4.0 – 5.0 98.6 23.1
1 5.0 – 6.0 96.9 25.6
1 6.0 – 7.0 92.8 32.8
1 7.0 – 8.0 91.1 30.8
1 8.0 – 9.0 66 43 88.2 26.7 CH
1 9.0 – 10.0 94.5 30.5
1 14.0 – 15.0 91.9 29.0
1 19.0 – 20.0 68 43 97.2 25.6 CH
1 24.0 – 25.0 22.3
1 29.0 – 30.0 23.6
1 34.0 – 35.0 22.7
1 39.0 – 40.0 21.3
1 44.0 – 45.0 104.4 21.6
1 49.0 – 50.0 63 40 102.7 21.4 CH
1 54.0 – 55.0 18.2
1 59.0 – 60.0 17.6
1 60.0 – 62.0 114.5 17.3
1 62.0 – 64.0 114.3 17.3
1 64.0 – 66.0 115.1 16.7
1 66.0 – 68.0 115.2 16.8
1 68.0 – 70.0 115.7 16.6
GEOTECHNICAL INVESTIGATION REPORT NO. 15841G
NORTEX 1.0 MG STORAGE TANK TOWNGATE DRIVE
WYLIE, TEXAS
Plate 3
SUMMARY OF ABSORPTION PRESSURE-SWELL TESTS
BORING NUMBER
DEPTH (ft.)
SWELL PRESSURE
(psf)
GAIN IN MOISTURE
(%)
PERCENT SWELL
(%)
MATERIAL DESCRIPTION
1 3.0 – 4.0 776.0 4.0 0.9 CLAY, hard, olive-brown
1 8.0 – 9.0 970.0 5.5 2.5 CLAY, hard, olive-brown
1 49.0 – 50.0 2,328.0 6.1 3.9 SHALE, soft, weathered, olive-brown
SUMMARY OF UNCONFINED COMPRESSION TESTS - SOIL
BORING NUMBER
DEPTH (ft.)
PEAK STRESS
(psi)
FAILURE STRAIN
(%)
MATERIAL DESCRIPTION
1 4.0 – 5.0 71.6 3.1 CLAY, hard, olive-brown
1 7.0 – 8.0 17.8 4.4 CLAY, hard, olive-brown
1 19.0 – 20.0 53.5 7.7 SHALE, soft, weathered, olive-brown
SUMMARY OF UNCONFINED COMPRESSION TESTS - ROCK
BORING NUMBER
DEPTH (ft.)
PEAK STRESS
(psi)
FAILURE STRAIN
(%)
MATERIAL DESCRIPTION
1 60.0 – 62.0 345.7 1.9 SHALE, firm, gray
1 62.0 – 64.0 339.9 2.3 SHALE, firm, gray
1 64.0 – 66.0 357.2 2.3 SHALE, firm, gray
1 66.0 – 68.0 345.6 2.2 SHALE, firm, gray
1 68.0 – 70.0 346.9 1.7 SHALE, firm, gray
TRIAXIAL COMPRESSION TEST STRESS-STRAIN PLOT
BORING N0.: 1DEPTH (FT.): 5.0-6.0CLAY, slightly silty, dark brown
0 5 10 15AXIAL STRAIN (%)
0
20
40
60D
EV
IATO
R S
TRE
SS
(PS
I)
MOISTURE CONTENT (%): 25.6 DRY UNIT WEIGHT (PCF): 96.9CONFINING PRESSURE (PSI): 5, 10, 20
0 20 40 60 80NORMAL STRESS (PSI)
0
10
20
30
40
SH
EA
RIN
G S
TRE
SS
(PS
I)
TEST TYPE:UNCONSOLIDATED-UNDRAINED TRIAXIAL COMPRESSION TEST (ASTM D 2850)
PLATE 4TEXAS FIRM REGISTRATION NO. F-1238
HJA NO.: 15841G DATE TESTED: 02/28/16
235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
NORTEX 1.0 MG STORAGE TANKTOWNGATE DRIVE
WYLIE, TEXAS
cr = 20 psiΦr = 6 degrees
TRIAXIAL COMPRESSION TEST STRESS-STRAIN PLOT
BORING N0.: 1DEPTH (FT.): 14.0-15.0SHALE, weathered, calcareous, olive-brown and light gray
0 5 10 15AXIAL STRAIN (%)
0
10
20
30
40D
EV
IATO
R S
TRE
SS
(PS
I)
MOISTURE CONTENT (%): 29.0 DRY UNIT WEIGHT (PCF): 91.9CONFINING PRESSURE (PSI): 7, 14, 28
0 20 40 60 80NORMAL STRESS (PSI)
0
10
20
30
40
SH
EA
RIN
G S
TRE
SS
(PS
I)
TEST TYPE:UNCONSOLIDATED-UNDRAINED TRIAXIAL COMPRESSION TEST (ASTM D 2850)
PLATE 5TEXAS FIRM REGISTRATION NO. F-1238
HJA NO.: 15841G DATE TESTED: 02/28/16
235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
NORTEX 1.0 MG STORAGE TANKTOWNGATE DRIVE
WYLIE, TEXAS
cr = 15.4 psiΦr = 3.5 degrees
HJA NO.: 15865G DATE TESTED: 02/22/16
CONSOLIDATION TESTVOID RATIO-LOG OF STRESS PLOT
BORING N0.: 1DEPTH (FT): 6.0-7.0CLAY, slightly silty, dark brown
0.1 1 10VERTICAL STRESS (TSF)
0.50
0.55
0.60
0.65
0.70
0.75
0.80
VOID
RAT
IO
e = 0.7818
TEST TYPE: CONSOLIDATION TEST (ASTM D 2435)
1E-0050.0001 0.001 0.01COEFFICIENT OFCONSOLIDATION(SQ CM/SEC)
TEXAS FIRM REGISTRATION NO. F-1238PLATE 6
MOISTURE CONTENT (%): 32.8DRY UNIT WEIGHT (PCF): 92.8
235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
NORTEX 1.0 MG STORAGE TANKTOWNGATE DRIVE
WYLIE, TEXAS
HJA NO.: 15841G DATE TESTED: 02/22/16
CONSOLIDATION TESTDIAL READING-LOG OF TIME PLOT
BORING N0.: 1DEPTH (FT): 6.0-7.0CLAY, slightly silty, dark brown
0.1 1 10 100 1000 10000TIME (MINUTES)
0.22
0.23
0.24
0.25
0.26
0.27
0.28
0.29
0.30
0.31
0.32
0.33
0.34
0.35
0.36
DIA
L R
EAD
ING
(IN
CH
ES)
1.28 tsf
2.56 tsf
5.12 tsf
10.24 tsf
TEST TYPE: CONSOLIDATION TEST (ASTM D 2435)
TEXAS FIRM REGISTRATION NO. F-1238PLATE 7235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
NORTEX 1.0 MG STORAGE TANKTOWNGATE DRIVE
WYLIE, TEXAS
HJA NO.: 15865G DATE TESTED: 02/22/16
CONSOLIDATION TESTVOID RATIO-LOG OF STRESS PLOT
BORING N0.: 1DEPTH (FT): 9.0-10.0CLAY, slightly silty, brown to light brown
0.1 1 10VERTICAL STRESS (TSF)
0.50
0.55
0.60
0.65
0.70
0.75
0.80
VOID
RAT
IO
e = 0.7511
TEST TYPE: CONSOLIDATION TEST (ASTM D 2435)
1E-005 0.0001 0.001COEFFICIENT OFCONSOLIDATION(SQ CM/SEC)
TEXAS FIRM REGISTRATION NO. F-1238PLATE 8
MOISTURE CONTENT (%): 30.5DRY UNIT WEIGHT (PCF): 94.5
235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
NORTEX 1.0 MG STORAGE TANKTOWNGATE DRIVE
WYLIE, TEXAS
HJA NO.: 15841G DATE TESTED: 02/22/16
CONSOLIDATION TESTDIAL READING-LOG OF TIME PLOT
BORING N0.: 1DEPTH (FT): 9.0-10.0CLAY, slightly silty, brown to light brown
0.1 1 10 100 1000 10000TIME (MINUTES)
0.24
0.25
0.26
0.27
0.28
0.29
0.30
0.31
0.32
0.33
0.34
0.35
0.36
DIA
L R
EAD
ING
(IN
CH
ES)
1.28 tsf
2.56 tsf
5.12 tsf
10.24 tsf
TEST TYPE: CONSOLIDATION TEST (ASTM D 2435)
TEXAS FIRM REGISTRATION NO. F-1238PLATE 9235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
NORTEX 1.0 MG STORAGE TANKTOWNGATE DRIVE
WYLIE, TEXAS
HJA NO.: 15865G DATE TESTED: 02/22/16
CONSOLIDATION TESTVOID RATIO-LOG OF STRESS PLOT
BORING N0.: 1DEPTH (FT): 44.0-45.0SHALE, weathered, calcareous, olive-brown and gray
1 10VERTICAL STRESS (TSF)
0.40
0.45
0.50
0.55
0.60
VOID
RAT
IO
e = 0.5852
TEST TYPE: CONSOLIDATION TEST (ASTM D 2435)
0.0001 0.001 0.01COEFFICIENT OFCONSOLIDATION(SQ CM/SEC)
TEXAS FIRM REGISTRATION NO. F-1238PLATE 10
MOISTURE CONTENT (%): 21.6DRY UNIT WEIGHT (PCF): 104.4
235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
NORTEX 1.0 MG STORAGE TANKTOWNGATE DRIVE
WYLIE, TEXAS
HJA NO.: 15841G DATE TESTED: 02/22/16
CONSOLIDATION TESTDIAL READING-LOG OF TIME PLOT
BORING N0.: 1DEPTH (FT): 44.0-45.0SHALE, weathered, calcareous, olive-brown and gray
0.1 1 10 100 1000 10000TIME (MINUTES)
0.26
0.27
0.28
0.29
0.30
0.31
0.32
0.33
0.34
0.35
0.36
DIA
L R
EAD
ING
(IN
CH
ES)
2.56 tsf
5.12 tsf
10.24 tsf
20.48 tsf
TEST TYPE: CONSOLIDATION TEST (ASTM D 2435)
TEXAS FIRM REGISTRATION NO. F-1238PLATE 11235 MORGAN AVE. DALLAS, TX 75203 I 214.941.3808 I WWW.HJA-ENG.COM
NORTEX 1.0 MG STORAGE TANKTOWNGATE DRIVE
WYLIE, TEXAS